Loading…
Loading…
Tender Value
₹69.0 L
EMD Value
₹1.4 L
Closing Date
1 Jun 2026, 3:00 pmClosed
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
60 days
Expenditure
Capital (Works)
ELEC. GENL
18 conditions · 7 needing a document upload
The tenderer must have minimum average annual contractual turnover of V/N or 'V' which ever is less; where V= Advertised value of the tender in crores of Rupees N= Number of years prescribed for completion of work for which bids have been invited The average annual contractual turnover shall be calculated as an average of "total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/ audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. The tenderers shall submit requisite information as per Annexure VI-B, along with copies of Audited Balance Sheets duly certified by the Chartered Accountant/ Certificate from Chartered Accountant duly supported by Audited Balance Sheet
As per Note (ii) of 5. Bid security Part I of Instructions to Tenderers(ITT) of GCC April 2022, "Any firm recognized by Department of Industrial Policy and Promotion (DIPP) as 'Startups' shall be exempted from payment of Bid Security detailed above". Bid security exemption cannot be claimed with Documents other than this and such offers will be summarily rejected.
Annexure VI B format of GCC April 2022 attested by Chartered Accountant has to be attached Mandatorily by tenderer along with Audited Balance sheet if the Advertised value of tender is Rs. 50 Lakhs and more.
Para 14 of Instructions to Tenderers of GCC April 2022 must be adhered by Tenderer and all the documents mentioned there has to be attached mandatorily according to the type of Constitution of business like Sole proprietorship, Company, LLP etc.
The contractor shall hold a valid Electrical Contractor License issued by the competent State Electrical Licensing Board / Chief Electrical Inspectorate, duly authorizing the execution of Low Tension (LT) electrical installation works up to 650 Volts, including 415 V three-phase systems. Submission of a valid electrical contractor license along with the bid is mandatory. Failure to upload the same shall render the offer liable for rejection.
The tenderer must have successfully completed or substantially completed any of the following during last 07 (seven) years, ending last day of month previous to the one in which tender is invited: 1. Three similar works each costing not less than the amount equal to 30% of advertised value, or 2. Two similar works each costing not less than the amount equal to 40% of advertised value or 3.One similar work each costing not less than the amount equal to 60% of advertised value Note: Separate completed works of minimum required values for each component can also be considered for fulfillment of technical eligibility criteria for different components.
The Similar nature of work adopted for this tender is "Works involving supply,erection,testing and commissioning of air-conditioning system in service buildings or auditorium or hospitals or hotels etc., with package type or centralized type air-conditioning plant system."Authority CEGE LetterNo:E.252/I/8/G Dt:02/08/2013.
32 conditions · 2 needing a document upload
The Stores materials which are supplied by Railways shall be collected from SSE/E/Works/SA stores duly transporting the same to the site by own cost borne by the contractor only. The released Railway materials if any should be handed over to the maintenance concerned SSE/Power stores duly getting forwarding acknowledgement from SSE/E/Works concerned.
I/We also hereby agree to abide by the updated Regulations of Tenders and Contracts and General Conditions of Contract issued by the Engineering Department of Indian Railways along with correction slips issued from time to time and to carryout the work according to the Special Conditions of Contract and specifications of materials and works as laid down by Railway in the Annexed Special Conditions / Specifications, Schedule of Work for the present contract.
All rates quoted in the tenders shall be deemed to be inclusive of CGST,SGST, IGST etc., payable by the contractor to the Government or anypublic body and no additional amount/rate or claim will be entertained onthis account by the Railways. Also no claim whatsoever will be accepted byRailways on account of revision of tax rates, new taxes of statutory natureby State/Central Govt.
The Contractor shall submit a statement to the effect that no retired Engineer or retired Gazetted Officer is associated with the tenderer as per Appendix-D. Tenders without the information above referred to or a statement to the effect that no such retired Engineer or retired Gazetted Officer is so associated with the tenderer, as the case may be, shall be rejected.
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
I/We have read the various conditions to tender attached hereto and agree to abide by the said conditions
I/We also agree to keep this tender open for acceptance for a period of 60 days from the date fixed for opening the same
I/We offer to do the work for Senior Divisional Electrical Engineer, GENERAL, Salem Division, Salem, at the rates quoted in the attached schedule and hereby bind myself/ourselves to complete the work in all respects within the period of completion stipulated in the tender document, from the date of commencement of work of the tender. The amount as stipulated in the tender document is herewith forwarded as Earnest Money. Full value of the earnest Money shall stand forfeited without prejudice to any other right or remedies in case my/our Tender is accepted and if :(a) I/We do not execute the contract documents as stipulated in performance guarantee clause of GCC 20222 as detailed in general instructions.(b) I/We do not commence the work within seven days after receipt of LOA/orders to that effect.
I/We hereby Confirm that the rates, rebates and/or other financial terms, if any, quoted by us in the relevant fields of the Financial Bid page will only be the ruling terms for deciding the inter-se ranking, and any such condition having financial repercussions, if quoted by us anywhere else including attached documents shall not be considered for deciding inter-se ranking
However, Railways shall have the right to incorporate any such condition quoted by us, in the contract, at their discretion, if contract is placed on us.
I/We have read the various conditions attached/ referred to in this tender document, and agree to abide by the said conditions.
All the tenderers/Contractors have to deposit full earnest money and tender document cost as stipulated for the tender, through online modes as permitted in IREPS application through multiple banks net banking, debit and credit cards only. On failing which offer will be summarily rejected.
The Tenderer should submit a copy of GST/PAN and NEFT Form.
Payment of Security Deposit/EMD and Tender form cost should be made on line only.
GCC 2022- All GCC clauses (updated including with all correction slips on date) are applicable.
i)For all the tenders having advertised cost of Rs. 10 lakh or above, the contractor shall have the option to take payment from Railways through a letter of credit (LC) arrangement. (ii)This option of taking payment through LC arrangement has to be exercised in IREPS (Indian Railway Electronic Procurement System - the e-application on which tenders are called by Railways) by the tenderer at the time of bidding itself, and the tenderer shall affirm having read over and agreed to the terms and conditions of the LC option.(iii)The option so exercised, shall be an integral part of the bidder's offer.(iv)The above option of taking payment through LC arrangement, once exercised by tenderer at the time of bidding, shall be final and no change shall be permitted, thereafter, during execution of contract.(v)In case tenderer opts for payment through LC, following shall be the procedure to deal release of payment through LC:(a)The LC shall be a sight LC.(b)The contractor shall select his Advising/Negotiating bank for LC. The incidental cost towards issue of LC and its operation thereof shall be borne by the contractor.(c)SBI, New Delhi, Main Branch will be the nodal branch for issue of LCs based on online requests received from Railway Accounts Units for tenders opened in financial year 2019-20. SBI branches where the respective Railway Accounts Office has its Account (local SBI branch) will be the issuance/reimbursing branch for LC issued under this arrangement. The Bank shall remain same for this tender till completion of contract. The incidental cost @ 0.15 % per annum of LC value, towards issue of LC and operation thereof shall be borne by the contractor and shall be recovered from his bills. (d)The LC shall be opened initially for duration of 180 to 365 days in consultation with contractor. The LC shall be extended time to time as per the progress of the contract, on the request of the contractor. The value of LC to be opened initially as well as extended thereafter shall be finalised by the engineer in consultation with the contractor on the basis of expected progress of work.(e)The LC terms and conditions shall inter-alia indemnify and save harmless the Railway from and against all losses, claims and demands of every nature and description brought or recovered against the Railways by reason of any act or omission of the contractor, his agents or employees, in relation to the Letter of Credit (LC). All sums payable/borne by Railways on this account shall be considered as reasonable compensation and paid by Contractor.
(f)The LC terms and conditions shall inter-alia provide that Railways will issue a Document of Authorisation after passing the bill for completed work, to enable contractor to claim the authorized amount from their bank. (g)The acceptable, agreed upon document for payments to be released under the LC shall be the Document of Authorisation. (h)The Document of Authorisation shall be issued by Railway Accounts Office against each bill passed by Railways. (i)On issuance of Document of Authorisation, a copy of Document of Authorisation shall be posted on IREPS for download by the contractor. A digitally signed copy of Document of Authorisation shall also be sent by Railway Accounts Office to Railway's bank (Local SBI Branch). (j)The contractor shall take print out of the Document of Authorisation available on IREPS and present his claim to his bank (advising Bank) for necessary payments as per LC terms and conditions. The claim shall comprise of copy of Document of Authorisation, Bill of Exchange and Bill. (k)The payment against LC shall be subject to verification from Railway's Bank (Local SBI Branch). (l)The contractor's bank (advising bank) shall submit the documents to the Railways Bank (Local SBI Branch). (m)The Railway's bank (issuing bank) shall, after verifying the claim so received w.r.t. the digitally signed Document of Authorisation received from Railway Accounts Office, release the payment to contractor's bank (advising bank) for crediting the same to contractor's account. (n)Any number of bills can be dealt within one LC, provided the sum total of payments to contractor is within the amount for which LC has been opened. (o)The LC shall shall be closed after the release of final payment including PVC amount, if any, to the contractor. (p)The release of performance guarantee or security deposit shall be dealt directly by Railway with the contractor i.e., not through LC
Replacement of Air conditioner at Control Room and Meeting hall at Divisional Railway Manager's Office at Salem
SA-E3-2026-27-W1
SA-E3-2026-27-W1
Open
Works - General
6 Months
Salem, Tamil Nadu
₹0
₹1.4 L
1 Jun 2026
9 May 2026
18 May 2026
63 items across 1 schedule
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | 68,99,818 | ||
| — | 136.00 | — | — | ||
| Supply, erection, testing and commissioning of energy efficient multi-compressor outdoor air-conditioning units of multi-scroll/twin rotary compressor type, as adopted in modern VRF /VRV multi-DX air-conditioning systems including a remotly operated control smart system As per Annexure-1. (Note: 1 JOB = 1 HP) (Note: 1. Tenderers are advised to study Annexure-1, including all technical specifications and scope of work, prior to quoting their rates for this item 2. Before commencement of the work, a General Arrangement Drawing (GAD) for the proposed work shall be prepared and submitted by the contractor, and approval shall be obtained from the concerned Railway authorities 3. This Item requires RITES inspection before supply of Material.) | — | — | — | 25,92,160 | |
| — | 4.00 | — | — | ||
| Supply, erection, testing and commissioning of 1.0 TR One Way Cassette Type Indoor Unit, complete with decorative fascia panel, copper tube-aluminium fin evaporator coil with anti- corrosive coating, electronic expansion valve, high-efficiency multi speed fan motor, washable air filter, built-in condensate drain pump, drain pan with anti-fungal treatment, and all standard accessories. The unit shall be suitable for operation on 230 V ±10%, 50 Hz, single-phase AC supply, compatible with VRF type outdoor units, sound level maximum 42d B, using R-32/R-410A refrigerant, and conforming to IS 1391 (Part 2), IS 8148 and IS 302, and latest manufacture recommendations and BEE norms applicable to the complete system. The item includes supply of all materials, accessories and incidentals required for proper installation such as MS/galvanized threaded hanging rods with nuts and washers, clamps, brackets, vibration isolators, thermal insulation for drain piping, connection of drain piping, connection of VRF refrigerant piping, and electrical interconnections from the nearest power/control point, including proper termination and earthing. The work shall cover alignment, leveling, sealing of ceiling cut-outs, insulation resistance testing, trial run, functional and performance testing, and final commissioning in accordance with the latest OEM installation guidelines and recommendation. The contractor shall hand over the installation in fully operational condition, along with operation manuals, test results, and warranty documents, complete in all respects as per site conditions and directions of the Engineer-in-Charge, Note: This Item requires RITES inspection before supply of Material. | — | — | — | 1,21,808 | |
| — | 17.00 | — | — | ||
| Supply, erection, testing and commissioning of 1.5 TR, 4-way cassette type air conditioner indoor unit, complete with decorative fascia panel, copper tube-aluminium fin evaporator coil with anti-corrosive coating, electronic expansion valve, high-efficiency multi speed fan motor, washable air filter, built-in condensate drain pump, drain pan with anti-fungal treatment, and all standard accessories. The unit shall be suitable for operation on 230 V ±10%, 50 Hz, single-phase AC supply, compatible with VRF type outdoor units, sound level maximum 38d B, using R-32/R-410A refrigerant, and conforming to IS 1391 (Part 2), IS 8148 and IS 302, and latest manufacture recommendations and BEE norms applicable to the complete system. The item includes supply of all materials, accessories and incidentals required for proper installation such as MS/galvanized threaded hanging rods with nuts and washers, clamps, brackets, vibration isolators, thermal insulation for drain piping, connection of drain piping, connection of VRF refrigerant piping, and electrical interconnections from the nearest power/control point, including proper termination and earthing. The work shall cover alignment, leveling, sealing of ceiling cut-outs, insulation resistance testing, trial run, functional and performance testing, and final commissioning in accordance with the latest OEM installation guidelines and recommendation. The contractor shall hand over the installation in fully operational condition, along with operation manuals, test results, and warranty documents, complete in all respects as per site conditions and directions of the Engineer-in-Charge, This Item requires RITES inspection before supply of Material. | — | — | — | 5,20,472 | |
| — | 6.00 | — | — | ||
| Supply, erection, testing and commissioning of 2.3 TR, 4-way cassette type air conditioner indoor unit, complete with decorative fascia panel, copper tube-aluminium fin evaporator coil with anti-corrosive coating, electronic expansion valve, high-efficiency multi speed fan motor, washable air filter, built-in condensate drain pump, drain pan with anti-fungal treatment, and all standard accessories. The unit shall be suitable for operation on 230 V ±10%, 50 Hz, single-phase AC supply, compatible with VRF type outdoor units, sound level maximum 41d B, using R-32/R-410A refrigerant, and conforming to IS 1391 (Part 2), IS 8148 and IS 302, and latest manufacture recommendations and BEE norms applicable to the complete system. The item includes supply of all materials, accessories and incidentals required for proper installation such as MS/galvanized threaded hanging rods with nuts and washers, clamps, brackets, vibration isolators, thermal insulation for drain piping, connection of drain piping, connection of VRF refrigerant piping, and electrical interconnections from the nearest power/control point, including proper termination and earthing. The work shall cover alignment, leveling, sealing of ceiling cut-outs, insulation resistance testing, trial run, functional and performance testing, and final commissioning in accordance with the latest OEM installation guidelines and recommendation. The contractor shall hand over the installation in fully operational condition, along with operation manuals, test results, and warranty documents, complete in all respects as per site conditions and directions of the Engineer-in-Charge, | — | — | — | 1,93,248 | |
| — | 13.00 | — | — | ||
| Supply, erection, testing and commissioning of 3.2 TR, 4-way cassette type air conditioner indoor unit, complete with decorative fascia panel, copper tube-aluminium fin evaporator coil with anti-corrosive coating, electronic expansion valve, high-efficiency multi speed fan motor, washable air filter, built-in condensate drain pump, drain pan with anti-fungal treatment, and all standard accessories. The unit shall be suitable for operation on 230 V ±10%, 50 Hz, single-phase AC supply, compatible with VRF type outdoor units, sound level maximum 46d B, using R-32/R-410A refrigerant, and conforming to IS 1391 (Part 2), IS 8148 and IS 302, and latest manufacture recommendations and BEE norms applicable to the complete system. The item includes supply of all materials, accessories and incidentals required for proper installation such as MS/galvanized threaded hanging rods with nuts and washers, clamps, brackets, vibration isolators, thermal insulation for drain piping, connection of drain piping, connection of VRF refrigerant piping, and electrical interconnections from the nearest power/control point, including proper termination and earthing. The work shall cover alignment, leveling, sealing of ceiling cut-outs, insulation resistance testing, trial run, functional and performance testing, and final commissioning in accordance with the latest OEM installation guidelines and recommendation. The contractor shall hand over the installation in fully operational condition, along with operation manuals, test results, and warranty documents, complete in all respects as per site conditions and directions of the Engineer-in-Charge, | — | — | — | 4,54,610 | |
| — | 3.00 | — | — | ||
| Supply, erection, testing and commissioning of 4.0 TR, 4-way cassette type air conditioner indoor unit, complete with decorative fascia panel, copper tube-aluminium fin evaporator coil with anti-corrosive coating, electronic expansion valve, high-efficiency multi speed fan motor, washable air filter, built-in condensate drain pump, drain pan with anti-fungal treatment, and all standard accessories. The unit shall be suitable for operation on 230 V ±10%, 50 Hz, single-phase AC supply, compatible with VRF type outdoor units, sound level maximum 48d B, using R-32/R-410A refrigerant, and conforming to IS 1391 (Part 2), IS 8148 and IS 302, and latest manufacture recommendations and BEE norms applicable to the complete system. The item includes supply of all materials, accessories and incidentals required for proper installation such as MS/galvanized threaded hanging rods with nuts and washers, clamps, brackets, vibration isolators, thermal insulation for drain piping, connection of drain piping, connection of VRF refrigerant piping, and electrical interconnections from the nearest power/control point, including proper termination and earthing. The work shall cover alignment, leveling, sealing of ceiling cut-outs, insulation resistance testing, trial run, functional and performance testing, and final commissioning in accordance with the latest OEM installation guidelines and recommendation. The contractor shall hand over the installation in fully operational condition, along with operation manuals, test results, and warranty documents, complete in all respects as per site conditions and directions of the Engineer-in-Charge, | — | — | — | 1,05,444 | |
| — | 47.00 | — | — | ||
| Supply, loading, transportation, unloading at site, installation, testing and commissioning of cordless (wireless) remote controllers including batteries complete in all respects suitable for operation of VRF indoor units, . The cordless remote controllers shall be OEM-approved, conforming to the manufacturer's standard specifications, and shall be of the same make as the corresponding VRF indoor units to ensure compatibility and warranty compliance. The scope shall include all necessary accessories, mounting arrangements, pairing and configuration with the indoor units, functional testing, and commissioning as directed by Engineer-in-Charge at site | — | — | — | 40,420 | |
| — | 600.00 | — | — | ||
| Supply, installation, testing and commissioning of hard drawn copper refrigerant piping of suitable sizes for gas (suction) and liquid lines, complete with fittings, supports and accessories, for VRF/VRV air-conditioning system including elbows, Reducers, Couplers, End caps, complete in all respects. Copper pipes shall be seamless deoxidised, hard drawn copper tubes of reputed make (according to manufacturer recommendation), conforming to relevant IS/ASTM standards, suitable for refrigerant application, with pipe sizes and wall thickness strictly as per OEM recommendations and system design, typically ranging from 1/2" to 1 3/8". All joints shall be silver brazed with mandatory nitrogen purging, and the interiors of pipes shall be thoroughly cleaned prior to brazing and kept sealed during installation to prevent ingress of moisture, dust or debris. All refrigerant piping shall be continuously insulated for the entire length, with closed-cell flexible elastomeric nitrile rubber insulation, of minimum 19 mm thickness for gas (suction) lines and minimum 13 mm thickness for liquid lines, as per manufacture recommendation, having density 40- 50 kg/m³, thermal conductivity not exceeding 0.037 W/m•K at 25°C mean temperature, CFC/HCFC free with zero ODP. External and exposed piping insulation shall be additionally protected with glass- cloth / UV-resistant coating or braided PVC sleeves for mechanical protection and weather resistance. Pipes shall be installed in accessible locations wherever possible, adequately supported at intervals not exceeding 1.8 m, using anti-vibration supports with high-density insulation saddles or PVC sleeves to prevent insulation compression, thermal bridging and condensation. Wherever pipes pass through walls or partitions, suitable sleeves shall be provided. Continuous, joint-less pipes shall be used for all concealed or inaccessible runs, and the number of joints shall be kept to a minimum, with all joints located only in accessible areas. After completion of piping, the entire refrigerant network shall be pressure tested with dry nitrogen at pressures as specified by the OEM, maintained for a minimum of 24 hours, followed by vacuum evacuation to 500 microns or better, using a calibrated vacuum gauge. The system shall be deemed complete only after satisfactory testing, evacuation, and readiness for refrigerant charging, as directed by the Engineer-in-Charge. This Item requires RITES inspection before supply of Material. | — | — | — | 9,96,000 | |
| — | 500.00 | — | — | ||
| Supply, loading, transportation, unloading at site, fixing, testing and commissioning of condensate drain piping in hard PVC of 25 mm - 50 mm diameter (as per site requirement), complete with all necessary fittings, bends, supports, clamps and accessories, and routing the same to the building drainage system, complete in all respects. The drain piping shall be suitably insulated with 9 mm thick Class 'O' closed-cell flexible elastomeric nitrile rubber foam insulation, pre-formed tubular type, having a nominal density of 40-50 kg/m³, thermal conductivity not exceeding 0.037 W/m•K at 25°C mean temperature, and conforming to ASTM D1667 or equivalent. The insulation material shall be CFC and HCFC free with zero Ozone Depletion Potential (ODP) and shall be securely bonded using approved adhesive compound, with proper joint sealing to ensure continuous vapour barrier. The quoted rate shall be inclusive of all materials, labour, tools, testing, commissioning and incidental works required for satisfactory completion of the item, as directed by the Engineer-in- Charge. | — | — | — | 1,80,000 | |
| — | 50.00 | — | — | ||
| Supply, loading, transportation, unloading at site, erection, testing and commissioning of OEM-approved refrigerant Refnet (Y-branch) joints suitable for VRF/VRV air- conditioning systems, for connection of indoor units of different capacity as in schedule 2,3,4,5,6 complete in all respects. The Refnet joints shall be designed, sized and selected strictly as per the manufacturer's engineering design and pipe sizing charts, corresponding to the connected indoor unit. The scope shall include cutting, alignment, brazing of copper connections, nitrogen purging, provision of all consumables, fittings and supports, and installation of the Refnet joints in the correct orientation and location as specified by the manufacturer and Engineer-in charge at site. The Refnet joints shall be adequately supported to avoid stress on connected piping, with proper spacing of supports, and shall be provided with thermal insulation of OEM approved thickness, including vapour-barrier sealing, joint taping and UV protection wherever exposed. and integration of the Refnet joints and verification of joint integrity, absence of leakage, proper refrigerant flow distribution to indoor units, and satisfactory system operation under trial run conditions. The complete system to be erected as directed by engineer-in charge | — | — | — | 3,20,050 | |
| — | 12.00 | — | — | ||
| Supply, loading, transportation, unloading at site, erection, testing and commissioning of OEM-approved refrigerant Refnet (Y-branch) joints suitable for VRF/VRV air- conditioning systems, for connection of outdoor units of different capacity as desired by the site conditions complete in all respects. The Refnet joints shall be designed, sized and selected strictly as per the manufacturer's engineering design and pipe sizing charts, corresponding to the connected indoor unit. The scope shall include cutting, alignment, brazing of copper connections, nitrogen purging, provision of all consumables, fittings and supports, and installation of the Refnet joints in the correct orientation and location as specified by the manufacturer and Engineer-in charge at site. The Refnet joints shall be adequately supported to avoid stress on connected piping, with proper spacing of supports, and shall be provided with thermal insulation of OEM approved thickness, including vapour-barrier sealing, joint taping and UV protection wherever exposed. and integration of the Refnet joints and verification of joint integrity, absence of leakage, proper refrigerant flow distribution to indoor units, and satisfactory system operation under trial run conditions. The complete system to be erected as directed by engineer-in charge | — | — | — | 81,492 | |
| — | 100.00 | — | — | ||
| Fabrication, supply and fixing of clamps made out MS flats of different sizes for fabrication of clamps and MS stand for copper pipes for various requirements. The clamp and stands shall be made out of MS flat of suitable size, painted with two coats in each of zinc chromate and grey enamel paint or suitable colour complete in an approved manner and as directed by Engineer in charge at site and using GI bolts with nuts of suitable size for fixing. | — | — | — | 7,200 | |
| — | 800.00 | — | — | ||
| Supply, loading, transportation, unloading at site, laying, dressing, testing and commissioning of shielded twisted pair communication cable for VRF/VRV air-conditioning system, for interconnection between VRF outdoor unit, indoor units and associated controllers, complete in all respects. The communication cable shall be 2-core twisted pair stranded copper conductor, with shielding and drain wire, suitable for low-voltage data communication and size as specified by the OEM recommendation. The scope shall include routing through conduits/cable trays, proper dressing and clamping, termination at indoor and outdoor unit terminals, earthing of shield at one end as per manufacturer's recommendations, ferruling, identification, continuity testing, communication integrity verification during the run time, and commissioning of the VRF control network. The complete system to be erected as directed by engineer-in charge | — | — | — | 56,800 | |
| — | 200.00 | — | — | ||
| Supply and installation of Cable tray of Size 300mmx50mm height using 50x50x6mm angles of perforated cable trays with perforation not more than17.5% fabricated out of Mild steel conforming to IS 2062/1079 and Hot dip galvanized as per IS 2629/4759 (galvanizing not less than80 microns) in convenient sections, jointed with connectors complete in an approved manner as directed by Engineer in charge at site. | — | — | — | 1,50,000 | |
| — | 200.00 | — | — | ||
| Supply, loading, transportation, unloading at site, charging, testing, and commissioning of refrigerant gas for top-up in VRF/VRV air-conditioning system, complete in all respects. The refrigerant gas shall be new, unused and OEM-approved type, compatible with the VRF system offered, and shall be charged strictly as per the manufacturer's recommendations based on the actual refrigerant piping length, pipe diameter and system configuration, after successful completion of pressure testing and evacuation and ensuring leak-free operation of the refrigerant circuit, as directed by the Engineer-in-Charge | — | — | — | 1,03,200 | |
| — | 1.00 | — | — | ||
| Supply at site, erection, testing & commissioning of Vertical flush/ wall mounting type , powder coated sheet steel , 12 way MCCB distribution board phosphatised and powder coated,400A "LS" Frame Double door with supply and fixing of 1 Nos. of 400 amps FP MCCB Adjustable thermal & Fixed magnetic with 50 KA breaking capacity , as incoming control with 12 Nos. of 63 amps TP MCCBs Adjustable thermal & Fixed magnetic with 25 KA breaking capacity as outgoing control, with Cable Alley Incoming 400A and outgoing 4P GF 12 way and provision of Ammeter-1 no, Voltmeter-1 No analog with selector switch and indicators for double door,3 Phase LED Voltmeter Cl 1-1 no,MFM 4405 LED meter Cl 0.5 with RS485 including internal wiring by suitable wire and incoming cable termination using suitable terminal block with suitable cable gland, earthing / neutral din channel complete with all accessories duly making necessary opening on the wall and masonry work for controlling power/lighting/fan circuits in each building in an approved manner as directed by the section in charge at site. Note:1.Bi-metallic washers must be provided for AL & Cu joints and for others GI bolts, Nuts & washers must be used. 2.Cable termination shall be using GI bolts & nuts with flat and spring washers &lugs invariably.3.Board shall be fixed in concealed manner. | — | — | — | 2,12,550 | |
| — | 800.00 | — | — | ||
| Supply and wiring by 5 nos of 10.0 sq.mm (3 phase) PVC insulated FRLS type flexible copper cable conforming to IS.No:694,1100 V grade through PVC conduit pipe already fixed. The Color coding shall be followed as directed by Engineer in charge at site(5 nos of 10.0 sq.mm copper cable shall be taken as 1Mtr for measurement purpose). | — | — | — | 3,57,600 | |
| — | 200.00 | — | — | ||
| Supply and wiring including termination by 3 nos. of 6sqmm PVC insulated fire retardant low smoke (FRLS)flexible copper cable conforming to IS. No: 694,1100 V grade through the existing PVC pipe already laid, Color coding shall be followed as directed by Engineer in charge at site(3nos. of 6 sqmm copper cable wire shall be taken as 1 m for measurement purpose) | — | — | — | 42,000 | |
| — | 200.00 | — | — | ||
| Supply and wiring including termination by 3 nos. of 4sqmm PVC insulated fire retardant low smoke (FRLS)flexible copper cable conforming to IS. No: 694,1100 V grade through the existing PVC pipe already laid, Color coding shall be followed as directed by Engineer in charge at site (3nos. of 4 sqmm copper cable wire shall be taken as 1 m for measurement purpose) | — | — | — | 34,800 | |
| — | 200.00 | — | — | ||
| Supply and wiring including termination by 3 nos of 2.5sqmm PVC insulated fire retardant low smoke (FRLS) flexible copper cable conforming toIS.No:694,1100 V grade through the existing PVC pipe already laid.Color coding shall be followed as directed by Engineer in charge at site (3 nos of 2.5 sqmm copper cable wire shall be taken as 1m for measurement purpose) | — | — | — | 25,000 | |
| — | — | — | Above/ 59200.00 Below/P | ||
| Supply and wiring (single phase) including termination by 3 nos. of 1.5 sqmm PVC insulated FRLS type flexible copper cable conforming to IS. No: 694, 1100 V grade through PVC conduit already fixed by concealed/open manner. Color coding shall be followed as directed by Engineer in charge at site(3 nos. of 1.5 sqmm copper cable wire shall be taken as 1 Mtr for measurement purpose). | — | 800.00 | — | — | |
| — | 200.00 | — | — | ||
| Supply and laying of ISI marked medium duty PVC rigid wiring conduit pipe of size 32 mm dia for open wiring including all accessories like bend, junction box etc., on existing wall/stanchion/portal/column and clamped at regular intervals as directed by Engineer in charge at site | — | — | — | 14,600 | |
| — | — | — | Above/ 44800.00 Below/P | ||
| Supply and fixing of PVC conduits of 20mm Dia confirming to IS:9537/P3/1983 or latest(ISI Marked) with wall thickness not less than 2.0 mm, all accessories like bend, junction box etc., on existing wall/stanchion/portal/column and clamped at regular intervals as directed by Engineer in charge at site. | — | 800.00 | — | — | |
| — | 100.00 | — | — | ||
| Supply and concealing of rigid PVC conduits of 20 mm Dia confirming to IS 9537/P3/1983 or latest (ISI marked) with wall thickness not less than 2.0mm along with the all accessories like bend, junction box etc and including cutting the wall/ceiling/chipping with re plastering and finishing the surface including painting to restore it to its original condition complete as directed by Engineer in charge at site. | — | — | — | 5,400 | |
| — | — | — | Above/ 27200.00 Below/P | ||
| Supply and fixing of PVC conduits of 25mm Dia confirming to IS:9537/P3/1983 or latest(ISI Marked) with wall thickness not less than 2.0 mm, all accessories like bend, junction box etc., on existing wall/stanchion/portal/column and clamped at regular intervals as directed by Engineer in charge at site. | — | 400.00 | — | — | |
| — | 100.00 | — | — | ||
| Supply and concealing of rigid PVC conduits of 25 mm Dia confirming to IS 9537/P3/1983 or latest (ISI marked) with wall thickness not less than 2.0mm along with the all accessories like bend, junction box etc and including cutting the wall/ceiling/chipping with re plastering and finishing the surface including painting to restore it to its original condition complete as directed by Engineer in charge at site. | — | — | — | 6,200 | |
| — | 2.00 | — | — | ||
| Supply at site, erection, testing & commissioning of Horizontal flush/ wall mounting type , powder coated sheet steel , SPN MCB 6 Way distribution board phosphatised and powder coated, double door with supply and fixing of 1 Nos. of 32 amps DP RCBO with 10 KA short circuitcapacity and 30mA sensitivity, as incoming control with 2 Nos. of 6-32 amps SP MCBs with 10 KA breaking capacity as outgoing control, including internal wiring by suitable wire and incoming cable termination using suitable terminal block with suitable cable gland, earthing / neutral din channel complete with all accessories duly making necessary opening on the wall and masonry work for controlling power/lighting/fan circuits in each building in an approved manner as directed by the section in charge at site. Note: 1.Bi-metallic washers must be provided for AL &Cu joints and for others GI bolts, Nuts & washers must be used. 2.Cable termination shall be using GI bolts &nuts with flat and spring washers &lugs invariably. 3.Board shall be fixed in concealed manner. | — | — | — | 9,910 | |
| — | 2.00 | — | — | ||
| Supply at site, erection, testing & commissioning of Horizontal flush/ wall mounting type , powder coated sheet steel , SPN MCB 8 Way distribution board phosphatised and powder coated, double door with supply and fixing of 1 Nos. of 32 amps DP RCBO with 10 KA short circuitcapacity and 30mA sensitivity, as incoming control with 4 Nos. of 6-32 amps SP MCBs with 10 KA breaking capacity as outgoing control, including internal wiring by suitable wire and incoming cable termination using suitable terminal block with suitable cable gland, earthing / neutral din channel complete with all accessories duly making necessary opening on the wall and masonry work for controlling power/lighting/fan circuits in each building in an approved manner as directed by the section in charge at site. Note: 1.Bi-metallic washers must be provided for AL &Cu joints and for others GI bolts, Nuts & washers must be used. 2.Cable termination shall be using GI bolts &nuts with flat and spring washers &lugs invariably. 3.Board shall be fixed in concealed manner. | — | — | — | 10,736 | |
| — | 6.00 | — | — | ||
| Supply at site, erection, testing & commissioning of Horizontal flush/ wall mounting type , powder coated sheet steel , SPN MCB 12 Way distribution board phosphatised and powder coated, double door with supply and fixing of 1 Nos. of 32 amps DP RCBO with 10 KA short circuitcapacity and 30mA sensitivity, as incoming control with 8 Nos. of 6-32 amps SP MCBs with 10 KA breaking capacity as outgoing control, including internal wiring by suitable wire and incoming cable termination using suitable terminal block with suitable cable gland, earthing / neutral din channel complete with all accessories duly making necessary opening on the wall and masonry work for controlling power/lighting/fan circuits in each building in an approved manner as directed by the section in charge at site. Note: 1.Bi-metallic washers must be provided for AL &Cu joints and for others GI bolts, Nuts & washers must be used. 2.Cable termination shall be using GI bolts &nuts with flat and spring washers &lugs invariably. 3.Board shall be fixed in concealed manner. | — | — | — | 38,058 | |
| — | 4.00 | — | — | ||
| Supply at site, erection, testing & commissioning of vertical Flush/wall mounting type ,powder coated sheet steel , SPN 16 Way distribution board phosphatised and powder coated, double door with supply and fixing of 1 Nos. of 32 amps DP RCBO with 10 KA short circuit capacity and 30mA sensitivity, as incoming control with 12 Nos. of 6-32 amps SP MCBs with 10 KA breaking capacity as outgoing control, including internal wiring by suitable wire and incoming cable termination using suitable terminal block with suitable cable gland, earthing / neutral din channel complete with all accessories duly making necessary opening on the wall and masonry work for controlling power/lighting/fan circuits in each building in an approved manner as directed by the section in charge at site. Note: 1.Bi-metallic washers must be provided for AL & Cu joints and for others GI bolts, Nuts & washers must be used. 2.Cable termination shall be using GI bolts & nuts with flat and spring washers & lugs invariably. 3. Board shall be fixed in concealed manner. | — | — | — | 30,940 | |
| — | 10.00 | — | — | ||
| Supply, erection and testing of L.T. Earthing arrangements duly stenciling of earth resistance value along with date as per Drg. no. CEE/CN/MS/16-2004, including supply and spreading of salt and charcoal 5 kgs in each for earth treatment etc , including supply / leading / laying /burying and concealing of 4 SWG GI wire from earth electrode to proposed MDB / SDB or elsewhere in an approved manner as directed by Section Engineer in charge at site. | — | — | — | 57,920 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
I_CT_GCC-
ATTACHMENT
Drawings_I_merged.pdf
ATTACHMENT
Tender Booklet
ATTACHMENT
Annexure-1.pdf
ATTACHMENT
GCC_April-2022_2022_CE-I_CT_GCC-2022_POLICY_27.04.22.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .