| 1 | L1₹49.1 LAccepted-Finance 6 1 SERANG LANE KOLKATA 700014 BARASAT NORTH 24 PARGANAS | KOLKATA | NORTH 24 PARGANAS | WEST BENGAL | 700014 | L1 | Accepted-Finance Quoting Lowest Amount | |
| 2 | L2₹52.4 L+₹3.3 L (6.74%)Rejected-Finance 34 1 TILAK NAGAR KOLKATA 700040 | KOLKATA | KOLKATA | WEST BENGAL | 700040 | L2 | Rejected-Finance Quoting Higher Amount | |
| 3 | L3₹53.3 L+₹4.2 L (8.61%)Rejected-Finance 448 MUZAFFAR AHMED STREET KOLKATA 700 016 | KOLKATA | KOLKATA | WEST BENGAL | 700016 | L3 | Rejected-Finance Quoting Higher Amount | |
| 4 | L4₹56.6 L+₹7.6 L (15.5%)Rejected-Finance 20F MATILAL BASAK LANE KOLKATA 700054 | KOLKATA | KOLKATA | WEST BENGAL | 700054 | L4 | Rejected-Finance Quoting Higher Amount | |
| 5 | L5₹60.6 L+₹11.6 L (23.6%)Rejected-Finance 1 B 1 UKILABAD BERHAMPORE MURSHIDABAD | BERHAMPORE | MURSHIDABAD | WEST BENGAL | 742101 | L5 | Rejected-Finance Quoting Higher Amount |
Tender Value
Refer Docs
EMD Value
₹1.3 L
Closing Date
13 Nov 2020, 3:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Superintending Engineer
Office of the Superintending Engineer, Western Electrical Circle , PWD, Purta Bhavan, 1st floor, Burdwan-713103
Electrical renovation work of the Main Building and Pathology Department at Uttarpara State General Hospital,Hooghly
2020_WBPWD_303135_1
WBPWD/SEWEC /HED /NIQ-06/2020-21_2nd Call
Open Tender
ELECTRICAL WORKS ORG
Item Rate
90 days
Hooghly
Please refer Tender documents.
4 documents required · 4 mandatory
₹1.3 L
Yes
Office of the Superintending Engineer, Western Ele
4 Dec 2020
3 Nov 2020
18 Nov 2020
3 Nov 2020
13 Nov 2020
6 Nov 2020
3 Nov 2020 - 5 Nov 2020
5 Nov 2020
30 days
Amount
Supply and installation of L.T. cubical type fully compartmentalized distribution panel board, having rigid and self supporting structure fabricated with 14 SWG CRCA sheet with M.S. angle iron frame (main frame with 50 x 50 x 6 mm angle and each vertical compartment with 40 x 40x6 mm MS angle iron). The base of panel should be made with 75mm x 40mm x 4.4 mm M.S. channel. [Manufacturer/Fabricator having Test Certificates from CPRI]. An Auto Cad Drawing of the panel has to approved by EIC before making of panel.
Construction Details : All incoming & outgoing switches are to be housed in respective compartments hinged and gasket doors at the front. All doors should have panel locking arrangement in such a fashion that it can not be on unless the feeder remains in off position. The rear panel should gasketed wire net guard for ventilation arrangement will be made of easy accessibility to each compartment by providing rear panel doors with locking system . The panel is to be properly gasketed to prevent the dust & vermin. All vertical bus bar chambers is to properly arrange and all electrical equipments are to be fixed by nuts and bolts on suitable Hylam board / porcelain insulators of adequate size and dimension. The outgoing feeder connection from respective switches are to be made at rear side of panel with suitable size tinned copper bar with proper insulation with coloured sleeving or on bush insulators for bus bar connection as per direction of EIC. Each compartment will be providing with DMC/FRP board at back side.
Incomming Switch : (a) 415V 315 Amps TPN SDF units with DIN type fuse link (Make:- L&T : Cat No.-SK95461 or equivalent cat of SIEMENS/ABB) in open exexution ------- 1 No.
Bus Bar : 500V, 300 Amp capacity 99.9% – 99.5% electrolytic tinned 4 bar copper bus bar [size of flat 4x50 mm x 5 mm or 4x25 mm x 10 mm] mounted on non-hygroscopic FRP/SMC/DMC insulator / hylam sheet having sufficient di-electric strength duly wrapped with colour PVC tapes (Red, yellow, blue & black) for phases & neutral identification - 1 set. The busbar is to be rigidly supported on suitable non-hygroscopic insulating materials of robust ration to with stand electromechanical stress in the event of earth fault. All connection to bus to made by suitable nuts & bolts. The busbar is too wrapped with coloured PVC (Red. Yellow, Blue & Black) for colour identifications.
Outgoing Switches : (a) 415V 200 Amps TPN SDF units with DIN type fuse link (Make:- L&T : Cat No.-SK95418 or equivalent cat of SIEMENS/ABB) in open exexution. ---- 1 no. (b) 415V 160 Amps TPN SDF units with DIN type fuse link (Make:- L&T : Cat No.-SK95713 or equivalent cat of SIEMENS/ABB) in open exexution---- 3 Nos. (c) 415V 125 Amps TPN SDF units with DIN type fuse link (Make:- L&T : Cat No.-SK95001 or equivalent cat of SIEMENS/ABB) in open exexution----3Nos. (d) 415V 63 Amps TPN SDF units with DIN type fuse link (Make:- L&T : Cat No.-SK95421 or equivalent cat of SIEMENS/ABB) in open exexution.----1No.
Metering Panel a) Advanced LED Multifunction Meter Digital Type Load Monitor ( Make L&T, Cat No.- WL442011OOOO) - 1 No. b)LED single function Meter ( Make L& T, Model- CAT No.- WL111020OOOO or equivalent)- for ammeter --- 3 nos. c)LED single function Meter ( Make L& T, Model no..WL112020OOOO or equivalent) for voltmeter-- 3 nos. d) 230V R.Y.B. LED indicator lamp -(SIEMENS/L&T) ---- 3 nos. d) 200/5 Amp ratio C.T (Kappa) --- 3 nos. e) S & F 6 Amp SPMCB(Make-SIEMENS/LT/Legrand)---6 nos.
Interconnection :- All interconnection between incoming main to Busbar are to be made with suitable size electrolytic tinned copper bars or equivalent flexible pvc insulated multistranded single core Cu cable and the same between busbar to each outgoing mains and & for metering arrangements are to be made by suitable size of Copper with proper socketing of the end of each wire leads.
Earthing :- A separate continuous aluminum earth busbar of size 50mm x 6mm shall run across the full length of the panel board and brought outside the panel. All electrical equipment are to be properly earthed with suitable size G.I. wire.
The complete panel board is to be spray painted after required surface treatment by 9 tanks process / sand blasting with 2 coat of red oxide primer & 2 coat of finished paint over dried or powder coating.
Installation :- The complete panel board is to be installed on suitable brick padestal as directed by the E.I.C. All incoming/outgoing switches is to be properly lebeled on Acrylic sheet as per direction of EIC.
Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) partly in 20mm size PVC rigid conduit 'FR' (Precision make) [for ceiling portion only] and in 19mm bore, 3mm thick polythene pipe [for horizontal & vertical run embedded in wall], with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Modular type switch (Legrand-Model Arteror/Myrius or equivalent model of Crabtree/Equivalent make as per direction of E.I.C) fixed on Modular GI switch board complete with 2 no. suitable size “Ph & N” copper bar with top cover plate making earthing attachment fixed on wall incl. mending good damages to original finish with following average run. [only PVC Rigid Conduit on ceiling and remaining portion concealed]
8 Mtr [4(c)/ E-25 ]
10 Mtr [4(e)/ E-25 ]
11 Mtr [4(f)/ E-25 ]
Distn. wiring in 3 X 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire in 19 mm bore, 3 mm thick polythene pipe complete with all accessories embedded in wall to 240 V 6A 5 pin plug point with MODULAR type switch as per GS.
On Board [ 3 (i) / E- 20 ]
4.5 mtr. [ 3 (iv) / E- 20 ]
Supplying and fixing PVC Rigid Conduit 'FR' [Precision Make] of following sizes on wall, ceiling with saddles and other accessories as required and mending good damages to building works
20 mm size [ 7(a)/ E- 16 ]
25 mm size [ 7(b)/ E- 16 ]
Cutting Channel of required size on masonry wall by Electric operated cutting machine incl. supplying & fixing of heavy gauge Polythene pipe of following diameter as per GS.
19 mm dia 3 mm thick [ 6 (a)/ E- 3 ]
25mm dia 3 mm thick [ 7 (a)/ E- 3 ]
Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire of the following sizes in the 19mm/25mm prelaid polythene pipe/PVC rigid conduit as per GS.
3 x (1.5 sqmm) [1(b) / E- 9 ]
2x(2.5 sqmm)+1x(1.5 sqmm) [ 1(s) / E-9 ]
2x(4 sqmm)+1x (2.5 sqmm) [ 1(v) / E- 9 ]
2x(6 sqmm)+1 x (4 sqmm) [ 1(y) / E- 9 ]
4x(10 sqmm)+2x (6 sqmm) [ 1(d1) / E- 9 ]
S & F solderless Copper socket by crimping of Copper wires.
a)1.5 sq mm
b) 2.5 sq mm [9(i) / F-5]
c) 4 sq mm [9(ii) / F-5]
d) 6 sq mm [9(iii) / F-5]
e) 10 sq mm [9(iv) / F-5]
Supplying & Fixing sheet metal inspection box (16 SWG) of the following sizes(in mm ) flushed in wall & 3 mm thick bakellite cover as per GS
175 x 100 x 65 [11(c)/E-4 ,13(c)/E-5]
200 x 150 x 65 [11(d)/E-4 ,13(d)/E-5]
240 x 240 x 65 [11(f)/E-4 ,13(f)/E-5]
Supplying and fixing double door Vertical TPN MCB Distribution board for MCCB incomer with IP-42/43 protection, on angle iron frame on wall as per GS as per direction of EIC.
12 Way ( Up to 160 A ) [Make - Legrand,Enclosure (607915)/ Siemens-Enclosure-(8GB31574RC)/Schneider-Enclosure-(A9HVD12M)/L&T Enclosure- ((LTVD12MGN) as approved by E.I.C] [15 / D- 11 ]
8 Way ( Up to 160 A ) [Make - Legrand, Enclosure 607914/Siemens-Enclosure-8GB31573RC)/Schneider-Enclosure-A9HVD08M/L&T Enclosure- (LTVD08MGN) as approved by E.I.C] [15 / D- 11 ]
Supplying and fixing 415 V Four Pole MCCB of Breaking capacity 25kA/35kA in existing Vertical DBs including necessary connection as per GS [ Make - Legrand/Siemens/ Schneider/L&T) as per direction of EIC.].
Supplying and fixing double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall as per GS.( Make - Legrand/ Schneider/ Crabtree) as per direction of EIC. )
8 Way [Make - Legrand, Enclosure-607717/ Schneider, Enclosure-A9HTND08/ Crabtree, Enclosure- (DCDKTHODCW08) as approved by E.I.C] [ 14 / D- 10 ]
6 Way [Make - Legrand, Enclosure-607716/ Schneider, Enclosure-A9HTND06 /Crabtree, Enclosure- (DCDKTHODCW06) as approved by E.I.C] [ 14 / D- 10 ]
Supplying and fixing double-door SPN MCB Distribution Board with IP-42/43 protection, concealed in wall as per GS.
2+12 Way [Siemens Enclosure(8GB32102RC14)/ Schneider Enclosure-(A9HSND12) or equivalent model of Legrand/Crabtree] as per direction of EIC. [ 13/D- 9 & D-10]
2+8 Way [Siemens Enclosure(8GB32102RC10)/ Schneider Enclosure-(A9HSND08) or equivalent model of Legrand/Crabtree] as per direction of EIC. [ 13 / D- 9 & D-10 ]
Supplying and fixing 240/415 V MCB Isolator on din rail of existing DBs and necessary connection as perGS [Make-Legrand/ Schneider/Siemens/ Crabtree/ L&T) as per direction of EIC. ]
Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connectionas per GS [Make-Legrand/ Schneider/Siemens/Crabtree/L&T) as per direction of EIC. ]
40 A / 63 A SP [ 7 / D- 6 ]
Supplying and fixing double door sheet steel (16SWG), powder coated cable end box for TPN DB horizontal / vertical / SPNDB enclosure with IP-42/43 as per GS
4/6/8/12 Way (Vertical) [16/D-12]
6 Way (Horizontal) [16/D-12]
8 Way (Horizontal) [16/D-12]
Supplying and fixing 415V TPN SFU with sheet steel enclosure of following rating on angle iron frame on wall with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating.( Make - L&T /Siemens/Havels)
250A, TPN SFU [4(a)/D-3]
160A, TPN SFU [4(a)/D-3]
100A, TPN SFU [4(a)/D-3]
63A, TPN SFU [4(a)/D-3]
Supplying and fixing Sheet steel Main Switches on flat iron frame on wall(240V DP with fuse on L&N) (Make-Havells/Standard/HPL)
Supplying and fixing 415V, TPN on load front operated Changeover switch with Sheet Steel enclosure on angle iron frame on wall with nuts bolts etc(Make-L&T /HPL/Havels)
Supplying & fixing sheet metal (16 SWG) Iron Clad Busbar chambers on angle iron frame on wall, incl. earthing attachment and painting as required – (As per Drawing no. 470 of PWD Specification Book – May 1991)
4 bars (415 V, 315 A) Dimension of Cu bars [85mm long](4 x 50x5mm) Dimension of Sheet Metal Box (500x150mm) [ D-12/19(b)]
4 bars (415 V, 200 A) Dimension of Cu bars [85mm long](4 x 20x5mm) Dimension of Sheet Metal Box (500x150mm) [ D-12/19(b)]
4 bars (415 V, 100/125 A) Dimension of Cu bars [85mm long](4 x 15x3mm) Dimension of Sheet Metal Box (500x150mm) [ D-12/19(b)]
2 bars (240 V, 63 A) Dimension of Cu bars [85mm long](2 x 20x5mm) Dimension of Sheet Metal Box (300x150mm) [ D-12/19(b)]
Supply of 4/3.5 Core XLPE Insulated & Sheathed Armoured Aluminium Conductor cables for Working Voltage up to 1100 Volts of following sizes [ Make Nicco / Gloster/KEI/Polycab]
3.5 Core 185 Sq. mm
3.5 Core 95 Sq. mm
4 Core 50 Sqmm
4 Core 35 Sq. mm
2 Core 10 Sqmm
Laying of cable in underground trench as per GS for the following numbers of Cables.
Above 35 and upto 185 Sq. mm [ 1(b)/ F- 2 ]
Laying of cable after cutting floor/pavement/wall as per GS for the following Sizes.
2.5 to 35 Sq. mm [ 5(i)/ F- 3 ]
Above 35 to 95 Sq. mm [ 5(ii)/ F- 3 ]
Above 95 sqmm [ 5(iii)/ F- 3 ]
Laying of cable from 3½ core 90 sqmm upto 3½ core 150 sqmm on wall/surface including S & F MS clams with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. as necy., mending good damages and painting. [2(e)/F-1]
Laying of cable from 3½ core 35 sqmm and upto 3½ core 50 sqmm on wall/surface including S & F MS clams with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making hole etc. as necy., mending good damages and painting. [2(c)/F-1]
Laying of cable upto 2 core 25 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 10 SWG GI (Hot Dip) Wire, making holes etc. as necy. mending good damages and painting [2(a)/F-1]
Supplying & fixing medium gauge GI Pipe ( ISI-Medium) Protection with necessary fittings as per GS
25mm dia [11(c)/F-6]
40mm dia [11(c)/F-6]
80mm dia [11(f)/F-6]
Supplying and fixing compression type gland and finishing those for following XLPE / PVC armoured cable (2/4/3.5)Core as per GS.
3.5Core 185 Sq. mm [ 7(d)/F4 & 8(b- xxi) /F5]
3.5Core 95 Sq. mm [ 7(d)/F4 & 8(b- xviii) /F5]
3.5Core 50 Sq. mm [ 7(c)/F4 & 8(b- xvi) /F5]
4Core 35 Sq. mm [7(d)/F4 & 8(b- xv) /F5]
2 Core 10 Sq. mm [7(a)/F4 & 8(b- iii) /F5 ]
Supplying and fixing MCB SS enclosure with IP-20/30 protection, powder coated provision for two/four pole MCB, concealed in wall after cutting the wall & mending good the damages to original finish incl. painting, connection & provision for earthing attachment
Supplying & Fixing GI Modular Switch Board of the following sizes complete with three no. suitable size Copper bar with holes (for Ph, N & E) fixed on bakelite/Hard Rubber insulator over the MS welded chairs incl. top cover flushed in wall for housing the board after cutting the brick wall incl. making earthing attachment, painting and mending good damages to building works
4 module 1(a)/E-17]
6 module 1(b)/E-17]
8 module 1(c)/E-17]
2 Row 12 module 1(e)/E-17]
Supplying & Fixing modular type socket /socket (Legrand-Model Arteror/Myrius or equivalent model of Crabtree/Equivalent make as per direction of E.I.C), in exsisting Modular board incl. connections.
16 A modular type socket [4(b)/E-17]
16 A modular type switch [3(b)/E-17]
6 A 5-pin modular type three pin socket [4(a)/E-17]
6 A modular type switch [3(a)/E-17]
Supply & Fixing 240 V, 6 A, 3 pin Modular type plug socket (Legrand-Model Arteror/Myrius or equivalent model of Crabtree/Equivalent make as per direction of E.I.C) with 6A Modular type switch, without plug top on 4 Module GI Modular type switch board with 3 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. [ 9(a) / E-18]
Supply & Fixing Modular type 240 V, 16A, 3 pin plug socket with separate 16 A Modular type switch on sheet metal switch board embedded in wall as per GS. (Legrand-Model Arteror/Myrius or equivalent model of Crabtree/Equivalent make as per direction of E.I.C) [ 9(b) / E-18]
Supplying & Fixing Industrial Plug & Socket board with 240 V, 20A, SPN & Earth Metal Industrial Plug socket & 20A Industrial top incl. S&F 20 A SP MCB breaking capcity 10kA (C- Curve) in SS enclosure fixed on wall and cecessary conection [ 17 /D-12]
Supplying & Fixing Industrial Plug & Socket board with 415 V, 30A, TPN & Earth Metal Industrial Plug socket & 30A Industrial top incl. S&F 32 A TPN/FP MCB breaking capcity 10kA (C- Curve) in SS enclosure fixed on wall and cecessary conection. [ 18 / D-12]
Supplying and fixing 32A, 415V TPN Changeover switch with Sheet Steel enclosure on angle iron frame on wall with nuts bolts etc as per GS [ Make L& T /Havells/HPL]. [2(b)/D-1]
Supply & Fixing 240 V, 25 A, Modular type AC starter (Brand approved by EIC) with 25A Modular switch type DP MCB (C-Curve) and 4 Module GI Modular type switch board with 4 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.[17 / E-19]
Supply & Fixing 240 V, 25 A, 3 pin Modular type plug socket (Brand approved by EIC), without plug top and switch with 2 Module GI Modular type switch board with top cover plate flushed in wall and making necy. connections with PVC Cu wire and earth continuity wire etc.[ 5(a) / E-17]
Supply & Fixing 240 V,25 A, 3 pin Modular type plug top with indicator (Brand approved by EIC) & necy. Connections..[ 5(b) / E-17]
Supply & Fixing 240 V, 4 nos. 6 A, 3 pin Modular type plug socket with 4 nos. 6A Modular type switch (Brand approvedby EIC), 16A Modular switch type MCB (C-Curve) and Indicator without plug top on 2 row 18 Module GI Modular type switch board with 2 row 18 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy.connections with PVC Cu wire and earth continuity wire etc. [ 12 / E-18]
S & F of 415 V, 3ph, MUG-10 DOL starter with relay range 13-21A on angle iron frame as per GS. [Make: L&T, Cat No.- SS95983 or equivalent model of SIEMENS/ABB]
Supply and delivery of single/twin Industrial LED Batten luminaries incl. Supply of 1 no./2nos. 18W LED Tube
Twin fittings [Philips make Cat No. TMC-501 P1xT-LED 22W P3242 or equivalent make CG / Bajaj / Wipro as approved by E.I.C] incl. 2 no. 18W Master LED Tube
Single fittings [Philips make Cat No. TMC-501 P1xT-LED 22W P3241 or equivalent make CG / Bajaj / Wipro as approved by E.I.C] incl. 1 no. 18W Master LED Tube
Fixing only single/twin LED batten light fitting suspended from the ceiling fixed with “L” type MS clamp for RC ceiling / MS pipe as per GS direction of EIC [ 17/C-2 ]
Fixing only single/twin LED Batten light fitting complete with all accessories Directly on wall/ceiling as per GS.[ 14d/C-2 ]
Extra for suspension exceeding 25 cm with S&F additional 2 no. 20 mm dia EI conduit (14 SWG) supports & necy. PVC insulated wire and painting etc. as required by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length. [16/C-2]
Supply & Fixing angular batten holder (Anchor) on 75mm dia PVCround block / round bakelite on wall/ceiling as per GS [ 22/D-13 ]
Supply and fixing 14W LED bulb(Bajaj/CG/Philips/wipro) on existing batten holder
Supplying & Fixing 240 V AC/DC superior type Ding-Dong Call Bell (Anchor) on HW board incl. S&F HW board as per GS [ 20( a )/D-13 ]
Supply of ceiling fans with burst-proof P2/S3 Capacitor complete with all accessories without regulator. ( Make - Usha-Striker or equivalent model of CG/Orient)
a. 1200 mm Sweep
b. 1400 mm Sweep
Supply & fixing heavy duty Exhaust fan(Make-EPC] of followinng sizes after making hole in wall and making good damages and smooth cement finish etc. as practicable as possible and providing necy. length of PVC insulated wire and making connection for exhaust incl. s&f louver shutter as per G.S. )
12"( 300mm ) Speed 920 RPM
9"( 230mm ) Speed 1370 RPM
Supply & Fixing GI sheet (20SWG) metal Cowl with MS flat iron frame & GI wire mesh on wall as per GS
Supplying & Fixing MS fan clamp of two piece type for RC ceiling as per approved specification as per GS. [ 29/D-14 ]
Supply & Fixing 240V, Modular Socket (2 Module) type fan regulator (Step type) ([Legrand-Model Arteror/Myrius or equivalent model of Crabtree or equivalent make as approved by E.I.C) ) on existing Modular GI switch board with top cover plate incl. making necy. connections etc. [10/E18]
Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc as per GS [ 21 (a) / C-3 ]
S & F of MS down rod 14 SWG 20 mm dia MS conduit as per GS
Engraving the deptt. number with 10 mm lettering on the body as per GS. [ 24 (a) / C-3 ]
Extra for additional one letter incl. hifen, stroke and stop [24(b)/C-3]
Painting upto 10 letters of the engraved number with approved black /red paint as required as per GS [ 26 (a) /C-3 ]
Supply & fixing 450mm sweep wall bracket fan(high speed) with metal body & blades(Orient - Wall-II Tornado or equivalent cat of CG/EPC/Cinni) with necessary wooden board on wall with nuts, bolts, washer etc.
S & D of 450/500 mm sweep pedestal fan with metal body, blade etc. (Make- Usha model no-TURBO-180 or equivalent model of Crompton Greaves/ Orient).
S&F of 250V timer DB (equivalent to 12 way SPNDB in size) with double door sheet steel enclosure, neutral bar, din rail, with lP43 protection comprises with 20/25A TPMCB(C-curve 10ka) and 1 no 24 hr analog time switch and 1 no 18/25A power contactor complete with internal wiring with suitable size of copper wire including 1 no toggle switch and LED indicator and earthing attachment as per direction of EIC (Make:- LT/SIEMENS/ABB or equivalent make as approved by E.I.C)
S & F 3 phase timer box Made of 14 SWG MS sheet (size approx– 400 X 350 X 175mm) with powder coated synthetic paint incl. hinged type MS door , inter locking system consisting the following materials : 1) S & F 24 Hr. timer (L & T , J648B1/Legrand) – 1 no. 2) S & F 440 Volt 40A 3P contactor (L & T, ML – 3 , SS91851) – 1 no. 3) 6 amp auto mannual toggle switch – 1 no. (L &T) 4) Indicating lamp B & G (L&T) – 2 nos. 5) 440V, 40A, 10KA, Cseries SP MCB (legrand)on din rail for incoming-1no 6) 100A capacity 4W Brass stud type connector on FRP chair for I/C & O/G- 2nos All control circuit wiring would be made by 1x1.5 sqmm stranded Cu wire(FRLS) and the I/G & O/G circuit with 1x6sqmm copper wire maintaining colour code incl taping, socketing to complete the work. The box should be fixed on wall with suitable size of flush nut and necy. Connection.
S & F mini pole on roof top by 80 mm dia., 2 Mtr. Long GI(M) pipe medium quality (Bansal/Jindal make) incl. making cc (6:2:1) muffing 600x600x750 mm in size with 3 mm thick neatly finished cement plaster incl. S & F 8”x6”x4” C.I. looping cable box incl. S & F 40 mm. dia. G.I.(M) 1.5 Mtr. Long arm bracket for fixing flood light & neccy connection by 2x 1.5 sq mm Cu wire. This is incl. painting as per GS.
S&F 50 mm. dia 1.5 mtr. long detachable type G.I. Single arm bracket, suitable for pole head. The arm bracket shall be properly welded with 15 mm. thick stifner plate of pole sleeve for strengthening incl. properly fixing arrangement with the pole by bolts, nuts and washer as per direction of EIC.
Supply & Fixing of 240V, 120 W LED Street light luminarie complete with all accessories and equipped with IP66 Protection (Crompton Geaves-Cat no.LSTP-120-CDL-M or equivalent model of Philips/Bajaj//wipro/other equivalent make as approved by E.I.C) on existing MS Pipe/Mini Pole as per direction of E.I.C
Supply of 240V 120 W LED flood light luminarie complete with all accessories and equipped with IP66 Protection (Crompton Geaves-Cat no. LFLN-120-CDL/60-M or equivalent model of Philips/Bajaj//wipro/other equivalent make as approved by E.I.C) as per direction of E.I.C
Fixing only Floodlight fittings on top of masonary structure by 3 Nos. 10 mm dia x 87 mm long rag bolts, nuts & double washers complete either 37 mm x 10 mm MS flat support/or by other means as required [20(b)/C-3]
Fixing only Floodlight Fitting with suitable tie clamps and MS plate for mounting on Pole/Tower or similar structure[20(a)/C-3]
Supply of 240V, 60 W LED Street light luminarie complete with all accessories and equipped with IP66 Protection (Crompton Geaves-Cat no.LSTP-60-CDL-M or equivalent model of Philips/Bajaj//wipro/other equivalent make as approved by E.I.C) on existing MS Pipe/Mini Pole as per direction of E.I.C
Fixing only outdoor/street light type fluorescent light fitting or MV light fitting complete with all accessories to be fixed /projected from the wall of the building incl. making holes/providing clamping arrangement & necy. GI reducer as required. S&F 40 mm GI pipe (ISI-Medium) quality 1.5 mts. average length having suitable bend S&F necy. length of 1.5 sqmm PVC insulated single core stranded annealed copper wire and making connections as required and mending good damages to wall incl. painting etc. [18/C-3]
S & F GI waterproof type looping cable box size 200x150x100 mmm deep having 4 mm thick comprising of one 250V 15A kit-kat fuse unit, one NL on porcelain insulator, one compression type brass cable gland for upto 2 core 16 sqmm PVC/A cable and having lined with rubber gasketted GI top cover with brass machine screws etc., earthing terminal with lug, on steel tubular pole near base, including S&F 40x6mm thick, MS clamps with bolts, nuts etc. including painting with anticorrosive paint [5/H-5]
Painting of Steel Tubular Pole of following lengths and 2 nos. of aluminium coats of paint over 1 coat of RO priming with ready mixed paint/primer of approved make, and brand incl. preparation of surface by sand paper/emery paper, cleaning etc. for receiving fresh coat of paint
Upto 9 mtr. long pole [4 (a)(i+ii)/ H- 2]
Painting of any steel/ iron surface with 2 nos. of aluminium coats of paint over 1 coat of RO priming with ready mixed paint/primer of approved make and brand incl. preparation of surface by sand paper/emery paper, cleaning etc. for receiving fresh coat of paint for single/double/triple arm bracket
Supply of 3 Star rated 1.5 ton capacity split Air-conditioner machine fitted with Rotary compressors suitable for Refrigerant-R410A/R-32. (Make-Hitachi -Model-ZUNOH-3100f or equivalent model of O-General//Daikin/Mitsubishi Electric).
Installation, testing & commissioning of the above-said split AC incl. Supply & fixing required Angle Iron Structure on wall & mending works as per direction of E.I.C..
Supplying, fabrication & fixing M.S platform structure made with 50 mm x 50 mm x 6 mm sizes main angle(2 nos.) of each legth-1m, 50 mm x 50 mm x 6 mm sizes supporting angle(1 nos.) of length 1.2m, 25 mm x 25 mm x 6 mm sizes horizontal cross angle(6 nos.) of each length 1.2m for making platform in respect of placement as well as easy maintenance of outdoor unit of the above-said 1 no. Hi-wall type split AC including cutting holes into the wall & grouting the same with cement concrete (1:1 ½ :3) etc. as per direction of E.I.C.
S & F 230 V, 50 HZ,15 Ltr capacity automatic Geyser(Metal body) incl. temperature control by thermo-stat,temperature indicator and fire retardant cable along with interconnecting hot & cold water metal flexible pipes (Make-Bajaj-Model : Caldia or equivalent model of Venus/AO-Smith/Equivalent as approved by EIC)
S & F Lightning Conductor Air Terminal made of 20 mm dia 1000 mm long GI pipe (ISI Medium) having five discharge prongs of 4 SWG GI (Hot Dip) wire at top duly soldered with 7/16 stranded GI (Hot Dip) wire and 85 mm dia 6 mm thick GI base plate at bottom incl. necessary holes etc. complete duly grouted on the parapet etc. in CC mortar (4:2:1) as per GS [ 14 / J2 ]
Supply & fixing GI (Hot Dip) strips 20 mm x 3 mm thick for horizontal run on the Parapet/Roof/ Wall with GI Saddles 1100 mm apart incl. mending good the damages to building works as per GS [ 9 / J-1 ]
Supply & fixing of GI (Hot Dip) strips 20 mm x 3 mm thick for vertical run on wall with GI saddles spaced not exceeding 1000 mm apart incl. mending good damages to building work as per GS [ 11(a) / J-1 ]
Making soldered joints between conductors, conductors and air terminals by 7/10 stranded GI (Hot Dip) wire or 20 mm x 3 mm thick GI (Hot Dip) wire / strip incl. supply of jointing materials & painting with 2 (two) coats of Bituminous paint [12a / J-2 ]
Making soldered joints between conductors and down pipes/ other metallic objects by 7/10 stranded GI (Hot Dip) wire including supply of necessary 4 SWG or 20 mm x 3 mm thick GI (Hot Dip) wire / strip incl. supply of jointing materials & painting with 2 (two) coats of Bituminous paint [12b / J-2 ]
Supply & Fixing of Testing Joints by 20 mm x 3 mm thick GI (Hot Dip) strip 125 mm long grouted on wall having clearance of 6 mm from wall for making connection with thimbles at the end of 7/10 SWG GI (Hot Dip) stranded Wire and 4 SWG GI (Hot Dip) wire of vertical conductor and conductor from earth electrode complete with S & F thimbles, GI bolts, nuts, check-nuts, spring washers etc. as required as per GS [ 13 / J-2 ]
Cutting cornices/ steps etc. including cutting recess in buildings etc. & supply & fixing 15 mm bore (ISI-Medium) GI pipe protection as below and mending good damages to the building works: as per GS
Length Upto 0.5 Mtr [ 4(a) / J1 ]
Length above 0.5 Mtr [ 4 (b) / J1 ]
Hiring charges for scaffolding arrangement including dismantling at the end of work and carriage, for LC installation of overhead reservoir (vertical run) as per GS [ 7 / J1 ]
Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level [ By TATA-Medium GI pipe] [2(a)/G-1].
Excavation of soil for installation of Earth Electrode and filling & ramming. (For Soft Soil) [1(a)/G-1]
Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement mortar (inside) Cl hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe. [3(a)/G-2]
Supply and laying 32 mm x 6 mm thick GI (Hot Dip) strips/tape directly in ground level from earth electrode and interconnecting all earth Electrodes surrounding lower portion of the building to form a grid structure as per direction of E.I.C
Connecting the equipments to earth busbar including S & F Solid GI (Hot Dip) wire of size as below as per GS
No.-4 SWG [5(a)(i)/G-2]
No.-6 SWG [5(a)(ii)/G-2]
No.-10 SWG [5(a)(iv)/G-2]
Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 25 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required [4(a)/G-2]
S & F of porcelain kit kat rewireable type fuse unit (Beat quality approved make) and base complete on Hard Wood Board size 600 x 300 x 25 mm fixed on wall with anchor fastener bolts.
Dismantling of existing electrical wiring, light fittings, fans, SPNDBs, PDBs, switch boards etc and clearing the site after completion of work
LIGHTING SOLUTION
RASH ELECTRICAL WORKS
EASTER CONSTRUCTION COMPANY
PARTHA SARKAR
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .