Superintending Engineer
S.E EUDC Office sec-18 Noida
Replacement of Damaged Pole, GI Wire, Gurding, etc.
2023_PVVNL_839496_1
E-Tender No. 54/2023-24, EUDC-II, Noida.
Open Tender
Electrical Works
Item Rate
90 days
S.E EUDC Office sec-18 Noida
Attached in DOC
2 documents required · 2 mandatory
₹1,180
S.E., EUDC-II Noida
₹4,000
4 Oct 2023
18 Sept 2023
30 Sept 2023
18 Sept 2023
30 Sept 2023
18 Sept 2023
Amount
fo|qr forj.k [k.M & v"Ve tsoj ds vUrxZr iz.kkyh lqn`<hdj.k tSls ttZj rkj] th0vkbZ0 ok;j o iksy cnyuk] xkfMZax bR;kfn lEcfU/kr dk;ZA (DETAIL OF WORK MENTIONED IN TENDER FORM)
Safe carriage of following stock material, from any of the Store Center of PVVNL to work site including Loading from Store and safe unloading at site for Item No. 3 to 5
ACSR Rabbit Conductor
PCC Pole 8.5 Mtr Long
ST Pole 11 Mtr Long
11 KV Polymeric Pin Insulator
11 KV Polymeric Disc Insulator
SUPPLY OF FOLLOWING MATERIAL BY THE CONTRACTOR FROM THE PVVNL APPROVED VENDORS AS PER GTP APPROVED.
V-Type Cross Arm 100x50x6 mm G.I channel
G.I. Wire 6 SWG
Stay set complete (G.I.Stay rod 16x1800mm, Stay wire 5Kg, Guy insulator, G.I.Stay clamp, bolt, nut & wasther with concrete grouting) for 11KV line as per specification
G.I Guarding angle 75x75x6 mm, (6.80kg/mt)
Supply and Errection of the Following material for completing the work as per RESPO.
The excavation of foundation pit in mix soil/normal soil/soft soil & hard rock as per site condition and its back filling and leveling etc. The size of the pit will be (750x450)mm and having depth of 1/6th of the full length of the support. Erection of support, complete with providing & fixing of all G.I.Clamps size of 75x10mm, 'F' bracket 75x10mm, G.I.Nut bolt & washer, Stone Pad Al. Binding wire and other accessories as per drawing. The work includes carriage and handling of supports from sectional store to pit site as well as an fabrication work if required. Single Pole (a) ST Pole 11 MtR Long and 8.5MTR. PCC POLE
Grouting of supports in CC 1:3:6 (Cement, sand & 20mm stone grift). Grouting will be done in the block of size (450x450)mm x1/6th of full length of the support, upto ground level, 300mm plinth above the ground level with C.C. 1:3:6 (Cement, Course sand and Stone grift) with muffing as per RESPO. Work includes back filling and proper ramming. Single Pole and Double Pole (a) ST Pole 11 MtR Long and 8.5MTR. PCC POLE
FIXING OF PIN INSULATOR WITH PIN, COMPLETE WORK IN ALL RESPECT.
FIXING OF DISC INSULATOR WITH FITTING, COMPLETE WORK IN ALL RESPECT.
Laying, spreading, lifting and final sagging of 3 phases ACSR Rabbit conductor in accordance with Line chart includidng binding and fixing of all accessories in 03Nos. Conductor in parallel as per site requirement. (12500mtr. Shamsham Nagar, 4000Mtr at Sarkari Hospital and 3900Mtr at Janta Inter College of 33/11 KV S/S Jewar Tehsil)
Providing and Driving of MS earth rod of size 20x2500 mm in earth and jointing through G.I. wire of 6 SWG between support and earth electrode by providing proper size of bolts and nuts for pole earthing. Supply Erection, fixing, grouting of stay rod in cement, sand and brick ballast in ration 1:4:8 in Block 600*600*300 mm with binding & nuzzling including providing & fixing of stay insulator complete in all respect with grouting. (All Work and Material in the scope of Contractor)
Fixing of 11 KV Top Channel as per site requirement.
Fixing of 11KV Cross Arm as per site requirement.
Fixing of 11KV Toff Channel as per site requirement.
Fixing, tightening & nozzling of stay wire with stay rod with the poles of required tension as per drawing, including providing & fixing of Stay Insulators of 11KV and Stay Clamps.
Grouting of stay rods (20x1800)mm including all work of excavation, cement concrete in size (0.60x0.60x0.30)m in ratio 1:3:6 cement, sand, 20mm Stone grift) as per drg. Including back filling of soil and proper ramming etc.
Fixing, tightening & nozzling of stay wire with stay rod with the poles of required tension as per drawing, including providing & fixing of Stay Insulators of 11KV and Stay Clamps.
Grouting of stay rods (20x1800)mm including all work of excavation, cement concrete in size (0.60x0.60x0.30)m in ratio 1:3:6 cement, sand, 20mm Stone grift) as per drg. Including back filling of soil and proper ramming etc.
Fixing of 11KV Cross Arm as per site requirement.
Providing and Fixing of Best Quality MS Holding Clamp as per site requirement.
Providing and Fixing of Best Quality F Clamps as per site requirement.
Guarding between two poles like single poles, double poles, four poles, etc. to guard L.T., 11KV Line telephone line and river crossing, road crossing etc. with G.I.wire No.6SWG, G.I.wire No.8SWG and G.I.wire No.16SWG including cutting with fabrication and fixing of G.I.Guarding angle 75x75x6mm with Providing & fixing G.I.clamps size 75x10mm, G.I.Turn buckle, G.I.Eye bolt, nut bolts & washer etc, as per drawing at Sarkari Hospital 11KV Line emanating from 33/11 KV S/S Jewar Tehsil.
Fixing of Guarding Angle as per site requirement at at Sarkari Hospital 11KV Line emanating from 33/11 KV S/S Jewar Tehsil.
Dismentaling of old and damaged ACSR Weasel Conductor and safe carriage of its from Site to any Store/Workshop of PVVNL including loading and unloading both ends.
Kunal Electricals
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .