Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹47.8 LAccepted-AOC 1 225 5 6 SADAR BAZAR DELHI CANTT 110010 | NEW DELHI | DELHI | 110010 | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹51.2 L+₹3.3 L (6.98%)Rejected-Finance RZ 212F D BLOCK RAJ NAGAR PART II PALAM COLONY NEW DELHI 110077 | SOUTH WEST | DELHI | 110077 | L2 | Rejected-Finance other than lowest | |
| 3 | L3₹58.5 L+₹10.7 L (22.3%)Rejected-Finance 3788 SHAH GANJ GB ROAD NEW DELHI 110006 | NEW DELHI | DELHI | DELHI | 110006 | L3 | Rejected-Finance other than lowest |
Tender Value
₹49 L
EMD Value
₹98,000
Closing Date
20 Jul 2024, 6:00 pmClosed
CWE New Delhi
HQ CWE New Delhi Rao Tula Ram Marg, Delhi Cantt-10
PROVN OF COMPACT SUB STATION ALONGWITH TRANSFORMER AND CABLE WITH OTHER CONNECTED ACCESSORIES AT CHANAKYA BAGH UNDER GE NEW DELHI
2024_MES_661092_1
CWE/ND-11/2024-25
Open Tender
Electrical and Maintenance Works
Item Rate
120 days
New Delhi
Please refer Tender documents.
10 documents required · 10 mandatory
₹500
GE NEW DELHI
₹98,000
11 Sept 2024
21 Jun 2024
22 Jul 2024
21 Jun 2024
20 Jul 2024
6 Jul 2024
Amount
Supply, Installation, Testing and Commisioning of 11 KV Compact Sub Station with 3 Way RMU consisting of 1 No. Fixed Manually operated 630A Load break Switch & 2 Nos. Fixed Manually operated 630A Vacuum Circuit Breaker in SF6 insulated stainless steel enclosure,HT Cable/Bus bar ,1 No transformer 630 KVA,11KV/433 CRT dry type & associated LT devices(ACB/MCCB/bus bar/Cable) complete including comprising of items as detailed below
Enclosure manufactured from 2.0/1.6 mm Galvanized/CRCA Sheet suitably with angles/channel, stiffeners and doors/covers as required. All Outer enclosure sheets will be minimm - 2.0 mm & All Inner Enclosure sheet shall be minimum- 1.6 mm thick. Base frame will be ISMC. Enclosure sides and doors/ covers shall be manufactured from CRCA & shall be Epoxy based Anti Corrosive powder coated, Powder coated As per manufecturer instruction, Enclosure shall be designed suitably for Outdoor application. Paint/ Powder coating Thickness shall not be less than 80 microns.
RMU-NON-Extensible type RLL 11kV, 21kA for 3 sec. Non – Extensible Compact switchgear (Type 1LBS + 2VCB) consisting of 1 No. Fixed Manually operated 630A Load break Switch & 2 Nos. Fixed Manually operated 630A Vacuum Circuit Breaker in SF6 insulated stainless steel enclosure along with below mentioned items. (i) Each Load Break Switch (IS) consists of : 1. Manually operated fixed mount 630A load breaker switch with built-in earth switch having full making capacity. 2. Mechanical position indicator. Switch ON/OFF/EARTHED. 3. Live Cable Indication. 4. Cable compartment cover interlocked with earth switch. 5. Cable termination bushings suitable for 3CX300mm2 XLPE cable. 6. Cable termination cover boots (Push on type).
(ii) Each VCB Feeder consists of following : 1. Manually operated fixed mount 630A manual close & open push buttons. 2. Self powered O/C & E/F relay type CSPR with Single core cast resin type CT (Protection Core 100/1A, 2.5VA & CL- 5P10) 3. Manually operated 630A load breaker switch with built-in earth switch having full making capacity. 4. Mechanical position indicator. Switch ON/OFF/EARTHED. 5. Live Cable Indication. 6. Cable compartment cover interlocked with earth switch. 7. Cable termination bushings suitable for 3C X 185mm2 XLPE cable. 8. Cable termination cover boots (Push on type) 9. ME: 11 KV Metering panel with CT,PT,MFM 10.11KV Interconnection Cable from outgoing of HT section to primary of Transformer by 3R X 1C X 95sq.mm. 11. Aluminium XLPE cable per phase Termination kit for 11kV Cable.
TRANSFORMER 630 KVA DRY TYPE , 11/0.415 KV , +5% to -5% off ckt tap link taps @ 2.5% step , CAST RESIN TYPE 50% Losses @75* Deg C : 3.34 KW 100% Losses @ 75 Deg C : 8.82 KW Impedance at 75°C = 5% Class F Insulation , winding rise 90°C, IP00, WTI - 7544
LT SECTION ACB(INCOMER); 800A, TPN, 50KA, MF type ACB with Microprocessor based release for overcurrent , Short circuit Protection & Earth fault (a) MCCB ; 500A, FP, 50KA, MF type MCCB with Microprocessor based release for overcurrent , Short circuit Protection & Earth fault -02 Nos (b)400A, FP, 50KA, MF type MCCB with Microprocessor based release for overcurrent , Short circuit Protection & Earth fault- 02 Nos (c) Metering CT ratio:- 800/5A, Class 1, 5VA (d) Digital A-METER, Cl-1 (e) Digital V- METER, Cl-1 (f) R,Y,B, LED for Phase Indication AC, (g) ON OFF, TRIP LED for Phase Indication AC (h)Aluminium Busbar - LT ACB INCOMER to OUTGOING 800A RATED (100% PH & 50% N with 1.0A/Sqmm Current Density) (j)Misc items - Terminals, Heaters, Sleeve,insulator, Hardware ,locks,handle,gasket, tie rods and other misc itmes
Supply, Installation, Testing and Commisioning of 11 KV, 1250 amp, indoor type, VCB horizontal ,drawout horizontal isolation floor mounting motorized panel with 230 V,motor mechanism & 24v dc shunt/close coil with CT & PT & IDMT relay, Suitable bus bar,Aux relay, Master trip, 6 window annunciator, with adapter box to connect with existing HT VCB panel board and other fittings & accessories along with below mentioned specifictions :-
(A) .VCB Horizontal isolation Horizontal draw Outdoor type 1 11KV, 630A, 18.4KA, VCB with Cu. bus bar 1 2 Degree of Protection – IP4X 1No. (3) Paint Shade – RAL 7032 1No. (4) Shunt Trip & Closing coils – 24Volt DC 1No. (5) Motor operated ( 230VAC ) 1No. (6) Emergency push button 1No. (B). EPOXY RESIN CAST RESIN, 1-Ph : CT/ PT 1). 100/50/5+5A, CL-1.0/5P10, Burden-15 VA Metering and Protection 3 Nos. (C). METERS 1). Ammeter – Digital 96 sq mm with S/S, 1 No. (D). INDICATING LAMPS 1).BREAKER ON – Red 1No. (2) BREAKER OFF – GREEN 1No. 3).TRIP CIRCUIT Healthy – White 1No. (4) SPRING Charged – Blue 1No. 5 ).Anti Pumping Device 1No.
Supply and fix Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrinktype joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified and directed
Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminium conductor, 11000 volts grade, of size 3 core 95 sq mm complete all as specified and directed
Supply and lay cable XLPE Insulated screened PVC bedded,galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 240 sq mm 3.5 core complete all as specified and directed
Supply and lay cable XLPE Insulated screened PVC bedded,ganized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 300 sq mm 3.5 core complete all as specified and directed
Excavation in trenches n.exc 1.5 mtr wide and n.exc 1.5 mtr in depth in hard/dense soil and getting out for laying of underground cables and foundation for poles etc.
M&L sand filling in and arround LT/HT cable 8cm thick below and 15cm above the cable respectively after laying the cable gently punning down complete all as specified and dircted.
Supplying and laying un-reinforced precast concrete cable cover class LV type-1, flat size 250mm x 150mm x 40mm for LT underground cable protection.
Returning, filling in including spreading, leveling, watering and well ramming in layers not exceeding 25 cms
Removing excavated materials n.exc 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point complete all as specified and directed.
M&L boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure complete all as specified and directed.
M & L for plate earthing complete with galvanized mild steel plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground vertically (in earth pit not less than 2.25 meter deep below ground level) with the top edge of earth plate at a depth not less than 1.5 meter below normal ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides and including GI strip 32x6 mm up to 7.50 RM bolted (with GI nuts, bolts & check nuts) and riveted to earth (Plate) electrode at one end and connected to main switch board / test point (including test point) at the other and watering GI pipe (medium grade) 20 mm bore from bottom of earth pit to top of electrode and 40 mm bore GI pipe light grade for earth strip protection complete with earth pit in PCC 1:2:4 type B0 using 12 mm graded crushed stone aggregate, RCC cover, funnel, wire mesh etc including necessary excavation and earth work in any type of soil, returning filling in and removal of surplus soil complete all as specified and directed.
S&F galvanised iron strip 32x6mm burried in ground or fixed on walls with saddles and fixing screws or down conductors all as specified and directed.
MV Engineers And Contractors
Commercial Traders
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .