| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.5 CrAccepted-AOC | ₹8.5 Cr Quoted ₹8.6 Cr | L1 | Accepted-AOC L1 |
| 2 | L2₹8.9 Cr+₹27.5 L (3.20%)Rejected-Finance | ₹8.9 Cr+₹27.5 L (3.20%) | L2 | Rejected-Finance L2 |
Tender Value
₹7.8 Cr
EMD Value
₹15.7 L
Closing Date
23 Jan 2024, 5:30 pmClosed
NAVIN KUMAR
ED - Gurgaon
Construction of new judicial courts complex Gurugram (Providing additional items for HVAC air conditioning system)
2023_HRY_337741_1
20239BCA9251 83E4 4266 BE4C 7DBB5C6F577F664BAR
Open Tender
Electrical Works
Works
350 days
Gurugram
2 documents required · 2 mandatory
₹20,000
₹15.7 L
Yes
21 Mar 2024
20 Dec 2023
24 Jan 2024
20 Dec 2023
23 Jan 2024
20 Dec 2023
Amount
PUMPS:Chilled Water Pumps:Primary Circuit:Supply, installation, testing and commissioning of end suction back pull out type centrifugal pumps for chilled water recirculation, complete with TEFC squirrel cage motors, base plate and all necessary accessories. Capacity of pump sets, net head is as given below. All the pumps mentioned below shall also be complete with vibration isolators (spring mounted), mechanical seals, gland drain connections, and shall be suitable for operation on 415 ± 10% Volts, 50 Hz, 3 Phase AC power supply. Motor shall be EFF1 type.Note: Total Head pressure given below is minimum required for the system. Actual static head shall be calculated and confirmed by the vendor on award.1000 USGPM x 20 m head. - (2W+1S) complete in all respect upto the entire satisfaction of ENgineer -in-Charge of the work.
Secondary Circuit Chilled water end suction back pull out type centrifugal pump sets with variable frequency drive, dedicated logic controller, differential pressure sensor /transmitters of approved make. Complete with all accessories, making it ready for commissioning on site (including coupling, base plate etc.). Motor shall be EFF1 type.Note: Total Head pressure given below is minimum required for the system. Actual static head shall be calculated and confirmed by the vendor on award.1000 USGPM x 30 m head. - (2W+1S) complete in all respect upto the entire satisfaction of ENgineer -in-Charge of the work.
Condenser Water Pump:Supply, installation, testing and commissioning of end suction back pull out type centrifugal pumps for condenser water recirculation, complete with TEFC squirrel cage motors, base plate and all necessary accessories. Capacity of pump sets, net head is as given below. All the pumps mentioned below shall also be complete with vibration isolators (spring mounted), mechanical seals, gland drain connections, and shall be suitable for operation on 415 ± 10% Volts, 50 Hz, 3 Phase AC power supply. Motor shall be EFF1 type.Note: Total Head pressure given below is minimum required for the system. Actual static head shall be calculated and confirmed by the vendor on award.1500 USGPM x 25 m head. ( 2W+1S) complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work
COOLING TOWERS: Supply, installation, testing and commissioning of FRP induced draught type cooling towers each complete with FRP basin having and auxiliary rectangular suction tank at the bottom. The basin shall be complete with connections for drain, overflow, makeup water, quick fill and float valve, plus hot dipped galvanised suction strainer FRP body, of sufficient strength to with stand wind velocities upto 60 m/s, vibrations and earth quakes, fan and motor assembly conforming to IP-55, protection for outdoor operation fill media of honeycomb design arranged in the suitable pattern for ease of replacement, distribution pipes consisting of PVC sprinkler pipes mounted on top of the main supply standby, sprinkler head mounted on ball bearings designed to take both radial and vertical thrust overflow pipe, ladder, vibration isolation pads complete as per specifications and drawing. Motor shall be EFF1 type.coling tower should be CTI approved.cooling tower should be twin cell minimum.18,89,968 Kcal per hr / Flow Rate - 1500 USGPM # CDW In / Out - 98*F / 88 *F & Ambient Design WB - 83*F ,approach of cooling tower should be minimum 5. complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work.
HOT WATER GENERATOR: Supply, installation, testing and commissioning of Electrical Hot Water generator of vertical/ horizontal construction equipped with sufficient number of flanges and electrical immersion heaters. The pressure vessel shall be constructed as per ASME standards and insulated on all sides with 100 mm thick fibreglass. The hot water generator shall be equipped with all automatic and safety controls such as manual reset high temperature water outlet, step controller and recycling relay, ON-OFF switch, thermostats, pilot light, ‘ON’ status of individual banks, low water cut off all as per manufacturers recommendations. All basic controls and terminal shall be located in an internal control cabinet, factory wired and tested. The hot water generator shall be suitable for 415 ± 10% volts, 50 cycles, 3 phase power supply. The entire hot water generator and control cabinet shall be factory assembled on common base and tested, requiring only connection to services.Inlet Water Temperature 50 °COutlet Water Temperature 55 °C200 KW Hot Water Generator as described above complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work.
Supply, installation, testing and commissioning of Electrical Hot Water generator Bms Interface Card For Hot Water Generator complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work.
Air seperator for chilled water systemSupply, installation, testing and commissioning of automatic air seperator system suitable for above system. Air Separator to remove dissolved air/gases or micro bubbles from closed or open hydronic, HVAC, boiler other water / fluid systems by separating undissolved impurities as well of M.S. construction, with flanged connections, the air separator is provided with a high capacity automatic air vent at the top. For chilled water application, it should be insulated with 50 mm thick insulation to the specifications and cladded with 26G Aluminum cladding complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work.
Floor Mounted Air handling Units With EC Fans Supply, installation, testing and commissioning of factory fabricated Double Skinned Chilled Water Air-handling unit horizontal type fabricated out of extruded aluminium section with 0.8mm pre-coated Galvanised steel sheet outside & 0.8 mm plain Galvanised steel sheet inside with EC plug fans for operation on 415 volts ± 10%, 50 Hz ± 5% AC supply,suitable Row cooling coil made of Aluminium finned Copper tube with coil section, space provision for EAC Filters , BMS Connectivity polished stainless steel drain panmade out of 22 G sheet duly insulated complete withmotor and belt drive package etc. without face and bypass dampers. The AHU panels shall be insulated with 25 mm thick & 38+/-2 Kg/m³ density PU foam. The complete AHU shall conform to standard specifications. The face velocity across cooling coil shall be limited to 500 FPM maxm.The capacity of Air-handlers shall be as follows. Floor Mounted AHUs 9,500 cfm 50 mm St. Pr. complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work.
Supply, installation, testing and commissioning of Water Cooled Ductable Units with Single phase motor & Direct Driven Fans. The Cooling Coils Shall be 4 row of following capacity complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work. 2000 cfm capacity 4 row coil cooling -25 mm St. Pr.
1400 cfm capacity 4 row coil cooling -25 mm St. Pr.
1100 cfm capacity 4 row coil cooling -25 mm St. Pr.
FAN COIL UNITS:Supply, installation, testing and commissioning of ceiling mounted type horizontal fan coil units complete with finned coil, fan section with motor, drain pans, air filters, filter box, as per specifications and drawings (3 Row Deep) 1.0 TR nominal capacity (3 Row Deep) complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work.
InLine Fans: Toilet Ventilation Supply, installation, testing, commissioning of inline fan complete as per specification and drawing. complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work. 650 cfm 12mm Static
500 cfm 12mm static
350 cfm 12mm Static
300 cfm 10 mm static
250 cfm 10mm static
150 cfm 10 mm static
Low Sound Ceiling Mounted Diffuser type Exhaust fan for Retiring Room's Toilet Exhuast Supplying, installing, testing & commissioning of imported ceiling mounted diffuser type exhaust fan with non return flap to prevent back flow. The Fan body shall be made up of high impact ABS plastic. Motor shall be capacitor operated with thermal switch. Front Diffuser type cover should be easily removable for Cleaning. Sound Pressure Level at 3m Meter distance should not be more than 44 DB(A). 100 cfm & 7mm Static complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work.
Supplying, fixing, testing and commissioning of condenser water pipes of following sizes of MS 'C' class along with necessary clamps, vibration isolators and fittings such as bends,tees etc.but excluding valves, strainers, gauges etc. adequately supported on rigid supports duly painted/buried in ground excavation and refilling etc. as per specification and as required complete in all respect. Note:-The Pipes size 150mm & below shall be M.S. 'C' class as per IS : 1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm dia. And from minimum 7mm thick MS sheet for pipes of 400 mm dia and above. complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work. 400mm Dia 7mm thick MS pipe
250 mm dia MS pipes (Minimum 6.35 mm thickness)
100 mm dia MS pipes
Condenser Water - Valves / Strainers / etc Providing and fixing in position the following butterfly valves (PN-16). - Valves 200 mm onwards gear operated type. complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work. 350 mm dia.
250 mm dia
250 mm dia - motorised actuator for chiller
200 mm dia - motorised actuator for cooling tower
150mm dia
125mm dia
80mm dia
50 mm dia
40 mm dia
Providing and fixing in position the following balancing valves :-250 mm dia for chiller complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work.
Providing and fixing in position the following dual plate non return valves :-250 mm complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work.
Providing and fixing in position the following suction guide250 mm complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work.
Providing and fixing in position the following flexible connectors :-250 mm complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work
Providing and fixing in position the following pot strainers :-350 mm complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work.
Supplying, laying/fixing, testing and commisioning of Insulated chilled water piping inside & Outside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 kg/m3 desity, thermal coductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation. Insulation shall be mechanically protected with two layers (07 mil thick each layer) of green building compliance lagcoating and Glass Cloth. as required complete in all respect. Note: The pipe of sizes 150 mm and below shall be M.S. 'C' class as per IS:1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick MS sheet for pipes upto 350mm dia and from minimum 7 mm thick MS sheet for pipes of 400mm dia and above300 mm dia MS pipes. 350 mm Dia(32 mm thick insulation with lagcoat) complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work.
Chilled Water / Condensate Drain Piping:Supplying, laying/fixing, testing and commisioning of following nominal sizes of chilled water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 kg/m3 desity, thermal coductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive complete including repairing of damage to building etc. as per specifications and as required complete in all respect. Note: The pipe of sizes 150 mm and below shall be M.S. 'C' class as per IS:1239 and pipes size above 150mm shall be welded black steel pipe heavy class as per IS: 3589, from minimum 6.35 mm thick MS sheet for pipes upto 350mm dia and from minimum 7 mm thick MS sheet for pipes of 400mm dia and above complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work. 300 mm dia MS pipes (32 mm thick insulation)
250 mm dia MS pipes (32 mm thick insulation)
200 mm dia MS pipes(32 mm thick insulation)
150 mm dia MS pipes (32 mm thick insulation)
125 mm dia MS pipes (32 mm thick insulation)
100 mm dia MS pipes (32 mm thick insulation)
80 mm dia MS pipes (32 mm thick insulation)
65 mm dia MS pipes (32 mm thick insulation)
50 mm dia MS pipes (32 mm thick insulation)
40 mm dia MS pipes (32 mm thick insulation)
32 mm dia MS pipes (19 mm thick insulation)
25 mm dia MS pipes (19 mm thick insulation)
Chilled Water - Valves / Strainers / etc ( All Valves shall be insulated similar to pipes as specified below )Providing and fixing in position the following butterfly valves. ( PN - 16). Valves 200 mm onwards gear operated type complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work. 250 mm dia
200 mm dia
200 mm dia - motorised actuator
150 mm dia
125 mm dia
100 mm dia
65mm dia
80 mm dia
50 mm dia
40 mm dia
32mm dia Ball valve
25mm dia Ball valve
Providing and fixing in position the following balancing valves as per specifications: 200 mm dia complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work
Providing and fixing in position the following dual plate non return valves:-200 mm dia complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work.
Providing and fixing in position the following suction guide:-200 mm dia complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work
Providing and fixing in position the following flexible connectors :-200 mm complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work.
Providing and fixing in position industrial type pressure gauges with gun metal/brass valves complete as required complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work.
Providing and fixing in position the mercury in glass industrial type thermometers complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work.
Controls - PIBCV Valves for AHUs & FCUs:Supplying, installing, testing & commissioning of PIBCV valve along with digital thermostat including necessary control wiring to maintain the inside design condition as required. The size of the valves are as follows: complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work. 50 mm dia
80 mm dia
65mm dia
40mm dia
32mm dia
25mm dia
20mm dia
Supply, installation, testing and commissioning of Y - STRAINER of Ductile CI Body flanged ends with stainless steel strainer for chilled / hot water circulation including insulation as specified complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work '80mm Dia
65mm Dia
50mm Dia
40mm Dia
32mm Dia
25mm Dia
Supply & installation of thermowells with Ball valve on all supply and retuen chilled water pipe for Air handling Units as a provision to install BTU meters complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work.
Expansion Tank: 'Supplying, installing ,testing & commissioning of HDPE horizontal/vertical Sintex water storage expantion tank including making holes in the tank of inlet, overflow, drains, fire inlet connection and vent pipes, drain valve, Float valve, duly insulated as per the specifications.1000 Litres complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work.
Supply, Installation, Testing and Commisioning of following thickness duly laminated alumnium foil of matt finish closed cell nitrile rubber ('class O' ) insulation on existing duct after applying suitable adhesive for nitrile rubber. The joints shall be sealed with 50mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required 19mm complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work.
Supplying, installation,balancing and commissioning of machine fabricated GSS sheet metal rectangular ducting as per SMACNA Standrads of following Guages complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work. 24 Gauge GSS Duct
22 Gauge GSS Duct
20 Gauge GSS Duct
18 Gauge GSS Duct
Supply Air Grills: Supplying, installing, testing and balancing of supply air grills of various sizes. Each grill shall have be with fixed horizontal front bar at 15 Dig. Deflection louvers, air distribution grid for staightening the air flow through the collar and register and removable key-operated volume control dampers..Powder Coated linear Aluminium grilles with volume control damper complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work.
Supply Air Diffuser Supplying, installing, testing and balancing of square supply air diffusers, air distribution grid for straightening the air flow through the collar and register and removable key-operated volume control dampers. Complete as per specification and drawingPowder Coated Aluminium square diffuser with volume control damper complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work.
Return Air Grills:Supplying, installing, testing and balancing of return air grilles without volume control dampers of various sizes. Each grill shall have be with fixed horizontal front bar at 15 Dig. deflection lovours, register Similar to supply air grilles complete as per specification and drawing.Powder Coated linear Aluminium grilles without volume control damper complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work.
Return Air DiffuserSupplying, installing, testing and balancing of square return air diffusers, air distribution grid for straightening the air flow through the collar and register and removable key-operated volume control dampers. Powder Coated Aluminium square diffuser with volume control damper complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work.
Fresh Air Louvers:'Supplying, installing and testing of fresh air GI intake louvers with bird screen complete as per specification & drawings Fresh Air Louver complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work.
Supply and application of 50mm thick fire retarded 24 kg density expanded polystyrene under deck insulation in roof slab complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work.
Supply, installation, testing & commissioning of 24 gauge Plenums for Above Diffusers complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work.
Supply, installation, testing & commissioning of thermal insulated flexible duct of following sizes duly supported at regular interval as per site requirement etc. complete as required as per specifications. 300 mm Dia with Spigot and other accessories complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work.
Supplying, Fixing,testing and commissioning of fire dampers insupply air duct/main branch and return air path as and where required of required sizes i/c control wiring. Dampers shall be of at least 90 minutes rating certified by CBRI Roorkee as per UL-555/1995. The damper shal be made of GI with 16 gauge Frame and 16g Blade Fire Damper shall be without extended Sleeve and 150mm deep. Actuator for Fire damper complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work.
Supply, installation, testing and commissioning of GI volume control duct damper of G.I. Sheet with Linkages Quadrants etc. -It should have 20G Blade and 20 gauge Frame complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work.
POWER & CONTROL CABLINGSupply and erection of under ground cable, loose in existing pipe or trenches complete with necessary connections complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work. 300 Sq. mm 3.5 Core Cable .
16 Sq. mm 3 Core Cable .
6 Sq. mm 3 Core Cable .
4 c 16 sqmm Al Cable
4 c 25 sqmm Al Cable
Control Cabling ( PVC insulated & PVC sheathed, armoured, Copper Conductor of 1.1 KV grade on existing cable trays).'For following Sizes' complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work. 3C X 1.5 Sq.mm
4C X 1.5 Sq.mm
Supply and installtion of Stranded Annealed Bare Copper Conductor /950° Mica Tape Wrapped/Cross Linkable Zero Halogen Insulation/Cores Laid up together/Fibre Glass Tape Wrapped/Zero Halogen Inner Sheathed/GI Wire Strip Armoured/ Zero Halogen Outersheathed Fire Survival Cables 6 Sq. mm 3 Core Cable complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work.
Axial Fans for Basment Ventilation Fresh Air Basement Ventilation Supplying, installing, testing and commissioning of Normal/smoke extract fans as per specifications. Fan shall be direct driven Vane axial fan complete with Fan & motor assembly .Motors shall be "F" Class insulation IE3 suitable for 415+10% volts, 50 cycles , 3 phase AC supply and static pressure shall be as indicated.The fan shall be equipped with mounting bracket.Fan shall be with flexible fire proof flexibel connection at inlet and outlet.Fan shall be AMCA certified for Air and sound performance.Fan capacity based on static pressure which shall be given below complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work. (i) 34000 CFM 30mm STATIC for Basement 2 Fresh air
31000 CFM 30mm STATIC for Basement 1 Fresh Air
24000 CFM 30mm STATIC for HVAC Plant Room Fresh Air
Axial Fans for Basment Ventilation Exhaust Air Supplying, installing, testing and commissioning of Normal/smoke extract fans as per specifications. Fan shall be direct driven Vane axial fan.The complete Fan & motor assembly shall be suitable for smoke exhaust application & rated for 250 Deg C for minimum 2 hour operation (as per EN12101-3: 2002). Motors shall be smoke spill "H" class insulation (IE3) suitable for 415+10% volts, 50 cycles , 3 phase AC supply and static pressure shall be as indicated.The fan shall be equipped with mounting bracket.Fan shall be with flexible fire proof flexibel connection at inlet and outlet if required.Fan shall be AMCA certified for Air and sound performance.Fan capacity based on static pressure which shall be given below complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work. (i) 34000 CFM 30mm STATIC for Basement 2 Fresh air
31000 CFM 30mm STATIC for Basement 1 Fresh Air
24000 CFM 30mm STATIC for HVAC Plant Room Fresh Air
17000 CFM 25MM STATIC for Lift well Presurrisation
34000 CFM 25MM STATIC for Lift well Presurrisation
36500 CFM 25MM STATIC for Lift well Presurrisation
Supply, installation, testing and commissioning of Variable Freqency Drive of IP-20 rating to be installed in the space provided in the dedicated panels complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work. 7.5 Kw For Airhandling Units & Axial Fans
11 Kw For Axial Fans
Supply, installation, balancing and commissioning of CO Sensor having Measuring range : 0-300 PPM, Sensing element : Electrochemical Diffusion, Measuring Gas: Carbon Monoxide Gas + Enhanced CO+ radicals Detection. Sensor element (cell):- Electrochemical Diffusion, Electrolyte type Gel based Gold plated Plug-in type Sensor transmitter. Connection: - Two wire sensor (for 4-20mA) and three wire for 2-10 VDC, Response time T90:- ≤ 50 Sec. Protection Class: IP 44 Stability & resolution: - ± 3 ppm Sensor life expectancy:- ≥ 5 years Calibration Interval: 1 Year. Sensor Coverage Area: - 700 m2 to 750m2, ideal condition. Humidity non-condensing : 15-90% RH Working temperature :- -10°C to 50°C Power supply:- 18 - 28 VDC ( Overload protected) Analog output signal :- 4-20 mA or 2-10 VDC complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work.
Supply, installation, balancing and commissioning of Main Centralized CO Gas Monitoring Master PLC HMI Control Display Alarm Panel having • 4x Analog input (4-20mA from Sensor) • 6x Digital output (potential-free relay contacts) • 8x Digital Input • 2x Analog Output • Modbus RS-485 output connect to Salave Panel • HMI 7 inch display with user-friendly Touch Screen Keypad • Operating voltage 220 VAC • Panel isolation using MCB & Fuse & Alarm Hooter (95dB) Audio Visual Alarm. • Rising / Falling alarm facility to trigger the relay for alarm hooter and Fire detection system • Housed in wall mount Rittal Metal Enclosure • Fully pre-programmed as per global standard and as per customer demand complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work.
Supply, installation, balancing and commissioning of Slave CO Gas Monitoring Master PLC HMI Control Display Alarm Panel that work with main panel having • 4x Analog input (4-20mA from Sensor) • 4x Analouge output (potential-free relay contacts)• Modbus RS-485 output connect to Salave Panel • HMI 7 inch display with user-friendly Touch Screen Keypad • Operating voltage 220 VAC • Rising / Falling alarm facility to trigger the relay for alarm hooter and Fire detection system • Housed in wall mount Rittal Metal Enclosure complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work.
Supply and Laying of 2 Core X 1 sqmm unarmoured copper cable for slave panel to sensors communication complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work.
Supply and laying of 3 Core X 1 sqmm unarmoured copper cable for master panel to slave panel communication complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work.
Supplying and fixing of 20mm of medium class MS conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required complete in all respect upto the entire satisfaction of Engineer -in-Charge of the work.
HILLTOP REF ENGINEERS PRIVATE LIMITED
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .