Tender Value
Refer Docs
EMD Value
₹48,600
Closing Date
26 Mar 2022, 11:00 amClosed
Office of the EE (EandM) M-2
Pkt-A, Dilshad Garden, Delhi-95
S/I/T/C of Pump set and allied works at East of Loni Road SPS.
2022_DJB_219231_8
NIT No. 18 (21-22)
Open Tender
Miscellaneous Works
Works
60 days
Loni Road SPS
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
Ac No. 50448339804
₹48,600
29 Mar 2022
19 Mar 2022
26 Mar 2022
19 Mar 2022
26 Mar 2022
19 Mar 2022
Supply of Horizontal Split casing pump for sewage water applications having discharge 380 m3/ hr, head 40 meter with (SS316) impeller& neck ring, SS 410 Shaft & sleeve, CI body, 78% efficiency, Pump suction/delivery size 150 mm X 150 mm respectively with 132 KW, 3 phase AC, 1450 rpm, TEFC squirrel cage induction motor mounted on a common fabricated MS base frame with CI tyre/ Pin bush coupling. Make:-Pump:-M&P/KBL/Jyoti/KBL/DJB approved make. Motor- KEC/Crompton/ ABB/Jyoti/ DJB approved make.
Supply of LT panel of following specifications: 400A, 36KA FP, MCCB with Thermal Magnetic Release Based (O\C,S\C) RELEASE - ABB - 1 Nos. Spreader Links & Extended ROH for 400A,36KA FP, MCCB - ABB - 1 Nos 3-Phase Digital Multifunction Meter ,CL-1.0, 96x96sq.mm. - Conzerv / L&T - 1 Nos 3-Phase Digital Voltmeter 0-500V ,CL-1.0, 96x96sq.mm. - Conzerv / L&T - 1 Nos 3-Phasc Digital Ammeter 0-400A ,CL-1.0, 96x96sq.mm. - Conzerv / L&T - 1 Nos CT For meter Resin Cast CL-1400A/5A,15VA - AE - 3 Nos CT For meter Resin Cast CL-1400A/5A,15VA for APFC Relay - AE - 1 Nos Phase indication light LED type 220V AC - L&T - Esbee / Vaishno - 1 Set Control MCB SP 6A ,10KA ABB - 3 Nos CT Shorting Terminal - C.Well / Elmex - 4 Nos Neutral Link - Reputed - 1 - Nos. Outgoing Section 1x250A MCCB O/G Feeder 250A,25KA TP, MCCB with Thermal Magnetic Release Based (O/C,S/C) RELEASE - ABB - 1 Nos. Spreader Links & Extended ROH for 250A,25KA TP, MCCB - ABB - 1 Nos. 3x100A MCCB O/G Feeder 318 | Page Delhi Jal Board SOR ( E & M ) 2021 ? 2 2 100A,25KA TP, MCCB with Thermal Magnetic Release Based (O/C,S/C) RELEASE - ABB - 3 Nos. Spreader Links & Extended ROH for 100A,25KA TP, MCCB - ABB - 3 Nos. 6x63A MCB O/G Feeder 63A TPN MCB 10KA - ABB - 6 Nos. Terminal 63A -C.Well / Elmex - 24 Nos. 4x32A MCB O/G Feeder 32A TPN MCB 10 KA - ABB - 6 Nos. Terminal 32A -C.Well / Elmex - 16 Nos. as per S.O.R code 10.1.4
Supply, 1.1 kV grade, XLPE insulated, stranded Aluminum conductor, galvanized steel flat strip / round wire Unarmored, extruded PVC type ST2 sheathed, conforming to IS:7098 (Part-1) & IEC:60502 (Part-1) of following sizes 3 Core x 300 Sqmm S.O.R code 18.1.14
Supply, 1.1 kV grade, XLPE insulated, stranded Aluminum conductor, galvanized steel flat strip / round wire Unarmored, extruded PVC type ST2 sheathed, conforming to IS:7098 (Part-1) & IEC:60502 (Part-1) of following sizes 3 Core x 240 Sqmm S.O.R code 18.1.13
Supply of MS pipe of size 150 mm of thickness 8 mm of heavy class of make Jindal/ DJB approved
Supply of MS bend of size 150 mm, Heavy Duty.
Supply of foot valve of size 150 m m dia, heavy Duty O.E.M rates S.O.R code 4.11.1. Make :- DJB approved make.
Supply of nut bolt of good quality
Supply of rubber packing sheet. Make: Jyoti/national/any DJB approved.
CIDF swing type non return valve as per IS 5312, PN 1.6 CI 13004 , door / bronze to rubber ring / CS 410 tuing pin of 150 mm dia S.O.R code- 14.10.7. Make :- DJB approved make.
CI double flanged non rising spindle sluice valve PN 1.6 IS :14 Sub, CI / Body / viedge / bronge ring / 55410 shabt contraction & SS CISI maked manual operation S.O.R code- 4.8.1. Make :- DJB approved make.
Supply Co2 Type Fire Extinguisher capacity 4.5 Kgs completes in all respect. Make: - Life Guard/Omex/ IS mark.
Supply of electrical insulated mats of dielectric strength up to 65KV of size (1mX2mX3mm) confirming to IS 15652. Make: -Jyoti/National
Installing, testing and commissioning of pumpset and accessories as per site requirement with the help of labour, fitter, welder. Electrician etc as per satisfaction of Engineer in charge
Making of RCC foundation of size 1:2:4 concrete including providing fixing of 6 nos. foundation bolt and grouting them with the help of tools and tackles as per satisfaction of Engineer in charge
Fixing the M.S. base frame on the RCC foundation the job includes proper leveling and alignment. Installation of the pump set as per original position with proper alignment and also making of all electrical connections, fitting all valves, bends etc. in original position and testing / commissioning of the pump set on NO load & full load after commissioning of all connections.
Super System Engineers
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .