Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹23.7 LAccepted-AOC ERODE 638 002 | ERODE | TAMIL NADU | 638002 | ₹23.7 L Quoted ₹24.2 L | L1 | Accepted-AOC WORK AWARDED |
| 2 | L2₹24.5 LRejected-AOC | ₹24.5 L | L2 | Rejected-AOC SECOND LOWEST |
| 3 | L3₹24.9 LRejected-AOC NO 1 2 BIG STREET SAKKARAMALLUR VILLAGE POST ARCOT TALUK RANIPET DISTRICT 632 511 | TIRUVANNAMALAI | TAMIL NADU | 632511 | ₹24.9 L | L3 | Rejected-AOC THIRD LOWEST |
| Sl No | Description | Qty | Unit | SURESHBABU L3 | R BALAMURUGAN L2 | R SURESHMANI L1 |
|---|---|---|---|---|---|---|
| 1.00 | Renewal by Supply and erection of 315 Amps capacity dust and vermin proof cubical panel board size of 5'X 5' X 2' made up of 16 SWG CRCA sheet steel for outer body, with doors, switch supports and seperations etc., and with supply and fixing of the following interior switch with bus bar chamber complete with Bus Bar (a) 25 X 10 mm tinned cu. Flat for 3 phase , neutral and (b) 25 x 6mm tinned cu flat for earth connections with bus bar insulators complete with the following tinned Cu flat should be used between busbar and switches for interconnection
Interconnection of bus bars : (1)315A TPN switch bus bar for Interconnection 25mmX10mm copper flat. (2)125 A TPN outgoing switch disconnector fuse units 25mm X6mm tinned cu. Flat
supply and fixing of KWh meter (Submeter) & indication lamps. The panel should be fabricated as per IE rules & CEIG specification.The housing accommodate the following switches.
Incoming Switch : (1)315 A TPN Incoming switch disconnector fuse units interior only with HRC fuses double break- 1 Nos, Outgoing Switch Switches : (2) 125 A TPN outgoing switch disconnector fuse units interior only with HRC fuses double break-7 Nos.
The panel board should be painted with two coats of high quality epoxy paint over one coat of red oxide primer with superscriptions. (lettering and numbering) The above cubical panel board rest on suitable angle iron base. ( Boys Hostel, Girls Hostel Examination Room , Nursing Hostel) | 6 | Nos | 1,40,710 ₹8.4 L | 1,38,700 ₹8.3 L | 1,38,000 ₹8.3 L |
| 2.00 | Renewal by Supply and erection of 250 Amps capacity dust and vermin proof cubical panel board size of 5'X 5' X 2' made up of 16 SWG CRCA sheet steel for outer body, with doors, switch supports and seperations etc., and with supply and fixing of the following interior switch with bus bar chamber complete with Bus Bar (a)25 x 10mm tinned cu flat for Inter connections, (b) 25 x 3 mm tinned cu flat for Interconnections and earth connections with bus bar insulators complete with the following tinned Cu flat should be used between busbar and switches for interconnection.
Interconnection of bus bars : (1)250A TPN switch bus bar for Interconnection 25mmX10mm copper flat. (2)125 A TPN outgoing switch disconnector fuse units 25mm X6mm tinned cu. Flat
supply and fixing of KWh meter (Submeter) & indication lamps. The panel should be fabricated as per IE rules & CEIG specification.The housing accommodate the following switches.
Incoming Switch : (1)250 A TPN Incoming switch disconnector fuse units interior only with HRC fuses double break- 1 Nos
Outgoing Switch Switches : (2)125A A TPN Incoming switch disconnector fuse units interior only with HRC fuses double break-7Nos. The panel board should be painted with two coats of high quality epoxy paint over one coat of red oxide primer with superscriptions. (lettering and numbering) The above cubical panel board rest on suitable angle iron base. | 2 | Nos | 1,16,460 ₹2.3 L | 1,14,790 ₹2.3 L | 1,10,910 ₹2.2 L |
| 3.00 | Renewal by Supply and erection of 200 Amps capacity dust and vermin proof cubical panel board size of 5'X 5' X 2' made up of 16 SWG CRCA sheet steel for outer body, with doors, switch supports and seperations etc., and with supply and fixing of the following interior switch with bus bar chamber complete with Bus Bar (a) 25 x 10mm tinned cu flat for Inter connections, (b) 25 x 3 mm tinned cu flat for Interconnections and earth connections with bus bar insulators complete with the following tinned Cu flat should be used between busbar and switches for interconnection.
Interconnection of bus bars : (1)200A TPN switch bus bar for Interconnection 25mmX10mm copper flat. (2)125 A TPN outgoing switch disconnector fuse units 25mm X6mm tinned cu. Flat
supply and fixing of KWh meter (Submeter) & indication lamps. The panel should be fabricated as per IE rules & CEIG specification.The housing accommodate the following switches.
Incoming Switch : (1)200 A TPN Incoming switch disconnector fuse units interior only with HRC fuses double break- 1 Nos
Outgoing Switch Switches : (2)125A A TPN Incoming switch disconnector fuse units interior only with HRC fuses double break-4 Nos. (3)63A A TPN Incoming switch disconnector fuse units interior only with HRC fuses double break-3 Nos. The panel board should be painted with two coats of high quality epoxy paint over one coat of red oxide primer with superscriptions. (lettering and numbering) The above cubical panel board rest on suitable angle iron base. | 2 | Nos | 1,13,460 ₹2.3 L | 1,11,835 ₹2.2 L | 1,08,050 ₹2.2 L |
| 4.00 | Renewal by Supply and Run of 4 of 10 sq.mm. PVC insulated SC unsheathed FRLS copper conductor of 1100 V grade in suitable PVC rigd pipe on wall and ceiling with continuous earth wire connection of 10 sq.mm copper wire with painting of suitable colour. (Run off for Vertical DB's Boys Hostel) | 265 | Mtrs | 660 ₹1.7 L | 650 ₹1.7 L | 630 ₹1.7 L |
| 5.00 | Supply and fixing of Vertical type 4way TPN MCCB DB (Double Door type) in sheet steel enclosure in flush with wall and making good of the concealed portion with inter connection and earth connection. The MCCB DB and MCB’s should be with ISI mark ( Legrand (MDS) / Hager (L&T) make) Incoming: 125A 4 pole MCCB -1no , Outgoing: 63A TP MCB - 4 nos) | 18 | Nos | 34,890 ₹6.3 L | 34,390 ₹6.2 L | 34,200 ₹6.2 L |
| 6.00 | GST @ 18 % | 1 | Nos | 3,79,264 ₹3.8 L | 3,73,810 ₹3.7 L | 3,68,725 ₹3.7 L |
Tender Value
₹23.7 L
EMD Value
₹22,000
Closing Date
31 Dec 2025, 3:00 pmClosed
SUPERINTENDING ENGINEER
The Supdt. Engr., PWD. Bldg. C and M, Cle, Vellore
Renewal of Power main panel Boards LTUG Cable arrangements to the Hostel Buildings in Govt. Vellore Medical College at Vellore in Vellore District
2025_PWD_636402_1
24/VLR-CLE/25-26-3/09.12.2025
Open Tender
Electrical Works
60 days
ADUKKAMPARAI IN VELLORE DISTRICT
Please refer Tender documents.
8 documents required · 8 mandatory
₹0
₹22,000
24 Mar 2026
26 Dec 2025
31 Dec 2025
26 Dec 2025
31 Dec 2025
26 Dec 2025
Amount
Renewal by Supply and erection of 315 Amps capacity dust and vermin proof cubical panel board size of 5'X 5' X 2' made up of 16 SWG CRCA sheet steel for outer body, with doors, switch supports and seperations etc., and with supply and fixing of the following interior switch with bus bar chamber complete with Bus Bar (a) 25 X 10 mm tinned cu. Flat for 3 phase , neutral and (b) 25 x 6mm tinned cu flat for earth connections with bus bar insulators complete with the following tinned Cu flat should be used between busbar and switches for interconnection Interconnection of bus bars : (1)315A TPN switch bus bar for Interconnection 25mmX10mm copper flat. (2)125 A TPN outgoing switch disconnector fuse units 25mm X6mm tinned cu. Flat supply and fixing of KWh meter (Submeter) & indication lamps. The panel should be fabricated as per IE rules & CEIG specification.The housing accommodate the following switches. Incoming Switch : (1)315 A TPN Incoming switch disconnector fuse units interior only with HRC fuses double break- 1 Nos, Outgoing Switch Switches : (2) 125 A TPN outgoing switch disconnector fuse units interior only with HRC fuses double break-7 Nos. The panel board should be painted with two coats of high quality epoxy paint over one coat of red oxide primer with superscriptions. (lettering and numbering) The above cubical panel board rest on suitable angle iron base. ( Boys Hostel, Girls Hostel Examination Room , Nursing Hostel)
Renewal by Supply and erection of 250 Amps capacity dust and vermin proof cubical panel board size of 5'X 5' X 2' made up of 16 SWG CRCA sheet steel for outer body, with doors, switch supports and seperations etc., and with supply and fixing of the following interior switch with bus bar chamber complete with Bus Bar (a)25 x 10mm tinned cu flat for Inter connections, (b) 25 x 3 mm tinned cu flat for Interconnections and earth connections with bus bar insulators complete with the following tinned Cu flat should be used between busbar and switches for interconnection. Interconnection of bus bars : (1)250A TPN switch bus bar for Interconnection 25mmX10mm copper flat. (2)125 A TPN outgoing switch disconnector fuse units 25mm X6mm tinned cu. Flat supply and fixing of KWh meter (Submeter) & indication lamps. The panel should be fabricated as per IE rules & CEIG specification.The housing accommodate the following switches. Incoming Switch : (1)250 A TPN Incoming switch disconnector fuse units interior only with HRC fuses double break- 1 Nos Outgoing Switch Switches : (2)125A A TPN Incoming switch disconnector fuse units interior only with HRC fuses double break-7Nos. The panel board should be painted with two coats of high quality epoxy paint over one coat of red oxide primer with superscriptions. (lettering and numbering) The above cubical panel board rest on suitable angle iron base.
Renewal by Supply and erection of 200 Amps capacity dust and vermin proof cubical panel board size of 5'X 5' X 2' made up of 16 SWG CRCA sheet steel for outer body, with doors, switch supports and seperations etc., and with supply and fixing of the following interior switch with bus bar chamber complete with Bus Bar (a) 25 x 10mm tinned cu flat for Inter connections, (b) 25 x 3 mm tinned cu flat for Interconnections and earth connections with bus bar insulators complete with the following tinned Cu flat should be used between busbar and switches for interconnection. Interconnection of bus bars : (1)200A TPN switch bus bar for Interconnection 25mmX10mm copper flat. (2)125 A TPN outgoing switch disconnector fuse units 25mm X6mm tinned cu. Flat supply and fixing of KWh meter (Submeter) & indication lamps. The panel should be fabricated as per IE rules & CEIG specification.The housing accommodate the following switches. Incoming Switch : (1)200 A TPN Incoming switch disconnector fuse units interior only with HRC fuses double break- 1 Nos Outgoing Switch Switches : (2)125A A TPN Incoming switch disconnector fuse units interior only with HRC fuses double break-4 Nos. (3)63A A TPN Incoming switch disconnector fuse units interior only with HRC fuses double break-3 Nos. The panel board should be painted with two coats of high quality epoxy paint over one coat of red oxide primer with superscriptions. (lettering and numbering) The above cubical panel board rest on suitable angle iron base.
Renewal by Supply and Run of 4 of 10 sq.mm. PVC insulated SC unsheathed FRLS copper conductor of 1100 V grade in suitable PVC rigd pipe on wall and ceiling with continuous earth wire connection of 10 sq.mm copper wire with painting of suitable colour. (Run off for Vertical DB's Boys Hostel)
Supply and fixing of Vertical type 4way TPN MCCB DB (Double Door type) in sheet steel enclosure in flush with wall and making good of the concealed portion with inter connection and earth connection. The MCCB DB and MCB’s should be with ISI mark ( Legrand (MDS) / Hager (L&T) make) Incoming: 125A 4 pole MCCB -1no , Outgoing: 63A TP MCB - 4 nos)
R BALAMURUGAN (BID ID -1549085)
SURESHBABU (BID ID -1549062)
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.22 MB
Condition-Ele-Hostel-GVMCH-Adukkamparai.pdf
Tender Documents • 0.42 MB
BOQ_761583.xls
BOQ • 0.39 MB
Download all tender documents and submit your bid