Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹11.4 LAccepted-AOC | ₹11.4 L | L1 | Accepted-AOC Successful bidder |
| 2 | L2₹15.4 L+₹3.9 L (34.5%)Rejected-Finance | ₹15.4 L+₹3.9 L (34.5%) | L2 | Rejected-Finance Not lowest bidder |
Tender Value
Refer Docs
EMD Value
₹21,400
Closing Date
20 Oct 2022, 5:00 pmClosed
GE AF Sambra
GE AF Sambra ATS Sambra Belgaum 591124
REPAIR REPLACEMENT OF LT PANEL FEEDER PILLAR BOX LT OVER HEAD AND UNDER GROUND CABLE INCLUDING EARTHING AND OTHER CONNECTED WORKS AT ATS SAMBRA
2022_MES_552334_1
8722/E78
Open Tender
Civil Works
Item Rate
335 days
GE AF Sambra
Please refer Tender documents
8 documents required · 8 mandatory
₹500
GE AF sambra
₹21,400
Yes
15 Nov 2022
16 Sept 2022
22 Oct 2022
16 Sept 2022
20 Oct 2022
7 Oct 2022
Amount
M & L for disconnecting from the panel LT cables of the following sizes along with cable glands, cutting out the burnt/over heated cable ends, making new connections using new aluminium lugs of appropriate size including insulation tapes, excavation etc, and refixing the cable gland and making all connections & testing for proper working complete all as directed for following cables :-
120-240 sq mm 3.5 core
50-95 sqmm 3.5 core
M & L LT under ground cable XLPE insulated armoured, heavy duty electric cable with aluminium conductor 1100 Volts grade in trenches / passing through pipes of following cross sectional area including taking out old existing unserviceable cables :-
3 1/2 core 120 sqmm
3 1/2 core 95 sqmm
3 1/2 core 70 sqmm
3 1/2 core 50 sqmm
3 1/2 core 35 sqmm
3 1/2 core 25 sqmm
4 core 16 sqmm Note for Item No 2 :- Excavation and earth work, brick protection and sand cushioning will be measured and paid separately under relevant items of this schedule
Excavation in trenches, not exceeding 1.50m wide and not exeeding 1.50m in depth for foundations, trenches of cable or pipe lines etc and getting out in hard/dense soil complete all as specified and as directed.
All as per item No 3 here-in-before but exceeding 1.5 m deep and not exceeding 3.0 m deep.
Returning filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25 cm thick in soil complete all specified and as directed.
Removing excavated materials/soil to a distance not exceeding 50 meters and depositing where directed at a level not exceeding 1.5 meters above the starting point all specified and as directed.
S & F of DWC Pipe inner dia 103 mm, outer dia 120 mm, IS-16205, for cable protection in wall/under gorund laying of UG cables including SNAP-FIT Coupler and all fittings as required at site complete all as specified and as directed
S & F of DWC Pipe inner dia 63 mm, outer dia 75 mm, IS-16205, for cable protection in wall/under gorund laying of UG cables including SNAP-FIT Coupler and all fittings as required at site complete all as specified and as directed
M & L Cutting the tar macadam road / hard standings for laying cable and excavating not exceeding 45cm wide and 75cm depth and getting out including filing back with PCC 1:4:8 type D-2 and finishing complete matching with the surroundings all as specified and as directed
S & F PVC spacers 4 way for LT OH line 1100 volts grade with necessary screws nuts bolts etc complete all as directed to prevent the lines touching each other on heavy wind or in rain as a preventive arrangement to the existing system including removing the existing unserviceable spacers all as specified and as directed
Taking down unserviceable MCCB of any capacity after disconnecting all the incoming and out going cable connections and offering necessary credit all as specified and as directed
M & L MCCB 400Amps capacity, 4 poles, 36KA, fixed thermal magnetic setting including connecting up with suitable aluminum cable lugs etc.complete all as specified and directed
M & L MCCB 250Amps, 4 poles, 36KA, fixed thermal magnetic setting including connecting up with suitable alumnium cable lugs etc.complete all as specified and directed
M & L MCCB 200Amps, 4 poles, 36KA, fixed thermal magnetic setting including connecting up with suitable alumnium cable lugs etc.complete all as specified and directed
M & L MCCB 100 Amps, 4 poles, 25 KA, fixed thermal magnetic setting with separate neutral link including connecting up with suitable alumnium cable lugs etc.complete all as specified and directed
M & L MCCB 63 Amps, 4 poles, 25 KA, fixed thermal magnetic setting with separate neutral link including connecting up with suitable alumnium cable lugs etc.complete all as specified and directed
M&L MCCB 100 Amps, 3 poles, 16 KA, fixed thermal magnetic setting with separate neutral link including connecting up with suitable alumnium cable lugs etc.complete all as specified and directed
M & L MCCB 63 Amps, 3 poles, 16 KA, fixed thermal magnetic setting with separate neutral link including connecting up with suitable alumnium cable lugs etc.complete all as specified and directed
Note for items 12 to 18 :- Quoted rate is deemed to be included the necessary minor modifications such as making additional holes / cutting slots etc in the existing panel if found required for fixing the MCCB.
Straining only existing loose ACSR conductors/ GI wire of any size or any numbers of wire in one span complete all as directed by Engineer in charge. Note :- One span shall not measure more than 50 metre measured as one unit.
Cutting tree branches below, top and around the OH conductors not less than two metre around the line and keeping the line clearance throughout the contract period by trimming the branches repeatedly as many times as required, depending on the growth of new branches including clearing the site and by depositing the branches to a distance not exceeding 50 m all as directed
M & L Stay assembly with complete accessories as shown in electrical plate No. 1 using 20 mm dia stay rod etc.complete all as specified and directed Note :-loop type insulator, stay clamps, excavation and concrete will be measured and paid separately.
M & L G I stay strand of size 7/4.00 mm complete all as specified and directed
M & L Loop type insulator large size with over all dimensions 90x140mm, clearance of hole 25.5mm complete all as specified and directed
M & L Aluminum conductor, steel reinforced ( ACSR ) drawn / fixed on poles including aluminum binding wire for jumpering including dismantling old unserviceable conductor complete all as directed
S & F Low Tension pre-stressed reinforced cement concrete poles 09 mtr long 102X172 mm at top and 102X279 mm at bottom class 10 erecting in vertical position including synthetic enamel painting RCC pole upto 1.2 mtr height from top of copping and then paint of 03 Nos of each black and yellow alternate strip of 20 cm width complete all as specified & directed.
M & L Plain cement concrete 1:4:8 Type D-2 using 40 mm graded crushed stone aggregate as in foundation filling for poles complete all as specified.
M & L Plain cement concrete 1:3:6 Type C-2 using 40 mm graded crushed stone aggregate as in foundation filling for poles complete all as specified.
M & L for providing cement concrete PCC 1:2:4 type B-1 using 20 mm graded crushed stone aggregate) as coping around poles etc complete including necessary formwork and finishing the exposed surfaces even and smooth without using extra cement all as specified and as directed.
M & L G I pipes light grade with all fitting and fixed complete to poles/route/drains etc and ceillings or laid in floors of following dia :-
40 mm dia
50 mm dia
80 mm dia
M & L Pin type porcelin vitreous white brown or green insulator including one galvanised steel spindle two galvanised washers and GI nut bolt 100 mm height for 1100 volts grade LT including taking down the old broken insulator complete all as specified and directed
All as per item No 30 but shackle type insulator for LT 1100 volts
M & L Straight through jointing heat shrinkable kit for cable of 185/120/95/70 sqmm 3.5 core suitable for aluminium conductor including earth work complete for LT cables
All as per item No 32 above but 50/35/25 sqmm x3.5 core
M & L Mild steel cross arms, angles, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated including painting with two coats of Aluminium paint over a coat of Red oxide primer all as directed
M & L Painting of PCC/RCC poles 9 mtr height with two coats of synthetic enamel paint alternatively with black and yellow strip of width 150mm up to a height of 1.50mtr from ground level and applying one coat of cement wash for the remaining height including writing pole Nos all as directed.
M & L for preparation of steel tubular poles 9 mtr height including cross arms and applying with one coat of aluminium paint from bottom to top all as directed.
Supply & fixing Aluminium lugs suitable for UG cable of size 3 .5 / 4 core, 25 / 35 sqmm including respective size of lugs for the neutral cable all as specified
All as per Sl item No 37 here in before but for UG cable of size 3.5 core 50 / 70 sqmm.
All as per Sl item No 37 here in before but for UG cable of size 3.5 core 95 / 120 / 185 sqmm.
M & L preparation of old treated steel surfaces of L T panel and spray painting two coats of synthetic enamel paint of smoke grey colour complete all as specified and as directed.
M & L writing MES/SM Number on Transformer, VCB etc in Block letters of size 50 mm x 50mm and letters not more than 32 numbers with synthetic enamle paint of white colour all as specified and directed.
M & L replacing broken hinges with 100mm M S medium weight butt hinges of L T panel, DB etc by electric welding including denting and painting with two coats of synthetic enamel paint over a coat of red oxide primer all as specified and as directed
S & F Galvanised steel wire 4 mm dia all as specified and as directed
Supply, install, testing and commissioning of floor mounted LT feedar pillar box, CPRI approved, AC 415 V, 50 HZ, 3 Phase 4 wire of suitable size for accomodating the following accessories, totally enclosed self supporting structure / cubicle, fully compartmentalized type, suitable for outdoor use, with bottom cable entry with suitable cable glands, structure made out of 3.15 mm thick CRCA steel sheet with angle iron 50X50X5 mm frame work with 4 legs grouted into PCC (1:2:4) type B1 necessary foundation block, with suitable mounting arrangement for bus bars, voltmeter, ammeter, changeover switch and MCCBs, hinged doors at front with suitable locking arrangement, Provision of louvers at sides, structure treated under 8 - tank metal treatment process duly powder coated, complete all as specified and directed :- (Main Panel) NOTE:- Connection from Main bus bar to Outgoing MCCB should be provided through bus bar of suitable rating instead of copper wires.
BUSBAR :- (a) Electronic copper bus bar 350 Amps, supported on non hygroscopic fibres and brass screws for mounting -04 Nos
M & L for HT/LT Cable route indicator with a welded/riveted disc of 4 inch dia and engraved with cable with cable route marker made out of angle iron 40 x 40 x4 mm thick dug in ground with in and incl PCC 1:3:6 type C1 using 20mm graded aggregate at approx distance 100 mtr including necessary earth work complete all as specified and directed by Engr-in-Charge
M/s. VIJAY ELECTRICALS
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .