HQ 138 WE
REPAIR/MAINT OF CENTRAL HEATING PLANTS AND REPLACEMENT OF INSULATION PPR PIPES, CONTROL VALVES, HEATERS TOPPING UP OF GLYCOL, HOT WATER SUPPLY AT TANGTSE UNDER GE 860 EWS
2024_MES_673302_1
138WE/L-85/2024-25
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE 860 EWS
As per Tender documents
6 documents required · 6 mandatory
₹500
GE 860 EWS
₹25,800
Yes
27 Nov 2024
9 Sept 2024
19 Oct 2024
9 Sept 2024
12 Oct 2024
23 Sept 2024
Amount
M & L for Dismantling of burner rod assy and removing of side cover of boiler capacity 4 lakh kilo/cal/hr and complete servicing the boiler by using coil shine chemical and removing the complete carbon/oil deposits including repair to coil assy if there is any leakage found or any other repair required at site and reassembling/testing the same complete all as specified and directed by Engr-in-Charge.
M & L for sequence controller suitable for 04 lakh Kilo/Cal/hr burner rod assy all as specified and directed by Engr-in-Charge. Make:Seimens/L&T/Schneider
M & L for ignition rod suitable for 4 Lakh Kilo/Cal/hr burner rod assy all as specified and directed by Engr-in-Charge.
M & L for replacement of Ignition Transformer with lead electronic type suitable for 04 lakh Kilo/Cal/hr burner rod assy all as specified and directed by Engr-in-Charge.Make:Danfoss/L&T/Schneider
M & L for replacement of diesel filters suitable for boiler of capacity 4 Lakh K cal/Hr as per existing complete all as directed by Engr-in-Charge.
M & L for complete servicing of diesel pumps suitable for boiler of capacity 4 Lakh K cal/Hr including replacement of bearings, seal etc as per site requirement complete all as directed by Engr-in-Charge.
Supply and replacement of old diesel burner set of capacity 4 Lac kcal/hr comprising of diffuser,nozzle,electrodes,blast tube,solenoid valve,air damper adjustment,gear pump,coupling set,oil supply pipe,gasket,ignition transformer,reset button,flame detector and controller complete. Make:Ecoflam,Aquatherm,Rapid therm
Supply and fixing of 1 HP Motor Electric driven single phase 230 volts complete all as specified and directed by Engr in Charge.
supply and fixing temp controller digital type DTC 503 with sensor suitable for 4 lakh Kilo/Cal/Hr LAL 2.25 burner rod assembly ,complete all as specified and as directed. Make- Siemens or equivalent.
Supply and fixing in replacement of High Pressure Fuel pipe 1.5 Mtr as per existing ,complete all as specified and directed by Engr in Charge.
Supply and fixing in replacement of Electrode suitable for burner of capacity 4 Lakh k/cal/hr, complete all as specified and directed by Engr in Charge.
Supply and fixing burner nozzle suitable for 3-4 Lakh kilo/Cal/hr complete all as specified and as directed by Engr in Charge.
M & L for replacement of digital type Amp meter complete with touch control switch and suitable CTs 0 - 300 Amps complete all as directed by Engr-in-Charge. Make : AE/L&T/ Schneider
M & L for replacement of indicating lamps RYB as per existing complete all as directed by Engr-in-Charge.Make : AE/L&T/ Schneider
M & L for replacement of push botton type ON/OFF switches as per existing complete all as directed by Engr-in-Charge.
M&L for Cleaning of MS diesel storage tanks of capacity up to 10000 ltrs by removing of sludge from tank and scraping the side walls by means of wire brush or emery paper and wash the same with castic soda and clear water and painting the internal walls with two coats of black rubber immelsion paint and painting the complete tank from out side with two coats of synthetic enamel paint complete all as specified and directed.
M&L for Cleaning of MS overhead Glycol storage tank of any capacity including all type of T&P and chemical required for the same, including welding work to leakage surface including opening and refixing the existing insulating materials to the external surfaces of the tank.
M&L for cleaning of MS overhead POL storage tank of capacity 2000/1000 Ltr including all type of T&P and chemical required for the same, including welding work to leakage surface including opening and refixing the existing insulating materials to the external surface of storage tank.
S&F in replacement insulation 13mm thick as per existing with all fixing arrangements to the all sizes of pipes properly complete all as specified and directed. Make-Caflese, K-Flex.
Supply only over load relay 1.25 to 2 Amps for contactor matching ser no 49 series 3 TF 33 Make- Siemens, complete all as specified and directed.
Supply and fixing in replacement PVC flexible copper multistranded wire 3 core of 6 Sqmm , complete all as specified and as directed.
S&F in replacement of FCU connection flexible pipe 20/16 mm as per existing, complete all as specified and directed. Make- Jindal/Kitetac.
S&F in replacement of inlet/outlet forged brass ball valve 15/20/25 mm with Y Stainer for FCU, hot water for -25 to 90 degree temperature as per existing,including supply and fixing suitable size of MS / GI nipple of size inch including welding work, cutting the existing rusty unserviceable MS/GI nipple complete all asspecified and directed.
M&L for Electrical Control Wiring for FCU of any size including electronic display complete as per sample all as specified and directed.
M &L for Servicing and Maint of existing FCU installed at 34 AP by detecting leakage and rectify the leakage by using clamps, washer, nut bolts etc all as directed at site by Engr-in-charge.
Dimantling/disconnecting all the electrical and pipe connection from the unserviceable Glycol circulating motor of 7.5/5 HP . Taking the motor to the authorised workshop at leh winding the same with copper wire of same size and turns including varnishing . shifting the same to the installation and fixing at the site complete all as specified and as directed by Engr-in-charge.
S&F in replacement Fuel feed pump with lead suitable for 4 Lakh K-Cal Burner of existing make and model complete all as specified and directed Make : Suntec and equivalent
Supply & Fix Cast iron gun metal butterfly valve of size 100 mm dia with CI drilled flanged ends (integrally cast) class PN-I.6, conforming to IS : 13095 / BS: 5155 with stainless steel spindle and iron wheel non rising type including jointing material complete such as rubber or fibre board insertion packing rings with requisite numbers of nuts, bolts & washers etc including taking out existing unserviceable valve complete all as specified and directed. Make : KIRLOSKAR/BIR/LEADER
M & L for Dismantling of burner rod assy and removing of side cover of boiler/burner of Hot Water Plant suitable for outpur 1 Lakh K-cal and complete servicing the boiler by using coil shine chemical and removing the complete carbon/oil deposits including descaling of pipe and arresting if there is any leakage found or any other repair required at site and reassembling/testing the same complete all as specified and directed by Engr-in-Charge.
S&F in replacement Fuel feed pump suitable for Hot Water Generator/Plant suitable for outpur 1 Lakh K-cal of existing make and model complete all as specified and directed Make : Suntec and equivalent
S & F in replacement pressure gauge range 0-10 Kg/cm2 of existing make and model suitable for hot water generator/plant complete all as specified and directed.
S & F in replacement pressure controller of existing make and model suitable for hot water generator/plant suitable for outpur 1 Lakh K-cal complete all as specified and directed.
M & L for ignition rod suitable for Hot Water Generator suitable for outpur 1 Lakh K-cal of existing make and model all as specified and directed by Engr-in-Charge.
M & L for replacement of Ignition Transformer electronic type suitable for hot water generator suitable for outpur 1 Lakh K-cal all as specified and directed by Engr-in-Charge.Make:Danfoss/L&T/Schneider
M & L for replacement of diesel filters suitable for Hot Water Generator suitable for outpur 1 Lakh K-cal as per existing complete all as directed by Engr-in-Charge.
M &L for repairing the main control panel of Hot Water Generator suitable for outpur 1 Lakh K-cal including replacement of unserviceable 4 pole contactor -2 Nos, Relay - 01 No. Timer-01 No. MCB TP 10-32 A - 01 No and wiring of panel of existing cap, make and model
S & F in replacement MCB TPN 32 Amps 4 pole, 415 Volt, 10 KA Braking capacity Make : L & T/Havells/Legrand
M & L for dismatling and taking out old US burnt electric motor 2/3 HP three phase and pump and replacing burnt copper winding with existing size wire, including heating, varnishing and insulating paper and replacing bearings complete refixing in position all as specified and directed
Supply and replacement of old diesel burner set of capacity 1 Lac kcal/hr comprising of diffuser,nozzle,electrodes,blast tube,solenoid valve,air damper adjustment,gear pump,coupling set,oil supply pipe,gasket,ignition transformer,reset button,flame detector and controller complete. Make:Ecoflam,Aquatherm,Rapid therm
M & L dismantling and takingh out unserviceable Boiler Coil of Capacity 4 Lakh K Cal Make Thermax and transporting the Coil to workshop for repair including cleaning and replacement of unserviceable parts as per requirement and re-asembling the same after repair including testing all as specified and directed by Engr-in-charge
-ditto- all as per item Ser No. 41 above but boiler coil of capacity 1 Lakh K Cal Make Thermax/Western
Supply and filling of Methy/Ethylene Glycol(MEG) of 99% purity and minus forty degree centigrade fressing temperature in Sealed Container for Central heating Plant Complete all as specified and directed by Engr in Charge.Note : Container is a deposited to MES Store Yard.
S & F in replacement MCCB 3 Pole, 415 V, fixed type, 250 'Amps with breaking capacity 36 KA
Supply and fix in repair On load change over switch 415 volt 50 Hz confirm to IS-13947-3 with enclosure and side handle of cap 200 Amp four pole including takind down old switch Make Havells /C&S/Indoasian
M/S LIBE & CO (BID ID -3130589)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .