Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹34.4 LAccepted-AOC G 86 DATA RAM SECTOR 18 ROHINI NEW DELHI DELHI 110085 | NORTH WEST DELHI | DELHI | 110085 | L1 | Accepted-AOC L1 | |
| 2 | L2₹36.5 L+₹62,264 (1.73%)Rejected-Finance | L2 | Rejected-Finance Other than lowest | |
| 3 | L3₹36.9 L+₹94,260.20 (2.62%)Rejected-Finance | L3 | Rejected-Finance Other than lowest | |
| 4 | L4₹40.4 L+₹4.5 L (12.6%)Rejected-Finance WZ 576 577 NANGAL RAYA NEW DELHI 110046 | NEW DELHI | NEW DELHI | DELHI | 110046 | L4 | Rejected-Finance Other than lowest | |
| 5 | L5₹45.9 L+₹10.0 L (27.8%)Rejected-Finance | L5 | Rejected-Finance Other than lowest |
Tender Value
₹43.5 L
EMD Value
₹86,900
Closing Date
4 Aug 2022, 6:00 pmClosed
GE NORTH DELHI CANTT-10
GE NORTH DELHI CANTT-10
REPAIR MAINT OF EXTRNAL ELECTRIC SUPPLY SYSTEM INCL STREET SECURITY LIGHTS WITH CONNECTED ITEMS WORKS AT OD SHAKURBASTI AND REPAIR MAINT OF INTERNAL ELECTRIFICATION WORK INCL REPLACEMENT OF UNSV VARIOUS TYPE OF LIGHT FITTINGS AND FIXTURES SUBMAIN
2022_MES_536684_1
GE/NORTH-24/2022-23
Open Tender
Civil Works
Item Rate
270 days
GE NORTH DELHI CANTT-10
As per NIT
8 documents required · 8 mandatory
₹500
Yes
GE NORTH DELHI CANTT-10
₹86,900
Yes
16 Sept 2022
8 Jul 2022
6 Aug 2022
8 Jul 2022
4 Aug 2022
22 Jul 2022
Amount
M&L for taking down carefully window/split type Air conditioner 2/1.5 Ton capacity of any type/make from window/wall and removing front grills, air filters and cleaning, removing dust, washing and servicing with chemical wash of cooling and condenser coil and re-assembling the dismantled components and fixing to its original position complete all as specified
M&L for servicing of water cooler of any capacity, any type/make including disconnection of electric /water supply connectin and servicing with washing, removing dust and fixing its original position including electric and water connection complete
M&L for charging of refrigerant R-22 / R-410 or any other recommended refrigerant gas in 1.5/2 Ton window/split Air conditioner/ Refrigerator/ Deep Freezer/ Water Cooler any cap including detecting leakage and rectify the leakage with proper brazing and testing on full load complete
S&F in repair starting/running capacitor 55 to 80 MFD, 240 volt suitable for water cooler/window AC /split AC including connection complete
S&F in repair starting relay suitable for air conditioner 1.5/2 Ton/ Water cooler/Deep Freezer/ Refrigerator any cap complete
S&F in repair fan motor assembly of water cooler any cap of cooling capacity 40 to 80 ltr per hour including all accessories complete
M&L for replacement of fan blower motor copper wound of window type air conditioner 1.5 /2 ton capacity with same rating 220/230 volt complete all as directed
M&L for replacement of fan blower motor blade of window type air conditioner 1.5 /2 ton capacity
S&F in replacement of thermostat switch suitable for window/split air conditioner, ISI marked of any make all as specified and directed.
S&F in replacement of thermostat switch with knob suitable for water cooler, ISI marked of any make/type capacity including making electric connection complete all as specified and directed.
M&L in repair copper tubing 1/2" dia with existing gauge for suction/discharge line of split air conditioner of 1.5 Ton/2Ton capacity including high quality puf insulation complete all as specified and directed.
M&L in repair copper tubing 3/8" dia with existing gauge for suction/discharge line of split air conditioner of 1.5 Ton/2Ton capacity including high quality puf insulation complete all as specified and directed.
S&F in repair outdoor unit suitable for 1.5 Ton split AC including rotary type compressor, high EER, copper material condenser unit, eco friendly refrigerent etc with all accessories complete all as specified and directed.
S&F in repair of cromium plated brass push cock 15mm dia, ISI Marked, for water cooler complete all as specified and directed.
S&F in replacement Motor single phase, 1/5 HP capacity for split type AC 1.5/2.0 ton capacity complete all as specified and directed.
S&F in replacement hermetically sealed rotary type compressor unit of capacity 1.5/2 T for split/window type AC and charging of adequate quantity of refrigerant gas and testing on complete all as specified and directed.
All as per above but for water cooler of any capacity/make complete all as specified and directed.
S&F in repair Power Circuit Board (PCB) suitable for split/ window type AC of capacity 1.5TR / 2.0 TR with all standard features i.e. power on-off, fan cooling speed, timer, temp etc complete all as specified and directed.
S&F in repair copper condensing unit of split air conditioning cooling coil unit 1.5/2 ton of any makecomplete all as specified and directed. (Charging of refrigerant will be measured and paid separately)
S&F in replacement of front grill of window type air conditioner 1.5 ton, any make/type complete all as specified and directed.
S&F in repair indoor unit suitable for 1.5 Ton split AC with PCB, LCD with temperature remote controller, noise level not less than 50 db etc with all accessories complete all as specified and directed.
S&F in replacement of transformer of compressor 0-15 volt , 500 miliampere of 24 TR central AC plant complete all as specified and directed.
S&F in repair transformer of compressor, 0-8 volt, 500 miliampere complete of 7.5 TR package type AC plant complete all as specified and directed.
S&F in repair motorized mixing valve, actuator 3 way, 65 mm dia for chiller pump with 50 mm thick EPS insulation and 26 gauge aluminium cladding of central AC plant complete all as specified and directed.
M&L for replacement micro processor panel unit PMN single, 7-22 amps soft halt, 220 volt with display remote circuit, time relay and FRP cable complete for package type AC plant complete all as specified and directed.
S&F in repair contractor 40 Amps, 3 pole, AC-3 rating complete of central AC plant complete all as specified and directed.
S&F in repair thermal overload relays range 3 to 5 amps for chillar pump of AC plant complete all as specified and directed.
S&F in repair thermal overload relays range 9 to 15 amps for blower motor of AC plant complete all as specified and directed.
S&F in repair thermal overload relay, range 0.3 to 0.5 amps, MN-2 type complete all as specified and directed.
S&F in repair heavy duty cast iron non return valve 80mm dia flanged type with 50 mm thick EPS insulation and 26 gauge aluminium cladding complete all as specified and directed.
S&F in repair of filter drier having 10 micron outlet filter ,100 % molecular sieve to maximize water absorption suitable for R-22/R-407C refrigerant all as specified and directed
M&L in replacement of condensing cooling fan motor, 1 HP, single phase with copper winding all as specified and directed
M&L for replacement of copper condensing /cooling coil with fin complete suitable for central/package type AC plant complete all as directed
S&F in repair of PCB with digital card of central AC plant 22 TR capacity including computerized programming of digital card with showing all connected features complete.
S&F in repair humidity heaters/ winter heating heater, 3 KW, type FSH, ISI marked complete all as specified and directed.
M&L for replacement of thermostatic expansion valve (TGEX) suitable for 11 TR compressor 38 KW, R-22/R-407C, PS-46 bar complete all as specified & directed
S&F in repair digital water pressure gauge 0-150 pound, 100 mm dia complete all as specified & directed
S&F in repair brass water flow switch for 25mm dia pipe, operating pressure 10 Kgs/Cm2, in line type complete all as specified and directed.
S&F in repair fan belt V type No. B-87, ISI marked, for AHU blower complete all as specified and directed.
M&L in repair water temperature sensor PT-100 complete all as specified & directed
S&F in repair heavy duty cast iron butterfly valve 80mm dia, flanged type with 50 mm thick EPS insulation and 26 gauge aluminium cladding complete all as specified & directed
S&F in repair Low pressure control 0-39 PSI for refrigerant . Model No. LF-08-24/3A complete all as specified & directed
S&F in repair High pressure control 0-377 PSI for refrigerant . Model No. NC-250 VAC/3A complete all as specified & directed
S&F in repair digital industrial thermostate 230 volt AC, 0-30 °C tempereture complete all as specified and directed.
S&F in repair blower motor fan belt No. A-32, ISI marked complete all as specified and directed.
M&L for servicing of chiller plant 22 TR capacity including AHU with cleaning, removing dust, chemical wash of cooling and condenser coil and re-assembling the dismantled components and fixing to its original position complete all as specified
M&L for servicing of package type plant 7.5 TR capacity with cleaning, removing dust, chemical wash of cooling and condenser coil and re-assembling the dismantled components and fixing to its original position complete all as specified
M&L for filling refrigerant R-407C in 24 TR chilling unit and detecting of leakage with repair of damage cooling coil tubes with necessary welding/brazing the same complete all as specified & directed
M&L for rewinding of condensing cooling fan motor 1 HP single phase with copper winding wire of existing gauge including dismantling and refixing the same complete all as specified & directed
M&L for rewinding of fan motor 15 HP, 3 phase of AHU with copper winding wire of existing gauge including dismantling and refixing the same all as directed
M&L for rewinding of fan motor 3 HP, 3 phase of AHU with copper winding wire of existing gauge including dismantling and refixing the same all as directed
M&L for filling refrigerant R-22 in 7.5 TR AC plant unit and detecting of leakage with repair of damage cooling coil tubes with necessary welding/brazing the same complete all as specified & directed
M&L for rewinding of rotory type semi shield compressor model No. 6D/18 of voltas make for 7.5 TR package type AC plant with copper winding wire of existing gauge and dismantaling cutting the compressor with servicing and refixing the same on its origanal position complete all as specified & directed
M&L for rewinding of blower motor 3 HP, 3 phase for 7.5 TR package type AC plant with copper windng wire of existing gauge including reeplacement of bearing and complete servicing with dismantling and refixing the same on its original position complete all as specified & directed
M&L for rewinding of fan motor of exhaust fan 600 mm sweep, 370 watt, 900 RPM of outdoor unit of package type AC Plant 7.5 TR with supper enamelled copper winding wire of same gauge and testing to get existing specified speed complete all as directed
Excavation in trenches not exc 1.5 Mtr wide and n.exc 1.5 mtr in depth, getting out for electric cable complete in soft soil complete all as specified & directed
Removing surplus excavated soil to a distance n.exc 50 mtr and depositing where directed at a level n. exc 1.5 mtr above starting point complete all as specified & directed
Returning, filling in, soil obtained from excavation including spreading, levelling, watering and well ramming in layers n.exc 25cm thick complete all as specified & directed
Supply and laying sub class 'B' bricks laid dry and flat across the length of cable for protection of cable complete all as specified & directed
M & L for sand cushioning for protection of cable with screen wash river sand complete all as specified & directed
Checking & locating of fault in underground HT/LT cable of any size by cable fault locator machine complete all as directed
Labour only for taking out and relaying/ re-routing old/existing PVC/XLPE armoured aluminium conductor cable after repair complete of following sizes (Note :- Excavation & earth work, sand cushioning, bricks protection & GI pipe where required shall be measured & paid seperately) :-
Upto size 25 sqmm 2/3.5/4 Core
Size 35 sqmm to 70 Sqmm 3.5 Core
Size 95 sqmm to 150 sqmm 3.5 core
Size 185 sqmm 3.5 core and above
Dismantling & taking out HT/LT burnt cable ends of any size from transformer/LT panel/LT feeder pillar box/trenches any type/size, for repair/making suitable for reconnection to cable, providing lugs to burnt end of cables, preparing fresh terminals and reconnection, fixing the removed portion of cable with transformer/in trenches/along pole/ panel/feeder pillar box, including excavation of loop & refilling complete using old bricks and sand returning filling the excavated soil complete
M&L (in replacement) for GI tubing light grade with all necessary fittings laid in trenches/under road crossing/fixed on pole/wall/under floor including suitable mild steel FI clamps of required size complete for following sizes :-
40 mm bore
50 mm bore
80 mm bore
Supply and laying in repair cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of following size (Note :- Excavation & earth work, sand cushioning, bricks protection & GI pipe where required shall be measured & paid seperately) :-
10 Sqmm 2 core
16 sqmm 2 core
16 Sqmm 4 core
25 Sqmm 3.5 core
35 Sqmm 3.5 core
50 sqmm 3.5 core
70 sqmm 3.5 core
95 sqmm 3.5 core
120 sqmm 3.5 core
185 sqmm 3.5 core
400 sqmm 3.5 core
Making hole below the road by drilling machine or hand drill without damaging road for inserting pipe upto 80 mm dia complete all as specified and directed (Note: GI pipe shall be measured & paid separately)
Dismantling & taking out defective LT PVC/ XLPE cable from trenches including excavation and earth work, cutting and removing defective parts and supply and fixing straight through joint heat shrink kit complete including jointing material and making connection of LT cables for the following sizes :-
25 sqmm 3.5 core to 50 sqmm, 3.5 core
70 sqmm 3.5 core to 120 sqmm, 3.5 core
150 sqmm 3.5 core to 400 sqmm 3.5 core
S&F in repair of 1100 volt grade, heavy duty cable PVC insulated aluminium conductor, unarmoured, multistranded, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended complete all as directed
16 Sqmm, twin core
10 Sqmm, twin core
Cutting/ pruning of tree branches along/around over head line at places within a radius of 2 mtr from fasted conductor and removing from site and stretching the ACSR conductor complete all as directed .
Checking all incoming & outgoing connections and Mechanism, cleaning, servicing, overhauling, testing it for proper tripping system complete of 11 KV VCB of Make Crompton Greaves/AREVA/Siemens, installed at sub-station bldg, inspecting, servicing and testing all the connections of control wiring availability of proper DC supply and AC supply, cleaning of contacts, & terminals, using the blower for dusting, servicing of gears, including replacement of faulty control fuses, faulty wiring & faulty indication lamp, checking & closing of tripping system, taking out relay (over current relay and earth fault relay) from the 11 KV VCB and calibrating the relay and proper setting of relay and refixing back in existing position & testing for proper tripping/functioning system complete all as specified & directed [Note : (i) Necessary certificate for calibration of relay with setting detail shall be submitted by the contractor. (ii) Spare parts will be measured and paid separately]
S&F charging handle rod suitable for existing 11 KV VCB 630 amps capacity of complete all as directed
S&F in repair Charging Motor assembly set in existing VCB panel of existing make incl all connections & fixing arrangement and testing complete all as directed
S&F in repair Spring charging gear assembly (big size) for VCB upto 630 Amp as per existing make of VCB complete all as directed
S&F in repair Spring charging gear assembly (small size) for VCB upto 630 Amp as per existing make of VCB complete all as directed
S&F in repair power pack unit suitable for 220 volts AC input & 110 volts DC output complete with 12 volts, 7 AH sealed lead acid batteries and suitable voltmeter etc suitable for operation of HT Panel complete all as specified and directed
S&F in repair Tripping coil assembly 24 V DC for VCB 11 KV as per existing make of VCB complete all as specified and directed
S&F in repair Closing coil assembly 24 V DC for VCB 11 KV as per existing make complete all as specified and directed
S&F in repair TNC switch (Trip Neutral Close), with 2 NO + 2 NC suitable LT/ HT Panel any type/size as per existing complete all as specified and directed
S&F in repair heater, 230 Volt, as per existing wattage suitable for 11 KV HT VCB panel including electric connection complete all as specified & directed (Make - As per sample)
Disconnection of all electric connection & taking out old/defective Current Transformer (CT) from 11 KV VCB panel and Supply, fixing, installation & testing of Current transformer, indoor, single phase resin cast CTs of 100-50/5+5 amps ratio, Class 5P-10 with suitable VA burden and accuracy suitable for protection & metering incl making suitable arrangement for fixing in existing VCB panel and connection incl disconnection & taking out old/faulty current transformers (CTs) from 11 KV VCB panel complete all as specified & directed (Make-ABB/Crompton/Schneider/Siemens/Pactil/AE) Note for item No. 70 to 80 :- (i) All the instruments and T&P required for the above jobs shall be arranged by the contractor at site and cost of the deemed to be included in the above rates. (ii) The all above checking, inspection, installation & testing work shall be performed by HT expert/ engineer.
M&L for on line Dehydration of HV/ EHV grade transformer oil including filteration using automatic centrifuging machine minimum three cycles to achieve dielectric strength 50 to 60 KV breaking capacity by absorbing and abolishing all sludge particles as per BS-66-1963 including topping up with new transformer oil as required complete all as directed Note - (i) Centrifuging Machine with all T&P & testing machine of oil required for dehydration shall be arranged by the contractor. (ii) Oil required for topping up the transformer will be measured & paid separately.
M&L (in replacement) of Silica Gel (Blue colour) in breather of transformer after cleaning of breather complete all as specified and directed
M&L (in replacement) of breather of transformer of any make/capacity upto 630 KVA with exising size complete all as specified and directed
M&L (in repair) cable jointing kit for 11 KV cable for end termination cold shrink type joint with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable complete all as specified and directed of following size:-
Size 70 sqmm to 185 sqmm, Indoor type complete all as specified and directed
Size 70 sqmm to 185 sqmm, outdoor type complete all as specified and directed
M&L (in repair) cable jointing kit for 11 KV (Earthed) grade cable for straight through cold shrink type joint with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable complete all as specified & directed for size 70 sqmm to 185 sqmm
Supply & laying in trenches/through pipes/ducts or on poles XLPE armoured cable of following sizes with aluminum conductor, 11 KV `E’ complete all as specified & directed of follwing sizes (Note :-Excavation & earth work, sand cushioning, bricks protection & GI pipe where required shall be measured & paid seperately) :-
95 Sqmm 3 core complete all as specified and directed
120 Sqmm 3 core complete all as specified and directed
M&L for chequered plate 5/6mm thick of required size for cable duct cover as required at site incl cutting & welding including painting with two coats of synthetic enamel paint over a coat of red oxide primer complete all as directed
M&L for painting of steel tubular poles 9 mtr to 11 mtr length with applying two coats of aluminium paint including cross arms and clamps except embedded portion of pole in ground and concrete after removing old painted surfaces by scraping of poles complete and two coat for making colour band/strip 30 CM with synthetic enamel paint of approved/yellow & black colour up to 1.2 mtr from coping level including numbering of poles complete all as directed
M&L for painting of RCC poles 8.5 mtr to 11 mtr long with two coat of cement based paint and two coat of synthetic enamelled paint in yellow & black stip 30cm up to 1.5 mtr above the ground level including preparation of surfaces complete and painting of connected cross arms, clamps with aluminium paint all as specified and directed.
M&L for spray painting of old/existing LT/HT panel/feeder piller box any size/type with powder coated paint withsmoke grey paint in outer/inner side of complete panel after cleaning and preparing surface complete all as specified & directed
M&L for replacement of door/ MS sheet of old/ existing LT panel board any type/size with cutting, welding & bend to shape and spray painting with powder coated paint with smoke grey paint in outer/inner side over one coat of primer after complete all as specified and directed
M&L for replacement of lock assembly with key of old/ existing LT panel board any type/sizecomplete all as specified and directed
M&L for repair/ overhauling of old LT panel board of any size/type, cleaning with compressed air, tightening of all electric connections to bus bar & switchgears, replacement of wornout lugs, nut, bolts, proper connection to main earth lead, glands to be provided/replaced as required at cable entries, fixing of door front & back side with proper locking arrangement, repair to PCC foundation as required at site and spray painting with powder coated paint with smoke grey paint in outer/inner side of panel after cleaning andpreparing surface incl sign writing complete all as specified and directed
Servicing & overhauling of Air Circuit Breaker (ACB) of any capacity by taking out from existing LT panel, cleaning all parts internally and externally, checking of the proper tension of the springs mechanical mechanism, tightening of connection of moving, fixing contact, floating contacts, servicing of motor & charging system incl replacement of faulty parts/spares and re-fixing it on its original position and testing complete all as directed (Note :- Spare parts will be measured and paid separately under respective item)
Supply only following item/spares for Air Circuit Breaker (ACB) :-
Closing release of air circuit breaker
Shunt release of air circuit breaker
Under voltage release with time relay
S&F in repair 3 pole Power Contactor, MNX type of rating 32/40 amp AC3, closing coil 220 volt with auxiliary block (1 NO + 1 NC ) including electric connection in existing panel complete
M&L (in replacement) danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white with letters, figures and conventional skull and bones in signal red colour and fixed with M.S clamps, bolts and nuts of approved size for LT/HT 20 x 15 cm size complete all as directed
S&F (in replacement) following items in the existing panel / location and connection with using aluminum lugs incl making necessary alteration in panel/ door as required for proper fixing & connection complete all as specified and directed :-
MCB 4 pole 63 amps, 10 KA breaking capacity, B'' Series, 415 Volt
MCB 4 pole 100 amps, 10 KA breaking capacity, B'' Series, 415 Volt
MCCB 3 pole 63 amps, 16 KA breaking capacity, 415 Volt
MCCB 3 Pole 100 amps, 16 KA breaking capacity, 415 Volt
MCCB 3 Pole 125 amps, 25 KA breaking capacity, 415 Volt
MCCB 3 Pole 200 amps, 35 KA breaking capacity, 415 Volt
MCCB 4 Pole 200 amps, 25 KA breaking capacity, 415 Volt
MCCB 4 Pole 250 amps, 35 KA breaking capacity, 415 Volt
Volt meter (0 to 500 volts) digital type, three phase of size 96mm x 96mm
Amp meter (0 to 300 amps) digital type, three phase of size 96mm x 96mm with suitable CTs
Indicator lamp, LED type
Multifunction Meter, digital type, three phase, size 80mm x 80mm, accuracy class 1.0 for monitoring of various electric parameters such as voltage, current, wattage, frequency, power factor etc. (Make : Schneider model No EM 6436H or equivalent in L&T/Siemens) Note :- (i) MCCB should be properly fited in existing compartment and operating handle of MCCB should be proper in opening existing cover/door of compartment of LT panel board. (ii) Make of MCCB/MCB/Contactor - Schneider/ABB/L&T/Legrand)
S&F in repair off load changeover switch with sheet metal enclosure 63 Amp, 4 Pole, 415 volt incl connection complete all as specified and directed
S&F steel tubular electric pole, swaged, type 410 SP-31 (9 metre long) complete with CI base plate, bolts, nuts & screws incl 06 Nos hole on top edge for holding of D-clamp & insulators complete all as specified including the following:-
(a) Excavation in post hole not exceeding 1.5 Mtr wide & 2 Mtr deep for pole foundation & getting out in soft loose soil, returning, filling in the excavated soil after fixing the pole in foundation, ramming earth around in layers n.exc 25 cm thick and disposal of surplus soil to a distance n.exc 50 metres. (b) M&L for Providing PCC 1:3:6, type C2 (using 40 mm graded stone aggregate) in foundation 600mm x 600mm x 1500 mm (planting depth) for concrete encasing the pole upto GL © M&L for Providing PCC 1:2:4, type B2 (using 40 mm graded stone aggregate) for plinth block /Collar above GL, 300 mm high and 450 mm dia
(d) M&L for painting of pole externally with one coats of black bituminous paint (upto planting depth) and above plinth block/ concrete collar with two coats of aluminium paint over a coat of red oxide primer including preparation of surfaces including painting of 30 cm wide black bands/strip 3 Nos with synthetic enamel paint in alternate layers upto the height of 1.5 Mtr above coping level
Dismantling and taking out unsv / damaged PCC pole any size/type complete all as specified and directed
Taking down defective/ damaged ACSR conductor of any size and supply, fixing and stringing ACSR (Not less than Weasel) conductor not less than weasel including provn of binding wire etc for LT distribution line and replacement of all wornout nut bolts and washers complete all as specified and directed.
Taking down defective/ damage GI earth wire and supply, fixing and stringing of galvanised steel wire 4 mm dia for continuous earthing complete all as specified and directed
S&F (in replacement) pin/ shackle insulator of 100 mm height, 65 mm dia for 1100 volt grade porcelain vitreous white brown or green including one galvanised mild steel spindle two galvanised iron washers and one galvanised iron nut all as specified and directed.
Dismantling & taking down defective stay asembly and S&F stay assembly compring of 7/10 SWG galvanised stay stranded wire of reqd length fixed to pole with and including flat iron clamp, bolts, nuts and washers, galvanised 14mm dia, 400mm long stay bow with 16mm dia 180 cms, long stay rod with threded ends, GI nut & washers GI stay plate 230 x 230 x 6mm thick plate 2 Nos thimble, MS clamp made out of 50 x 6mm flat iron loop insulator 90mm x 140mm dia, hole 25mm porcelain complete all as specified and shown in electrical plate No 1 of SSR Part I including cost of the following:- (a) Excavation in post holes in any type of soil, returning filling and well ramming including disposal of surplus soil to distance n.exc 50mtrs from starting points. (b) PCC (1:3:6) type C2, using 40mm graded stone aggregated as in foundation.
M&L for replacement of galvanised stay strand 7/2.5 with proper tightening complete all as specified and directed
M&L for galvanised stay bow of 14mm dia including threaded end with nut complete all as specified and directed
M&L in repair for cross arms, bracing, supports, clamps and back plate, fabricated from structural steel section including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size including painting with two coats of synthetic enamel paint over a coat of red oxide primer complete all as directed after dismantling and taking out damage/rusted cross arms, bracings, supports, clamps and back plates from existing poles / pole structures complete all as directed.
S&F (in replacement) bracket for street light made out of 40 mm bore GI pipe medium grade not less than 1.2 mtr length bent to shape fixed on pole/wall with and including 50x6mm FI clamps = 02 Nos with nut bolts, washers including painting of clamps with two coats of synthetic enamel paint over a coat of red oxide primer complete
Taking down defective street light fitting any wattage from pole and repair the same including replacement of defective/ faulty LED driver and re-fixing the same incl connection complete all as directed
M&L in repair for loop junction box, outdoor type, size 30cmx20cmX15cm, made out of engineering plastic one piece moulding type, bus bar rating 63 amps 4 strips aluminium with bus bar mounting colour R, Y, B, N on DMC unbreakable insulator with cable entry main supply from bottom side and pole light connection from back side, simens grey colout, shock proof, rust proof, fire retardant, having front opening and locking arrangement with MCB SP 10 amps - 01 No, box duly fixed on the pole with flat iron clamp of size 25 mmX3mm with nuts & bolts complete all as specified and directed (Note : Cost of incoming& outgoing cable lugs & glands of suitable size deemed to be included in the quoted rate)
M&L (in replacement) for LED street/security light fittings 60 watt, made up of of pressure die cast aluminium housing with toughned glass and individual high power LEDs with secondary optics, IP 66 protection, clamp type suitable for 32-50mm dia bracket pipe, to be mounted on existing/ new GI bracket and connecting the street light fitting using 1.5 Sqmm PVC insulated copper cable complete all as directed. (Note - New GI bracket with clamp shall be measured & paid seperately)
M&L for LED Flood Light luminaire, energy saving & enviornmental friendly, long life diecast aluminium, IP65, with high power LED as light source incl necessary fixing arrangement with clamps of suitable size and connection using 1.5 Sqmm PVC insulated copper cable complete all as directed for following wattage.
M&L for replacment of double compression stainless steel gland for power cable incl electric connection complete with new lugs/ thimble complete all as directed of following sizes :-
Size 22.9 mm dia suitable for 16 sqmm 4 core LT cable
Size 28.9 mm dia suitable for 25 Sqmm 3.5/4 core LT cable
Size 32.1 mm dia suitable for 35 to 50 sqmm 3.5/4 core LT cable
Size 37.7 mm dia suitable for 70 sqmm 3.5/4 core LT cable
Size 41.7 mm dia suitable for 95 sqmm 3.5/4 core LT cable
Size 47.1 mm dia suitable for 120 sqmm 3.5/4 core LT cable
Size 51.4 mm dia suitable for 150 sqmm 3.5/4 core LT cable
Size 56.6 mm dia suitable for 185 sqmm 3.5/4 core LT cable
M&L for earthing complete with galvanised steel earth plate electrode 600x600x6mm thick directly buried in ground (earth pit not less than 2.25 m deep below ground level) with top edge of earth plate not less than 1.5m below the ground level connected to GI strip 32 x 6mm by means of bolts nuts check nuts and washers of galvanised iron at 2 points & GI pipe 15 mm bore light grade for protection of earthing wire PCC chamber 1:3:6 (type C-1) using 20mm graded stone aggregate, watering pipe 20mm bore light grade, funnel with wire mesh, 50 mm thick cover of RCC 1:2:4 type B-1 using 20mm graded stone aggregate reinforced with 8 mm MS bars at 150 mm centre to centre both ways and charcoal dust and common salt all as shown in electrical plate No. 3 of MES SSR part-I and including excavation & earth work & connecting the earthing point/equipment and testing complete all as specified and directed
M&L for earthing complete with galvanised steel earth plate electrode 600x600x6mm thick directly buried in ground (earth pit not less than 2.25 m deep below ground level) with top edge of earth plate not less than 1.5m below the ground level connected to 4mm by means of bolts nuts check nuts and washers of galvanised iron at 2 points & GI pipe 15 mm bore light grade for protection of earthing wire PCC chamber 1:3:6 (type C-1) using 20mm graded stone aggregate, watering pipe 20mm bore light grade, funnel with wire mesh, 50 mm thick cover of RCC 1:2:4 type B-1 using 20mm graded stone aggregate reinforced with 8 mm MS bars at 150 mm centre to centre both ways and charcoal dust and common salt all as shown in electrical plate No. 3 of MES SSR part-I and including excavation & earth work & connecting the earthing point/equipment and testing complete all as specified and directed
Supply of HT electric Rubber Mat sheet of size 1m x 2 m x 25 mm thick, ISI marked complete all as specified and directed
All as above but for LT 15 mm thick complete all as specified and directed
Supply only bitumen HT tape impregnated size 25 mm width complete all as specified and directed
S&F Galvanised iron nut, bolt & washer any size as required at site complete all as specified and directed
M&L for fabrication of sign board made out of heavy duty MS square pipe 40 x 40 mm for legs, MS angle iron 40x40 x5 mm thick for frame and MS sheet 3 mm thick and legs of sign board embedded in PCC (1:2:4) in 20 mm graded aggregate upto 45 cm including painting with one coat of red oxide paint and two coat of synthetic enamelled paint complete all as specified and directed
M&L for writing letters or figures (Block, Roman,italic or indian ) n exc. 30 cm hight complete all as specified and directed
S&F in repair time switch, digital type having suitable rating street light timer panel incl connection complete all as specified and directed
S&F in repair of PVC line seperator 10mm dia suitable for high wire overhead conductor complete all as specified and directed
S&F in repair PVC insulated and sheathed flexible cable 3 core Multi-stranded copper conductor size 2.5 Sqmm 1100 volt grade after taking out old unserviceable one including electric connection complete all as specified and directed
M&L for Servicing of DG set, 3 phase, 30 KVA capacity, 415 volt, 50 Hz of Make-Ashok leyland with replacing the air filter, diesel filter, super by pass filter, lubricating filter,heavy duty coolant,15W40 lubricating oil (Make-HP/castrol/Valvoline/CAT), fuel pipe with bengo bolt, hose pipe complete set and vent housing with clamp incl servicing and cleaning of radiator & alternator assembly & diesel tank as per manufacturer instructions incl testing after repair & servicing all as specified and directed (Note:- Servicing of DG set shall be valid for 6 months or 250 Hrs which is earlier)
M&L for Servicing of DG set, 3 phase, 160 KVA capacity, 415 volt, 50 Hz of Make-Ashok leyland with replacing the air filter, diesel filter, super by pass filter, lubricating filter,heavy duty coolant,15W40 lubricating oil (Make-HP/castrol/Valvoline/CAT), fuel pipe with bengo bolt, hose pipe complete set and vent housing with clamp incl servicing and cleaning of radiator & alternator assembly & diesel tank as per manufacturer instructions incl testing after repair & servicing all as specified and directed (Note:- Servicing of DG set shall be valid for 6 months or 250 Hrs which is earlier)
S&F maintenance free lead acid battery ,12 volt of following capacity :-
150 AH, 23 plates
180 AH, 25 plates
Repair of earth pit incl required exacavation, earth work and PCC work to make good damaged/disturbed surfaces of earth pit chamber & making new pit cover of RCC 1:2:4 type B-1 using 20mm graded stone aggregate reinforced and lifting handle on RCC cover with 8 mm MS bars at 150 mm centre to centre both ways incl supply & fixing of wire mesh and funnel including re-connection of earth wire/strip with panel/transformer using GI nut, bolts & washer complete all as specified & directed
S&F (in replacement) Digital Over Current Relay, single phase, 50 Hz suitable for 11 KV VCB panel, incl connection with proper setting and testing complete all as specified and directed (Make : Crompton Greaves model No CGI 14N or equivalent in L&T / Siemens)
Taking down carefully copper/aluminium point wiring (light/fan/socket or power) complete including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets etc including making good the disturbed surfaces to match with the existing complete
Taking down unserviceable main switches, DBs including MCBs, bus bars chambers etc from wall / existing main boards and removing from site complete
M&L for point wiring with single core FRLS, PVC insulated, unsheathed multi stranded copper conductor of size 1.5 sqmm alongwith 1.5 sqmm earth wire of multi strand copper conductor (with same specification) drawing through existing conduit pipe including replacement of sunk zinc coated pressed steel terminal box of 1.60mm thick with 3mm thick plastic laminated sheet top cover, brass screws, cup washers etc and making good to the disturbed surfaces to match the existing complete for the following :-
One light point controlled by one switch
One ceiling/exhaust fan point controlled by one switch
One socket outlet 5 Amps controlled by one switch on same board
One socket outlet 5 amps controlled by one switch on independent board
One bell point controlled by one bell push switch
All as per item No 133 above but wiring with 2.5sqmm copper wire and 1.5sqmm earth wire for socket out let 16 Amps on independent board
All as per item No 133 above but wiring with 4 sq mm PVC insulated multi-stranded copper conductor for industrial socket outlet 3 pin 16 / 20 Amps point and one single core 2.5 sq mm PVC insulated unsheathed copper cable as earth continuity conductor
M&L for point wiring concealed type with 1.5 Sq.mm nominal cross sectional area, single core, 1100 Volts grade, multi-stranded, PVC insulated, unsheathed FRLS copper conductor cable including continuous earth wire of size 1.5 Sqmm nominal cross sectional area, single core, 1100 Volts grade, multi-stranded, PVC insulated, unsheathed, FRLS copper conductor cable connected to common earth and earth dolly with suitable copper lugs drawing into and including rigid non-metallic PVC surface conduit of 20mm dia or higher, medium grade complete with all PVC conduit accessories, GI metal flush box of 1.60 mm thick suitable for modular/conventional switches/sockets/fan regulators with cover plates (modular/ conventional type as required), blanking plates, brass screws, cup washers etc including all cutting / chases etc in walls and making good to the disturbed surfaces to match the existing complete all as specified and directed for the followings :-
One light point controlled by one switch
One ceiling/exhaust fan point controlled by one switch
One socket outlet 5 Amps controlled by one switch on same board
One socket outlet 5 amps controlled by one switch on independent board
One bell point controlled by one bell push switch
All as per serial item No 136 above but with 2.5 Sqmm nominal cross sectional area copper conductor cable for one 16 Amps socket outlet point on independent board with 1.5 Sqmm nominal cross sectional area copper conductor cable as continuous earth wire.
All as per item No.136 above but wiring with 4 sq mm PVC insulated multi-stranded copper conductor for industrial socket outlet 3 pin 16 / 20 Amps point and one single core 2.5 sq mm PVC insulated unsheathed copper cable as earth continuity conductor
S&F Switch piano flush type 5/6 Amps single pole one way 230 Volts complete
S&F Switch piano flush type 15/16 A single pole one way 230 Volts complete
S&F Socket Outlet 2 in 1, 3 pin 5 Amps flush type 230 Volt complete
S&F Socket Outlet 2 in 1, 3/6 pin 5 and 15 Amp flush type 230 Volts complete
S/F Bell push, flush type 5 Amps 230 Volts complete
S&F electronic fan step regulator flush switch type 100/120 watt, 230 Volt complete
S&F ding dong bell, AC, 230 volts, single pole complete
S&F lamp holder, 230 volt AC, PVC / Polycarbonate type with back plate suitable for batten fitting including 9 watt LED bulb inverter type upto 4 Hrs back up 6500 K complete all as specified & directed
S&F ceiling rose, 6 Amps, 250 volts, AC with three terminals and PVC / Polycarbonate insulated body of 50 x 25mm size complete
S&F modular switch 6/10 Amps, one way, one module 240 volts complete
S&F modular socket, 3 pin 6 Amps,240 volts, 2 module complete
S&F modular switch 16 A, 1 module,240 volts complete
S&F modular socket 6/16 A, 5 pin, 2 module, 240 volts complete
S&F modular Bell push 6 Amps, one module 240 volts complete
S&F modular fan regulator, step type, 120 W, humfree, AC, 230 volts, 2 module complete
S&F sheet metal enclosure with Single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 20 Amps 'C' curve, 240 Volt complete
M&L in repair for two single core (submain) PVC insulated cable with 4 sqmm nominal cross sectional area stranded copper conductor and one single core green PVC insulated 4 sqmm stranded copper conductor earth continuity cable drawn through non metallic rigid PVC conduit 20 mm dia or higher size, concealed in wall including all conduit and fixing accessories including cutting chases & making disturbed surfaces complete
M&L in repair for two single core (submain) PVC insulated cable with 6 sqmm nominal cross sectional area stranded copper conductor and one single core green PVC insulated 6 sqmm stranded copper conductor earth continuity cable drawn through non metallic rigid PVC conduit 20 mm dia or higher size, concealed in wall including all conduit and fixing accessories including cutting chases & making disturbed surfaces complete
S&F MCB DB, single pole and neutral with 200 Amps rated bus bar, 230 volts, glazed, double door type, IP-43, including connecting all connections of wire to MCBs with proper lugs & making good to the disturbed surface complete for the following no of way :-
S&F loadline distribution box 4 way, AC, TP & neutral metal enclosure, Glazed double dooor, 415 V, AC, IP-43, concealed type with suitable bus bar, neutral link, earth link suitable for MCCB 63/100 Amps as incomer and MCB SP as out going complete all as directed
S&F MCB DP/SPN, 240 Volts, AC of breaking capacity 10 KA, 'C' curve and connections by using suitable copper lugs complete of following rating :-
S&F MCB SP, 240 Volts, AC, 6 to 32 amps, breaking capacity 10 KA, 'C' curve and connection by using suitable copper lugs complete
S&F MCCB 3 Pole, 415 volt, AC, fixed type, with breaking capacity 16 KA suitable for load line DB & connection complete of following rating :-
63 amps rating
100 amps rating
S&F in repair of switch piano, flush type, 5/6 Amp, single pole, one way, 230 volts complete all as specified & directed
S&F in repair of socket outlet 2 in 1, 3 pin, 5/6 Amp, flush type, 230 volts complete all as specified & directed
S&F in repair of switch piano flush type 15/16 Amp, single pole, one way, 230 volts complete all as specified & directed
S&F in repair of socket outlet 2 in 1, 3/6 pin 5 and 15 Amp, flush type, 230 volts complete all as specified & directed
S&F in repair of Bell Push, flush type, 6 Amp, 230 Volts complete all as specified & directed
S&F in repair electronic fan step regulator switch fiush type 120 watt, 230 Volt complete all as specified & directed
S&F in repair of modular switch 10 amps single pole one module, 230 volts complete all as specified & directed
S&F in repair of universal moudlar socket ,10 Amps, 5 pin, 2 module, 230 volts complete all as specified & directed
S&F in repair of modular switch 16/20 amps single pole one module, 230 volts complete all as specified & directed
S&F in repair of modular socket 16/20 amps, 2 module, 230 volts complete all as specified & directed
S&F in repair of modular bell push with indicator 6 amps, one module complete all as specified & directed
S&F in repair of modular fan step regulator 120 watt 2 module , 230 volts complete all as specified & directed
S&F in repair LED Bulkhead luminaire 10 watt of polycarbonate housing and enclosed with acrylic diffuser IP-65 protection incl connection complete all as specified & directed
S&F in repair LED Post top lantern luminaire with die cast aluminium spigot, lid cover and clear acrylic cover 40 watt, 5700 K with IP-65 protection incl connection complete all as specified & directed
S&F in repair wall mounted LED batten with aluminium housing and integrated electronic drive 18/20 watt fixture 4 feet provided for efficient heat dissipation with polycorbonate diffuser and integrated electronic driver and all accessories pre-wired including connecting up with twin core flat flexible copper conductor cable of suitable size complete all as specified & directed
S&F in repair surface and wall mounted LED batten 10 watt 2 feet long extruded aluminium housing provided for efficient heat dessipation with polycarbonate diffusser and integrated electronic drive, pre-wired including connecting up with twin core flat flexible copper conductor cable of suitable size complete all as specified & directed
S&F in repair wall mounting bracket decorative luminaire powder coated housing,SS finish fixture with opal glass diffuser suitable for GLS, B-22 lamp incl connection complete all as complete all as specified & directed
S&F in repair highly efficient round shape downlighter 25 watt, 240 volt, CCT 5700 K with driver suitable for ceiling cutout 225 mm dia incl connection complete all as specified & directed
S&F (in replacement) LED landscape bollard light 10 watt, 230 volt, inverted pyramid tripod type with soft 360 degree distribution, IP-65 protection, incl necessary civil work for grouting & foundation work of suitable size with PCC work complete all as specified and directed.
S&F in repair 5 W LED T5 TL fitting (1ft) attractive wall mounted type suitable for mirror fittings, all accessories pre wired including up with twin core flat flexible copper conductor cable of suitable size complete all as specified and as directed.
S&F LED Bed side reading stainless steel wall light fitting 3/5 Watts, 230 volt, AC, rectangular/round, flexible neck/Gooreneck, cool day light complete with all accessories incl connection complete all as specified & directed
S&F in repair surface/ceiling mounted LED panel type of size 2ft x 2ft, 36W, 230V, 5700K complete with driver full window glarefree opal diffuser LED panel with CRCA powder coated white housing complete with all accessories required for connection and making good the disturbed ceiling complete all as specified & directed
S&F in repair of LED linear surface/ suspended fittings, extruded aluminium body with opal polycarbonate diffuser, 38 watt, 4 ft long, CCT 6000 K incl connection complete all as specified & directed
S&F in repair LED energy efficient flood light of 30 watt, 230 volt,anti glare diffuser ,IP-65 incl connection complete all as specified & directed
S&F in repair exhaust fan 300 mm sweep, 230V, AC, steel body with louver shutter etc complete and connection from ceiling rose to fan terminal incl cutting of hole at wall for required size and making good disturbed surface and depositing old fan to store yard complete all as specified & directed
S&F in repair wall mounting fan 400 mm sweep, adjustable, plastic blade grill for protection, pull cord control for speed and oscillation on-off, ABS body incl connection and depositing old fan to store yard complete all as specified & directed
S&F in repair PVC flexible twin twisted copper conductor cable multi strand of size 0.5 sqmm nominal cross section complete all as specified & directed
S&F electronic energy meter, current rating 10-60 amps, 240 Volt, AC, single phase, 2 Wire, accuracy Class 1.0, with LCD display incl/ fitted with temper proof meter box, weather proof, transparent, made out of FR polycarbonate, dust proof, good mechanical strength conforming to IS: 14772/2000,IP-65, size not less than 260 mm x 190 mm x 120 mm incl connection and depositing old meter to MES store complete all as specified & directed
M&L for earthing with Galvanised Steel earth plate electrode 60cmx60cmx6mm thick buried directly in ground vertically at a depth not less than 2.25metre below normal ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level, earth plate surrounded from all sides by 15cm thick packed layer of charcoal dust and common salt filling in alternate layers and electrode connections by using GI wire of size 4mm dia as earthing lead (upto the body of the equipment) by means of GI bolts, nuts, check nuts and washers and thimbles and protected by light grade 40mm dia GI pipe connected to main switch board or main control board and GI pipe medium grade 20mm bore for watering and including funnel, wire mesh, RCC pit cover and PCC chamber pit with PCC (1:3:6) type C-2 using 40mm graded stone aggregate, including excavation and earth work in any type of soil, returning, filling in approved soil and disposal of surplus soil to a distance not exceeding 50m all as specified and shown in electrical plate No 5 of SSR 1991(Part-I) complete all as specified & directed
Taking down carefully electric geyser of any type and capacity by disconnecting electric and water supply connection, opening nut, bolt, washer and reassembling after cleaning and replacing defective parts and re-installing the same in original position and making necessary electric and water supply connection and testing complete all as specified and directed. (Note: Spare items shall be measured and paid seperately)
S&F geyser inner water tank 35/50Ltrs capacity steel body as per sample, duly tested complete all as specified and directed.
All as per above item but 25 Ltrs capacity complete all as specified & directed
S&F heating element capacity 1.5 KW (Round/Triangular) ISI marked suitable for geyser (as per sample) complete all as specified & directed
All as per above item but capacity 2 KW complete all as specified & directed
S&F thermostat suitable for 50/35/25 ltrs capacity geysers complete all as specified & directed
S&F Heavy duty hot water connection, SS rope threaded type with brass unions at both ends, 45cm long 15mm bore complete all as specified & directed
S&F indicator lamp, Red/Green suitable for geyser of any type/capacity (Make as per sample)
S&F geyser base plate assembly of any type(having 6 or 9 hole) any model complete all as specified & directed (Make as per sample)
S&F in replacement of outer cover MS sheet/ABS body of geysers 25 to 50 Ltrs capacity complete all as specified & directed
S&F in repair Plug top, 3 pin, 05 amps, 230 volt complete all as specified & directed .
S&F in repair Plug top, 3 pin, 15 amps, 230 volt complete all as specified & directed .
S&F in repair PVC insulated and sheathed flexible cable 3 core Multi-stranded copper conductor size 2.5 Sqmm 1100 volt grade after taking out old unserviceable one including electric connection complete all as specified and directed.
S&F in repair of precast RCC earthing pit with CI cover ISI marked including angle iron frame made out of 35x35x4mm thick for supporting the edges of pit cover as dimension shown in Electrical plate No-2 of SSR part-I complete all as specified & directed
M&L for dismantling of unsv C/Fan of any make/model/sweep, cutting and removing the old defective/burnt winding, cleaning the core of fan motor and rewinding the fan motor with super enamelled copper winding wire of same gauge with insulating material and varnishing the core assembly, drying the moisture content to get appropricate speed and re-assemble the same complete all as directed (Note :- The cost of copper winding wire is deemed to be included in the quoted rate)
All as per above item No 205 but for exhaust fan upto 300mm sweep size complete all as specified & directed
All as per above item No 205 but for exhaust fan of 380/450mm sweep size complete all as specified & directed
S&F in repair capacitor 2.5/3.15 MFD suitable for C/fan incl connection complete all as specified & directed
S&F in repair pedestal fan 500 mm sweep with strong copper wound motor for better air delievery, smooth oscillation, superior low voltage performance, heavy base for stability, 3 speed control regulator, speed not less than 1400 RPM and old to be deposited in store yard complete all as specified & directed
M&L in repair ball bearing suitable for any type/size/make of fan complete all as specified & directed
S&F in repair fan motor kit assembly of 500 mm sweep, single phase, not less than 145 watt, 230 volt, AC, 50 Hz, copper wound with blade for desert cooler complete all as specified & directed
S&F in repair plastic submersible pump suitable for desert cooler any size complete all as specified & directed
S&F desert cooler pad (set of three) made out of wood wool etc for desert cooler any size complete all as specified & directed
Schedule of Credit - Total contract sum shall be calculated after deduction of Sch of Credit amount Credit amount - 1,54,583.00
M/s Prakash Enterprises
M/s S.G. BUILDERS
Shiv Enterprises
Surjit and Sons
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .