Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹3.8 CrAccepted-AOC KARNATAKA | RAICHUR | KARNATAKA | 584123 | ₹3.8 Cr | L1 | Accepted-AOC Being L1 |
| 2 | L2₹4.4 Cr+₹62 L (16.4%)Rejected-Finance | ₹4.4 Cr+₹62 L (16.4%) | L2 | Rejected-Finance Being L2 |
| 3 | L3₹4.6 Cr+₹79.2 L (20.9%)Rejected-Finance | ₹4.6 Cr+₹79.2 L (20.9%) | L3 | Rejected-Finance Being L3 |
Tender Value
₹3.5 Cr
EMD Value
₹4.2 L
Closing Date
15 Jan 2019, 6:00 pmClosed
CE AF UDHAMPUR ZONE
CE AF UDHAMPUR ZONE
PROVN OF MTRS COMPLEX AT AF STN LEH
2017_MES_113018_1
CEAFU-34/2016-17
Open Tender
Civil Works
Lump-sum
610 days
LEH
Please refer Tender documents.
9 documents required · 9 mandatory
₹2,000
GE (P) AF LEH
₹4.2 L
Yes
27 Feb 2020
4 Oct 2018
17 Jan 2019
4 Oct 2018
15 Jan 2019
6 Dec 2018
11 Oct 2018 - 13 Oct 2018
Amount
SCHEDULE 'A' PART-I (SECTION-I) BLDG WORK
SCHEDULE 'A' PART-I (SECTION-II) Design, supply , Fabrication & Erection of Pre Engineered steel structure for hangar including necessary foundation & civil works alongwith side cladding, roofing, flooring including Ramp, Doors, windows complete, including all surface finishes, complete work as per following list of drgs (Arch & Schedule of finishes) :- (a) CEAF/AR-569/2018 Sheet No. 1R/3 to 3R/3. (b) CEAF/SF-569/2018 Sheet No. 1R/1 (c) CEAF/EM-569/2018 Sheet No. 1/1. (Note : Drawings for internal electrificationand internal water supply are for guidance and work details are as per BOQ attached seperately).
Note :- Rates quoted by the contractor shall also deem to be included the cost of the following :- (i) Design of PEB structure Hangar portion along with structural system for hangar door from PEB approved firm/vender as listed in particular specifications along with vetting of design/drawing from IIT . (ii) Design of combined footing of hangar column with annexe column footing. (iii) Arch drgs provided by the department will form part of contract however structural drawings for hangar provided by contractor, which will be vetted by IIT. (iv) The structural steel members shall be designed as specified here in before and in particular specifications.
(v) The electro mechanical power operated , telescopic door system for Rear & front doors for the hangar, shall be designed as specified in particular specifications. (vi) The design for structural system for the Hangar door will also be vetted by the same organisation vetting the steel Hangar Design.
Total amount of Sch 'A' part-II (Internal water supply)
Total amount of Sch 'A' part-III ( Plumbing Work)
Total amount of Sch 'A' part-IV (Section-I) (Internal Electrification Works)
Total amount of Sch 'A' part-IV (Section-II) (Internal Electrification Works)Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only
Industrial highbay luminaire LED type of 100 watt including fixing arrangements complete all as specified and as directed .
Integrated batten T5 of 18/20Watt, 4 FT, white, indoor decorative PVC extruded T5 LED batten integrated type complete all as specified and as directed .
Lamp holder insulated body with back plate ISI marked for batten fittings including LED lamp 9 Watt complete all as specified and as directed .
Surface mounted LED luminare for mirror lighting 10 watt Complete with lamp including connecting electricaly to ceiling rose using cord flexible 3 core PVC insulated over all sheathed with flexible copper conductor of size 0.50 sqmm complete all as specified and directed.
LED Street light of 20 Watt , IP66 powder coated pressure die cast aluminium compact high power LED street light with heat resistant toughened glass including street light bracket made out of 40mm bore GI pipe light grade 1.2 metre long ,bent to shape, with all necessary fittings i.e nuts,bolts, two numbers (02 Nos.) clamps made out of flat iron 50X6mm complete all as specified and as directed .
Bulk head luminare LED type surface mounted comprising of high brightness LEDs of 10 Watt complete all as specified and as directed .
Aviation yellow painted die-cast aluminium alloy housing, red coloured polycarbonate dome LED 9 Watt complete with fixing arrangement and all accessories complete all as specified and directed.
Heavy duty exhaust fan copper wound (as per BEE recommendation) 380mm sweep single phase 230 volts 50 Hz AC supply totally enclosed heavy duty motor with die cast aluminium rotor mounted on two ball bearings with louvers, connecting electrically using 3 core 0.75 Sq mm PVC insulated flexible copper conductor cable over all sheathed complete all as specified and directed.
Heavy duty exhaust fan copper wound (as per BEE recommendation) 300mm sweep single phase 230 volts 50 Hz AC supply totally enclosed heavy duty motor with die cast alumn rotor mounted on two ball bearings with louvers , connecting electrically using 3 core 0.75 Sq mm PVC insulated flexible copper conductor cable over all sheathed complete all as specified and directed.
Bus bar chambers of size 600X 450 mm iron clad with 4 Nos 200 Amp rated copper bus bar mounted on porcelain insulators fixed flush on wall complete all as specified and directed.
MCB TPN 63 Amps 10 KA rupturing capacity ISI marked complete all as specified and directed.
MCB single pole and neutral 240 volts 16 to 32 amps,with rupturing capacity 10 KA, ISI Marked complete all as specified and directed.
MCB single pole 240 volts 16 to 32 amps,with rupturing capacity 10 KA, ISI Marked complete all as specified and directed.
MCB single pole 240 volts 06 - 16 amps, with rupturing capacity 10 KA, ISI Marked complete all as specified and directed.
Distribution board TPN 100Amps MCCB DBs for MCB iron clad, double door with IP-43 1K-09 protection suitable for MCCB as incommer and MCB TP as outgoing 415 Volts 3 phase 50 c/s 4 way, complete with appropriate size copper bus bar and neutral link complete with one MCCB 100 Amp 4 pole 415 Volts 100 Amps rating with rupturing capacity 16 KA of the same make as of distribution board and including fixing DB complete all as specified and directed.
Total amount of Sch 'A' part-V (RAMP AND HARD STANDING WORKS)
Total amount of Sch 'A' part-VI (Lightning Protection Work)
Total amount of Sch 'A' part-VII (Sec-I) (Sewage Disposal Works)
Total amount of Sch 'A' part-VII (Section-II) (Sewage Disposal Works) Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only
Supply and instalation of Bio-digester tank of size 2.4 X1.25 X1 m specifically designed double walled FRP with outer wall thickness 3mm and inner wall thickness 2mm and double wall of 100mm insulation filled between two FRP walls with liquid poly urethane foam of 150mm with two partition of 5mm thickness and bacteria immobization sheet and bacteria quality of 40% of the volume of tank (tank volume 3 metre cube) alongwith (i) heating element 100watts-02 Nos (ii) Sensor and thermostat-01 No NOTE:-Contractor shall procure Biodigester tank before 03 Months of physical completion.If the contractor procure the same before the time mentioned,no payment will be allowed in the RAR.
Total amount of Sch 'A' part-VIII (Section-I) (External Water Supply Works)
Sch 'A' Part-VIII Section-II (External Water Supply) Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only.
Contruction of brick masonary valve pit of size 60 x 60 x 90 cm (internal dimension) built in cement mortar 1:4 including all excavation and earth work in any type of soil and disposal of surplus soil to a distance not exceeding 50 metre including 15mm thick plastering internally in CM 1:4 and flush pointing masonry in same mortar externally as work proceeds and cement concrete in foundation PCC (1:4:8) type D-2 using 40 mm graded crushed stone aggregate , PCC coping 1:3:6 type C-1 using 20 mm graded crushed stone aggregate , mild steel sheet cover 3.15 mm thick mild steel angle iron frame, handle, locking arrangement and two coats of synthetic enamel paint over a coat of red oxide painting to steel surfaces complete all as specified and shown on drawings.
Supply and fixing of Stainless steel (Fire retardant, closed cell, chemically cross linked insulation material with thermal and Acoustic Insualation) water tank, Volume 1000 litre, 1950mm HT with stand, 1050mm diameter approximate and LID diameter 420 mm, with 38mm discharge, 38mm overflow, 25mm inlet and 50mm outlet with 20mm Air vent including complete fitting, installation and testing complete as specified and directed . cat. part No.CYL/10110/16-04 /SS of Neropure or equivalent in Nector.
Cuting the existing GI tubing of bore 80mm and inserting tee of size 80x80x50mm for taking out branch connection including connected material required for such connection such as GI nipple union socket earth work etc all as specified and directed
Total amount of Sch 'A' part-IX (Section-I) (Central air heating system Works)
Total amount of Sch 'A' part-IX (Section-II) (Central air heating system Works) Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only
Design, Supply, fixing, commissioning and testing of vertically mounted Thermic Fluid Heater (TFH) capable of delivering a heat output 50000 K Cal/Hr using HSD oil complete in all respect, including following item of work with the following parameters :- (i) Out side temp (-) 30 degree centigrade (ii) Inside temp 22 degree centigrade (iii) And also considering suitable clatimatic conditions of leh. (iv) Out of two boiler one will be working and 1 will be standby (a) Heater unit: heat exchanger, consisting of closely wound , helical, concentric coils, arranged to give adequate no of passes on flue gas side & made out of MS ERW tubes, confirming to IS 3059 Pt-I, suitable for high temperature all as per manufacturer design and of required head and capacity. (b) Pressure jet burner : suitable for light oil firing with stepless modulation mechanism all as per manufacturer design and of required head and capacity. (c) Combustion air fan with drive motor assembly all as per manufacturer design and of required head and capacity. (d) Control Panel : Dust protected pre-wired unit mounted air cooled control panel housing a burner management system , switchgear consisting of contractors, overload relays, fuses and MCB etc.all as per manufacturer design and of required capacity. (e) Circulating Pumps : Centrifugal Thermic fluid circulating pumps suitable for heigh temp operation, coupled with electric motor drive, mounted on common base frame all as per manufacturer design and of required head and capacity.
(f) DE Tank : Derator cum expansion tank consisting of expansion, derator and buffer vessels , gauge glass assembly and level switches. Nozal for inlet and outlet on derator for drain on buffer vessel and for overflow, air vent and topup on expansion vessel all as per manufacturer design and of required head and capacity. (g) Fuel pump : with drive motor assembly all as per manufacturer design and of required head and capacity. (h) Piping work : required inside the plant room, including valves, pressure indicating instruments, insulation material, protective works etc all as per manufacturer design and of required head and capacity. (j) Oil line : with duplex filters on fuel line at the inlet of fuel pump, Y strainer on fuel line between fuel pump and burner, non return valve on fuel pump outlet and bypass line, non return valve on modulation and circulation line, fuel oil regulation valves for burner modulation, burner solenoid valve, fuel oil pressure gauge at burner inlet, fuel pressure gauge on by pass line etc all as per manufacturer design and of required head and capacity. (k) Thermic fluied line : inside the plant room with insulating material, spring loaded safety relief valves , Temp controller for stepless burner modulation on thermic fluid outlettemp of the heater, switch for burner on off cycle, burner interlocking with temp of thermic fluid at , differential pressur switch between inlet / outlet of fluid outlet all as per manufacturer design and of required head and capacity. (l) Burner programmer with matching flame sensor all as per manufacturer design.
(m) Hooter mounted on control panel for audible safety alarm all as per manufacturer design. (n) Temp indicator cum-switch for high stack temp alarm for flue gases all as per manufacturer design.Note :- Thermic fluid and thermic fluid line including lagging from plant room to work place shall be provided as separate item of work . Note :- (i) The tenderer should work out detailed of heat load calculations and technical parameters based on the building plan outside/inside parameters and design parameters as given in the tender and quote accordingly. (ii) The tenderer shall be responsible for the designe of plant to meet required parameters and should get design and approval of IIT/NIT for conditioning basis irrespective of the full load capacity given in the schedule, which is given on not less than basis. (iii) The tenderer should get the plant installed by any of the original equipment manufacturer viz Voltas/Blue star /carrier with their recommended makes of compatible components/items. (iv) In case of any change in the technical parameter considered required to provide the design conditions, the tenderer should furnish the revised technical parameters along with the tender.
Supply and Installation of Diesel(fuel) storage tank of capacity of 500 litres made out of 5mm thick mild steel sheet complete all as specified and directed
Supply and fixing Kaiflex insulation tubing of size 60mm bore and 19 mm thick including jointing, fixing material such as solvent adhesive, tape insulation self adhesive and polyshield coating, including polyglass tape and (Resin+hardner) two coats as per manufacturers recommendation complete all as specified and as directed.
Supply and fixing Kaiflex insulation tubing of size 90mm bore and 19 mm thick including jointing, fixing material such as solvent adhesive, tape insulation self adhesive and polyshield coating, including polyglass tape and (Resin+hardner) two coats as per manufacturers recommendation complete all as specified and as directed.
Supply and fixing Kaiflex insulation tubing of size 35mm bore and 19 mm thick including jointing, fixing material such as solvent adhesive, tape insulation self adhesive and polyshield coating, including polyglass tape and (Resin+hardner) two coats as per manufacturers recommendation complete all as specified and as directed.
Supply in barrels and filling of thermic fluid of capacity above 200 degree Celsius temprature as vapourisation temperature complete all as specified and as directed.
Supply ,installation and errection of chimney 10metre height as per design for 50000 kcal/hr complete all as specified and as directed.
MCB TPN 32A ,415Volts with rupturing capacity 10KA ,ISI Marked complete all as specified and as directed.
Design and installation of Thermic fluid storage tank of capacity 500Lts made out of 5mm thick MS sheet complete with supply arrangement for toping up of service tanks including control drains valves all as specified and directed.
Kaiflex insulation tubing 19mm thick of size 28mm internal dia including jointing material such as tape aluminum for self adhesive solvent adhesive etc including aluminum foil cladding complete all as specified and directed
Supply and mounting suspended/wall mounted type fan coil of 20SWG GI casing powder coated with two numbers air blowers motor driven.3 row heating coil,12mm thick pre-filter with drain pan insulated with 12 mm thick closed cell nitric insulation of 1.5 Ton capacity including inlet/outlet valves air gauge valve ,thermostatic control with all connected accessories and fittings required including internal wiring with PVC insulated flexible copper conductor cable of appropriate size complete all as directed by Engr-in-Charge
Supply and mounting suspended/wall mounted type fan coil of 20SWG GI casing powder coated with two numbers air blowers motor driven.3 row heating coil.12mm thick pre-filter with drain pan insulated with 12 mm thick closed cell nitric insulation of 2.0 Ton capacity including inlet/outlet valves air gauge valve ,thermostatic control with all connected accessories and fittings required including internal wiring with PVC insulated flexible copper conductor cable of appropriate size complete all as directed by Engr-in-Charge.
Gun-metal, globe or gate valves of 80mm dia, heavy duty, with iron wheel head, screwed both ends (ISI marked) fixed on GI / PPR(PE-AL-PE) pipes of size 50 mm dia complete all as specified and as directed by Engr-in-Charge.
Total amount of Sch 'A' part-X (Section-I) (EXTERNAL ELECTRIFICATION WORKS)
Total amount of Sch 'A' part-X (Section-II) (EXTERNAL ELECTRIFICATION WORKS) Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only
(B) Electric Starter equipment shall be comprise of the following :- (i) Maint free battery duly initially charged of suitable capacity and battery lead of aqequate capacity Make of Battery Exide/Amron/ (ii) Starter Motor (iii) Starter gearing (iv) Start/Stop push button (v) Invertor cum battery charger 500 VA capacity suitable to work on 230 volts 50 Hz Ac supply system for charging of DG set batteries to charge the set batteries externally when DG set is in off postion Make : sukam/ Exide/Schneider (vi) Alternator/dynamo of suitable capacity whiles DG set is running complete with auto cut out all as per manufacturer recommendation (e) PCC foundation for LT Panel of suitable size including 1 metre working space all around the LT Panel and 0.2 metre above and 0.3 metre below F.F.L all as per manufacturer recommendation and as directed by Engineer-in-charge.
(A) Supply, Installation, Commissioning and testing of silent type with accoustic encloser diesel engine Generating set complete with panel for automatic starting on main failure output of 128 KW/160 KVA and working temperature range (-) 30 degree Celsius to (+) 35 degree Celsius and alternator of suitable capacity and RPM coupled with each other and capable to taking 10% overload for one hour on every 12 hours with flexible coupling mounted on common base plate and anti-vibration pad on foundation as recommended by manufacturer. The DG set shall comprise of electric starter motor with batteries of 24 volts, 160 AH including suitable lead for charging with copper/brass terminals. The DG set shall have turbo charger after cooled type and electronic govering. AVR with all standard fittings, fixtures and all piping etc comprising of following :- a) Multifunctional meter for measuring DG parameters as per manufacturing Design
b) Indicator lamp with LED type 230 Volts core Gen set/Main supply ON/OFF indication and different relay position etc all as required and recommended by manufacturer. c) Bakelite fuse base carrier with HRD fuses 160 Amps 415 Volts suitable for and including knife type HBC fuse link - 08 Nos. d) All accessories should have prewired with suitable size PVC insulated copper conductor cable of appropriate size including foundation as per manufacturer recommendation. e) PCC foundation as per manufacturer's instructions / recommendations or required at site and as directed .( Cost of the same shall be deemed to be included in the lump sum cost of DG set quoted by tenderer). (Note :- The engine shall be affixed with label mention the following :- i) Name and address of the engine manufacturer. ii) Type approval certificate number. iii) Date of manufacture of engine. iv) The complete generating set inclusive control panel base frame coupling etc., shall be from the OEM and shall be assembed and tested at engine manufacturer's workshop and test certificate shall be provided by contractor).
(B) Environement i) Engine conforms to environment (protection) rule 1986. ii) Humidity upto 95% (non condensing). iii) Operating temperature range (-) 10 degree centigrade to (+) 40 degree Celsius. iv) Height above mean Sea level (MSL) 2100 feet. (C) Alternator The Alternator 128 KW/160 KVA , 3 Phase, 415 Volt, 0.8 Power Factor, 4 wire, H-class insulation, self excited, self regulated, screen protected drip proof type with two end ball bearing / roller bearing with damper winding in each pole faces as per IS 4722 or BS 2613-1970 all as specified below :- a) Time permitted to build up rated voltage < 5 seconds. b) Short circuit with stand time 10 seconds. c) Short circuit ratio 0.4. d) Overload withstand capacity minimum 150% for 15 seconds. e) Type of cooling system alternator - Air cooled system. f) Temperature rise of armature winding - 125 degree Celsius. g) Temperature rise of field winding - 125 degree Celsius h) Flow of alternator - 15 m4/min. (approximately) j) Heat rejection by alternator - 7
(D) Efficiency of Alternator :- i) at 100% MCR & rated PF - 94.0% ii) at 75% MCR & rated PF - 94.1% iii) at 50% MCR & rated PF - 93.6% (E) Diesel Engine Diesel Engine air cooled and electric start suitable to drive above alternator independently coupled directly through flexible coupling, multi cylinder four stroke, cold starting 1500 RPM industrial type as per BS-649 or IS 1601 with A1 class electronic governor integral with fuel system, providing capability for isochronous governing to regulate speed of DG set from no load to full load complete with fuel tank of capacity as per manufacturers recommendation including lowest weight to power ratio of 2.18 for engine, silencer, exhaust pipe duly insulated with asbestos rope and support and silencer muffler etc., for contineous operation and standard accessories sump pre-heater etc., all as directed and as follows :- (Note : Nine free service checks during warranty period) a) Aspiration - Turbo charged & after cooled. b) Staring system - 24 volts, electric. c) Exhaust silencer type - Residential / Hospital grade. d) Exhaust noise level (with silencer ) @ 1 M - < 75 DB (A)
(e) Recovery time in governor system (-) <8 seconds f) Max time to start from cold & attain rated speed & ready to start - 5 seconds. g) Overload capacity - 10% for 1 hour in 12 hours of operation. (F) Control panel :- The standard control panel comprising of control cubical fabricated sheet steel construction indoor type suitable for mounting accessories as given below :- Operator interface :- Threshold Warning Indication:- a) Manual start/stop (a) Low oil pressure b) Auto/remote start (b) Low engine coolant temperature c) Auto LED (c) High engine coolant temperature d) Not in Auto LED (d) Low coolant level e) Manual LED (e) Low Battery voltage f) Common shutdown LED (f) High Battery voltage g) Common warning LED (g) Battery alternator charge fault h) Exercise LED (h) Over current j) Emergency stop (local and remote) (j) Overload k) Alphanumeric screen l) Remote start input active LED m) Fault reset
G) Measurement & Instrumentation - (Engine Side) a) Oil Pressure b) Oil Temperature c) Water Temperature d) Engine Speed e) Hours Run f) Number of starts g) Battery Voltage h) Exhaust Temperature (H) Measurement & Instrumentation - 3 Phase L-L & L-N Voltage and Frequency (Alternator side) a) 3 Phase Current b) KWh c) Total KVA d) Total KW & KVAr e) PF f) Per Phase, KVAr, KW g) Per Phase KVA Shutdown Protection and indication : - (Engine side) (Alternator side) a) Low Fuel Level i) Under & Over Voltage b) High Fuel Level ii) Under & Over Frequency c) Low Oil Pressure iii) Over Current d) High Engine Coolant tenprature iv) Earth Leakage e) Failure to Crank Shutdown v) Reverse Power f) Over Crank (failure to start) vi) Reverse Var
(J) Power Transfer Function :- a) Open Transition Transfer b) Hard Closed Transition c) Soft Closed Transition (ramping) d) Transfer and Base Load (Utility) e) Generator /Mains Breaker Status Protection (K) Electric Starter Equipment - The equipment will comprise the following :- a) Maintenance free battery duly initially charged and battery lead with copper/brass terminals with 160 AH capacity. b) Starter motor c) Starter gearing d) Start / stop push button e) Invertor cum battery charger 500 VA capacity suitable to work on 230 Volts, 50 Hz, AC supply system for charging of DG set batteries externally when DG set is in off position. f) Alternator/dynamo of suitable capacity to charge the batteries while DG set is running complete with auto cut out all as per manufacturer recommendations.
(L) AMF PANEL:- Auto mains failure panel 415 Volts, 50 Hz suitable for 160 KVA DG sets made out of 16 guage steel sheet factory made cubical type floor mounted front and rear door openable doors with locking arrangement duly powder coated suitable for including the followings :- a) Microprocessor based auto transfer switch 4 pole 400 Amps 415 volts MCCB 02 Nos electronic control box for automatic switching on and off of DG set and transfer of load pre assembled and ready to use complete in all respect equipped. b) On load change over switch 4 pole, 415 volts, 50 Hz, 400 Amps in open execution for manual change over of supply of AMF panel failure.
Supply and fixing LED Flood light 80 Watt hanging type luminaire with high efficiency, exclusive innovative designed, long life versatile pressure die-cast aluminium IP65 flood light luminaire with high power LED as light source complete all as specified and directed Cat Part NoBAYBRITESAUCERHBP 80W LED 757S90DTOLTG of Havells or equivalent in make Philips/CG
(A) Supply and fixing servo controlled voltage stablizer 150 KVA (Conforming to BIS : 9815 : Part 1 : 1994 reaffirmed 2009) 3 phase, 50 Hz, Naturally Oil Cooled, Indoor/outdoor, Unbalanced Type, copper wound, Digital Display, Relay free Smooth and silent operation with first (1st ) filling of Transformer oil ( Conforming to IS 335 : 1993 reaffirmed 2005 ) having following specification :- (i) Input voltage 340V - 480V or as per ground requirements (ii) Output voltage stabilized at any designed/desired voltage 415 ± 1% (Adjustable) (iii) Rated frequency 50 Hz (iv) No distortion in wave form (v) Response time not to exceed 10 milli seconds (vi) Sensitivity (±) 1% (vii) Rate of correction 8 volt / second for single phase and 20 volt / second for phase to phase. (viii) No load losses less than 0.5% (ix) Full load losses less than 2.5 % (x) Duty cycle- continuous 24 x 7 (xi) Efficiency more than 95% (xii) Type of load 3 phase, unbalance type (xiii) Digital display voltmeter/ Ammeter (B) Protections (i) Over load/Short circuit protections (ii) High/low voltage cut off (iii) By pass arrangement in case of emergency (iv) Single phase sequence change protection
Cable Tray made out of GI sheet 3mm thick of size 150x50mm including necessary anchor bolts angle iron for supporting with wall/structure all as specified and directed.
Total amount of Sch 'A' part-XI (EOT Crane Works) Note : This schedule is not pre priced by MES and the pre priced rate indicated as "Rs. 0.00" under Col.5 signifies this fact only
Design,Supply, installation, testing and commissioning of 4 tons capacity EOT Crane, electrically operated through pendant push button station floor operated type having hoisting height of 4.80 metres approximately, double girder box type complete with and including main frame, bridge girders/box girders, end carriages, trolley with frame, crab, buffers, gears with gear boxes, shafts, rope drum, rope sheaves, wire rope, wheels, lifting hook, brakes, motors, limit switches, control panel, pendant push button station, micro speed arrangements, wiring etc. IS-3177 and IS-807.All as specified below:- i) Capacity 4 Tons (4000 Kgs) ii) Span 17 metres approximately iii) Lift 4.8 metres approximately iv) Bay Length Wall to Wall 23 metres approximately v) Hoisting Speed (Fast) 3 metres per minute approximately vi ) Hoisting Speed (Slow) 0.3 metres per minute approximately (Achieved through AC Drive) vii) CT Speed 10 metres per minute approximately viii) LT Speed 10 metres per minute approximately ix) LT Motor Twin Drive 1HP each with gear box x) CT Motor 2 HP(2 no.s) xi) Hoisting Motor of suitable size xii) Main Girder Box Type xiii) Operation Pendant Push Button from floor xiv) Class of Duty Class – II (Indoor) B) Mechanical Works : For long travel girder/ISMB 450 and rail will be 50mm square bar on both sides of long travel 23x2=46 metres approximately NOTE:-Item shall be executed as per PS Clause 45 to 47.1.1.5 on Srl Page no. 165 to 172 of CA.
Total amount of Sch'A' Part-XII ( Site clearance , excavation and earth works)
N K Gupta Builders Pvt. Ltd.
M/S MIR HILAL CONSTRUCTIONS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .