EE/BED/PWDTE
PWD Compound, Kenduadihi, Near Bhairabsthan,Bankura-722102
Vertical Extension of Emergency building (1st floor) for Male Ward of Bankura Sammilani Medical College and Hospital at Gobindanagar, Bankura-- SITC of ceiling suspended ductable type Split Air Conditioner Machine
2021_WBPWD_355422_1
WBPWDTE/EE/BED/NIQ_142/Q of 2021-22
Open Tender
ELECTRICAL WORKS ORG
Item Wise
30 days
BANKURA
Please refer Tender documents.
3 documents required · 3 mandatory
₹46,597
22 Nov 2022
10 Dec 2021
27 Dec 2021
10 Dec 2021
24 Dec 2021
10 Dec 2021
Amount
Supply & Delivery of Microprocessor based air cooled 11.0TR ceiling suspended ductable type Split Air Conditioner having nominal cooling capacity of 132000 BTU/hr. at ISI condition suitable for operation on 415V, + 5% - 50 Hz. - 3Ph AC supply. Each unit consist of 1nos. Scroll compressor with R-410A Refrigerant .(one running Condition & One Stand By Condition.) (Make: Hitachi/ Daikin/ OGeneral/ Mitshubishi)
Erection Charges for 11.0 TR Ductable Split Air Conditioner
Nitrogen flashing, Preasure testing & Commissioning Charges for 11.0 TR Ductable Split Air Conditioner
Copper Refrigeration pipe line for Liquid Line (1/2" OD hard drawn with 0.7 mm thick) withelbow, socket supports & brackets for 11.0Tr Ductable Split air Conditioner(make: Ryoku/Nippon)
Copper Refrigeration pipe line for Suction Line (7/8" OD hard drawn with 1 mm thick) with elbow, socket supports & brackets for 11.0 Tr Ductable Split air Conditioner (make: Ryoku/Nippon)
Supply & Fixing Pipe Insulation for Suction Line (7/8" OD with 9 mm thick) with supports & brackets for 11.0/5.5 Tr Concealed Split air Conditioner (make: Accroflex/Suprime)
Supply & Proper Fixing Al Foil Tape on Cu Pipe Insulation
Control Cabling from Condensing Unit to Control Panel 4 Core 1.5sq. mm. Communication Cable 11.0 Tr Ductable (Make : Polycab/KEI/Finolex)
Power Cabling from Condensing Unit to Control Panel 4 Core 2.5 sq. mm. Communication Cable 11.0 Tr Ductable Split (Make : Polycab/KEI/Finolex)
Supply & laying PVC Drain Pipe 25mm dia (Make: Suprime/Oriplast)
Supply & laying PVC Drain Pipe 32 mm dia (Make: Suprime/Oriplast)
Supplying, fabrication & fixing 3 Nos. M.S u-channel of 6 mm thick of size (75 mm x 40 mm x 40 mm) of 1m length for making Base Frame for installation of outdoor unit of 11.0/5.5 TR Ductable split AC incl. drilling 2 nos holes in each channel including cutting holes into the wall & grouting the same with cement concrete (1:1 ½ :3) etc. fabricated with 2 Nos. horizontal angle of 50 mm x 50 mm x 6 mm of 1.2m length. (Approx Weight 110 KG)
Supply & Fabrication & fixing of MS U Channel of 6 mm thick of size(75mm x 75mm x 40mm) for making Base frame for installation of Inndoor unit of 11.0 TR Ductable split AC incl. drilling 2nos.holes in each channel & proper fixing Roof trace & fabricated with 2 nos. horizontal angle of 50mm x 50 mm x 6 mm(Approx Weight 140 KG)
Supply & Fabrication & fixing of MS U Channel of 6 mm thick of size(75mm x 75mm x 40mm),8mm Full theared Rod & 6mm thick 40 mm x 40 mm Angle for making duct supports & Hangers.
Supply & fixing of fire retardant nonporous double layer flexible connection between each unit and duct as per direction of E.I.C.
S/F of aluminium Powder Coated Defuser with VCD(Make: Air Kolkata/Primier)
R/F of aluminium Powder Coated Defuser without VCD(Make: Air Kolkata/Primier)
Supply & Fabication of Sheet metal Supply ducting complete with supports Hanger etc.of the following as per direction EIC. 24 SWG ( Make: Sail/Tata)
Supply & Fabication of Sheet metal Return ducting complete with supports Hanger etc.of the following as per direction EIC. 22 SWG ( Make: Sail/Tata)
Supply & Fabication of Sheet metal Pleanum Chamer complete with sheet flange supports Hanger etc.of the following as per direction EIC. 22 SWG ( Make: Sail/Tata)
Supply & fixing of 9 mm thick Nitrile rubber thermal insulation on duct complete with all accessory as required.(Make- Supreme,K-flex.) as per direction EIC..
Supply & fixing of 9 mm thick open sheel Nitrile rubber Acoustic insulation on duct complete with all accessory as required.(Make- Supreme,K-flex.) as per direction EIC..
Supply & Fixing of 22 G GI aerofoil blades type Non Return Dampers complete with linkages, levers, fittings, supports, all accessories any other item required to make the system complete as per direction of E.I.C.
Supply & Fixing of 22 G GI aerofoil blades type Fire Control Duct Dampers complete with linkages, levers, fittings, supports, all accessories any other item required to make the system complete as per direction of E.I.C.
Scaffolding & Lifting charges of ODU & IDU UNIT
25mm Thick O Class Close cell Nitrile Rubber Underdeck Insulation fitted on Roof.Fitted with Adhesive Gum & GI Wire(Make- K Flex/Suprime)
Supply & Fixing of IDU & Duct Covered with 22 SWG ACP Board (Make:Aludecor) Coplete with linkages, levers, fittings, supports, all accessories any other item required to make the system complete as per direction of E.I.C.
Chrages for Trap door with 22 SWG ACP Board (Make:Aludecor) Coplete with linkages, levers, fittings, supports, all accessories for IDU Maintenance make with ACP Board as per direction of E.I.C.
Lyric International
S.R. REFRIGERATION AND APPLIANCES
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .