Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹25.0 CrAdmitted-Finance | ₹25.0 Cr | L1 | Admitted-Finance |
| 2 | L2₹25.4 CrAdmitted-Finance | ₹25.4 Cr | L2 | Admitted-Finance |
| 3 | L3₹26.5 CrAdmitted-Finance | ₹26.5 Cr | L3 | Admitted-Finance |
| 4 | L4₹26.5 CrAdmitted-Finance WZ 487 2 MS BLOCK HARI NAGAR NEW DELHI 110064 | NEW DELHI | NEW DELHI | DELHI | 110064 | ₹26.5 Cr | L4 | Admitted-Finance |
| 5 | L5₹29.6 CrAdmitted-Finance NATIONAL TOWER 5TH FLOOR SCO 89 DSC RANJIT AVENUE AMRITSAR 143001 PUNJAB | AMRITSAR | AMRITSAR | PUNJAB | 143001 | ₹29.6 Cr | L5 | Admitted-Finance |
| Sl No | Description | Qty | Unit | Pooja Singla Builders And Engineers Pvt Ltd L6 | NAFREF ENGINEERS PVT LTD L5 | Pawansut Infra Projects Pvt. Ltd. L1 | M/s Khanna Enterprises L3 | M/S Shiv Shakti Enterprises L4 | SOM BUILDERS L2 |
|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Lump sum price worked out by the tenderer for “BUILDING WORK" as listed in Schedule ‘A’ Part - I | 1 | Lump sum | 22,47,00,000 ₹22.5 Cr | 20,00,00,000 ₹20 Cr | 15,69,87,812 ₹15.7 Cr | 15,10,00,000 ₹15.1 Cr | 14,69,00,000 ₹14.7 Cr | 13,70,05,345.14 ₹13.7 Cr |
| 2.00Subtotal | |||||||||
| 3.00 | Lump sum price worked out by the tenderer for “INTERNAL ELECTRIFICATION WORK" as listed in Schedule ‘A’ Part - II | 1 | Lump sum | 35,36,211.6 ₹35.4 L | - | 27,50,000 ₹27.5 L | - | 24,00,000 ₹24 L | 32,56,180.11 ₹32.6 L |
| 4.00Subtotal | |||||||||
| 5.00Schedule ‘A’ Part - II (INTERNAL ELECTRIFICATION WORK) | |||||||||
| 6.00 | Supply, installation, testing and commissioning of DALI dimmable recess mounted accent light with non-integral fixed output driver having LED light source engine, 12 to 36° beam angle of light source, luminous flux ≥ 2000 lm, rated luminous efficacy ≥ 100 lm/W, power consumption ≤ 20 W, power consumption tolerance ±10%, initial correlated colour temperature (CCT) 4000K, colour rendering index (CRI) ≥ 80, Power Factor (fraction) ≥ 0.9, median useful life L70B50 @ Ta = 45 °C ≥ 40000 hrs, surge protection level ≥ 2.5 kV with aluminium alloy housing and polycarbonate optical cover / lens material, IP20 & IK02 protection, EMI / EMC (B1) compliant, and suitable for 240 V input voltage, 50 Hz line frequency, ambient temperature range 0 to 45 °C, class B serviceability, ceiling cutout dia. ≤ 5" (125 mm) and fixture height ≤ 150 mm along with all necessary accessories complete all as specified and directed by the engineer-in-charge. | 151 | Each | 5,100 ₹7.7 L | 950 ₹1.4 L | 2,150 ₹3.2 L | 2,250 ₹3.4 L | 6,500 ₹9.8 L | 2,000 ₹3.0 L |
| 7.00 | Supply, installation, testing and commissioning of DALI dimmable recess mounted accent light in fixed type with non-integral fixed output driver having COB type LED, 36° beam angle of light source, luminous flux ≥ 4000 lm, rated luminous efficacy ≥ 100 lm/W, power consumption ≤ 42 W, power consumption tolerance ±10%, initial corrected colour temperature (CCT) 4000/6500K, colour rendering index (CRI) ≥ 80, power factor (fraction) ≥ 0.9, median useful life L70B50 @ Ta = 45 °C ≥ 40000 hrs, surge protection level ≥ 4 kV with die cast aluminium housing and polycarbonate optical cover / lens material, IP20 & IK02 protection, EMI / EMC (B1) compliant, and suitable for 140-270 V input voltage, 50 Hz line frequency, ambient temperature range 0 to 45 °C, class B serviceability, ceiling cutout dia. ≤ 8" (200 mm) and fixture height ≤ 75 mm along with all necessary accessories complete all as specified and directed by the engineer-in-charge. | 76 | Each | 6,350 ₹4.8 L | 6,000 ₹4.6 L | 5,150 ₹3.9 L | 4,500 ₹3.4 L | 6,750 ₹5.1 L | 5,000 ₹3.8 L |
| 8.00 | S & F low height recess mounted downlight in circular form-factor with non-integral fixed output driver having LED light source engine, 120° luminaire light beam spread, luminous flux ≥ 2000 lm, rated luminous efficacy ≥ 110 lm/W, power consumption ≤ 19 W, power consumption tolerance ±10%, initial correlated colour temperature (CCT) 6500K, colour rendering index (CRI) ≥ 80, SDCM < 5, THD(i) < 10%, Power Factor ≥ 0.95, median useful life L70B50 @ Ta = 45 °C ≥ 50000 hrs, surge protection level ≥ 2.5 kV with aluminum die cast housing and polycarbonate optical cover / lens material, IP20 & IK02 protection, EMI / EMC (B1) compliant, and suitable for 130- 320 V input voltage, 50 Hz line frequency, ambient temperature range 0 to 45 °C, class B serviceability, ceiling cutout dia ≤ 5" (125 mm) and fixture height ≤ 40 mm along with all necessary accessories complete all as specified and directed by the engineer-in-charge. | 84 | Each | 1,500 ₹1.3 L | 980 ₹82,320 | 1,150 ₹96,600 | 1,250 ₹1.1 L | 2,000 ₹1.7 L | 1,400 ₹1.2 L |
| 9.00 | S & F low height recess mounted downlight in circular form-factor with non-integral fixed output driver having LED light source engine, 120° luminaire light beam spread, luminous flux ≥ 1500 lm, rated luminous efficacy ≥ 110 lm/W, power consumption ≤ 13.5 W, power consumption tolerance ±10%, initial correlated colour temperature (CCT) 6500K, colour rendering index (CRI) ≥ 80, SDCM < 5, THD(i) < 10%, Power Factor ≥ 0.95, median useful life L70B50 @ Ta = 45 °C ≥ 50000 hrs, surge protection level ≥ 2.5 kV with aluminum die cast housing and polycarbonate optical cover / lens material, IP20 & IK02 protection, EMI / EMC (B1) compliant, and suitable for 130- 320 V input voltage, 50 Hz line frequency, ambient temperature range 0 to 45 °C, class B serviceability, ceiling cutout dia ≤ 5" (125 mm) and fixture height ≤ 40 mm along with all necessary accessories complete all as specified and directed by the engineer-in-charge. | 121 | Each | 1,425 ₹1.7 L | 560 ₹67,760 | 1,150 ₹1.4 L | 1,050 ₹1.3 L | 1,800 ₹2.2 L | 1,250 ₹1.5 L |
| 10.00 | S & F of surface mounted circular downlight with integral fixed output driver having LED light source engine, luminous flux ≥ 2000 lm, rated luminous efficacy ≥ 110 lm/W, power consumption ≤ 19 W, power consumption tolerance ±10%, initial corrected colour temperature (CCT) 6500K, colour rendering index (CRI) > 80, SDCM < 5, THD < 10%, Power Factor ≥ 0.90, median useful life L70B50 @ Ta = 45 °C ≥ 30000 hrs, surge protection level ≥ 2.5 kV with aluminium pressure die cast housing and polycarbonate optical cover / lens material, IP20 & IK02 protection, safety class I, and suitable for mounting on normally flammable surfaces, 220- 240 V input voltage, 50 Hz line frequency, ambient temperature range 0 to 45 °C, overall diameter ≤ 7" (175 mm) and fixture height ≤ 60 mm along with mounting bracket and all necessary accessories complete all as specified and directed by the engineer-in-charge. | 24 | Each | 1,500 ₹36,000 | 2,993 ₹71,832 | 1,250 ₹30,000 | 1,150 ₹27,600 | 2,100 ₹50,400 | 1,350 ₹32,400 |
Updated dates
Tender Value
₹18.9 Cr
EMD Value
₹12.7 L
Closing Date
27 Dec 2025, 6:00 pmClosed
Chief Engineer Bathinda zone
HQ CE Bathinda Zone, Bathinda Mil Stn-151004
PROVN OF AUDITORIUM AT FARIDKOT MIL STN UNDER GE FARIDKOT
2025_MES_728013_2
84528 CE BTZ/FDK/TOKEN-34 OF 2025-26
Open Tender
Civil Works
548 days
GE faridkot
As per NIT
8 documents required · 8 mandatory
₹3,000
GE Faridkot
₹12.7 L
Yes
29 Dec 2025
22 Nov 2025
29 Dec 2025
22 Nov 2025
27 Dec 2025
6 Dec 2025
Amount
Lump sum price worked out by the tenderer for “BUILDING WORK" as listed in Schedule ‘A’ Part - I
Subtotal
Lump sum price worked out by the tenderer for “INTERNAL ELECTRIFICATION WORK" as listed in Schedule ‘A’ Part - II
Subtotal
Schedule ‘A’ Part - II (INTERNAL ELECTRIFICATION WORK)
Supply, installation, testing and commissioning of DALI dimmable recess mounted accent light with non-integral fixed output driver having LED light source engine, 12 to 36° beam angle of light source, luminous flux ≥ 2000 lm, rated luminous efficacy ≥ 100 lm/W, power consumption ≤ 20 W, power consumption tolerance ±10%, initial correlated colour temperature (CCT) 4000K, colour rendering index (CRI) ≥ 80, Power Factor (fraction) ≥ 0.9, median useful life L70B50 @ Ta = 45 °C ≥ 40000 hrs, surge protection level ≥ 2.5 kV with aluminium alloy housing and polycarbonate optical cover / lens material, IP20 & IK02 protection, EMI / EMC (B1) compliant, and suitable for 240 V input voltage, 50 Hz line frequency, ambient temperature range 0 to 45 °C, class B serviceability, ceiling cutout dia. ≤ 5" (125 mm) and fixture height ≤ 150 mm along with all necessary accessories complete all as specified and directed by the engineer-in-charge.
Supply, installation, testing and commissioning of DALI dimmable recess mounted accent light in fixed type with non-integral fixed output driver having COB type LED, 36° beam angle of light source, luminous flux ≥ 4000 lm, rated luminous efficacy ≥ 100 lm/W, power consumption ≤ 42 W, power consumption tolerance ±10%, initial corrected colour temperature (CCT) 4000/6500K, colour rendering index (CRI) ≥ 80, power factor (fraction) ≥ 0.9, median useful life L70B50 @ Ta = 45 °C ≥ 40000 hrs, surge protection level ≥ 4 kV with die cast aluminium housing and polycarbonate optical cover / lens material, IP20 & IK02 protection, EMI / EMC (B1) compliant, and suitable for 140-270 V input voltage, 50 Hz line frequency, ambient temperature range 0 to 45 °C, class B serviceability, ceiling cutout dia. ≤ 8" (200 mm) and fixture height ≤ 75 mm along with all necessary accessories complete all as specified and directed by the engineer-in-charge.
S & F low height recess mounted downlight in circular form-factor with non-integral fixed output driver having LED light source engine, 120° luminaire light beam spread, luminous flux ≥ 2000 lm, rated luminous efficacy ≥ 110 lm/W, power consumption ≤ 19 W, power consumption tolerance ±10%, initial correlated colour temperature (CCT) 6500K, colour rendering index (CRI) ≥ 80, SDCM < 5, THD(i) < 10%, Power Factor ≥ 0.95, median useful life L70B50 @ Ta = 45 °C ≥ 50000 hrs, surge protection level ≥ 2.5 kV with aluminum die cast housing and polycarbonate optical cover / lens material, IP20 & IK02 protection, EMI / EMC (B1) compliant, and suitable for 130- 320 V input voltage, 50 Hz line frequency, ambient temperature range 0 to 45 °C, class B serviceability, ceiling cutout dia ≤ 5" (125 mm) and fixture height ≤ 40 mm along with all necessary accessories complete all as specified and directed by the engineer-in-charge.
S & F low height recess mounted downlight in circular form-factor with non-integral fixed output driver having LED light source engine, 120° luminaire light beam spread, luminous flux ≥ 1500 lm, rated luminous efficacy ≥ 110 lm/W, power consumption ≤ 13.5 W, power consumption tolerance ±10%, initial correlated colour temperature (CCT) 6500K, colour rendering index (CRI) ≥ 80, SDCM < 5, THD(i) < 10%, Power Factor ≥ 0.95, median useful life L70B50 @ Ta = 45 °C ≥ 50000 hrs, surge protection level ≥ 2.5 kV with aluminum die cast housing and polycarbonate optical cover / lens material, IP20 & IK02 protection, EMI / EMC (B1) compliant, and suitable for 130- 320 V input voltage, 50 Hz line frequency, ambient temperature range 0 to 45 °C, class B serviceability, ceiling cutout dia ≤ 5" (125 mm) and fixture height ≤ 40 mm along with all necessary accessories complete all as specified and directed by the engineer-in-charge.
S & F of surface mounted circular downlight with integral fixed output driver having LED light source engine, luminous flux ≥ 2000 lm, rated luminous efficacy ≥ 110 lm/W, power consumption ≤ 19 W, power consumption tolerance ±10%, initial corrected colour temperature (CCT) 6500K, colour rendering index (CRI) > 80, SDCM < 5, THD < 10%, Power Factor ≥ 0.90, median useful life L70B50 @ Ta = 45 °C ≥ 30000 hrs, surge protection level ≥ 2.5 kV with aluminium pressure die cast housing and polycarbonate optical cover / lens material, IP20 & IK02 protection, safety class I, and suitable for mounting on normally flammable surfaces, 220- 240 V input voltage, 50 Hz line frequency, ambient temperature range 0 to 45 °C, overall diameter ≤ 7" (175 mm) and fixture height ≤ 60 mm along with mounting bracket and all necessary accessories complete all as specified and directed by the engineer-in-charge.
Supply, installation, testing and commissioning of of surface mounted, dust penetration protected, jet-proof LED downlight having LED light source engine, integral driver, luminous flux ≥ 4000 lm (±10%), rated luminous efficacy ≥ 105 lm/W, correlated colour temperature (CCT) 6500K, colour rendering index (CRI) > 80, high-gloss mirror optic, reflector type optical cover, luminaire light beam spread 60°, power factor (fraction) ≥ 0.9, power cpnsumption ≤ 36 W (±10%), initial chromaticity (0.31, 0.32) SDCM < 5, driver failure rate ≤ 1% at 5000 h, median useful life L70B50 50000 hrs, aluminum die cast housing, reflector and optic, IP65 & IK02 protection, safety class I, suitable for input voltage 220 to 240 V and line frequency 50 Hz complete all as specified and directed by the engineer-in-charge.
S & F 4' surface mounted / suspended batten having LED light source engine delivering full window illumination, integral fixed output driver, 120° beam angle of light source, luminous flux ≥ 4000 lm, luminous efficacy ≥ 120 lm/W, power consumption ≤ 34 W, power consumption tolerance ±10%, initial correlated colour temperature (CCT) 6500K, colour rendering index (CRI) ≥ 80, SDCM < 5, power factor > 0.95, median useful life L70B50 @ Ta = 45 °C ≥ 50000 hrs, surge protection level ≥ 4 kV with steel housing, polycarbonate optical cover / lens, IP20 & IK02 protection, and and suitable for mounting on normally flammable surfaces, 140- 270 V input voltage, 50 Hz line frequency, ambient temperature range 0 to 45 °C, class I safety, along with surface / suspended (asymmetric / symmetric) mounting device and all necessary accessories complete all as specified and directed by the engineer-in-charge.
S & F 4' waterproof surface mounted / suspended batten having LED light source engine delivering full window illumination, integral fixed output driver, SY120° / diffused light distribution, luminous flux ≥ 4400 lm, luminous efficacy ≥ 120 lm/W, power consumption ≤ 37 W, power consumption tolerance ±10%, initial correlated colour temperature (CCT) 6500K, colour rendering index (CRI) ≥ 80, SDCM < 5, THD < 20%, power factor > 0.85, median useful life L70B50 @ Ta = 45 °C ≥ 30000 hrs, surge protection level ≥ 2.5 kV with polycarbonate co-extrusion housing, high transmittance PC diffuser, IP65 & IK08 protection, BIS approbation & RoHS sustainability compliance and suitable for 140- 270 V input voltage, 50 Hz line frequency, ambient temperature range -10 to 45 °C, class B serviceability, along with Click Fix mounting bracket and all necessary accessories complete all as specified and directed by the engineer-in-charge.
S & F water-proof wall light (mirror / bathroom light) having built-in water-resistant LED light source, luminous flux ≥ 450 lm, lifetime up to 15000 hrs, power consumption ≤ 8 W, IP44 protection (Class of Protection II- double protection) with electrical connection complete all as specified and directed by engineer-in-charge.
S & F neatly designed step light having long life LED source, beautiful light pattern, robust finish, aluminum housing, LED integrated lamp base, luminous flux ≥ 85 lm, initial correlated colour temperature (CCT) 3000K, power consumption ≤ 3 W, IP44 protection with electrical connection complete all as specified and directed by engineer-in-charge.
S & F of LED strip of dimension 1 mm X 8 mm X 5000 mm (H X W X D) for indirect illumination of false-ceiling coves in officers' chambers having 120° luminaire light beam spread, symmetric optic, luminous flux ≥ 800 lm, luminous efficacy ≥ 105 lm/W, power consumption tolerance ±10%, initial correlated colour temperature (CCT) 4000K, colour rendering index (CRI) ≥ 80, SDCM < 5, power factor (fraction) > 0.90, median useful life L70B50 @ Ta = 45 °C ≥ 30000 hrs, 2P connection unit and 1P cables without plug, with aluminum housing, IP20 protection, RoHS compliance and suitable for 24 V DC input voltage, ambient temperature range -20 to 35 °C, class III safety, along with all necessary accessories complete all as specified and directed by the engineer-in-charge.
S & F of emergency exit sign having 3 hrs duration, LED light source engine with luminaire light beam spread 55°, upward light output ratio 0.01, luminous flux 85 lm, luminous efficacy ≥ 32 lm/W, luminous flux tolerance ±5%, initial chromaticity ≤ 0.33, colour rendering index (CRI) > 80, initial colour rendering index tolerance ±2%, correlated colour temperature 6500 K, standard tilt angle post top 0°, standard tilt angle side entry 0°, power factor 0.4, internal control interface (no external connection), suitable for input voltage 220-240 V at line frequency 50 Hz having initial / average / end CLO power consumption 4 W, inrush current 4 A, inrush time 100 ms, power consumption 4 W, 2 Push-in connector 3-pole connection, lithium battery (LiFePO4) suitable for 4 W power consumption during central DC emergency mode, 85 lm emergency lux, polycarbonate housing, UV stabilized polycarbonate optic cover, having overall dimensions 30 X 186 X 330 mm (H X W X D) complete all as specified and directed by the engineer-in-charge.
S & F of BEE 5-star rated energy efficient ceiling fan of sweep size 1200 mm complete wit blades, downrods, ZZ shielded double ball bearing, BLDC motor and remote control having speed control, boost mode, timer & sleep mode to ensure air delivery of ≥ 235 CMM having fan speed ≤ 360 rpm, energy consumption ≤ 28 W, service value ≥ 6.7, power factor ≥ 0.98 and suitable for input voltage 140-285 V, frequency 48-52 Hz, including wiring, fan box, etc. and other necessary accessories complete all as specified and directed by the engineer-in-charge.
M & L for point wiring using 1.1 kV grade single core FR-LSH flexible wires 2.5 sqmm, conforming to IS 694: 2010, having multi-drawn thin strands of electrolytic copper conductors and insulation for phase, neutral, and earth continuity conductor connecting to earth dolly, colour-coded as per IS 11353: 1985, drawn in medium grade stove enamelled steel surface / recessed conduits, conforming to IS 9537 (Part- 2): 1981, of size not less than 20 mm NB, including cutting chases, factory made not less than 1.2 mm thick sunken, modular flush sheet galvanized metal enclosure haing zinc coating not less than 120 GSM, conforming to IS 14772: 2000, having top, bottom, side and back-wall knockouts for conduit entry from any direction, suitable modular cover-plates and making good of disturbed surfaces of wall / ceiling / floor, etc. complete all as specified in IS 732: 2019 and directed by the engineer-in-charge.
[ii] Sunken modular flush sheet metal enclosures shall be measured and paid for as separate item.
[iii] Modular cover plates shall be measured and paid for as a separate item.
One light point controlled by one switch, with cables 2.5 mm² size
One additional light point on the same switch, with cables 2.5 mm² size
One light point controlled by two 2-way switches, with cables 2.5 mm² size
One 6 A socket outlet, on the same board with other switches, with cables 2.5 mm² size
One 6 A socket outlet, independent, with cables 2.5 mm² size
One 6/16 A socket outlet, independent, with cables 2.5 mm² size
One 25 / 32 A socket outlet, independent, with cables 4 mm² size
S & F modular type 6 A 2-way SP switch conforming to IS 3854: 2012 with finger-proof terminal complete all as specified in IS 732: 2019 and directed by the engineer-in-charge.
S & F modular type 16 A 1-way SP switch conforming to IS 3854: 2012 with finger-proof terminal complete all as specified in IS 732: 2019 and directed by the engineer-in-charge.
S & F modular type 2/3 pin combined shuttered type 6 A socket, conforming to IS 1293: 2005 complete all as specified in IS 732: 2019 and directed by the engineer-in-charge.
S & F modular type 3 pin combined shuttered type 6/16 A socket, conforming to IS 1293: 2005 complete all as specified in IS 732: 2019 and directed by the engineer-in-charge.
S & F 3 pin, 6 A, 250 V ceiling rose conforming to IS 371: 1999 and having terminal capacity 3 X 1.5 mm² with IK 04 and IP 20 protection complete all as specified in IS 732: 2019 and directed by the engineer-in-charge.
S & F factory made screwless, dust proof cover plates having superior finish, rounded corners, and solid strength supported by plastic frame behind with flexible wall alignment, horizontal adjustment facility complete all as specified and directed.
1 module
2 module
3 module
4 module
6 module
8 module
S & F factory made not less than 1.2 mm thick sunken, modular flush sheet galvanized metal enclosure haing zinc coating not less than 120 GSM, , conforming to IS 14772: 2000, having top, bottom, side and back-wall knockouts for conduit entry from any direction, suitable modular cover-plates complete all as specified and directed by the engineer-in-charge.
1/2 module
3 module
4 module
6 module
8 module
M & L for submain wiring using 1.1 kV grade single core FR-LSH flexible cable conforming to IS 694: 2010, having multi-drawn thin strands of electrolytic copper conductors and insulation for phase, neutral and earth continuity conductor connecting to earth dolly, colour-coded as per IS 11353: 1985, drawn in medium grade stove enamelled steel surface / recessed conduits, conforming to IS 9537 (Part- 2): 1981, of size not less than 25 mm NB, including making good of disturbed surfaces of wall / ceiling / floor all complete as specified in IS 732: 2019 and directed by engineer-in-charge.
2 X 1.5 mm² + 1 X 1.5 mm² earth wire
2 X 2.5 mm² + 1 X 2.5 mm² earth wire
2 X 4.0 mm² + 1 X 4.0 mm² earth wire
S & F 4' surface mounted / suspended batten having LED light source engine delivering full window illumination, integral fixed output driver, 120° beam angle of light source, luminous flux ≥ 4000 lm, luminous efficacy ≥ 120 lm/W, power consumption ≤ 34 W, power consumption tolerance ±10%, initial correlated colour temperature (CCT) 6500K, colour rendering index (CRI) ≥ 80, SDCM < 5, power factor > 0.95, median useful life L70B50 @ Ta = 45 °C ≥ 50000 hrs, surge protection level ≥ 4 kV with steel housing, polycarbonate optical cover / lens, IP20 & IK02 protection, and and suitable for mounting on normally flammable surfaces, 140- 270 V input voltage, 50 Hz line frequency, ambient temperature range 0 to 45 °C, class I safety, along with surface / suspended (asymmetric / symmetric) mounting device and all necessary accessories complete all as specified and directed by the engineer-in-charge.
4 X 4.0 mm² + 1 X 4.0 mm² earth wire
4 X 6.0 mm² + 1 X 6.0 mm² earth wire
Note : Phase & neutral conductors, earth continuity conductor and surface / recessed conduit shall be measured combined as one length.
S & F single pole & neutral, modular type, double door, metallic distribution board conforming to IEC 61439-3, suitable for flush / surface mounting with provision for DP RCCB / RCBO / Isolator / MCB as incomer and SP MCBs as outgoing, reversible metal door, 100 A copper busbar, fully shrouded neutral bar, earth bar, wire set & cable ties for cable management, pre fitted masking sheet, etc. having IK 09 & IP 43 protection complete all as specified in IS 732: 2019 and directed by the engineer-in-charge.
single pole & neutral double door DB, 18 way
S & F triple pole & neutral double door, modular type, double door, per phase isolation metallic distribution board conforming to IEC 61439-3, suitable for flush / surface mounting with provision for FP RCCB / RCBO / Isolator / MCB as incomer and SP MCBs as outgoing, reversible metal door, 100 A copper busbar, fully shrouded neutral bar, earth bar, wire set & cable ties for cable management, pre fitted masking sheet, etc. having IK 09 & IP 43 protection complete all as specified in IS 732: 2019 and directed by the engineer-in-charge.
triple pole & neutral double door PPI DB, 4 way
triple pole & neutral double door PPI DB, 6 way
triple pole & neutral double door PPI DB, 8 way
triple pole & neutral double door PPI DB, 12 way
S & F vertical triple pole & neutral, double door metallic modular distribution board conforming to IEC 61439-3, suitable for flush / surface mounting with provision for MCCB up to 160 A as incomer and SP/TP MCBs as outgoing, reversible metal door, fully insulated 160 A copper busbar for each phase, two fully insulated & shrouded neutral bars, two earthbars, cable ties for cable management, prefitted masking sheet, etc. having IK 09 & IP 43 protection complete all as specified and directed by engineer-in-charge.
vertical triple pole & neutral double door DB, 12 way
vertical triple pole & neutral double door DB, 8 way
S & F MCB for AC applications conforming to IS/IEC 60898-1-2002, having breaking capacity Icn = 10 kA, sliding bottom clamp, colour coded on/off indication on dolly, bi-connect IP 20 protected lower terminals and sliding shutters, etc. complete all as specified in IS 732: 2019 and directed by the engineer-in-charge.
16 A, 230 V, 50 Hz, SP MCB (C curve)
6 A, 230 V, 50 Hz, 1P MCB (D curve)
16 A, 230 V, 50 Hz, SP MCB (D curve)
32 A, 415 V, 50 Hz, SP MCB (D curve)
40 A, 415 V, 50 Hz, DPN MCB (D curve)
40 A, 415 V, 50 Hz, DPN MCB (C curve)
32 A, 415 V, 50 Hz, TPN MCB (D curve)
40 A, 415 V, 50 Hz, TPN MCB (C curve)
40 A, 415 V, 50 Hz, TPN MCB (D curve)
S & F residual current device (RCD) conforming to IS 12640 (Part 2): 2016, assembled for AC applications having front face indication for earth leakage fault, sliding shutters, IP 20 protected terminals suitable for cable sizes up to 35 mm² , colour coded on / off indication on dolly, integrated label holder, etc. complete all as specified in IS 732: 2019 and directed by the engineer-in-charge.
16 A, 30 mA. 230 V, 50 Hz RCBO
25 A, 30 mA. 230 V, 50 Hz RCCB
25 A, 100 mA. 230 V, 50 Hz RCCB
S & F moulded case circuit breaker (MCCB), four pole, in single frame size up to 250 A with thermal magnetic trip unit (TMD), compression lug connectors, protection against overloads (Ir adjustable from 0.7- 1 X In), protection against short circuits (Isd adjustable from 1.5- 10 X Ir), inbuilt encapsulated double break roto active type instanteneous protection, earth fault leakage protection, etc. having Ics = 100% Icu = 25 kA as per IEC 60947-2 complete all as specified and directed by engineer-in-charge.
160 A, 415V, 25 kA, 50 Hz 4P MCCB
100 A, 415V, 25 kA, 50 Hz 4P MCCB
Supply, installation, testing and commissioning 3 channel DALI high frequency ballast controller for T4 / fluorescent / LED lamps with 3# 20A relay, allowing to control up to 192 DALI devices with 3 channels altogether, having DIN-rail mountable integral DALI bus power supply removing the need for an additional external device, programmed to operate automatically isolate the power circuit when all associated DALI channels are at 0%, suitable for 100 to 240 V, 50 / 60 Hz, 1-Ph supply at 0.1 A complete with accessories all as specified and directed by the engineer-in-charge.
The DALI high frequency ballast controller shall consist of the following:
[i] Control Outputs: 3 X DALI control outputs, each supporting a full DALI universe of 192 channels including backward channel DALI bus power supply
[ii] Internal 24 V rated 250 mA Control IO: 1 X RS485 DyNet serial port / DMX, 1 X AUX programmable dry contact input
[iii] DC supply 12V @ 200 mA
Supply, installation, testing and commissioning of wall-mounted 6 button keypad, mounted on a 2 module GI box, having front cover with backlight, built-in proximity & temperature sensors capable of automatically adjusting air-conditioning when integrated into the system, loaded icons like presentation scenario / meeting scenario / master on-off, power saving mode, etc. along with an LED indicator for each operation, available with icon labelling customization, having fully programmable options for individual control / group control / scene control / tasks, etc. and suitable for operating on 12 to 24 V DC SELV class II @ 32 / 20 mA from network complete with accessories all as specified and directed by the engineer-in-charge.
M & L RoHS compliant and UL listed category 6A, 4 pair F/UTP (shielded) LSZH 23 AWG twisted pair cable, having bare copper conductor, polyolefin insulation, LSZH jacket, aluminium / polyester shield (tape), characteristic impedance 100 ±15% Ω , maximum DC resistance 7.8 Ω/100 m, maximum delay skew 45 ns, normal velocity of propagation (NVP) 69%, maximum operating voltage 80 V, segregation Class c, fully compliant with the recommendations set forth by IEEE 802.3bt (Type 4) for the safe delivery of power over LAN cable when installed according to ISO/IEC 14763-2, CENELEC EN 50174-1, CENELEC EN 50174-2 or TIA TSB-184-A complete all as specified and directed by the engineer-in-charge.
Supply, installation, testing and commissioning of fully microprocessor-based, online double conversion, indoor, compact UPS of 30 kVA rating with latest generation 3-level IGBT (high-frequency PWM) inverter bridge technology, connected in parallel to have N+X redundancy up to a maximum of 4 units with built-in isolation transformer, VRLA-AGM lead-acid, sealed, maintenance-free batteries of suitable size and quantity along with mounting rack(s) to provide 30 minutes back up time, connecting cables (for UPS to battery and battery to battery) suitable size, 5” touch-screen display to monitor UPS status in real-time, relay contact board, Modbus RS485, SNMP-ethernet, USB, net interface, configurable acoustic alarms and signals, complete with all necessary components and accessories as specified and directed by the engineer-in-charge.
Make: Numeric, Reillo, Schneider
Make: Numeric, Reillo, Schneider
The UPS shall conform to the following specification:
[A] General Features
[1] Power: 30 kVA
[2] UPS Topology: ON LINE- Double Conversion
[3] Nominal Apparent Output Power: 30 kVA / 30 kW (unity power factor)
[4] Efficiency in Double Conversion Mode: Up to 94%
[5] Efficiency of AC to AC conversion in Eco Mode: > 98%
[6] UPS Operating Temperature: 0 to 40 °C
[7] Relative Humidity (non-condensing): < 95%
[8] Degree of Protection: IP20
[9] Audible Noise Level: < 65 dB
[10] Electromagnetic Compatibility EMI: As per IEC EN 62040-2 (CE marking)
[11] Safety: AS per IEC EN 62040-1
[12] Test and performance: As per IEC EN 62040-3
[13] Accessibility: Front access
[14] Installation: Against the wall
[15] Front Panel: 5" touch-screen
[16] Serial Communication Interface: RS485 (Modbus RTU protocol)
[17] Parallel Configuration: Up to 3+1 (redundant parallel) or up to 4 (power parallel)
[B] Input: Rectifier and Battery Charger
[1] Power: 30 kVA
[2] Input: 3-Ph (3P4W)
[3] Nominal Input Voltage: 415 V
[4] Input Frequency: 50 Hz
[5] Input Frequency Range: ±10%
[6] Input Power Factor: > 0.99 @ rated linear load
[7] Input THDi < 3% @ rated linear load
[C] Batteries
[1] Power: 30 kVA
[2] Type: VRLA-AGM lead-acid, sealed, maintenance-free batteries
[3] Battery Test: As per standard
[D] Output Inverter
[1] Power: 30 kVA
[2] Nominal Active Power Output: 30 kW
[3] Output: 3P4W
[5] Output Voltage Frequency: 50 Hz
[6] Overload Capability: Upto 110% for 1 Hour,125% for 10 Min & 150% for 1 Min
[7] Output Waveform: Sinewave
[8] Maximum Creast Factor without Derating: 3:1
[9] Isolation Transformer: Integrated
M & L for earthing complete with copper earth plate electrode of 60 cm x 60 cm x 6 mm size, buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5 m below normal ground level, connected to copper strip of size 20 mm x 3 mm as earth lead, by means of bolts, buts, check nuts and washers of galvanised iron or steel, galvanized iron pipe of 40 mm diameter, connected to earthing test point, all as shown in electrical plate No. 5 connected to earthing test point all as specified or indicated including testing on completion and including excavation, earthwork, PCC earth pit of dimensions 550 mm X 550 mm (outer) and 300 mm X 300 mm (inner) and 250 mm deep, with a 10 mm thick CI cover, hinged to CI frame on ground level, GI watering pipe, funnel, etc. as all specified and directed by the engineer-in-charge.
M & L for earth contuinity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required 20 mm X 3 mm copper strip complete as specified and directed by the engineer-in-charge.
M & L for GI strip of size 25 mm x 4 mm as earth lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc complete all as specified and directed by the engineer-in-charge.
M & L for 8.0 mm diameter GI wire as earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. complete as all specified and directed by the engineer- in- charge.
Subtotal
Lump sum price worked out by the tenderer for “INTERNAL WATER SUPPLY WORKS" as listed in Schedule ‘A’ Part- III
Subtotal
Schedule ‘A’ Part- III (INTERNAL WATER SUPPLY WORKS)
Supply and fixing 15mm two way anlge cock with flange chromium plated, screwed down, high pressure, with crutch or butterfly handle, screwed for iron pipe or for unions complete all as specified and directed. (Make: Jaquar (continental series)/Hindware (contessa plus series)/Cera (ocean series or equivalent make).
Supply and fixing 15mm bore central hole basin mixer chromium plated for WHB complete all as specified and directed. (Make: Jaquar (continental series)/Hindware (contessa plus series)/Cera (ocean series or equivalent make).
Subtotal
Lump sum price worked out by the tenderer for “ROAD , PATH & CULVERTS WORKS" as listed in Schedule ‘A’ Part - IV
Schedule ‘A’ Part- IV (ROAD , PATH & CULVERTS)
Providing and consolidating 50 mm thick premix Dense Bituminous Macadam (DBM Grading-11) using min 4.5% VG 40 grade binder by weight of total mix aggregate gradation as per Grading 2 of Table 5001 0 of MaRTH specification for road and bridge works 2013, rolled and compacted to required camber and gradient complete all as specified and directed
M&L for Thermoplastic road marking paint 2mm thick painting (lines,dashes,arrows,letters etc) with road safety spikeries glass beads @ 8% by weight including preparation of new or previously treated road surfaces and applying paint by using special applicator machine with heating arrangement complete all as specified and as directed.
M&L for Pre-cast cement concrete type B1 1:2:4 (20 mm graded stone aggregate) as in kerb stone, masonry with solid blocks, exc. 10 cm in width and setting in cement mortar 1:3, shape & size decided by GE complete all as specified and directed.
Subtotal
Lump sum price worked out by the tenderer for “AREA DRAINAGE WORKS" as listed in Schedule ‘A’ Part -V
Lump sum price worked out by the tenderer for “SEWAGE DISPOSAL WORKS" as listed in Schedule ‘A’ Part VI
Schedule ‘A’ Part VI (SEWAGE DISPOSAL WORKS)
DWCPE Pipe ISI Marked, class SN-8, with all fittings, laid in trenches and jointed, complete all as specified of size:-
(a) 200mm bore
Subtotal
Lump sum price worked out by the tenderer for “COMPOUND WALL, FENCING & GATE" as listed in Schedule ‘A’ Part -VII
Lump sum price worked out by the tenderer for “EXTERNAL WATER SUPPLY" as listed in Schedule ‘A’ Part -VIII
Schedule ‘A’ Part -VIII (EXTERNAL WATER SUPPLY)
M & L centrifugally cast ductile iron pipe (K7 class), conforming to IS 8329: 2000 with flanged type (including suitable size of rubber gasket, nut & bolt) and fittings conforming to IS 9523: 2000 in any length laid in trenches complete as specified and directed by the engineer-in-charge.
M & L PN 1.6 rated GI Puddle Flange designed & manufactured as per BS 1560-3.1 & BS 4504 for suction of water pumps from water tank all complete all as specified and directed by the engineer-in-charge.
M & L PN 1.0 rated 50 mm NB swing type foot valve, conforming to IS 4038: 1986, suitable for vertical installation and having cast iron body & strainer, nitrile reinforced ball, nitrile sealing ring, CS fasteners, enamel paint, threaded end connection and accessories complete all as specified and directed by the engineer-in-charge. Make: Kirloskar, Normex, Flomatic
M & L for PN 1.0 rated swing check type reflux (non return) valve, conforming to IS 5312 (Part 1): 2004, having cast iron body, door & diaphram, Leaded Tin Bronze seat rings, SS hinge pin, threaded end connection and accessories complete all as specified and directed by the engineer-in-charge. Make: Kirloskar, Leader, Venus
Supply, installation, testing and commissioning of automatic air-vent valve with 20 mm end connections, brass OT 58 body and cover, polyacetal lever, high density expanded polyethylene float, EPDM rubber plug, stainless steel spring, polyamide cap etc. suitable for maximum operating pressure of 16 bar and maximum operating temperature 115 °C respectively, installed on all high points in the water piping system to automatically remove the trapped air complete all as specified and directed by the engineer-in-charge. Make: Sant, Leader, Venus
Supply, installation, testing and commissioning of centrifugal monoset pump suitable for 2.0 litre/s discharge @ 28 mWC head, conforming to IS 9079: 2018 & tested as per IS 5120: 1977 having cast iron casing, enclosed type dynamically balanced cast iron impeller, carbon steel pump shaft, gland packed sealing, deep groove ball bearings, etc. with energy efficient (IE4) TEFC squirrel cage induction motor, conforming to IS 12615: 2018, and suitable for operation on 3-Ph, 415 V±10%, 50 Hz AC supply, base plate, mounting channel frame, accessories and fittings, viz. pressure gauges, thermometers, drains, coupling, coupling guard, vibration isolation arrangement by means of spring / rubber type mounting complete with accessories all as specified and directed by the engineer-in-charge. Make: Grundfos, KSB, Wilo Mather & Platt, Xylem
NOTES:
[i] The contractor shall verify pump head before placing the purchase order of pumps.
[ii] Necessary civil work viz. foundation for placement of pump and pump accessories shall be covered in the scope of work.
[iii] Pressure gauges, thermometers and drains shall be measured and paid for separately.
Supply, installation, testing and commissioning of factory made PLUNBING mcc of suitable size tested and IEC coded. It shall be CPRIapproved pane and having modular extensible design suitable for indoor mounting, internal arc compliance of minimum 70 kA for 0.5s, made out of 2.0 mm thick mild steel CRCA sheet, having both sides openable with hinged doors and locking arrangement, IP 54 & IK 10 protection, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labelling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel vitreous enamelled (white) with letters, figures and conventional skull and bones in signal red colour suitable for 3-Phase, 4-Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length and size, including fixing lugs, bolts, screws, etc. complete all as specified and directed by the engineer-in-charge.
Make: ABB, Schneider, Siemens and L&T
The Plumbing MCC shall comprise of the following:
[A] BUSBAR CHAMBER
[i] Set (3L + N) of copper busbar of rated capacity 100 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection- 1#
[B] INCOMING
[i] Circuit Breaker
(a) 63 A, 415 V, Ics = 100% Icu = 25 kA, 50 Hz 4P MCCB, conforming to IEC 60947-2: 2016, having thermal magnetic trip unit, adjustable overload setting, adjustable short-circuit setting, front indication LEDs, etc.- 06. Nos.
[ii] Instrumentation & Measurement
(a) Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 01#
(b) 80/5A Cl. 1.0 C.T. with 10 VA burden- 01#
(c) 6A, 10kA, 415V, 50 Hz 4P MCB- 01#
[iii] Indication & Annunciation
(a) LED phase indicators (Red, Yellow, Blue)- 01 Set
(b) LED status indicators (ON, OFF, TRIP)- 01 Set
[C] OUTGOING
[i] Circuit Breaker
(a) 32 A, 415 V, Ics = 100% Icu = 25 kA, 50 Hz 3P MCCB, conforming to IEC 60947-2: 2016, having thermal magnetic trip unit, adjustable overload setting, adjustable short-circuit setting, front indication LEDs, etc.- 03#
[ii] Motor Starter / Drive
[iv] Instrumentation & Measurement
(a) 50/5A Cl. 1.0 C.T. with 5 VA burden- 03#
(b) 0-50 A ammeter- 03#
[v] Indication & Annunciation
(a) LED status indicators (ON, OFF, TRIP)- 03 Set
NOTES:
[i] The busbars shall be of double deck arrangement for rating ≥ 1600A interleaved /non-interleaved design as per OEM. Separation of busbar shall be as per Form 4b.
[ii] ACBs shall have separately powered, individual fault trip indication LEDs (For overload, short circuit, earth fault and trip-unit failure) shall be available on the trip unit which shall function even in the absence of external power supply to the breaker.ACB shall be suitable for ZSI. Trip units shall have thermal memeory as standard.
[iii] All the MCCBs up to 250 A shall be with thermal magnetic trip unit & above 250A shall be with microprocessor trip units. To ensure failsafe emergency tripping of the breakers (ACBs & MCCBs), it shall be supplied with continuous rated shunt trip coils.
[iv] Necessary control and switching devices to execute the switching and control logic shall be deemed inclusive of the scope of supply irrespective of them being specified / not specified above or in the SLD.
[v] The Panel / Switchboard shall be tested to withstand vibration caused by an earthquake in accordance with IEC 60068-3-3:2013 or IS 1893 Zone V.
[vii] All the necessary noble components (viz., structural, Door noble like hinge, Bush, Door alignment guage and Bus bar noble - Bus bar support, Close profile structure - horizontal & vertical) of the Panel shall be supplied by the OEM.
[ix] The Contractor shall intimate the Engineer-in-Charge of the routine tests in the OEM factory in presence of a representative nominated by the Engineer-in-Charge before dispatch.
M & L for 1.1 kV grade XLPE insulated armoured cable conforming to IS 7098 (Part 1): 1988, having stranded compact shaped conductors as per Cl. 2 of IS 8130: 1984, PVC inner sheath, single armouring of galvanised steel strip/wire and PVC Type ST-2 outer sheath conforming to IS 5831: 1984, including necessary clamping / dressing with cable ties and termination complete as all specified and directed by engineer- in- charge. Make: Havells, Polycab, RR Kabel
3 core 4 mm2, 2XWY
S & F perforated hot dipped galvanized iron cable tray having galvanization thickness not less than 50 microns and perforation not more than 17.5% including fittigs viz. joints, bends, tees, etc. in convenient sections of length, including fixing arrangement suitable for site conditions complete all as specified and directed by the engineer-in-charge.
100 mm X 50 mm X 1.6 mm
Subtotal
Lump sum price worked out by the tenderer for “EXTERNAL ELECTRIC SUPPLY" as listed in Schedule ‘A' Part -IX
Schedule ‘A’ Part -IX (EXTERNAL ELECTRIC SUPPLY)
Supply, installation, testing and commissioning of factory fabricated, damp & vermin-proof, metal clad, fully compartmentalized, floor-standing, dead front, fully type tested indoor type 11 KV ICOG Panel, conforming to IEC 62271-100, IEC 62271-102 & IEC 62271-200, with VCB compartment, cable compartment, busbar compartment and LV compartment and readily extensible on both sides, suitable for severe tropical climate conditions conforming to IEC 60068-2-30, having horizontal isolation, horizontal draw-out & floor mounted trolley type VCB, SCADA compatible facilities, ingress protection rating IP 4X & IP 53 (for 12 kV, 21 kA for 3 second), automatic independent safety shutters to prevent accidental contact with live parts, pad lockable door to ensure operator safety, internal arc classification AFLR up to 40 kA for 1 second and 50 kA for 0.5 second, surge arrestors, annunciator, power pack, earthing truck, integral earthing switch, safety interlocks, viz., secondary disconnecting switch (SDS) interlocks, breaker rack in / rack out interlocks, earthing interlocks, etc., made out of 2.0 mm thick mild steel CRCA sheet, etc. along with short-circuit and earth fault protection for rupturing capacity of 350 MVA complete with accessories all as specified and directed by the engineer-in-charge. Make: ABB, Schneider, Siemens
The 11 KV ICOG PANEL shall comprise of the following:
[A] CIRCUIT BREAKER
(a) 630 A, 11 kV, 3P VCB, conforming to IEC 62271-100, with air as the insulating medium in a metal clad enclosure, conforming to IEC 62271-200, and having short-time current rating 26.3 kA (for 3 second), mechanical endurance class M2, electrical endurance class E2, inbuilt anti-pumping, true close door operation, individual shutter assmbly and default test / service indication with mechanical life > 10000 operations, suitable for operating sequence O-0.3s-CO-3 min-CO, break time < 3 s, IP 4X protection, 24 V, 110 V, 220 V DC closing and tripping coil voltage, 24 V, 110 V, 220 V DC / 230 V AC spring charging motor voltage, 6 NO + 6 NC auxiliary contacts - 01 Nos.
[B] PROTECTION DEVICES
(a) Undervoltage Relay: 01 Nos.
(b) Reverse Phase or Phase Balance Current Relay: 01 Nos.
(c) Phase Sequence or Phase Balance Voltage Relay: 01 Nos.
(d) Machine or Transformer Thermal Relay: 01 Nos.
(e) Instantaneous Overcuurent Relay: 01 Nos.
(f) Instantaneous Overcurrent (Neutral) Relay: 01 Nos.
(g) AC Inverse Time Overcurrent Relay: 01 Nos.
(h) AC Inverse Time Overcurrent Relay (Neutral): 01 Nos.
(i) Overvoltage Relay: 01 Nos.
(j) Pressure Switch (Transformer): 01 Nos.
(k) AC - Reclosing Relay: 01 Nos.
(l) DC Supply Supervision Relay: 01
(m) Frequency Relay: 01 Nos.
(n) Master Trip (Lock Out) Relay: 01 Nos.
(o) Differential Protective Relay (bus): 01 Nos.
(p) Trip Circuit Supervision Relay: 01 Nos.
(q) P.T Fuse Failure Relay: 01 Nos.
(r) Surge Arrestor: 01 Nos.
[C] INSTRUMENTATION & MEASUREMENT
(a) Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 01 Nos.
(b) 80/5A Cl. 5P10 C.T. with 15 VA burden- 02 Nos.
(c) 80/5A Cl. 0.5 C.T. with 15 VA burden- 01 Nos.
(d) 11/√3 kV / 110/√3 V Cl. 3P P.T. with 50 VA burden- 01 Nos.
(f) HT HRC fuse- 01 Nos.
(g) 6A, 10kA, 415V, 50 Hz 4P MCB- 01 Nos.
[D] INDICATION & ANNUNCIATION
(a) LED phase indicators (Red, Yellow, Blue)- 01 Set
(b) LED status indicators (ON, OFF, TRIP, TCH)- 01 Set
(c) LED status indicators (SC, SP, TP, DF, AF)- 01 Set
(d) Auto / Manual Switch- 01 Set
(e) EM (emergency) Switch- 01 Set
(f) TNC Switch- 01 Set
(g) Annunciator: 01 Nos.
(h) Hooter: 01 Nos.
NOTES:
[i] The Panel shall be purchased from the original equipment manufacturer (OEM) or OEM authorized franchises only.
[ii] The Contractor shall intimate the Engineer-in-Charge of the routine tests in accordance with IEC 62271-200 & IEC 62271-100 in the OEM factory and the tests shall be performed in presence of a representative nominated by the Engineer-in-Charge before dispatch.
[iii] The Contractor shall furnish dimensional drawings of the items offered indicating all the fittings, dimensional tolerances, typical GADs, etc. to the Engineer-in-Chargee for approval of the MEP Consultant and thereafter A.O. / representative.
[iv] Digital type multi- function meter displaying A, V, PF, Hz, kW, kVA, kVAr, kWh, kVArh, etc.) of class 0.5 accuracy with RS485 port for communication in Modbus protocol shall be provided.
[vi] CTs shall be double core window / bar primary. Maximum VA burden shall be 15 VA and rated for full short circuit current for 1 s. CTs shall be of a minimum accuracy of class 0.5/5P10 and CT Secondary rating shall be 5 A unless otherwise specified.
[vii] PT shall be 3-Phase, 3-Limb type with 50 VA per phase of class 0.5/3P accuracy and shall be mounted on incomer breaker truck. The same shall be mounted in a separate withdrawable truck in a separate verticle panel for bus connected PT.
[viii] Control supply for closing and tripping shall be 110 / 220 V DC through an external battery source. 230 V, 50 Hz 1-Ph AC supply shall be also be available for the operation of spring charging motor and cubical space heater. Wattage rating of clossing and tripping coils shall be within 250 W.
[ix] All other secondary wiring in the panel shall have high quality FR-LHS insulation and the same shall have conductor size of not less than 1.5 m2 copper.
Supply, installation, testing and commissioning of factory made, main LT panel of suitable size tested and IEC codes. It shall be CPRIapproved panel and having modular extensible design suitable for indoor mounting, internal arc compliance of minimum 70 kA for 0.5s, made out of 2.0 mm thick mild steel CRCA sheet, having both sides openable with hinged doors and locking arrangement, IP 54 & IK 10 protection, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labelling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel vitreous enamelled (white) with letters, figures and conventional skull and bones in signal red colour suitable for 3-Phase, 4-Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length and size, including fixing lugs, bolts, screws, etc. complete all as specified and directed by the engineer-in-charge. Make: ABB, Siemens, Schneider and L&T.
The MAIN LT PANEL shall comprise of the following:
[A] BUSBAR CHAMBER
[i] 01 Set (3L + N) of copper busbar of rated capacity 1000 A, 50 kA, 415V, 50 Hz covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection
[B] INCOMING
[i] Circuit Breaker
[ii] Instrumentation & Measurement
(a) Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 02 Nos.
(b) 1000/5A CL5P10 C.T. with 15 VA burden- 02 Nos.
(c) 1000/5A Cl. 1.0 C.T. with 15 VA burden- 03 Nos.
(f) 6A, 10kA, 415V, 50 Hz 4P MCB- 02 Nos.
[iii] Indication & Annunciation
(a) LED phase indicators (Red, Yellow, Blue)- 02 Set
(b) LED status indicators (ON, OFF, TRIP)- 02 Set
(c) LED status indicators (SC, SP, TP)- 02 Set
(d) Auto / Manual Switch- 02 Set
(e) EM (emergency) Switch- 02 Set
(f) TNC Switch- 02 Set
[C] OUTGOING
[i] Circuit Breaker
(b) 320 A, 415 V, Ics = 100% Icu = 25 kA, 50 Hz 4P MCCB, conforming to IEC 60947-2: 2016, having microprocessor based trip unit, adjustable overload setting, adjustable short-circuit setting, adjustable neutral protection, front indication LEDs, etc.- 02 Nos.
(c) 320 A, 415 V, Ics = 100% Icu = 25 kA, 50 Hz 3P MCCB, conforming to IEC 60947-2: 2016, having microprocessor based trip unit, adjustable overload setting, adjustable short-circuit setting, adjustable neutral protection, front indication LEDs, etc.- 01 Nos.
(d) 160 A, 415 V, Ics = 100% Icu = 25 kA, 50 Hz 4P MCCB, conforming to IEC 60947-2: 2016, having thermal magnetic trip unit, adjustable overload setting, adjustable short-circuit setting, front indication LEDs, etc.- 02 Nos.
(e) 80 A, 415 V, Ics = 100% Icu = 25 kA, 50 Hz 3P MCCB, conforming to IEC 60947-2: 2016, having thermal magnetic trip unit, adjustable overload setting, adjustable short-circuit setting, front indication LEDs, etc.- 01 Nos.
(f) 63 A, 415 V, Ics = 100% Icu = 25 kA, 50 Hz 4P MCCB, conforming to IEC 60947-2: 2016, having thermal magnetic trip unit, adjustable overload setting, adjustable short-circuit setting, front indication LEDs, etc.- 06. Nos.
[ii] Indication & Annunciation
(a) LED status indicators (ON, OFF, TRIP)- 14 Set
(b) LED status indicators (SC, SP, TP)- 14 Set
(c) LED status indicators (SC, SP, TP)- 02 Set
(d) Auto / Manual Switch- 02 Set
(e) EM (emergency) Switch- 02 Set
(f) TNC Switch- 02 Set
NOTES:
[i] The busbars shall be of double deck arrangement for rating ≥ 1600A interleaved /non-interleaved design as per OEM. Separation of busbar shall be as per Form 4b.
[ii] ACBs shall have separately powered, individual fault trip indication LEDs (For overload, short circuit, earth fault and trip-unit failure) shall be available on the trip unit which shall function even in the absence of external power supply to the breaker.ACB shall be suitable for ZSI. Trip units shall have thermal memeory as standard.
[iii] All the MCCBs up to 250 A shall be with thermal magnetic trip unit & above 250A shall be with microprocessor trip units. To ensure failsafe emergency tripping of the breakers (ACBs & MCCBs), it shall be supplied with continuous rated shunt trip coils.
[iv] Necessary control and switching devices to execute the switching and control logic shall be deemed inclusive of the scope of supply irrespective of them being specified / not specified above or in the SLD.
[v] The Panel / Switchboard shall be tested to withstand vibration caused by an earthquake in accordance with IEC 60068-3-3:2013 or IS 1893 Zone V.
[vi] The Panel shall be purchased from the original equipment manufacturer (OEM) or OEM authorized franchises only.
[vii] All the necessary noble components (viz., structural, Door noble like hinge, Bush, Door alignment guage and Bus bar noble - Bus bar support, Close profile structure - horizontal & vertical) of the Panel shall be supplied by the OEM.
[viii] The Contractor shall furnish dimensional drawings of the items offered indicating all the fittings, dimensional tolerances, typical GADs, etc. to the engineer-in-charge for approval of the MEP Consultant and thereafter A.O. / representative.
[ix] The Contractor shall intimate the Engineer-in-Charge of the routine tests in the OEM factory in presence of a representative nominated by the Engineer-in-Charge before dispatch.
Supply, installation, testing and commissioning of free-standing indoor semi-compartmentalised cubical type 100 kVAr APFC Panel made out of 2.0 mm thick CRCA sheet and built upon rigid framework, having MPP type capacitor with 7% aluminium wound reactor units type tested in accordance with CPRI approved panel or IS 16636: 2017 with contactor switching, IP 4X protection and including air system provided by axial flow fan or centrifugal fan, control wiring with FR-LSH copper wires complete as specified and directed by the engineer-in-charge. Make: ABB,LK E&A, Schneider, Siemens
The APFC Capacitor Bank shall comprise of the following:
(c) 320 A, 415 V, Ics = 100% Icu = 25 kA, 50 Hz 3P MCCB, conforming to IEC 60947-2: 2016, having microprocessor based trip unit, adjustable overload setting, adjustable short-circuit setting, adjustable neutral protection, front indication LEDs, etc.- 01 Nos.
[ii] High performance microprocessor based APFC relay with auto / manual switch option- 01 Nos.
[iii] 3- Phase power analyser with in-built digital VAF meter, phase indicating LED lamps (R, Y, B), step indicating LED lamps, ON / OFF push buttons, timer, CT- 400/5 A, Cl1.0, 15 VA- 01 Nos.
[iv] MPP capacitor of 100 (3 X 10 + 1 X 20 + 1 X 50) kVAr
[v] 10 kVAr- 03 STEPS
[a] 32 A, 415, Ics = 100% Icu = 50 kA, 50 Hz 3P MCCB with fixed magnetic settings and adjustable thermal settings- 03 Nos.
[b] 3P, 10kVAr power contactor (capacitor duty), 415 V, 50 Hz 230 VAC coil- 02 Nos.
[c] 7% detuned reactor, 3- Ph, 10 kVAr, 440 V, 50 Hz- 03 Nos.
[vi] 20 kVAr- 01 STEPS
[a] 50 A, 415, Ics = 100% Icu = 50 kA, 50 Hz 3P MCCB with fixed magnetic settings and adjustable thermal settings- 01 Nos.
[b] 3P, 20 kVAr power contactor (capacitor duty), 415 V, 50 Hz 230 VAC coil- 01 Nos.
[c] 7% detuned reactor, 3- Ph, 25 kVAr, 440 V, 50 Hz- 01 Nos.
[vi] 50 kVAr- 01 STEPS
[a] 80 A, 415, Ics = 100% Icu = 50 kA, 50 Hz 3P MCCB with fixed magnetic settings and adjustable thermal settings- 01 Nos.
[b] 3P, 50 kVAr power contactor (capacitor duty), 415 V, 50 Hz 230 VAC coil- 01 Nos.
[c] 7% detuned reactor, 3- Ph, 50 kVAr, 440 V, 50 Hz- 01 Nos.
NOTES:
[i] The APFC Panel shall be purchased from the original equipment manufacturer (OEM) or OEM authorized franchises only.
[ii] To ensure safety, reliability and accountability of component coordination, all the major capacitor bank components such as capacitor units, detuning reactors, PF controllers, circuit breakers, contactors and the enclosure system called for in this specification should preferably be from a single manufacturer. The OEM shall preferably manufacturer PFC components and switchgear.
[iii] The APFC Panel shall have 10% extra space for future expansion.
[iv] The APFC Panel shall be Internet of things (IoT) enabled and communicable / integrable with EMS.
[v] ACBs shall have separately powered, individual fault trip indication LEDs (For overload, short circuit, earth fault and trip-unit failure) shall be available on the trip unit which shall function even in the absence of external power supply to the breaker.ACB shall be suitable for ZSI. Trip units shall have thermal memeory as standard.
[vi] All the MCCBs up to 250 A shall be with thermal magnetic trip unit & above 250A shall be with microprocessor trip units. To ensure failsafe emergency tripping of the breakers (ACBs & MCCBs), it shall be supplied with continuous rated shunt trip coils.
[vii] Necessary control and switching devices to execute the switching and control logic shall be deemed inclusive of the scope of supply irrespective of them being specified / not specified above or in the SLD.
[viii] The Panel / Switchboard shall be tested to withstand vibration caused by an earthquake in accordance with IEC 60068-3-3:2013 or IS 1893 Zone V.
Supply, installation, testing and commissioning of IP54 rated sandwich type (3L+N+PE) busbar trunking system complete with two runs of 50 mm X 6 mm aluminium earthing strip and accessories all as specified and directed by engineer-in-charge.
1000 A BTS (from T/R to MLTP) complete as per manufacturer's instruction
Make: ABB, L&T, Schneider, Siemens
The BTS shall conform to the following technical specifications:
[A] GENERAL
[i] The busbar trunking system (BTS), both feeder and plug-in, shall be of sandwich construction. All components and fittings (straight length, elbow, tee, flanged end, cable tap-off box and circuit breaker etc.) shall conform to IEC 61439-6:2012 or UL 857 and shall be procured from the OEM of BTS. The BTS shall have IP 65 protection with canopy for outdoor application and IP 66 protection in accordance with IEC 60529: 1989.
[ii] The rated operation voltage of BTS shall not be less than 1 kV. The neutral conductor shall have the same cross-sectional area as the phase conductor and the earth busbar shall be provided on both sides of the housing.
[B] CERTIFICATE
[i] The busbar, of full range and each rating, shall pass full type tests specified in IEC 61439-6-2012. The certificate shall be issued by an international independent testing authority, e.g. ASTA. KEMA. UL, ERDA, CPRI etc.
[ii] A product safety mark, e.g. KEMA-KEUR, ASTA DIAMOND, UL and ERDA, CE, etc. shall be on the product offering a visual assurance of full product safety testing, factory inspection and ongoing surveillance under independent authority.
[iii] The BTS shall be certified for siesmic tests conforming to IEEE 693-2018 for seismic zone V.
[C] SHORT-CIRCUIT RATINGS & TESTS
[i] The entire BTS (busduct and plug-in box assembly) shall be capable of withstanding the short-circuit of electrical installation without undergoing any electrical, mechanical or thermal stress under fault condition at a service voltage of 1 kV at 50 Hz frequency. The minimum rated insulation voltage shall be 1 kV.
[ii] The certified minimum short-current withstand capacity
(a) for 800 A rating shall be 50 kA for 1 sec
(b) 1000 A rating shall be 50 kA for 1 sec
(c) for 1250 A rating shall be 65 kA for 1 sec
(d) for 1600 A rating shall be 80 kA for 1 sec
(e) for 1600 A rating shall be 80 kA for 1 sec
(f) for 2000 A rating shall be 80 kA for 1 sec
(h) for 2500 A rating shall be 80 kA for 1 sec
(i) for 3200 A rating shall be 100 kA for 1 sec
(j) forfor 4000 A rating shall be 100 kA for 1 sec.
(j) for 4000 A rating shall be 100 kA for 1 sec.
(k) for 5000 A rating shall be 100 kA for 1 sec.
(l) withstand capacity for 5000 A rating shall be 100 kA for 1 sec.
(m) withstand capacity for 6300 A rating shall be 100 kA for 1 sec.
[D] HOUSING
[i] The busbar trunking housing shall be constructed of 1.6 mm thick electro-galvanised steel and shall be provided with a suitable protective finish of epoxy paint.
[ii] The busbar trunking housing shall be totally enclosed non-ventilated for protection against mechanical damage and dust accumulation and it shall be tested for its characteristics offering resistance against corrosion. It shall also pass at least 1000 salt spray test to ensure its anti-corrosion ability.
[iii] The totally enclosed housing shall be manufactured by the BTS OEM and modifications of busbar trunking to make it totally enclosed by housing other than the busbar trunking OEM shall be unacceptable without written consent of the OEM.
[E] BUSBARS
[i] The busbars shall be of aluminium with tin / silver plating at joint and conductivity of the joint shall be > 60% IACS
[ii] There shall be no bolts passing through the busbars of the BBT.
[iii] Each busbar shall be insulated with Class-F (155 ⁰C) multilayer PET insulation. Epoxy and Mica insulation shall be unacceptable.
[iv] The temperature rise at any point of busbar trunking enclosure shall not exceed 55 ⁰C above the ambient temperature of 40 ⁰C when operated at the rated current.
[F] JOINTS
[i] The busbar trunking joint shall be of one-bolt type utilizing high strength steel bolt(s) and Belleville washers to maintain proper pressure over a large contact surface area.
[ii] The bolt(s) shall be torque indicating and at earth potential.
[iii] The nut(s) shall be of two-headed design to indicate proper torque has been applied and shall require only a standard long handle wrench to be properly activated.
[iv] Access shall be required to only see one side of the busbar trunking to tighten joint bolts.
[v] It shall be possible to remove any joint connection assembly to allow electrical isolation or physical removal of a busbar trunking length without disturbing adjacent busbar trunking lengths.
[G] PLUG-IN OPENING
[i] The connecting jaw of a plug-in unit shall plug directly onto the busbar and have full contact with busbar itself. Welded tab at plug-in busbar is unacceptable.
[ii] All contact on joint and plug-in opening shall be of copper strip in order to avoid external force damage on busbar while plugging in or plugging out operation.
[iii] On plug-in busbar trunking there shall be three dead front, hinged cover type plug-in opening on each side.
[iv] All openings shall be usable simultaneously. Busbar trunking shall be installed in such a manner that plugs are side mounted to permit practical use of all plug-in openings.
[v] It shall be possible to inspect the plug-in opening and busbars prior to the installation of plug-in units.
[H] SUPPORT STRUCTURE
[i] Support structure shall be provided as per OEM's recommendation.
[ii] Indoor feeder and plug-in busbar trunking shall be approved for hanger spacing of up to 3 m for horizontally mounted run and 4.88 m for vertically mounted runs. Outdoor feeder busbar trunking shall be approved for spacing up to 1.5 m for horizontally or vertically mounted runs.
[I] VOLTAGE DROP
[i] The voltage drop (sending end voltage minus receiving end voltage) specified shall be based on the busway operating at full rated current and stabilized operating temperature in
[ii] The 3- Phase line to line voltage drop shall not exceed 3.4 V per 100 feet length at 40% power factor concentrated load which may exist during motor starting.
[iii] The line to line voltage drop shall not exceed 4.1 V per 100 feet at the load power factor which produces the maximum voltage drop in the busway.
[J] INSPECTION / SUPPORT OF INSTALLATION
[i] The installation of busbar trunking system (BTS) shall be executed by skilled professionals with minimum experience of 5 yrs. having sufficient installation base & pre-commissioning experience.
[ii] The entire installation shall be directly supervised by the OEM.
[iii] The OEM shall also furnish a commissioning report underlining satisfactory installation after the commissioning of BBT system.
M & L for 1.1 kV grade XLPE insulated armoured cable conforming to IS 7098 (Part 1): 1988, having stranded compact shaped conductors as per Cl. 2 of IS 8130: 1984, PVC inner sheath, single armouring of galvanised steel strip/wire and PVC Type ST-2 outer sheath conforming to IS 5831: 1984, including necessary clamping / dressing with cable ties and termination complete as all specified and directed by engineer- in- charge.
4 core 10 mm2, 2XWY
4 core 6 mm2, 2XWY
4 core 4 mm2, 2XWY
M & L for 1.1 kV grade fire survival cable, conforming to IS 17505-1: 2021, and having electrolytic annealed plain / tinned copper (Class 1/2) conductor conforming to IS 8130: 2013, mica tape layer(s) primary insulation, cross linked PE (XLPE) / cross linked HFFR secondary insulation, thermoplastic HFFR inner sheath, glass fibre heat barrier tape, galvanized round wire armour, thermoplastic HFFR (HFS-TP 90) / Cross Linked HFFR (HSF-XL 90) outer sheath including necessary clamping / dressing with cable ties and termination complete as all specified and directed by engineer- in- charge. Make: Havells, Polycab, RR Kabel
3.5 core 35 mm2, (FS) 2XWY
Supply, installation, testing and commissioning of UL listed clean-agent fire suppression system designed to provide a uniform concentration within the electrical panels, conforming to NFPA 2021: 2022 complete all as specified and directed by the engineer-in-charge.
Make: Kanex, Ceasefire, Minimax, Agni
The clean-agent fire suppression system shall conform to the following technical requirements:
[A] GENERAL
[i] Provide all engineering design and materials for a complete agent suppression system including Clean Agent storage cylinders with steel bracket, extinguishing agent, detection tube, cylinder valve and associated accessories including but not limit to; adaptors, pressure switch, Fire Detection tube fittings etc, required for complete operation of system.
[ii] The necessary nomenclature such as pressurization level, agent volume, gross/net weight of cylinder shall be clearly marked on cylinder.
[B] STANDARDS
The design and installation of the Clean Agent based Fire Detection tube system is based on the latest applicable codes and also as per the manufacturer’s recommendations; the required Clean Agent gas quantity is arrived as per the volume of the respective panels to be protected. In addition, the following standards, references and rules and regulations shall be applicable:
[i] NFPA-2001-Standard on Clean Agent Fire Extinguishing System
[ii] Green Gas needs to use as per EPA/SNAP with low GWP
[iii] Detection components must be UL as per UL 521
[iv] Suppression agent as per NFPA-2001 & UL listed
[C] SYSTEM DESCRIPTION
[i] The UL detection tube shall be fixed with cylinder valve at top of cylinder. The tube shall be pressurized with dry nitrogen at 16 bars. In case of fire and on reaching of pre-determined temperature (120-140 °C), the tube shall rupture and gas shall be released from tube over the protected area.
[ii] The CE/UL listed pressure switch shall be provided for indication of discharge of gas.
[iii] The Extinguishing Agent (FK 5112 gas) shall be stored in PESO approved cylinder, super pressurized with dry nitrogen.
[iv] The PESO approved cylinder shall be equipped with direct low pressure valve, pressure gauge (to monitor agent pressure) and isolation valve for maintenance purposes. The cylinder bracket shall be of steel construction with quick release clamp.
[v] The Fire detection tube shall be installed throughout the compartments of panel. The location and spacing of tube shall be above the hazard, to be protected.
[vi] With system activation, a signal should be generated via Audio Visual Alarm installed at convenient location as per Engineer-in-Charge.
[D] SYSTEM COMPONENTS
[i] Storage Cylinder(s) (dedicated for each electrical cabinet/panel) to be PESO approved
[ii] UL/FM approved FK 5112 Clean Agent gas as per NFPA-2001
[iii] Low Pressure Direct Type Valve
[iv] Pressure Switch- CE/UL listed
[v] Fire Detection Tubing- UL listed with approval marking and red in color
[vi] End of Line adapter with pressure gauge, T connector, End of plug as per OEM
[vii] Control panel for indication and should be with potential free contacts to integrate with existing BMS/SCADA/Fire alarm system
[viii] Each cylinder shall have pressure gauge and low-pressure switch to provide visual and electrical supervision of the cylinder pressure. The low-pressure switch shall be wired to the Audio-Visual Alarm to provide audible and visual trouble alarm in the event of drop of pressure. The pressure gauge shall be color coded to provide an easy, visual indication of cylinder pressure
[E] APPROVALS
[ii] Clean agent FK 5112 gas- UL certificate
[iii] Pneumatic Heat Sensing Tube - UL Listed and marked certificate
[iv] Pressure Switch Assembly: CE/ UL Listed certificate
[v] PESO Approved filling station certificate
Clean Agent Fire Supression System for Main LT Panel (MLTP)
Clean Agent Fire Supression System for HVAC Panel
Clean Agent Fire Supression System for Fire MCC
M & L for GI octagonal poles complete with single arm brackets as specified all for 6 m long with 70 mm top diameter and 130 mm bottom diameter, made of 3 mm thick tensile sheet along with base plate of size 225 X 225 X 12 mm thick, including 04 Nos. of M24 X 750 long 'J' type foundation bolts, MCB with 4-way heavy duty connector 32 A, single arm bracket and RCC foundation as per manufacturer's drawing(s) complete as specified and directed by engineer-in-charge. Make: Bajaj, Utkarsh, Valmont
Supply, installation, testing and commissioning of streetlight with integral driver having LED light source engine with 120° beam angle of light source & 130° X 88° luminaire light beam spread, luminous flux ≥ 4200 lm, luminous efficacy ≥ 120 lm/W, nominal correlated colour temperature (CCT) > 70, power consumption ≤ 35 W, power consumption tolerance ±10%, power factor ≥ 0.95, surge protection level ≥ 4 kV, median useful life L70B50 ≥ 50000 hrs, polycarbonate distribution symmetric wide outdoor optic, aluminium pressure die cast housing, mounting device (spigot), IP 66 & IK 07 protection, suitable for ambient temperature range -10 to 50 °C, input voltage 140- 270 V, line frequency 50 Hz, etc., along with all necessary accessories complete with electric connection all as specified and directed by the engineer-in-charge. Make : Signify BRP331 LED42 CW R5N PC PSU S1 or equivalent model of iGuzzini, Trilux or ENDO Lighting
M & L for GI strip of size 50 mm x 6 mm as earth lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc complete all as specified and directed by the engineer-in-charge.
M & L for GI strip of size 32 mm x 3 mm as earth lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc complete all as specified and directed by the engineer-in-charge.
S & F perforated hot dipped galvanized iron cable tray having galvanization thickness not less than 50 microns and perforation not more than 17.5% including fittigs viz. joints, bends, tees, etc. in convenient sections of length, including fixing arrangement suitable for site conditions complete all as specified and directed by the engineer-in-charge.
300 mm X 50 mm X 1.6 mm
150 mm X 50 mm X 1.6 mm
100 mm X 50 mm X 1.6 mm
Supply, installation, testing and commissioning of silent LT Diesel GenSet of 625 kVA rating, conforming to ISO 8528-1, along with AMF panel with associated switchgear, control panel and exhaust piping as per latest CPCB norms (with amendments up to date at the time of execution), necessary foundation, HSD oil storage & distribution system etc. with all necessary statutory approvals complete all as specified and directed by the engineer-in-charge.
[A] GenSet
(i) Minimum Rating: 625 kVA / 500 kW
(ii) Maximum Rating: 688 kVA / 550 kW
(iii) Emissions / Fuel Strategy: Fuel Optimised
(iv) Starting System: 24 V DC electrical
(v) Overload: 10% for 1 hr in every 12 hrs
(vi) Cooling System: Radiator Cooled
(vii) Silencer Type: Residential
(viii) DG Set noise level as per CPCB norms: < 75 dBA
(ix) Mounting Type: AVM Pad
[B] Starting System
(i) Type of Starting System: Battery Starting System (Ele.)
(ii) Type of Battery: SMF VRLA type
(iii) Battery Voltage: 12 V
(iv) Number of Battery: 02 Nos.
(v) Ah Capacity: 180 Ah
[C] Engine
(i) Rated Output (Prime Rating) as per ISO 3046: 552 kW (750 HP)
(ii) Governing Class: G3
(iii) Governor Type: Electronic-A1
(iv) Specific Fuel Consumption @ 75% load: ≤ 144 g/Hp-hr
(v) Specific Fuel Consumption @ 100% load: ≤ 143 g/Hp-hr
(vi) Fuel consumption @ 50% load: ≤ 70 litre/hr
(vii) Fuel consumption @ 75% load: ≤ 100 litre/hr
(viii) Fuel consumption @ 100% load: ≤ 135 litre/hr
(ix) Fuel tank capacity: ≥ 990 litre (outside)
(x) Fuel tank thickness & MOC: 3 mm thick mild steel
(xi) Lube oil sump capacity: ≥ 50 litre
(xii) Lube oil consumption: ≤ 0.12% of SFC
(xiii) Lube oil Grade: CHW 15W 40
[D] Alternator Details
(i) Rating: 625 kVA
(ii) Phase / Voltage: 3 / 440 V
(iii) Power Factor (PF): 0.8 lag
(iv) Insulation: Class H
(v) Temperature Rise: Limited to Class H
(vi) Degree of Protection: IP 23
(vii) Rated Speed: 1500 RPM
(viii) Time to built up rated voltage at rated RPM 12-15 sec.
(viii) Excitation System: Separately Excited
(ix) Frequency: 50 Hz
(x) Voltage Variation: ±5%
(xi) Voltage Regulation: ±0.5%
[E] Integrated DG Set Controller
(1) Control:
(i) Run/ Off / Auto Switch
(ii) Emergency Stop
(iii) Manual Run Stop Control Switch
(iv) Idle / Run Mode Control
(2) Metering (Engine):
(i) Starting Battery Voltage
(ii) Lube Oil Temperature & Pressure
(iii) Engine coolant Temperature
(iv) Coolant Pressure
(v) Engine rpm
(vi) Operating Hours
(vii) Number of Starts
(3) Electrical:
(i) Current
(ii) Voltage
(iii) Frequency
(vii) kVA
(4) Protection / Warning (Engine):
(i) Overspeed Shutdown
(ii) Low Lube Oil Pressure Warning / Shutdown
(iii) High coolant Temperature Warning / Shutdown
(iv) Low coolant Temperature Warning
(v) Low Coolant Level Warning / Shutdown
(vi) Low and High Battery Voltage Warning
(vii) Weak Battery Warning
(viii) Over Crank Shutdwn
(ix) Fail to Crank Shutdown
(x) Magnetic Pickup Failure Shutdown
(4) Alternator:
(i) Overcurrent
(ii) High Voltage
(iii) Low Voltage
(iv) Under / Over Frequency
(v) Reverse Power (kVA & kVAr)
(vi) Phase Sequence
(i) Digital AVR
(ii) Amp Sentry Protection
(iii) Sensor Failure Indication
(iv) Programmable Idle Speed Control
(v) Digital Synchronizing Function
(vi) Sync Check
(vii) Synchronoscope
(viii) Auto Load Sharing
(ix) Compatibility to Remote Monitoring
(x) Smart Starting
[F] Exhaust System
(i) Exhaust piping of size 12" dia. (300 mm NB), 4.85 mm thick plate and 16" dia. & (400 mm NB) 5 mm thick, MS Class B pipes conforming to IS 3589: 2001 with 75 mm thick glasswool / mineral wool insulation with wire chicken mesh over insulation and 24 gauge aluminium sheet cladding over the exhaust pipes from silencer to atmosphere including welding joint(s), bend(s), clamp(s), dash fasteners, flanges, nuts, bolts, etc. complete as required and as per specification
(ii) Aluminium cladding for residential silencer with mineral wool 50 mm thick, density 64 kg/m3, wire mesh and 24 gauge aluminum cladding
(iii) MS self-support structure for exhaust piping
(iv) SS flexible bellows, 16" dia. (400 mm NB) complete with counter flanges, heat resistant gaskets, nuts, bolts and washers, etc. complete as required
(v) Lightning arrester with GI strip upto earth pit
[G] Power Cabling
(i) 3# of 1.1 kv grade 3.5 core, 185 mm2 2XWY cable, specified separately.
[H] CONTROL CABLES & TERMINATION KITS
(i) 24 core, 2.5 mm2, Cu conductor, XLPE insulated armoured control cable as required along with necessary termination kits
(ii) 4 core, 2.5 mm2, Cu conductor, XLPE insulated armoured control cable as required along with necessary termination kits
(iii) 2 core, 2.5 mm2, Cu conductor, XLPE insulated armoured control cable as required along with necessary termination kits
(iv) 4 core, 4 mm2, Cu conductor, XLPE insulated armoured control cable as required along with necessary termination kits
(v) 3 core, 6 mm2, Cu conductor, XLPE insulated armoured control cable as required along with necessary termination kits
[I] FUEL PIPE
(i) 50 mm NB MS Class C pipe of required length (ii) Fuel pipe fittings, viz. bends, flanges, valves, tees, elbows, etc as required
NOTES:
[iv] Necessary civil work viz. foundation for placement of the DG Set shall be deemed included in the scope of work.
[v] 3# of 3.5 core, 300 mm2 2XWY power cabling from the DG Set to the Main LT Panel shall be measured and paid for separately.
[ix] The Contractor shall intimate the Engineer-in-Charge of the routine tests in the OEM factory in presence of a representative nominated by the Engineer-in-Charge before dispatch.
Subtotal
Lump sum price worked out by the tenderer for “AIR CONDITIONING AND REFRIGERATOR" as listed in Schedule ‘A’ Part- X
Schedule ‘A’ Part - X (AIR CONDITIONING AND REFRIGERATOR)
Supply, installation, testing and commissioning of factory designed, pre-fabricated and floor-mounted AHRI certified screw type water-cooled chiller machine of actual capacity ≥ 115 TR, complete with semi-hermetic / hermetic screw compressors having single refrigerant circuit and automatic stepless capacity control, water-cooled S/T type condenser as per ASME / BIS, horizontal flooded type evaporator with carbon steel shell and seamless copper tubes with elastomeric insulation, suction gas cooled, hermetically sealed squirrel cage induction motor of appropriate rating with class 'B' insulation, etc., unit mounted VFD along with necessary drive arrangement, lubrication system as per manufacturer's design required for smooth and trouble-free operation of the chiller package, common base-frame, interconnected copper refrigerant piping along with elastomeric insulation, fittings, valves, expansion valves and accessories to interconnect compressor, condenser, chiller and expansion valve, microprocessor based control panel comprising of controls including sensors and equipped with a keyboard, LCD touchscreen access input system, protection and monitoring devices to perform control functions, wiring, vibration isolators, gauge panel, automatic safety controls, flow switch at evaporator and condenser connection ends and ozone friendly, CFC-HCFC free refrigerant complete all as specified and directed by the engineer-in-charge.
The chiller shall conform to the following requirements / specifications:
Chiller OEM and compressor shall be of same make not involved of 3rd party manufecturer
[i] Chilled water inlet/outlet temperature: 54 °F / 44 °F
[ii] Evaporator fouling factor: 0.00010 ⁰Fft²hr/Btu
[iii] Evaporator side pressure drop: 4 m of H2O (maximum)
[iv] Condenser water inlet/outlet temperature: 90 °F / 100 °F
[v] Condenser fouling factor: 0.00025 ⁰Fft²hr/Btu
[vi] Condenser side pressure drop: 6 m of H2O (maximum)
[vii] Minimum COP @ 100% load: 6 at AHRI conditions
[viii] Minimum IPLV @ 100% load: 0.38 at AHRI conditions
[ix] Minimum NPLV : 0.39 at site conditions
[x] Maximum Cooling ikW/TR @ 100% Load at site Condition: 0.7
[xi] Refrigerant: CFC & HCFC free ozone friendly refrigerant of A1 safety class as per ASHRAE Standard 34 having zero ODP.
[xii] Test standard: ARI 550 / 590
(xiii) Temperature shall be 25 ± 2 degreeand RH shall be 55 ± 5
NOTES:
[i] The chiller unit shall be at least 4 star-rated in conformity with the Table-3 of the gazette notification GE-DL-E-19092023-248822 issued by Ministry of Power, UoI, dated September 18, 2023.
[iii] Mapping shall be required for all critical points displayed on the chiller control panel. The chiller shall be BMS compatible and shall have RS485 / RS232 serial communication protocol.
[iv] The unit shall be suitable for 3- Phase, 415 V ± 10%, 50 Hz AC electric supply, with a built-in microprocessor based control panel.
[vi] Necessary civil work viz. foundation for placement of chillers, etc. shall be deemed included in the scope of work.
Supply, installation, testing and commissioning of volute type, single suction, horizontal centrifugal long coupled pump conforming to IS 9079: 2018 and suitable for 19.0 litre/s discharge @ 19 mWC head having cast iron casing, enclosed type dynamically balanced bronze impeller, carbon steel pump shaft, gland packed sealing, deep groove ball bearings, etc., with energy efficient (IE4) 4 pole TEFC squirrel cage induction motor, conforming to IS 12615: 2018, and suitable for operation on 3-Ph, 415 V±10%, 50 Hz AC supply, base plate, mounting channel frame, accessories and fittings, viz. pressure gauges, thermometers, drains, coupling, 360° covered coupling guard, vibration isolation arrangement by means of spring / rubber type mounting duly insulated with FM approved highly- flexible, closed-cell thermal insulation of elastomeric foam based on synthetic rubber (NBR) of appropriate thickness laminated with UV resistant polymer based non-metallic covering on one side along with adhesives and other necessary accessories complete all as specified and directed by the engineer-in-charge.
NOTES:
[i] The contractor shall verify pump head before placing the purchase order of pumps.
[ii] The pump assembly shall be suitable for speed regulation through VFD / VSD drive.
[iii] Necessary civil work viz. foundation for placement of pump and accessories shall be covered in the scope of work.
[iv] Pressure gauges, thermometers and drains shall be measured and paid for separately.
[v] Insulation shall be measured and paid for separately.
Supply, installation, testing and commissioning, factory assembled, industrial duty, induced draft, counter-flow type, film-fill FRP cooling tower suitable to cool 930 USGPM water from 36 ºC to 32 ºC (∆T 4 ºC) at entering wet bulb temperature 27.5 °C [3345 MBH / 981 kW / 280 TR actual heat rejection] having uniform water distribution and optimal heat transfer having casing of at least 3 mm thick UV stabilised fiberglass reinforced plastic (FRP) panels, laminated to each other providing a watertight seal, with HDG steel support structure of sufficient structural strength to withstand vibrations and wind velocity up to 50 m/s, 5 mm FRP fan deck acting as mechanical access platform, FRP hot water basin for water distribution with gravity-fed nozzles and a splash box for each hot water basin, open ended connection(s) for inlet to cooling tower, cross corrugated film type thermoformed PVC counter flow fill suitable for entering water temperatures up to 55 °C (supply water from chiller should not reach temperature exceeding 52 °C), thermoformed UV resistant polypropylene cellular drift eliminators having drift losses ≤ 0.005% of the water flow rate, propeller type gear-driven fan incorporating wide-chord geometry and having FRP blades and aluminium / HDG steel hubs, TEFC squirrel cage induction motor(s) to be installed outside moist air stream, conforming to IS 12615: 2018, with class 'F' insulation complete with accessories all as specified and directed by the engineer-in-charge.
NOTES:
[i] Necessary civil work viz. foundation, supporting structure, etc. for placement of cooling tower shall be deemed included in the scope of work.
[ii] The fan motor shall be suitable for 3- Phase, 415 V ± 10%, 50 Hz AC supply.
Supply, installation, testing and commissioning of volute type, single suction, horizontal centrifugal long coupled pump conforming to IS 9079: 2018 and suitable for 30 litre/s discharge @ 18 mWC head having cast iron casing, enclosed type dynamically balanced bronze impeller, carbon steel pump shaft, gland packed sealing, deep groove ball bearings, etc., with energy efficient (IE3) 4 pole TEFC squirrel cage induction motor, conforming to IS 12615: 2018, and suitable for operation on 3-Ph, 415 V±10%, 50 Hz AC supply, base plate, mounting channel frame, accessories and fittings, viz. pressure gauges, thermometers, drains, coupling, 360° covered coupling guard, vibration isolation arrangement by means of spring / rubber type mounting and other necessary accessories complete all as specified and directed by the engineer-in-charge.
NOTES:
[i] The contractor shall verify pump head before placing the purchase order of pumps.
[ii] Necessary civil work viz. foundation for placement of pump and accessories shall be covered in the scope of work.
[iii] Pressure gauges, thermometers and drains shall be measured and paid for separately.
HOT WATER GENERATOR
Supply, installation, testing and commissioning of fully BMS and SCADA compatible IP 55 rated electric Hot Water Generator (HWG) in vertical configuration, suitable for 275 kW heat output or 23276 kg/hr water flowrate, 2.5 to 4.0 kg/cm2 operating pressure range and 30 °C to 95 °C operating temperature range, having automatic stage sequence reversal, slave SCR power controller to modulate the entire load from 0-100%, embedded LCD, RS-232C / RS-485 port & ethernet port for communication, in-built self-diagnostic tool, etc. complete all as specified and directed by the engineer-in-charge.
The HWG shall conform to the following requirements / specifications:
[A] HEATING ELEMENTS
[i] Pressure-rated flanged type immersion heaters, conforming to IS 4159: 2002, consisting of multiple tubular heating elements formed into hairpins which are silver-brazed to a mating flange
[B] PRESSURE VESSEL
[i] Water Vessel, conforming to IS 2825: 1969 rated for 160 psig maximum working pressure at 120 °C and tested at 300 psig having top openable thick MS plate designed for maximum element to water contact for efficient operation, welded to shell flange
[ii] Connections for water inlet & outlet with mating flanges
[iii] Descaling point & drain connection for system drainage
[C] INSULATION
[i] 50 mm thick resin bounded fibreglass wool of density 32 kg/cum and cladded with aluminum sheet to minimum heat loss
[D] CONTROL CABINET
[i] Integral control panel made out of 2.0 mm thick powder coated CRCA sheet having louvers to insure adequate ventilation of the control and heater terminal compartment
[ii] Base frame fabricated out of ISMC100 channel
[iii] hinged doors with lockable padlocks for access to all control compartments
[E] CONTROL & SAFETY
[i] Incomer MCCB with electrolytic grade copper busbar and mechanical interlock for safe operation
[ii] Magnetic Contactors with MCB / HBC fuses for heater switching
[iii] Pilot lights indicating the functional operation, i.e. Phase Indication, Each Stage ON, Supply ON, etc.
[iv] Alarm package to de-energiz the boiler and give audible and visual indications of high temperature, low water level or zero flow rates (each condition should be indicated with a separate pilot light)
[v] Pressure Relief Valve & Air Purge Valve
[vi] Temperature & Pressure gauges at both inlet and outlet
[F] STEP CONTROLLER
[I] Temperature Control using microprocessor based multi-stage electronic progressive staging sequencer with thermistor sensor to control the HWG in stages
[ii] Logic and Control circuits to continuously monitor the input signal to determine if more or less heat is required
HOT WATER PUMP (1W + 1S)
Supply, installation, testing and commissioning of volute type, single suction, horizontal centrifugal long coupled pump conforming to IS 9079: 2018 and suitable for 7.0 litre/s discharge @ 18 mWC head having cast iron casing, enclosed type dynamically balanced bronze impeller, carbon steel pump shaft, gland packed sealing, deep groove ball bearings, etc., with energy efficient (IE4) 4 pole TEFC squirrel cage induction motor, conforming to IS 12615: 2018, and suitable for operation on 3-Ph, 415 V±10%, 50 Hz AC supply, base plate, mounting channel frame, accessories and fittings, viz. pressure gauges, thermometers, drains, coupling, 360° covered coupling guard, vibration isolation arrangement by means of spring / rubber type mounting duly insulated with FM approved highly- flexible, closed-cell thermal insulation of elastomeric foam based on synthetic rubber (NBR) of appropriate thickness laminated with UV resistant polymer based non-metallic covering on one side along with adhesives and other necessary accessories complete all as specified and directed by the engineer-in-charge.
NOTES:
[i] The contractor shall verify pump head before placing the purchase order of pumps.
[ii] Necessary civil work viz. foundation for placement of pump and pump accessories shall be covered in the scope of work.
[iii] Pressure gauges, thermometers and drains shall be measured and paid for separately.
EXPANSION TANK
Supply and fixing PVC tank of following capacity incldingconnecting etc all as specified and directed.
HVAC PANEL
Supply, installation, testing and commissioning of factory made, fully compartmentalized bolted type HVAC Panel (design verified assembly- DVA) of suitable size with CPRI approved panel and having modular extensible design suitable for indoor mounting, internal arc compliance of minimum 70 kA for 0.5 s, made out of 2.0 mm thick mild steel CRCA sheet, having both sides openable with hinged doors and locking arrangement, IP 43 & IK 10 protection, supported and fixed on structural frame of angle iron of suitable size, including earthing stud, labelling, painting to all internal & external exposed steel surfaces with powder coating paint (7 tank process), duly fixed in ground with PCC foundation (1:2:4) type B1, with danger notice plate of 1.6 mm thick mild steel vitreous enamelled (white) with letters, figures and conventional skull and bones in signal red colour suitable for 3-Phase, 4-Wire system, 500 V grade with necessary wiring, PVC sheathed stranded copper conductor of appropriate length and size, including fixing lugs, bolts, screws, etc. complete all as specified and directed by the engineer-in-charge.
The HVAC Panel shall comprise of the following:
[A] BUSBAR CHAMBER
[i] Set of (3L + N) of copper busbar of rated capacity 800 A, covered with PVC insulated sleeves including insulator, nuts, bolts, etc. with complete connection- #01
[B] INCOMING
[i] Circuit Breaker
[ii] Instrumentation & Measurement
(a) Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 01#
(b) 800/5A Cl. 1.0 C.T. with 15 VA burden- 01#
(c) 6A, 10kA, 415V, 50 Hz 4P MCB- 01#
(a) Cl 1.0 multi-function meter capable of measuring V, A, F, PF, W/VA, Wh/VAh, Runhrs. Onhrs & interupts- 01#
(b) 800/5A Cl. 1.0 C.T. with 15 VA burden- 01#
(c) 6A, 10kA, 415V, 50 Hz 4P MCB- 01#
[iii] Indication & Annunciation
(a) LED phase indicators (Red, Yellow, Blue)- 01#
(b) LED status indicators (ON, OFF, TRIP)- 01#
(c) LED status indicators (SC, SP, TP)- 01#
(d) Auto / Manual Switch- 01#
(e) EM (emergency) Switch- 01#
(f) TNC Switch- 01#
[C] OUTGOING
[i] Circuit Breaker
(b) 320 A, 415 V, Ics = 100% Icu = 36 kA, 50 Hz 4P MCCB, conforming to IEC 60947-2: 2016, having microprocessor based trip unit, adjustable overload setting, adjustable short-circuit setting, adjustable neutral protection, front indication LEDs, etc.- 03#
(c) 100 A, 415 V, Ics = 100% Icu = 25 kA, 50 Hz 3P MCCB, conforming to IEC 60947-2: 2016, having thermal magnetic trip unit, adjustable overload setting, adjustable short-circuit setting, front indication LEDs, etc.- 03#
(d) 40 A, 415 V, Ics = 100% Icu = 25 kA, 50 Hz 3P MCCB, conforming to IEC 60947-2: 2016, having thermal magnetic trip unit, adjustable overload setting, adjustable short-circuit setting, front indication LEDs, etc.- 13#
[ii] Motor Starter / Drive
(a) Variable Frequency Drive (VFD) of 7.5 kW rating comprising of the following complete with accessories of ABB, Danfoss, LK, Schneider or Siemens make- 04#
The VFD drive shall conform to the following technical specification.
(1) built-in dual 5% impedance DC link reactor (harmonic filters) on the positive and negative rails of the DC bus of the variable frequency drive (VFD).
(2) built-in EMC filters (electro magnetic compatibility filters) for restriction of conducted emissions to comply with IEC61800: 3 (unrestricted distribution): 2004 category C 1 (50 meter)
(3) three feedback PID controller having capability to simultaneously accept 3 feedback signals from temperature sensors or pressure sensors
(4) integral graphical keypad.
[ii] Instrumentation & Measurement
(a) 50/5A Cl. 1.0 C.T. with 5 VA burden- 13#
(b) 0-50 A ammeter- 13#
[iii] Indication & Annunciation
(a) LED status indicators (ON, OFF, TRIP)- 18#
(b) LED status indicators (SC, SP, TP)- #02
(c) Auto / Manual Switch- 02#
(d) EM (emergency) Switch- 02#
(e) TNC Switch- 02#
NOTES:
[i] All the MCCBs up to 250 A shall be with thermal magnetic trip unit & above 250A shall be with microprocessor trip units. To ensure failsafe emergency tripping of the breakers (ACBs & MCCBs), it shall be supplied with continuous rated shunt trip coils.
[ii] Necessary control and switching devices to execute the switching and control logic shall be deemed inclusive of the scope of supply irrespective of them being specified / not specified above or in the SLD.
[iii] The Panel / Switchboard shall be tested to withstand vibration caused by an earthquake in accordance with IEC 60068-3-3:2013 or IS 1893 Zone V.
[v] All the necessary noble components (viz., structural, Door noble like hinge, Bush, Door alignment guage and Bus bar noble - Bus bar support, Close profile structure - horizontal & vertical) of the Panel shall be supplied by the OEM.
[vii] The Contractor shall intimate the Engineer-in-Charge of the routine tests in the OEM factory in presence of a representative nominated by the Engineer-in-Charge before dispatch.
ELECTRIC CABLE
M & L 1.1 kV grade XLPE insulated armoured cable conforming to IS 7098 (Part 1): 1988, having stranded compact shaped conductors as per Cl. 2 of IS 8130: 1984, PVC inner sheath, single armouring of galvanised steel strip/wire and PVC Type ST-2 outer sheath conforming to IS 5831: 1984, including necessary clamping / dressing with cable ties and termination complete as all specified and directed by engineer- in- charge.
4 core, 70 mm² 2XFY (Copper Cable for Chiller)
3 core, 10 mm² 2XFY (Copper Cable for CDP & CT)
3 core, 6 mm² 2XFY (Copper Cable for CWP)
3 core, 4 mm² 2XFY (Copper Cable for HWP)
4 core, 25 mm² A2XFY (Aluminium Cable for AHU Panel)
3.5 core, 300 mm² A2XFY (Aluminium Cable for HWG)
CABLE TRAY
S & F perforated hot dipped galvanized iron cable tray having galvanization thickness not less than 50 microns and perforation not more than 17.5% including fittigs viz. joints, bends, tees, etc. in convenient sections of length, including fixing arrangement suitable for site conditions complete all as specified and directed by the engineer-in-charge.
300 mm X 50 mm X 1.6 mm
150 mm X 50 mm X 1.6 mm
100 mm X 50 mm X 1.6 mm
CONDENSER WATER PIPING
M & L condenser water piping including necessary fittings viz., flexible connections, bends, tees, reducers, flanges, air purge valves, drain valves, structural support, necessary clamps, vibration isolators, etc. including painting and supporting / fixing the pipe in excavated trenches or on floor / wall / ceiling with clamps, hangers, angles, channels (using anchor fasteners) with necessary accessories complete all as specified and directed by the engineer-in-charge.
NOTES:
[i] The pipe size 150 mm NB & below shall be MS Class 'C' as per IS 1239 (Part- 1): 2004 & IS 1239 (Part- 2): 2011.
[ii] The pipe size above 150 mm NB shall be welded black steel pipe heavy class as per IS 3589: 2001.
[iii] Minimum thickness of MS sheet for pipe size above 150 mm NB and up to 350 mm NB shall be 6.35 mm and it shall be 7 mm for pipe size 400 mm NB and above.
'Y'-TYPE STRAINER
Supply, installation, testing and commissioning of cast steel bolted PN 1.6 rated cover Y-type strainer with CCS body conforming to ASTM A- 216 Gr. WCB, AISI 304 screen with 1.2 mm diameter perforation, 40 kg/cm2 body test pressure & 20 kg/cm2 maximum working pressure and standard flange end conforming to BS 10 Table F / Class-150, duly insulated complete all as specified and directed by the engineer-in-charge.
POT STRAINER
Supply, installation, testing and commissioning of PN 1.6 rated POT strainer, conforming to BS 6755-1, suitable for high capacity flow throughout full size inlet / outlet, having CI body & strainer bonnet, stainless steel perforated filter section, black rubber body / bonnet gasket, SS-410 valve and flange drilling standard end connections, etc., with accesories complete all as specified and directed by the engineer-in-charge.
MANUAL BUTTERFLY VALVE
Supply, installation, testing and commissioning of PN 1.6 rated wafer type, short / medium pattern cast iron (CI) butterfly valve, conforming to IS 13095: 2020, having CI Gr. FG200 body conforming to IS 210: 2009, seat having EPDM / nitrile rubber lining, SG iron / ductile cast iron disc, SS AISI- 410 stem, flanged end connection, conforming to BS 10 Table D/E & ANSI B 16.1 CI- 125 with necessary accessories complete all as specified and directed by the engineer-in-charge.
BALL VALVE
M & L CL#125 two-piece design cast iron (CI) straight pattern ball valve, conforming to IS 9890: 1981 and having FG 200 cast iron body conforming to IS 210: 2009, AISI 410 stem, stainless steel AISI 304 ball, renewable PTFE seat & gland packing and screwed female BSP parallel threaded ends conforming to BS 21 with necessary accessories all complete as specified and directed by the engineer-in-charge.
NON-RETURN VALVE
Supply, installation, testing and commissioning of wafer type PN 1.6 rated swing check type multidoor reflux valve (NRV), designed & tested as per IS 5312 (Part- 2): 1986, suitable to handle clear water having turbidity up to 5000 PPM, having CI body, door and diaphragm, leaded tin bronze seat rings and flange drilling standard end connection, etc., duly insulated and conforming to IS 1538: 1993 with necessary accessories complete all as specified and directed by the engineer-in-charge.
BALANCING VALVE
Supply, installation, testing and commissioning of PN 1.6 rated precise balancing double regulation type cast iron (CI) balancing valve having CI Gr. FG200 body, EPDM / nitrile seal, stainless steel disc, ASTM A 276, Gr SS410 stem, EPDM / nitrile bush, MS gland nut, ASTM A 276 spindle, CI bonnet, SS304 baancing nut, MS bonnet cap, CI hand wheel, MS plug, stainless steel fastener, flanged end connection, etc., and duly insulated with elastomeric thermal insulation with necessary accessories complete all as specified and directed by the engineer-in-charge.
CHILLED / HOT WATER PIPING
MS CLASS- C PIPE
Supply, installation, testing and commissioning of chilled/ hot water piping including necessary fittings viz. flexible connections, bends, tees, reducers, flanges, air purge valves, drain valves, structural support, necessary clamps, vibration isolators, etc. including painting and supporting / fixing the pipe in excavated trenches or on floor / wall / ceiling with clamps, hangers, angles, channels (using anchor fasteners) with necessary accessories, duly insulated complete all as specified and directed by the engineer-in-charge.
NOTES:
[i] The pipe size 150 mm NB & below shall be MS 'C' class as per IS 1239-1: 2004 & IS 1239-2: 2011.
[ii] The pipe size above 150 mm NB shall be welded black steel pipe heavy class as per IS 3589: 2001.
[iii] Minimum thickness of MS sheet for pipe size above 150 mm NB and up to 350 mm NB shall be 6.35 mm and it shall be 7 mm for pipe size 400 mm NB and above.
[iv] Insulation shall be measured and paid for separately.
Y- STRAINER
Supply, installation, testing and commissioning of cast steel bolted cover PN 1.6 rated Y-type strainer with CCS body conforming to ASTM A- 216 Gr. WCB, AISI 304 screen with 1.2 mm diameter perforation, 40 kg/cm2 body test pressure & 20 kg/cm2 maximum working pressure and standard flange end conforming to BS 10 Table F / Class-150, duly insulated complete all as specified and directed by the engineer-in-charge.
NOTES:
[i] Insulation shall be measured and paid for separately.
MANUAL BUTTERFLY VALVE
Supply, installation, testing and commissioning of PN 1.6 rated wafer type, short / medium pattern cast iron (CI) butterfly valve, conforming to IS 13095: 2020, having CI Gr. FG200 body conforming to IS 210: 2009, seat having EPDM / nitrile rubber lining, SG iron / ductile cast iron disc, SS AISI- 410 stem, flanged end connection, conforming to BS 10 Table D/E & ANSI B 16.1 CI- 125 with necessary accessories complete all as specified and directed by the engineer-in-charge.
NOTES:
[i] Insulation shall be measured and paid for separately.
NON-RETURN VALVE
Supply, installation, testing and commissioning of wafer type PN 1.6 rated swing check type multidoor reflux valve (NRV), designed & tested as per IS 5312 (Part- 2): 1986, suitable to handle clear water having turbidity up to 5000 PPM, having CI body, door and diaphragm, leaded tin bronze seat rings and flange drilling standard end connection, etc., duly insulated and conforming to IS 1538: 1993 with necessary accessories complete all as specified and directed by the engineer-in-charge.
NOTES:
[i] Insulation shall be measured and paid for separately.
BALANCING VALVE
Supply, installation, testing and commissioning of PN 1.6 rated precise balancing double regulation type cast iron (CI) balancing valve of having CI Gr. FG200 body, EPDM / nitrile seal, stainless steel disc, ASTM A 276, Gr SS410 stem, EPDM / nitrile bush, MS gland nut, ASTM A 276 spindle, CI bonnet, SS304 baancing nut, MS bonnet cap, CI hand wheel, MS plug, stainless steel fastener, flanged end connection, etc., and duly insulated with elastomeric thermal insulation with necessary accessories complete all as specified and directed by the engineer-in-charge.
INSULATION FOR UNDER-GROUND CHW PIPING
S & F fire-retardant quality expanded polystyrene moulded pipe section (EPS) insulation of density 20 kg/m3, with a thick coat of cold setting adhesive (CPRX compound) wrapping with 500g polythene faced hessian and finally sand cement plaster and tar felt cladding complete with type, grade-1 roofing felt strip, conforming to IS 1322: 1993, at joints repairing of damage to building etc. for the following diameters as required complete all as specified and directed by the engineer-in-charge.
150 mm NB (75 mm thickness)
100 mm NB (50 mm thickness)
65 mm NB (50 mm thickness)
50 mm NB (50 mm thickness)
DRAIN & INSTRUMENTATION PIPING
GI CLASS 'B' PIPE
M & L GI piping including necessary fittings viz. flexible connections, bends, tees, reducers, flanges, air purge valves, drain valves, structural support, necessary clamps, etc., for drain water, including painting and supporting / fixing the pipe on floor / wall / ceiling with clamps, hangers, angles, channels (using anchor fasteners) with necessary accessories, duly insulated, complete all as specified and directed by the engineer-in-charge.
NOTES:
[i] The pipe size 150 mm NB & below shall be MS 'C' class as per IS 1239 (Part- 1): 2004 & IS 1239 (Part- 2): 2011.
BALL VALVE
S & F PN 1.6 rated forged brass ball valve, having lever operated two piece design, renewable P.T.F.E. seat, brass ball, machined brass nickle plated stem, P.T.F.E. packings, full bore port opening, screwed female BSP parallel thread end connections, duly insulated with elastomeric thermal insulation with adhesives and other necessary accessories complete all as specified and directed by engineer-in-charge.
PIPING ACCESSORIES
AIR VENT VALVE
M & L PN 1.6 rated 25 mm air vent valve having brass body, cover, adopter, disc assembly & cap, stainless steel strainer, plastic float and 20 mm screwed threaded ends suitable for maximum operating temperature 100 °C installed on all high points in the water piping system to automatically remove the trapped air with necessary accessories all complete as specified and directed by the engineer-in-charge.
TEMPERATURE GAUGE
S & F 6" dual scale (°F / °C), lower mount (radial), bimetal thermometer having 0.5 NPT process connection, Grade A accuracy class as per ASME B40.200, stem diameter 6.35 mm, laminated safety glass window, stainless steel 304 case, steam, process connection & joint, aluminium dial & pointer, IP67 protection, scale range 0- 60 °C with necessary accessories all complete as specified and directed by the engineer-in-charge.
PRESSURE GAUGE
S & F 4" bourdon tube pressure gauge conforming to EN 837-1, having copper alloy process connection & pressure element, plastic black pointer & case, plastic crystal-clear window, snap-fitted in case, accuracy class 2.5, scale range 0- 25 bar with necessary accessories all complete as specified and directed by the engineer-in-charge.
AIR DISTRIBUTION
AIR HANDLING UNIT
Supply, installation, testing and commissioning of double-skin type horizontal, floor-mounted, top / side discharge, air handling unit (AHU) capable of delivering 15000 ft3/min air @ 300 Pa ESP having thermal break profile complete with air-tight casing using gaskets and self-adhesive tapes, 0.8 mm thick pre-plasticized GI sheet for outer skin and 1 mm thick aluminum sheet for inner skin, 25 mm thick double skin panel with pressure injected CFC / HCFC free PUF having 'k' value ≤ 0.035 W/°C/m & density ≥ 40 kg/m³, energy efficient backward curved electronically commutated (EC) fans integrated with continuous speed control in (n+1) configuration, frame mounted modular EU4 pre-filter, EU7 fine-filter, UVGI system, combination of 6/8 rows deep chilled water coil(s) of cooling capacity ≥ 112 TR, electric heating coil for humidity control, PVC / nylon hinges & handles, view port & marine lamp, limit switch, SS-304 drain pan, vibration isolators / rubber pads (minimum 1" thick) inspection windows / doors, mixing box and supply / return / fresh air openings fitted with aluminium volume control dampers, thermostat & humidistat, AHU Panel etc. complete all as specified and directed by the engineer-in-charge.
The AHU shall comprise of the following:
[a] AMCA certified (for sound & vibration) single inlet single width (SISW) multi blade backward curved type IP54 integral EC motor direct drive, having an integral high efficiency permanent magnet electrically commutated motor complete with control electronics, sealed bearings and all necessary motor protection and safety devices, single point power connection Modbus RTU compatible for communication with BMS, class 'F' thermal insulation, suitable protection from moisture & hot climate, over/under voltage protection, short-circuit protection, locked rotor protection, line fault detection, active temperature management for thermal protection or motor and electronics, alarm relay 250V/2A, over-temperature protection, external LED display, etc meeting all necessary EMC (electromagnetic compatibility) directives & applicable EMC standards e.g., EN 61000-6-3.
[b] Flexible connection made with airtight ASTM E84 (Class I) polyester fire retardant cloth riveted on periphery of cloth with extruded aluminium 'L' angle flange as per fan size at discharge duct / plenum
[c] CE certified, UL listed self-cleaning (washable) filter meeting EU4 criteria at velocities < 2.5 m/s, start pressure drop approximately 50 to 150 Pa, final pressure drop approximately 150 Pa, having particulate efficiency 90% down to 10 micron
[e] CE certified, UL listed electrostatic air cleaner filter meeting EU7 criteria at velocities between 2.0 to 3.0 m/s, start pressure drop approximately 50 to 100 Pa, final pressure drop approximately 150 Pa, having particulate efficiency 99.9% down to 3 micron
[f] High output Ultraviolet Germicidal Irradiation (UVGI) lamp mounted on a dish antenna shaped parabolic reflector made of anodized aluminium with high spectral reflectivity suitable for use in low temperature applications
[g] 6 / 8 rows deep chilled water cooling coil section with 0.15 mm thick aluminium fins and 12.7 mm OD copper tubes (0.41 mm thickness) tested on 21 kg/cm², with SS sandwiched drain tray, etc. (a 350 mm service section between eliminator and heater is required).
[h] 2 / 4 rows deep hot water heating coil section with 0.15 mm thick aluminium fins and 12.7 mm OD copper tubes (0.41 mm thickness) tested on 21 kg/cm², with SS sandwiched drain tray, etc. (a 350 mm service section between eliminator and heater is required)
[i] Condensate drain pan fabricated from 18 gauge SS 304, powder coated and insulated with elastomeric insulation of suitable thickness
[j] AHU panel made out of 2.00 mm thick mild steel CRCA sheet, duly powder coated in compartmentalised construction with incomer and outgoing feeders for AHU motor, AHU filters, 2-way valve actuator, fire damper actuator, electric heating coil etc. complete with required drives, relays, timers, contactors, PT, push buttons, switches, internal wiring, etc.
NOTES:
[i] The AHU shall meet the efficiency crieria laid for the Super ECBC Building category in ECBC 2017.
[iii] Necessary civil work viz. foundation for placement of AHU, mounting of AHU Panel, construction of opening(s) for fresh / exhaust air etc. shall be covered in the scope of work.
[iv] The contractor to confirm the TSP before commencement of the work.
FIRE & SMOKE DAMPER
Supply, installation, testing and commissioning of CBRI certified 16-gauge GI fire damper, at least of 120 minutes fire-rating, spring activated on melting of fusible link having melting point 67.13° C complete with smoke detector / thermistor, fusible link etc. and actuator as required for operation, located in the SA / RA ducts, at all fire rated crossovers (shafts, walls, etc.) along with control panel (located in such a way that the reset may easily be done), interlocked with the building management system for the fire detection or HVAC to trip / close in the event of fire / smoke in the respective zone and tested as per UL-555 complete all as specified and directed by the engineer-in-charge.
Motorized, spring return type, combination fire and smoke damper
Control panel actuator, including electrical spring type actuator, remote indication of the fire damper position.
The fire dampers shall meet the following criteria:
[i] Bare fire dampers with 400 mm sleeve
[ii] Control panel actuator, including electrical spring type actuator, remote indication of the fire damper position
[iii] Interconnection wire for the fire detection & alarm system with the AHU and the smoke dampers
[iv] Sealing any openings around the sleeve of the fire dampers with approved fire sealant as per the specification & recommandations of the manufacturer.
Supply, installation, testing & balancing and commissioning of factory fabricated GI round / rectangular low pressure ducting of following sheet thickness having zinc coating of 120 g/m² total on both sides and complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, volume control dampers, hangers, supports, etc. as per approved drawings and conforming to IS 655: 2006 & the latest edition of HVAC Duct Construction Standards - Metal and Flexible of SMACNA along with required scaffolding work to install the ducts at site complete all as specified and directed by engineer-in-charge.
VOLUME CONTROL DAMPER
Supply, installation, testing and commissioning of high performance airfoil class 1A leakage rated GI volume control damper having galvanised steel hat channel frame reinforced with corner braces, galvanised steel airfoil shaped blades (double skin construction) of 14 gauge thicknes, neoprene blade edge seals, flexible metal compressible jamb seals, stainless steel sleeve, linkage concealed in frame, etc. tested as per AMCA Standard 500-D-98 complete all as specified and directed by engineer-in-charge.
AIR TERMINALS
M & L 450 mm diameter round neck ceiling supply diffuser with a 360° discharge pattern, designed for neck velocity ≤ 600 ft/min, throw ≥ 5’ at 150 ft/min terminal velocity, and noise criteria (NC) ≤ 25 at airflow ≥ 760 CFM; constructed with frame and inner cones, by means of its adjustable cones, air pattern can be adjusted from horizontal to vertical discharge pattern, heavy-gauge steel butterfly volume control damper can be easily adjusted through the face of the unit and finished with a baked anodic acrylic coating, all in accordance with ANSI/ASHRAE Standard 170-1991, complete as specified and as directed by the Engineer-in-Charge.
M & L 400 mm diameter round neck ceiling supply diffuser with a 360° discharge pattern, designed for neck velocity ≤ 600 ft/min, throw ≥ 5’ at 150 ft/min terminal velocity, and noise criteria (NC) ≤ 23 at airflow ≥ 600 CFM; constructed with frame and inner cones, by means of its adjustable cones, air pattern can be adjusted from horizontal to vertical discharge pattern, heavy-gauge steel butterfly volume control damper can be easily adjusted through the face of the unit and finished with a baked anodic acrylic coating, all in accordance with ANSI/ASHRAE Standard 170-1991, complete as specified and as directed by the Engineer-in-Charge.
M & L 355 mm diameter round neck ceiling supply diffuser with a 360° discharge pattern, designed for neck velocity ≤ 600 ft/min, throw ≥ 4’ at 150 ft/min terminal velocity, and noise criteria (NC) ≤ 23 at airflow ≥ 450 CFM; constructed with frame and inner cones, by means of its adjustable cones, air pattern can be adjusted from horizontal to vertical discharge pattern, heavy-gauge steel butterfly volume control damper can be easily adjusted through the face of the unit and finished with a baked anodic acrylic coating, all in accordance with ANSI/ASHRAE Standard 170-1991, complete as specified and as directed by the Engineer-in-Charge.
M & L 315 mm diameter round neck ceiling supply diffuser with a 360° discharge pattern, designed for neck velocity ≤ 600 ft/min, throw ≥ 3’ at 150 ft/min terminal velocity, and noise criteria (NC) ≤ 22 at airflow ≥ 330 CFM; constructed with frame and inner cones, by means of its adjustable cones, air pattern can be adjusted from horizontal to vertical discharge pattern, heavy-gauge steel butterfly volume control damper can be easily adjusted through the face of the unit and finished with a baked anodic acrylic coating, all in accordance with ANSI/ASHRAE Standard 170-1991, complete as specified and as directed by the Engineer-in-Charge.
M & L 250 mm diameter round neck ceiling supply diffuser with a 360° discharge pattern, designed for neck velocity ≤ 600 ft/min, throw ≥ 3’ at 150 ft/min terminal velocity, and noise criteria (NC) ≤ 21 at airflow ≥ 225 CFM; constructed with frame and inner cones, by means of its adjustable cones, air pattern can be adjusted from horizontal to vertical discharge pattern, heavy-gauge steel butterfly volume control damper can be easily adjusted through the face of the unit and finished with a baked anodic acrylic coating, all in accordance with ANSI/ASHRAE Standard 170-1991, complete as specified and as directed by the Engineer-in-Charge.
M & L 450 mm diameter round neck ceiling return diffuser with a 360° discharge pattern, designed for neck velocity ≤ 600 ft/min, throw ≥ 5’ at 150 ft/min terminal velocity, and noise criteria (NC) ≤ 25 at airflow ≥ 760 CFM; constructed with frame and inner cones, an inner core assembly consisting of fixed cones and finished with a baked anodic acrylic coating, all in accordance with ANSI/ASHRAE Standard 170-1991, complete as specified and as directed by the Engineer-in-Charge.
M & L 400 mm diameter round neck ceiling return diffuser with a 360° discharge pattern, designed for neck velocity ≤ 600 ft/min, throw ≥ 5’ at 150 ft/min terminal velocity, and noise criteria (NC) ≤ 23 at airflow ≥ 600 CFM; constructed with frame and inner cones, an inner core assembly consisting of fixed cones and finished with a baked anodic acrylic coating, all in accordance with ANSI/ASHRAE Standard 170-1991, complete as specified and as directed by the Engineer-in-Charge.
M & L 355 mm diameter round neck ceiling return diffuser with a 360° discharge pattern, designed for neck velocity ≤ 600 ft/min, throw ≥ 4’ at 150 ft/min terminal velocity, and noise criteria (NC) ≤ 22 at airflow ≥ 330 CFM; constructed with frame and inner cones, an inner core assembly consisting of fixed cones and finished with a baked anodic acrylic coating, all in accordance with ANSI/ASHRAE Standard 170-1991, complete as specified and as directed by the Engineer-in-Charge.
M & L of a 315 mm diameter round neck ceiling return diffuser with a 360° discharge pattern, designed for neck velocity ≤ 600 ft/min, throw ≥ 3’ at 150 ft/min terminal velocity, and noise criteria (NC) ≤ 21 at airflow ≥ 225 CFM; constructed with frame and inner cones, an inner core assembly consisting of fixed cones and finished with a baked anodic acrylic coating, all in accordance with ANSI/ASHRAE Standard 170-1991, complete as specified and as directed by the Engineer-in-Charge.
S & F double louver grille of size 62" X 8" made of extruded aluminium frame of 20 mm width, 46 mm depth & 1.15 mm thickness having individually adjustable blades to set the angle of deflection, suitable for delivering 1700 CFM air flow @ core velocity 2.5 m/s & 8 Pa maximum velocity pressure, 25 dB noise criteria, extruded aluminium opposed blade volume control damper and tested as per ANSI / ASHRAE standard 70-2006 complete all as specified and directed by the engineer-in-charge.
S & F double louver grille of size 86" X 10" made of extruded aluminium frame of 20 mm width, 46 mm depth & 1.15 mm thickness having individually adjustable blades to set the angle of deflection, suitable for delivering 3000 CFM air flow @ core velocity 2.5 m/s & 8 Pa maximum velocity pressure, 28 dB noise criteria and tested as per ANSI / ASHRAE standard 70-2006 complete all as specified and directed by the engineer-in-charge.
S & F double louver grille of size 62" X 8" made of extruded aluminium frame of 20 mm width, 46 mm depth & 1.15 mm thickness having individually adjustable blades to set the angle of deflection, suitable for delivering 1700 CFM air flow @ core velocity 2.5 m/s & 8 Pa maximum velocity pressure, 25 dB noise criteria and tested as per ANSI / ASHRAE standard 70-2006 complete all as specified and directed by the engineer-in-charge.
S & F double louver grille of size 20" X 6" made of extruded aluminium frame of 20 mm width, 46 mm depth & 1.15 mm thickness having individually adjustable blades to set the angle of deflection, suitable for delivering 450 CFM air flow @ core velocity 2.5 m/s & 8 Pa maximum velocity pressure, 20 dB noise criteria and tested as per ANSI / ASHRAE standard 70-2006 complete all as specified and directed by the engineer-in-charge.
S & F double louver grille of size 14" X 4" made of extruded aluminium frame of 20 mm width, 46 mm depth & 1.15 mm thickness having individually adjustable blades to set the angle of deflection, suitable for delivering 350 CFM air flow @ core velocity 2.5 m/s & 8 Pa maximum velocity pressure, 19 dB noise criteria and tested as per ANSI / ASHRAE standard 70-2006 complete all as specified and directed by the engineer-in-charge.
THERMAL INSULATION
S & F flexible closed-cell elastomeric thermal insulation made of elastomeric foam based on synthetic rubber (NBR / PVC) with UV resistant polymer based non-metallic covering on one side, having thermal conductivity λ ≤ 0.035 W/mK at mean temperature of base foam θm = 0 ºC as per EN 12667, moisture diffusion resistance factor of base foam µ ≥ 7000 as per EN 12086, water absorption by volume of base foam ≤ 0.2% as per ASTM C 209 / C1763, flame spread index (FSI) of base foam Class 1 as per BS476 Part 7 for surface spread of flame and Class ‘O’ fire propagation as per BS476 Part 6, density of base foam between 40- 55 kg/m3 & of laminated insulation material between 50 to 70 kg/m3, tensile strength of the base foam with covering > 1.5 MPa (32 mm) in MD & > 0.4 MPa (32 mm) in CD, elongation of the base foam with covering > 40% (32 mm) in MD & > 38% (32 mm) in CD, tear strength of the base foam with covering > 35 kN/m (32 mm) in MD & 25 kN/m (32 mm) in CD with covering material of multiple layered laminate of polymeric material reinforced with scrim with a special UV protection with necessary accessories complete all as specified and directed by the engineer-in-charge.
19 mm thick thermal insulation (for supply air ducting)
13 mm thick thermal insulation (for return air ducting)
The insulation shall conform to the following technical specifications.
[i] The insulation material shall be dust, fibre, formaldehyde and CFC & HCFC free.
[ii] The insulation material shall withstand maximum surface temperature of +85°C and minimum surface temperature of 0°C as per EN 14706.
[iii] The base insulation material shall have ODP (Ozone Depletion Potential) and GWP (Global Warming Potential) of Zero.
[iv] Covering material shall be non-metallic, mat finish and provide mechanical resistance with an excellent aesthetic look.
[v] Covering material shall be of 380 ± 20 GSM as per ASTM D 646.
[vi] Covering material shall be of 380 – 400 microns as per ASTM E 252.
[vii] Covering material shall have good puncture and tear resistance and the tensile strength of > 5 MPa in MD & CD as per ASTM D 638.
[viii] Covering material shall have good UV resistance as per ISO 4892-2 Method A tested for 1000 hrs and shall withstand maximum surface temperature of +75 °C and minimum surface temperature of -25 °C as per EN 14706.
[ix] Covering material shall be installed with 30-50 mm overlaps on all horizontal and longitudinal joints. Joints along the material length shall be installed facing downward. The joints shall be secured with 50 mm – 75 mm tapes. Manufacturer recommended adhesive can be used for flat sheets, or where restricted access prevents use of rivets. All joints and overlaps must be finished with manufacturer recommended PSA Tape.
[x] For fittings of an unusual shape, or large size, the covering material should be cut and installed as per traditional metal cladding.
ACOUSTIC LINING
S & F FM approved fibre-free, super-silent, microbe resistant, easy to apply acoustic duct lining insulation of open cell elastomeric foam based on synthetic rubber tested for acoustic performance as per EN ISO 354, EN ISO 11654: 1997 & ASTM C 423, service temperature range -20- 85 ˚C as per EN 14706 & EN 14304, thermal conductivity λ ≤ 0.047 W/mK at mean temperature θm = 20 ˚C as per EN 12667, Class 1 surface spread of flame as per BS 476 7: 1997, flammability HB, V-0 as per UL- 94, anti-microbial behaviour (no fungal growth visible with the naked eye & no bacterial growth) as per EN ISO 846, air erosion resistance (no erosion, cracking or delamination at air velocity of 10000 FPM) as per ASTM C 1071- 05, density 140- 180 kg/m3 along with adhesives and other necessary accessories complete all as specified and directed by the engineer-in-charge.
10 mm thick acoustic insulation
HYDRONIC CASSETTE UNIT
Supply, installation, testing and commissioning of Eurovent certified BLDC chilled water cassette unit having lower height design (≤ 300 mm), lower noise levels, 360° round flow panel, 3 air swing pattern control, draft prevention & soil prevention, turbo fan with BLDC motor, 2-pipe coils, individual louver control, 5-speed DC fan for perfect comfort, 20% fresh air intake hole, built-in high head drain sump and water flow switch, etc., complete all as specified and directed by the engineer-in-charge.
Chilled Water Cassette Unit 1.2 TR @ 462 CFM (±10% tolerance)
Chilled Water Cassette Unit 1.6 TR @ 6678 CFM (±10% tolerance)
Supply, installation, testing and commissioning of pre-assembled connection and regulation kit for HVAC terminal units complete with pressure independent control valve with proportional linear actuator, 3-way shut-off valves, single moulded integreated bypass, Venturi device with pressure test ports, filtering cartridge and pre-formed shell insulation made of PPE, dezincification resistant alloy body and adjustment headwork complete with stainless strainer mesh, EPDM diaphragm, obturtor and seals, etc. and suitable for 50 °C ambient temperature, linear or exponential flow rate adjustment characteristic which can be set up by actuator depending on the characteristics of the terminal unit all as specified and directed by the engineer-in-charge.
The connection and regulation kit shall conform to the following technical specification:
[i] Maximum Working Pressure: 25 bar
[ii] Maximum Differential Pressure with Actuator Installed: 5 bar
[iii] Nominal Operation Differential Pressure Range: 25- 400 kPa
[iv] Working Temperature Range: -10 to 120 °C
[v] Strainer Mesh Size: 800 micron
[vi] Medium: Water and Glycol Solution (Maximum Percentage of Glycol limited to 50%)
Supply, installation, testing and commissioning of AMCA certified (in accordance to AMCA211 & AMCA311 standards) in-line centrifugal duct fan of size from 100 to 315 mm and suitable for capacities up to 1700 m3/hr (1000 ft3/min) and static pressure up to 1000 Pa, designed for direct in-line connection with industrial circular ducting of standard diameter, suitable for mounting in any position with enclosed single phase external rotor type motor, worm drive flexible duct connection clips, plastic sections for the connection of two ducts of different duct diameters, steel sheet pieces allowing the connection of two ducts of the same duct diameter, etc., complete all as specified and directed by the engineer-in-charge.
The in-line centrifugal duct fan shall conform to the following technical specification.
[i] The motor and impeller assembly shall be suitable for operation at any angle and deliver exceptional airflow performances against the high static pressures typically found in ducted ventilation systems.
[ii] The fan casing shall be manufactured from corrosion resistant pressed galvanised sheet steel.
[iii] Non-stalling backward curved impeller shall be factory matched to the corresponding external rotor motor and dynamically balanced to ISO 1940 standards for vibration free operation.
[iv] The fan shall be supplied with a remotely mounted wiring junction box to provide the installer with a completely flexible choice for positioning and installation
[v] Enclosed, single phase, 230 V, 50 Hz external rotor type, motors shall include sealed IP44 protection with an internal automatic reset safety thermal overload protection device as standard.
[vi] Motors shall be fully speed controllable using electronic or autotransformer voltage control regulators.
[vii] The AMCA certification shall be for both sound and vibration.
[viii] The noise level shall not exceed 60 dB(A) @ 3 metre distance when measured in hemispherical reverberant room conditions.
600 CFM, (10 mm Static Pressure)
400 CFM, (10 mm Static Pressure)
250 CFM, (10 mm Static Pressure)
150 CFM, (10 mm Static Pressure)
M&L for 150 mm diameter round neck toilet exhaus air diffuser connected with frame and inner cone, an inner core assyble, consisting of fixed cones and finished with baked anodic acrylic coating, complete all as specified and directed.
Supply, installation, testing and commissioning of Propeller fans along with gravity louvers for exhaust complete with motor suitable for 220 volts 50 Hz, single phase AC supply with supporting arrangement etc. as required at site and as per specifications and providing and applying using gun applied transparent silicon sealant for making exhaust fan openings air and water light complete as required.
648 CFM, Ø250 mm
Supply, installation, testing and commissioning of 1-Ph electric motor driven storage type water cooler having in-situ PUF insulation, (CFC free) eco-friendly R-134a refrigerant, high efficiency heat transfer coil of high quality copper tubes with rippled aluminum fins, stainless steel tank, trough and faucets, hermetic type compressor with suction gas cooled motor & equipped with overload protector, propeller type (quiet) condenser fan, thermostat, pre-coated partial stainless steel outer body and food grade plastic parts suitable for nominal cooling capacity and storage capacity 60/120 litres conforming to IS 1475 (Part-1): 2001 complete all as specified and directed by the engineer-in-charge. Make: Bluestar, Usha, Voltas
Supply, installation, testing and commissioning of 1-Phase mainline voltage stabilizer of 2 kVA rating having input voltage range 90 V to 300 V and output voltage range 180 V to 250 V and conforming to IS 8448: 1989, complete all as specified and directed by the engineer-in-charge. Make: Luminous, V-Guard, Voltas
Subtotal
Schedule ‘A’ Part - XI (STAGE LIGHTING ARRANGMENT)
SITC of Suspender cum clamps designed made out of MS material, Black powder coated finish All the materials under gone through 7 tank process with various chemical treatment to keep them rust free Suitable to hold various type grid & other rigging systems.
C PROFILE FOR CURTAIN TRACK
SITC of C Profile MS Hot rolled strips, All the materials under gone through 7 tank process with various chemical treatment to keep them rust free Makes easier to suspend all the stage machinery Duly powder coated Matt black texture finish paint
CIRCUIT BOX
SITC of Cable Connecting Circuit Boxes for the termination of cables from Electrical panel to the grid level point made out of MS Sheet metal fabricated housing duly powder coated with matt black texture finish paint, fitted with required channels and ivory connectors, necessary glands etc.
POWER CABLE
SITC of 1.1 kV grade XLPE insulated armoured cable conforming to IS 7098 (Part 1): 1988, having stranded compact shaped conductors as per Cl. 2 of IS 8130: 1984, PVC inner sheath and PVC Type ST-2 outer sheath conforming to IS 5831: 1984, including necessary clamping / dressing with cable ties and termination complete as all specified and directed by engineer- in- charge. Make: Havells, Polycab, RR Kabel
4 core, 4.0 mm² 2XY Cable
MAIN CURTAIN FABRIC
SITC of High quality Velvet fabric fire retardant treated as per approved colour and make with a gathering of 100% stitched as per site condition, curtain provided with eyelets at every 200/250mm for uniform fixing on to curtain trollies (For Main Curtain) Make: Nexgen, Omphile, Stage Works, Auditorium Works
REAR CURTAIN FABRIC
SITC of Glazed Cotton fabric fire retardant treated as per approved colour and make with a gathering of 50% stitched as per site condition, curtain provided with eyelets at every 200/250mm for uniform fixing on to curtain trollies (For Rear Curtain) Make: Nexgen, Omphile, Stage Works, Auditorium Works
FRILLS
SITC of Glazed Cotton fabric fire retardant treated as per approved colour and make with a gathering of 50% stitched as per site condition, curtain provided with eyelets at every 200/250mm for uniform fixing on to curtain trollies (For Frills) Size: 17Mtr x 1.2Mtr. Make: Nexgen, Omphile, Stage Works, Auditorium Works
VALANCE
SITC of High quality Velvet fabric fire retardant treated as per approved colour and make with a gathering of 100% stitched as per site condition, curtain provided with eyelets at every 200/250mm for uniform fixing on to curtain trollies (For Main Valance) Size: 24Mtr x 1.5Mtr Make: Nexgen, Omphile, Stage Works, Auditorium Works
WINGS
SITC of Glazed Cotton fabric fire retardant treated as per approved colour and make with a gathering of 0% stitched as per site condition, curtain provided with eyelets at every 200/250mm for uniform fixing. (For Wing) 8Mtr x 1.5Mtr Make: Nexgen, Omphile, Stage Works, Auditorium Works
FRILL BAR
SITC of On Stage Fixed Frill Bar 17Mtrs Length Straight as per the design made out of 40NB 48 OD Mild steel pipe dual barrel, supported to hang the frill, connected with MS Flat duly powder coated with matt black texture finish paint. All the materials under gone through 7 tank process with various chemical treatment to keep them rust free Make: Citizen, Dayal Fabric, Leska, Reliance, Stage Works, Auditorium Works
VALANCE BAR
SITC of On Stage Fixed Valance Bar 24 Mtr Length Straight as per the design made out of 40NB 48 OD Mild steel pipe dual barrel, supported to hang the Main Valance of the stage system duly powder coated with matt black texture finish paint. All the materials under gone through 7 tank process with various chemical treatment to keep them rust free Make: Citizen, Dayal Fabric, Leska, Reliance, Stage Works, Auditorium Works
FIXED WING STRUCTURE
SITC of Fixed Wing Structure designed as per site condition for a height approx 8Mtr x 1.5Mtr made up of MS Square tube of 25mm or higher size rested on pivotable trolley on a track for the rotation of the wing. Adjustable floor locking screw jacks with rubber grips. Inverted 4-Wheeler Trolley with Flexi Adaptor Clamp and 360° Rotatable. Make: Citizen, Dayal Fabric, Leska, Reliance, Stage Works, Auditorium Works
MAIN CURTAIN MOTOR
SITC of Motorized Main Curtain, Centre parting as per design. This mechanism shall be provided with 01 Nos. of 1 HP /1.5HP, 1440 RPM, 90 B5 frame, 3Ph. 415VAC Motor with Brake for Motor System to lift a load which should be synchronized with Motor Control centre Panel. Winch shall have 3 phase motor with an RPM of 1440, KW (HP): 0.74(1)/1.1(1.5), Frame: 90S, EFF:75.0%, MTG : B5, AMP :2.7Y, Volt:415v, DE BRG : 62052Z, DUTY:S1, FREQ:50Hz, NDE BRG:62052Z, IP:55, AMB:50 degree. The outer surface temperature is limited. It shall have a Worm Reduction Gearbox with GMRV-90 80:1, 90B5, Single Reduction 7.5:1 to 100:1 and the size shall be 90. It shall have a drive unit base frame to fix the gear box which contains one shaft Made up of I Track for complete length Curtain holding trollies with ball bearings for smoother noiseless movement consisting of 4-wheeler master trolley and 2-wheeler trolley placed uniformly at specific interval of200mm /250 mm throughout the track Overlap of 0.5~0.9 Mtrs. Motor Cable termination box Trollies are uniformly distributed along the track at every 200/250mm with a master trolley. Open and close limit controller. Drive unit with suitable capacity of motor unit, Wire Rope shall be of GI Wire ropes Min 3mm Dai Undergone through various chemical treatment to keep them rust free, Black texture finish paint. All metal parts are powder coated Make: Citizen, Dayal Fabric, Leska, Reliance, Stage Works, Auditorium Works
REAR CURTAIN MOTOR
SITC of Motorized Rear Curtain, Centre parting as per design. This mechanism shall be provided with 01 Nos. of 1 HP /1.5HP, 1440 RPM, 90 B5 frame, 3Ph. 415VAC Motor with Brake for Motor System to lift a load which should be synchronized with Motor Control centre Panel. Winch shall have 3 phase motor with an RPM of 1440, KW (HP): 0.74(1)/1.1(1.5), Frame: 90S, EFF:75.0%, MTG : B5, AMP :2.7Y, Volt:415v, DE BRG : 62052Z, DUTY:S1, FREQ:50Hz, NDE BRG:62052Z, IP:55, AMB:50 degree. The outer surface temperature is limited. It shall have a Worm Reduction Gearbox with GMRV-90 80:1, 90B5, Single Reduction 7.5:1 to 100:1 and the size shall be 90. It shall have a drive unit base frame to fix the gear box which contains one shaft Made up of I Track for complete length Curtain holding trollies with ball bearings for smoother noiseless movement consisting of 4-wheeler master trolley and 2-wheeler trolley placed uniformly at specific interval of200mm /250 mm throughout the track Overlap of 0.5~0.9 Mtrs. Motor Cable termination box Trollies are uniformly distributed along the track at every 200/250mm with a master trolley. Open and close limit controller. Drive unit with suitable capacity of motor unit, Wire Rope shall be of GI Wire ropes Min 3mm Dai Undergone through various chemical treatment to keep them rust free, Black texture finish paint. All metal parts are powder coated Make: Citizen, Dayal Fabric, Leska, Reliance
CYCLORAMA SCREEN
SITC of Perforated plastic cyclorama screen with perforation on 1side with gathering of 0% stitched as per site condition, curtain provided with eyelets at every 200/250mm for uniform fixing on to curtain trollies. Size:14 x 8Mtr Make: Citizen, Dayal Fabric, Leska, Reliance
CYCLORAMA SCREEN MOUNTING ARRANGEMENT
SITC of Fixed Cyclorama arrangement of 14 Mtrs straight as per design made up of I Track for complete length with Trollies uniformly distributed along the track at every 200/250mm. All metal parts are powder coated with black texture finish paint. All the materials under gone through 7 tank process with various chemical treatment to keep them rust free Make: Citizen, Dayal Fabric, Leska, Reliance, Stage Works, Auditorium Works
STAGE LIGHTING SYSTEM
PARCAN LIGHT
SITC of 150W High Quality LED Parcan Light complete with, Lamp source 3200K CCT Colour temperatureCRI & TLCI Values above 95COB LED source from reputed make DmX 512 dimming with 3 channel controlBeam Angle of 11˚ / 25˚ / 35˚Total Power Consumption of 160W High quality output replacing 1000W Halogen Par Flicker Free 100% for Tv & Film Cameras 11.7KHz Refresh Rate, Linear Dimming 0 ~ 100%Fuse and Internal safety protections Strobe option Adjustable 1~25 times/Sec Variable Fixture provided with Yoke of Manual Adjustment, Black powder coated body. Certification having BIS compliant to IS 10322 (Part 5/ Sec 1):2012.
PROFILE SPOT LIGHT
SITC of 300 W LED Profile Spot 14 Degree Light complete with 3200K CCT Colour Temperature COBLED source from reputed make (LM80 to be provided) CRI & TLCI above 95 Strobe option Adjustable 1 ~ 25 times / Sec 4 Kinds of dimming curves, Black finish housing Manual Focus with 4 Beam shaping cutters Efficient and well-designed Lamp reflector Efficient Copper tube based Heat Sink for Heat Dissipation Sleek and Unique Designed Light weight body Fixture provided with Yoke of Manual Adjustment DmX 512 dimming with 1 or 3 Channel modes IP20 protection having Lux @ 3Mtr above 38142suitabletoilluminatethekeypresenterortalentonstage.illuminatethe key presenter or talent on stage havingBIScomplianttoIS10322(Part5/Sec1):2012.
LED BLINDER LIGHT
SITC of 400W LED Blinder Light 30 Degree complete with 3200K CCT 4x100W Chip On Board LED Lamp sourceCOBLEDs (LM80 to be provided) DmX 512 dimming with 8 Channel modesCRI & TLCI Value > 95 Strobe option Adjustable 1 ~ 25 times / Sec Variable Beam Angle 30 DegreeTotal Power Consumption of 410W11.7KHz Refresh RateIn built preset’s for effectsFuse and Internal safety protectionsActive Cooling with Low Noise Fan DmXHigh quality well designed inbuilt reflectorFlicker Free 100% for Tv & Film CamerasBlack finish housing, IP20 protection Having Strobe option and smooth dimmingilluminate Stage with uniform light intensity levels. RDM Control options with latest technology having BIS complianttoIS10322(Part5/Sec1):2012.
LED FRESNEL LIGHT
SITC of 200W LED CCT Tuneable Fresnel Light having COB LED source from reputed make. Seamless CCT tuning from 3000K to 6000K at constant power output of 200W along with the flood to spot zooming option from 10 Deg to 50 Deg.High quality uniquely designed Fresnel Lens CRI,TLCI and R9 value above 95LED COB Based Source , Beam Angle 10 ~ 50 degree. No Multiple Shadows –Single Source illumination Total Power Consumption of 210W Linear dimming 0~100%Adjustment Flicker Free for High FPS, Power AC100 - 240V, 50Hz Working Temperature -+40°~-30°Active Cooling with DmX & RDM Control options with latest technologyFixture provided with Yoke of Manual Adjustment Manual and DMX control Option mode through 5pin/3pin xlr Black powder coated fabricated housing with normal yoke. Certification having BI Scompliantto IS10322(Part 5/ Sec 1):2012.
LED RGBW PAR LIGHT
SITC of 200W LED SpotLight RGBW, Beam Angle 15°/25°complete with LED source from reputed make. RGBW Lamp source DmX 512 dimming with 8 Channel Unlimited Colour Mixing through DmX 0~100% Linear dimming, Inbuilt presets for different colours Strobe Mode 20 times/SecData DmX through 3 / 5 Pin XLR’s65dB ~ 130dB Sound sensing capacity Power In and Out Connections High precision colours, IP20 protection Powder coated Black finish housing Having Sound Control & Master Slave Auto Run Mode Illuminate the Indoor stage with unlimited colour effectsRigidly built pressure die-casted Aluminium body. Certification having BIS compliant to IS10322 (Part5/Sec1) : 2012
LED MONO PAR LIGHT
SITCof54x3WLED3200KParLightBeamAngle25°complete with 3200K 3W Lamp source x 54 Pcs LEDsourcefromLumiled/Seoul/Nichiaorreputedmake(LM80 to be provided) Having CRI TLCI Values above 95 Flicker Free for high FPS Smooth fade in and Fade outHigh precision steady colour No heat, DmX 512 dimming with 2 Channel 0 ~ 100%, Powder coated Black finish housing Rigidly built pressure die-casted Aluminium body LED Easy view display Data DmX through 3 / 5 Pin XLR’s65dB ~ 130dB Sound sensing capacityPower In and Out Connections Total Power Consumption of 180W Sound Active Mode Control IP20 protection.RDMControloptionswithlatesttechnology(RDMIDtobespecified)LM79 Certificates from NABL Accredited laboratoryCertificationhavingBIScomplianttoIS10322(Part5/Sec1):2012 CECertificationcomplianttoEN60598-1:2015,EN61437-2-13:2014 Brandembossedimpactonthelightbodyforgenuineproduct
MOVING HEAD BEAM LIGHT
SITC of Moving Head Beam effect light 12R Base High bright long throw beam with linear zoom range Zoom range from o to 3.8 DegreeLamp Source: Yodn 280W 12R Arc Lamp Total Power Consumption of 450W, Electrical: AC 100-240V, 50/60Hz16 Channel DmX ControlColor System:1 color wheel+14pcsPrism:8prism+48prism with rotation effect16 Bit Dimmer ControlGobos System: 16+1pcs gobos.Double chip Stroboscopic (0.5 ~ 9 times /SEC),Pan Angle 540°, Tilt Angle 270°IP20 rated product.Electrical: AC 100-240V, 50/60Hz
CYCLORAMA WASH LIGHT
MOUNTING CLAMP
SITC of Aluminium O Type clamp made up of high grade aluminium having thickness not less than 5mm suitable for round tubes provided with fixture mounting 25mm M8 bolt and wingnut, minimum 100 KGs of safe working load, 40mm boltand wing nut for pipe locking.
DUAL SAFETY CHAIN
SITC of Light Fixture dual safety Chain made up of GI wire rope Bundled and twisted together Having load bearing capacity above 200 Kgs Sleeve on the rope. Carabiner Clip
SUSPENDER CUM CLAMP
SITC of Suspender cum clamps designed made out of MS material 150mm x 150mm x 5mm MS Base plateThreaded rod, Black powder coated finish All the materials under gone through 7 tank process with various chemical treatment to keep them rust free Suitable to hold various type grid & other rigging systems.
STAGE LIGHT BAR
SITC of Fixed stage Lighting bar / w inch of 16 Mtr length constructed with an dual construction light bar with an Mild Steel 40 NB 48 OD black matt finish with an supporting flat patti of height 200 mm x 50 mm x 6mm thickness for the extra support with 2 holes of 10 mm diameter to fix the cable tray on the bar. It shall be hanged from the roof to accommodate various type of stage light fittings. It should hang from the roof with MS angle which is suspended from the fish plate of 5mm thickness which is fixed on the rcc roof with 4 anchor fasteners of 10mm which can take an total load of 400KG each fastener.Made out of 48mm Outer Dai, 40 Nominal BoreMaterial for the light bar shall be of Mild Steel Pipe. Dual Barrel Arrangement Powder coated with MattblackTexture Fixing Through Suspenders as per site conditions Dual Construction and an additional End Caps on the Pipe end shall be there Light bar Length shall be of customized type as per site condition.Upper pipe of dual construction is used to anchor the bar lower pipe is effectively used to hang the light fixtures
FOH LIGHT BAR
SITC of Fixed FOH Lighting bar/winch of 17Mtr length constructed with an dual construction light bar with an Mild Steel 40NB 48 OD black matt finish with an supporting flat patti of height 200mm x 50mm x 6mm thickness for the extra support with 2 holes of 10mm diameter to fix the cable tray on the bar. It shall be hanged from the roof to accommodate various type of stage light fittings. It should hang from the roof with MS angle which is suspended from the fish plate of 5mm thickness which is fixed on the rcc roof with 4 anchor fasteners of 10mm which can take an total load of 400KG each fastener. Made out of 48mm Outer Dai, 40 Nominal Bore Material for the light bar shall be of Mild Steel Pipe. Dual Barrel Arrangement Powder coated with Matt black Texture Fixing Through Suspenders as per site conditions Dual Construction and an additional End Caps on the Pipe end shall be there Light bar Length shall be of customized type as per site condition. Upper pipe of dual construction is used to anchor the bar lower pipe is effectively used to hang the light fixtures
LIGHTING POWER DISTRIBUTION PANEL
SITC of Power Distribution Electrical panel. Floor mount / rack mount / wall mount. Miniature circuit brakers of single poles shall be fixed of different ratings from 6/10/16/25A as per the lighting fixtures. Wiring inside the module for power, control protection and instrument etc. shall be done with use of 1100 V. All welding slag grounded off and welding pits wiped smooth with plumber metal. Power panels shall be designed in such a way that the internal space is sufficient for hot air movement, and the electrical component does not attain temperature more than 40 degree Celsius. Fabricated panel. shall be supported with ms anglem to hold the structure. Neutral separation made using incomer of L&T or Schneider make, Voltmeter, Ammeter display for reading visualization Individual MCB control for RYB Phase indicators internally wired using IS certified wires and cables. Terminal for both incoming and outgoing cable shall be suitable for 1100 volts grade, aluminium/copper conductor PVC insulated and sheathed and shall be suitable for connections. Provided with ivory connectors for the internal terminations and external outgoing connecting points Custom built as per specification and project requirement.
POWER JUNCTION BOX
SITC of High quality power junction box 4 way made up of MS Sheet metal fabricated housing. Snap fit fixing /15 (1.5mm ) Total Max Rating 10A, 250V A.C 20˚C to +70˚C Operating Temp Mouldings: Nylon, Flammability Rating UL94V-0 Black powder coated, fibre glands of suitable size fitted with Powercon or IEC connector Box 10A. Clamp arrangement for fixing or Raul plug arrangement for wall / floor fixing
SITC of High quality power junction box 2 way made up of MS Sheet metal fabricated housing. Snap fit fixing /15 (1.5mm ) Total Max Rating 10A, 250V A.C 20˚C to +70˚C Operating Temp Mouldings: Nylon, Flammability Rating UL94V-0 Black powder coated, fibre glands of suitable size fitted with Powercon or IEC connector Box 10A. Clamp arrangement for fixing or Raul plug arrangement for wall / floor fixing
IN-DIMMING JUNCTION BOX
SITC of High quality Dimming In junction box 1 way made up of MS Sheet metal fabricated housing High temperature resistant insulator material All metal housing offers best overall RF protection & electromagnetic shielding Black powder coated, fibre glands of suitable size fitted with 5 Pin DmX XLR Male socket Clamp arrangement for fixing or Raul plug arrangement for wall /floor fixing
OUT-DIMMING JUNCTION BOX
SITC of High quality Dimming Out junction box 1 way made up of MS Sheet metal fabricated housing High temperature resistant insulator material All metal housing offers best overall RF protection & electromagnetic shielding Black powder coated, fibre glands of suitable size fitted with 5 Pin DmX XLR Female socket Clamp arrangement for fixing or Raul plug arrangement for wall /floor fixing
DMX LOOP JUNCTION BOX
SITC of DmX Loop Junction Box having 1 No. of DmX 5 Pin XLR Female Socket & 1 No. DmX XLR Male Socket fitted on to a sheet metal fabricated compact Junction box powder coated with matt black texture finish paint. High temperature resistant insulator material All metal housing offers best overall RF protection & electromagnetic shielding. Clamp arrangement for fixing or Raul plug arrangement for wall /floor fixing
EARTH COMPONENTS
SITC of Internal Earthing System with copper bare conductors all along the cable trays, metal parts and Installation Hardwares
CABLE TRAY
SITC of Black Powder coated cable trays made out of MS Sheet fabricated for a size of 40 x 75 x 40mm & 1.6 mm thickness undergone through 7 tank process with various chemical treatment to keep them rust free with perforation for heat dissipation provided with lid.
SITC of Black Powder coated cable trays made out of MS Sheet fabricated for a size of 40 x 75 x 40mm & 1.6 mm thickness undergone through 7 tank process with various chemical treatment to keep them rust free with perforation for heat dissipation provided with lid.
DMX CONNECTOR
supply installation testing and commissioningof DmX Male Female Connectors having rubber sheeth protection for Cross connecting DmX wiring connections Approved Make OEM
LIGHTING CONSOLE
DmX Touch Screen based controller having 7” Multi touch screen option 2 DmX Outlets 5 Pin XLR’s, 512 Channels each, Optically isolated outputs, 4 Smooth Encoders for control operation of attributes, Backlit keys, 12 Fader Stacks, 600+ Playbacks, 350+ Group saving, 350+ Presets, User defined shape effects, Macro saving options, External Midi timecode options, Internal clock, Shortcut user interfaces, Master fader, Blackout Key under Master fader, Numerical keypad for the light command entry inbuilt embedded within controller, USB interface, Scene saving options, Show saves and load save features, custom built user interface library for fixture files.
DMX SPLITTER
POWER CABLE
SITC of 1.1 kV grade XLPE insulated armoured cable conforming to IS 7098 (Part 1): 1988, having stranded compact shaped conductors as per Cl. 2 of IS 8130: 1984, PVC inner sheath and PVC Type ST-2 outer sheath conforming to IS 5831: 1984, including necessary clamping / dressing with cable ties and termination complete as all specified and directed by engineer- in- charge. Make: Havells, Polycab, RR Kabel
3 core, 1.5 mm² 2XY Cable
DMX CABLE
supply installation testing and commissioningof 3 Core DmX Cable with Sheathed housing on the cable, well designed insulation, low noise suitable to transmet DmX signal. OEM
STAGE VIDEO SYSTEM
PROJECTOR
Supply Installation Testing and Commissioning of High Brightness WUXGA Projector. It must have a minimum of Resolution: WUXGA (1920 x 1200). Contrast Ratio: 2,000,000:1. Light Source: DuraCore laser. Light Source Life: Up to 30,000 hours. Technology: DLP. Aspect Ratio: 16:10. Keystone Correction: ± 40° horizontal and vertical. Lens Shift: Full horizontal and vertical lens shift. Warping and Edge Blending: Integrated processor for warping and edge blending. Redundancy: Built-in redundancy mode and redundant input with fast switching. Dust Resistance: IP5X dust resistance rating. Operating Temperature: 0~50°C
PROJECTOR MOUNTING
supply installation testing and commissioningof Projector Mounting Hardware - Approved Make - OEM
WALL PLATE AVIP ENCODER
supply installation testing and commissioning of Wall Mount type network Encoder Digital Video Input: HDMI, DVh D*, Dual-Mode DisplayPort (DP++)Analog Video Input: HD-15 VGA, Component Video Output: Video Output Formats: HDMI, DVI- D*, Dual-Mode DisplayPort (DP++)*, HDCP content protection support, RGBHV, YPbPr Progressive Input Resolutions Supports most common HD up to 1920x1200. Latency: 10 ms at 60 fps Bandwidth: 840 Mb/s (varies with resolution) Ethernet: 10/100/1000 Mbps, auto-negotiating, auto-sensing, full/ half duplex, DHCP, Auto IP, and Static IP HDMI: HDCP, EDID management etc. all complete & as per the direction of Engineer-in-Charge. Bidder Shall Submitted oem authorization along with technical bid
AVIP DECODER
supply installation testing and commissioning of Digital Video Input Network video over Ethernet via RJ45 ports Video Output HDMI, DVI-D (through adapter) Formats HDMI, DVI-D (through adapter), HDCP content protection support Output Resolutions Supports most common HD up to 1920x1200. See website for all supported resolutions. Video Latency 10 ms at 60 fps Audio Latency Standard SVSi audio stream= 17-msec (synched to video); AES67 = <1-msec adjustable to 17-msec Ethernet PO 10/100/1000 Mbps, auto-negotiating, auto-sensing, PoE, full/half duplex, DHCP, Auto IP, and Static IP P1 10/100/1000 Mbps, auto-negotiating, auto-sensing, full/half duplex, DHCP, Auto IP, and Static IP +12V 2A One 12 Volt DC power input Input Signal Types Network video over Ethernet via RJ45 Bidder Shall Submitted oem authorization along with technical bid
DISPLAY FOR FEEDBACK WITH MOUNTING
55" 4K UHD Professional Display with Adjustable Wall Mount
DISPLAY FOR TELE-PROMPTER WITH MOUNTING
65" 4K UHD Professional Display with Adjustable floow mount stand for Teleprompter purpose.
GIGABIT AV LINE POE SWITCH
supply installation testing and commissioning of AV line Switches10G Base-X Fiber SFP+ Ports12 # 1/10G Base-T Copper PortsEthernet: Out-of-band 1G port (Front)Console: RJ45 RS232 (Front)Console: Mini-USS (Front)Storage: USB (Front)Half-width 1-unit 1U rack mountCPU/ MemoryCPU: 800 MHzRAM: 1 GBPacket buffer memory: 32 MBStack height: 8 switchesFlash: 256 MBSwitching fabric: 480 Gbps Line7Rate (non blocking fabric)Throughput: 357 Mpp sForwarding mode: Store7and-forwardAddress database size: 16,000 MAC addresses (48-bit MAC address)Number of VLANs: 4,093 (IEEE 802.1Q) simultaneously Number of multicast groups= 2K IPv4Number of multicast groups= 2K IPv6ARP/NDP= 2KNumber of LAGs (802.3ad): 128 LAGs with up to 8 ports per groupNumber of hardware queues for QoS: 8 (Standalone)Number of routes: 512 IPv4 Unicast Protocol (MVRP)LAG HashingLAG Member Port Flaps TrackingUDLD supportDistributed Link AggregationStorm Bidder Shall Submitted oem authorization along with technical bid -
AV CONTROLLER
supply installation testing and commissioning of Integrated Controller ,Dual Network Interface card ,Should support IPv6 Should Supports IEEE Standard for Port-based Network Access Control with the ability to grant or deny network access to devices wishing to attach to a LAN based on credentials tied to the device rather than to a user Should have High Performance Architecture, Flexible Programming Platform ( Java) - ,Should have ability to manage secure port TLS and SSH communications with a remote device or server ,Enhanced Diagnostics On Serial and IR Ports , shall be supplied with OEM powersupply ,Hardware I Software should be Built for 24/7/365 Operation ,Should have Ultra-Fast 1600 processor, 512 MB Onboard RAM , 1 M Non-Volatile Memory, 8 GB SDHC FLASH Memory ,1 RU Rack Space ,10/100 LAN Interface ,4 Digital 1/0 Ports , 1 RS-232 /422/485 Port , 3 RS-232-Only Ports , 4 IR/Serial Output Ports , 4 Relay Ports ,Regulatory Compliance :UL 60950-1 and RoHS ,WEEE etc. all complete & as per the direction of Engineer-in-Charge. Bidder Shall Submitted oem authorization along with technical bid
CONTROL TOUCH PANEL FOR VIDEO SWITCHING
supply installation testing and commissioning of 10.1" Table Top Touch Panel, Shall have Graphics Engine and Quad Core Processing, Built-in Web Browser and Content Viewers, "Display Type: TFT Active Matrix Color LCD, Display Size: Minimum 10" diagonal, Resolution :1280x800 Aspect Ratio (WH) Landscape: 16:9, ,Brightness minimum 400 cd/m2, Contrast Ratio 700:1, Color Depth 16.7M colors, Illumination LED, Touch Overlay Projected Capacitive, multi-touch support, Viewing Angle Vertical ± 89°, Horizontal± 89°, SDRAM 2 GB, Flash 16 GB, Maximum Project Size 12 GB flash, available for apps and touch panel files, "Ethernet 10/100 Auto MDI-X port, RJ-45 connector., USB (1) for Firmware upgrade, touch panel file transfer, document and image viewing etc. all complete & as per the direction of Engineer-in-Charge. Bidder Shall Submitted oem authorization along with technical bid
4K ACTIVE HDMI CABLE
supply installation testing and commissioningof 5M 4K 60Hz: Tobo Fiber Optic HDMI 2.0b Cable High Speed HDMI to HDMI 18Gbps Subsampling 4:4:4/4:2:2/4:2:0, HDTV, HDCP2.2, 3D 2160P 1080P Ethernet, ARC, HOR, Ultra HD, UHD 4k HDMI Cor High Speed 18Gbps Supports HDR/CEC/EDID /HDCP2.2, 1536KHz Sample Rates, 4K@60Hz, 32 Uncompressed Audio and Video Sync, ARC, Chroma Bidder Shall Submitted oem authorization along with technical bid
supply installation testing and commissioningof 3M 4K 60Hz: Tobo Fiber Optic HDMI 2.0b Cable High Speed HDMI to HDMI 18Gbps Subsampling 4:4:4/4:2:2/4:2:0, HDTV, HDCP2.2, 3D 2160P 1080P Ethernet, ARC, HOR, Ultra HD, UHD 4k HDMI Cor High Speed 18Gbps Supports HDR/CEC/EDID /HDCP2.2, 1536KHz Sam Bidder Shall Submitted oem authorization along with technical bidple Rates, 4K@60Hz, 32 Uncompressed Audio and Video Sync, ARC, Chroma Bidder Shall Submitted oem authorization along with technical bid
CAT 6A CABLE
M & L RoHS compliant and UL listed category 6A, 4 pair F/UTP (shielded) LSZH 23 AWG twisted pair cable, having bare copper conductor, polyolefin insulation, LSZH jacket, aluminium / polyester shield (tape), characteristic impedance 100 ±15% Ω , maximum DC resistance 7.8 Ω/100 m, maximum delay skew 45 ns, normal velocity of propagation (NVP) 69%, maximum operating voltage 80 V, segregation Class c, fully compliant with the recommendations set forth by IEEE 802.3bt (Type 4) for the safe delivery of power over LAN cable when installed according to ISO/IEC 14763-2, CENELEC EN 50174-1, CENELEC EN 50174-2 or TIA TSB-184-A complete all as specified and directed by the engineer-in-charge.
AUDIO SYSTEM
FLYABLE LINE ARRAY FOR FOH
Supply, installation, testing & Comissioning of Front-of- House left and right clusters with a 15" LF driver or better and HF drivers loudspeaker system; with Individual Module free field Frequency Range (-10dB) of 34Hz to 20kHz or better & Continuous Power Handling of >=600W AES,or batter The Loudspeaker module shall have a 135dB continuous, 141dB peak@ 1m Sensitivity should 96dB@ 1W/1m It should have Horizontal near dispersion pattern of 90° or better, vertical dispersion of the array shall be 60 degrees or better. Bidder Shall Submitted oem authorization along with technical bid
Supply, installation, testing & Comissioning of Front-of- House left and right clusters with a 15" LF driver or better and HF drivers loudspeaker system; with Individual Module free field Frequency Range (-10dB) of 34Hz to 20kHz or better & Continuous Power Handling of >=600W AES,or batter The Loudspeaker module shall have a 135dB continuous, 141dB peak@ 1m Sensitivity should 96dB@ 1W/1m It should have Horizontal near dispersion pattern of 60° or better, vertical dispersion of the array shall be 40 degrees or better. Bidder Shall Submitted oem authorization along with technical bid
ARRAY FRAME / HANGING MOUNT ARRANGEMENT
Supply, installation, testing & Commissioning of OEM array frames/ Hanging/ Mounting arrangement for Suspension of upto 4 array modules offered above, Shall offer multiple rigging points for achieving desired pitch settings Bidder Shall Submitted oem authorization along with technical bid
SUBWOOFER FOR FOH
Supply, installation, testing & Commissioning of a Dual 18" subwoofer. The louspeaker shall meet the following performance criteria: Frequency Range (-10 dB) of 28Hz to 1KHz. It should have an ground stack position. Sensitivity of> = 102dB @ 1W/1m or more delivering a ground position Max. Calculated SPL(peak) of >=136 dB; Nominal impedance of 4ohm or higher and continuous 1600W AES, 6400W peak or more. The loudspeaker system shall be comprised of a 16 mm Birch plywood Bidder Shall Submitted oem authorization along with technical bid
SURFACE MOUNTED POINT SOURCE SPEAKERS FOR FRONT FRILL
Supply, installation, testing and commissioning of Front Fill Speakers must have two-way 8" -inch with 120x60 deg horn or better high SPL surface mount loudspeaker. Frequency Range (-10 dB) of 52Hz to 20kHz or better; Nominal Dispersion :90° conical or better; Power handling of 375W AES, 1000W peak or more; Sensitivity 92dB@ 1W/1m or better and the 116dB continuous with a Nominal impedence of 8 ohms.Bidder Shall Submitted oem authorization along with technical bid
SURFACE MOUNTED POINT SOURCE SPEAKERS FOR BALCONY
Supply, installation, testing and commissioning of Front Fill Speakers must have two-way 8" -inch with 120x60 deg horn or better high SPL surface mount loudspeaker. Frequency Range (-10 dB) of 52Hz to 20kHz or better; Nominal Dispersion :90° conical or better; Power handling of 375W AES, 1000W peak or more; Sensitivity 92dB@ 1W/1m or better and the 116dB continuous with a Nominal impedence of 8 ohms.Bidder Shall Submitted oem authorization along with technical bid
POWERED STAGE MONITOR
Supply, installation, testing and commissioning of Powered Stage Moniters two-way 12" -inch or better high SPL surface mount loudspeaker. Frequency Range (-10 dB) of 50Hz to 20kHz or better; Nominal Dispersion :90° x 50°r; Power handling of 1000W AES, 2000W peak or more. SPL at 132dB peak@ 1m or more with a Nominal impedence of 8 ohms.
SURFACE MOUNTED POINT SOURCE SPEAKERS FOR GREEN ROOM
Supply, installation, testing and commissioning of Compact 8" -inch 2 way loudspeaker high SPL surface mount loudspeaker. Frequency Range (-10 dB) of 53Hz to 20kHz or better; Nominal Dispersion :90° x 50° or better; Power handling of 700W AES, 1500W peak or more; Sensitivity 94dB@ 1W/1m or better and the 120dB continuous with a Nominal impedence of 8 ohms.Bidder Shall Submitted oem authorization along with technical bid
4-CHANNEL POWER AMPLIFIER FOR LINE ARRAYS
supply installation testing and commissioning of 4 Channel Power Amplifiers Each Amplifier Should Deliver Minimum Power 1900 Watts Per Channel @ 8 Ohms, 2400 Watts Per Channel @ 4 Ohms And 4800 Watts In Bridge Mode @ 8 Ohms. Frequency Response Should Be 20hz To 20khz +- 0.25 Db. Damping Factor Greater than 5000 And Minimum Signal To Noise Ratio Of 108db. Cooling Air flow from front to rear Protection Fuseless short circuit protection, ultrasonic and RF protection, thermal protection Load Protection Turn on delay, No fault protection, Ultrasonic limiting with Built in DSP along with communication protocol like Blu-Link and Network connectivity. Bidder Shall Submitted oem authorization along with technical bid
4-CHANNEL POWER AMPLIFIER FOR SUBWOOFER
supply installation testing and commissioning of 4 Channel Power Amplifiers Each Amplifier Should Deliver Minimum Power 1250 Watts Per Channel @ 8 Ohms, 1250 Watts Per Channel @ 4 Ohms And 2500 Watts In Bridge Mode @ 8 Ohms. Frequency Response Should Be 20hz To 20khz +- 0.25 Db. Damping Factor Greater than 1500 And Minimum Signal To Noise Ratio Of 108db. Cooling Air flow from front to rear Protection Fuseless short circuit protection, ultrasonic and RF protection, thermal protection Load Protection Turn on delay, No fault protection, Ultrasonic limiting. Bidder Shall Submitted oem authorization along with technical bid
4-CHANNEL POWER AMPLIFIER FOR FRONT FRILL, BALCONY & GREEN ROOM
supply installation testing and commissioning of 4 Channel Power Amplifiers Each Amplifier Should Deliver Minimum Power 1250 Watts Per Channel @ 8 Ohms, 1250 Watts Per Channel @ 4 Ohms And 2500 Watts In Bridge Mode @ 8 Ohms. Frequency Response Should Be 20hz To 20khz +- 0.25 Db. Damping Factor Greater than 1500 And Minimum Signal To Noise Ratio Of 108db. Cooling Air flow from front to rear Protection Fuseless short circuit protection, ultrasonic and RF protection, thermal protection Load Protection Turn on delay, No fault protection, Ultrasonic limiting. Bidder Shall Submitted oem authorization along with technical bid
24 CHANNEL DIGITAL MIXER
DIGITAL STAGE BOX
Supply Installation Testing and Commissioning of Digital Stage Box. 32 Channel Stage box with Ethernet Connecvitiy with Madi Card. It must have Frequency Response Mic / Line Input to any Output: +0/-1dB, 20Hz – 20kHz T.H.D. Mic Sensitivity -30dBu: < 0.01% @ 1kHz Noise Residual noise: -85dBu Mic Input E.I.N. (maximum gain): -125dBu (150Ω source) Mix noise, masters at unity: < -86dBu 1 input to mix at unity gain: -84dBu CMRR mic @1KHz (max gain): -86dBu Crosstalk (@ 1kHz) Mic – Mic: <-80dB @ 1kHz Input Gain Mic Gain: -5dB – 58dB integrated pad design 1dB steps Max. input level: +24dBu Max. output level: +22dBu Sample rate: 48kHz Convertor resolution: 24 bit Latency: 1.5ms Internal clock accuracy: +/- 25ppm Mains power consumption: 33W Mains voltage operating range: 90 — 264 VAC, 47 — 63Hz Operating temperature range: -10oC — +50oC Relative humidity: 0 — 90% Storage temperature range: -10oC — +50oC. Bidder Shall Submitted oem authorization along with technical bid.
FEEDBACK SUPPRESSOR
Supply Installation Testind and Commissioning of Advance Feedback Suppressor. It must have Number of Inputs: 2, Input Connectors : Female XLR and 1/4” TRS, Input Type : Electronically balanced/unbalanced, RF filtered, Input Impedance : Balanced 50kΩ, Unbalanced 25kΩ, Max input line level +20 dBu, CMRR > 40dB, typically >55dB @ 1kHz, Number of Outputs : 2, Output Connectors : Male XLR and 1/4” TRS, Output Type : Electronically balanced/unbalanced, RF filtered, Output Impedance : Balanced >120 Ω, Unbalanced >60 Ω, Max Output Level : +20 dBu, A/D Dynamic Range >113 dB A-weighted, >110 dB unweighted, 22kHz BW Type IV Dynamic Range >119 dB, A-weighted, 22kHz BW; >117 dB, unweighted, 22kHz BW A/D Conversion 24-bit, Sample Rate : 48kHz D/A Dynamic Range 112 dB A-weighted, 109 dB unweighted D/A Conversion 24-bit Dynamic Range 109 dB A-weighted, 106 dB unweighted, 22kHz BW THD+Noise 0.003% typical at +4 dBu, 1 kHz Frequency Response 20Hz – 20kHz, +/- 0.5dB Interchannel Crosstalk >80 dB typical Crosstalk input to output >80 dB Operating Voltage 100-120VAC 50/60 Hz - EU: 220-240 VAC 50/60 Hz Power Consumption 9 W. Bidder Shall Submitted oem authorization along with technical bid.
DIRECT INJECTION BOX FOR INSTRUMENT MIC
supply installation testing and commissioning of Active Direct injection box with Hi-Z ¼" Input Jack< Parallel ¼" Thru Jack < Transformer Isolated Balanced XLR Lo-Z Output < 3-Way 0/20/40 dB Pad Switch +48V Phantom Powered Operation Direct injection box must have ground lift switch to solve potential hum and buzz problems due to ground loops. input filter Switchable: Low Pass @ 6 kHz Main Output CMRR (60 Hz): 128 dB typical@60 Hz Output Polarity: Switchable: Normal / Invert Bidder Shall Submitted oem authorization along with technical bid
DUAL CHANNEL WIRELESS HAND-HELD MICROPHONE SET
Supply, Installation testing & commissioning of Wireless Handheld microphone with Frequency response : S0Hz - 15kHz or better; 8 hours of operation; 18 frequency banks; Microphone type: Dynamic; Polar Pattern : Cardioid or better; RF Power : 30mW or better; Senstivity : 2.1mV/Pa or better complete with all standard accessories. Bidder Shall Submitted oem authorization along with technical bid
DUAL CHANNEL WIRELESS LAPEL MICROPHONE SET
Supply, Installation testing & commissioning of Wireless Lapel Microphone with Frequency response : 25Hz - 1BkHz or better; Maximum SPL: 125 dB or better; Signal to noise ratio : > 50 dB or better; 8 hours of operation; 18 frequency banks; Pattern : Omni-directional or better; Microphone type: Condenser; RF Power : 30mW or better; Senstivity : 20mV/Pa or better; complete with all standard accessories. Bidder Shall Submitted oem authorization along with technical bid
WIRED GOOSENECK MICROPHONE FOR PODIUM
Supply, Installation testing & commissioning of Gooseneck Microphone with on/off switch having Frequency response : 50 Hz to 19 kHz or better; Nominal impedance : < 2000 or better; Max SPL : 107dB or better; Phantom power: +12V to +48V; Pattern : Cardioid or better; Microphone Type : Pre-polarized condenser, complete with all standard accessories.
WIRED HAND-HELD MICROPHONE
Supply, Installation testing & commissioning of Wired handheld microphone with Frequency response : 70-20000hZ or better; Pattern : SuperCardioid or better; Microphone type: Dynamic ; Senstivity : 2.6mV/Pa or better, complete with all standard accessories. Electrical Imedance - 600 Ohms and Load Impedance - 2000 Ohms. Bidder Shall Submitted oem authorization along with technical bid
WIRED INSTRUMENT MICROPHONE
Supply, Installation testing & commissioning of Wired Instrument Microphone with Frequency response: 50-20000Hz or better; Pattern : Cardioid or better; Microphone type: Dynamic Pressure Gradient Microphone ; Senstivity : 2.5mV/Pa or better, Equivalent noise level 18 dB(A) (IEC 60268-4) Max. SPL for 1 % / 3 % THD 147 dB SPL / 156 dB SPL Electrical impedance at 1000 Hz ≥ 600 Ohms Recommended load impedance ≥ 2000 Ohms complete with all standard accessories.Bidder Shall Submitted oem authorization along with technical bid
CONTROL ROOM MONITOR
Providign and Fixing of Control Room Moniters Frequency Response 74 Hz - 20 kHz(± 2.5 dB) Low cutoff -6dB 67 Hz High cutoff -6dB 25 kHz Short term max SPL e:96 dB Max. short term sine wave acoustic output on axis in half space, averaged 100 Hz - 3 kHz at 1 m.Long term max SPL e:91 dB Self-generated noise Self-generated noise ,;5 dB Harmonic distortion 70...400 Hz ,;3 % > 400 Hz ,;Q,5 % Amplifiers One (B) bass amplifier 25 W Class D G One (B) treble amplifier 25 W Class D Mains voltage 100-240 VAC 50/60Hz Power consumption ISS Active ,;Q,5 W Idle ,;5 WFull output 30 W Input RCA female, 7 kOhm.CrossoverBass/Treble 3000 Hz- Bidder Shall Submitted oem authorization along with technical bid
DIGITAL PODIUM
Supply Installation Testing and Commissionin of Digital Podium. Must be made with Mild Steel Material | Stand alone Digital Podium | Wheels with lock | Smooth round edge at the top | Tray For Keyboard | Single sliding tray with lock for protection of the Interactive Panel , Document Camera and Contro ler | Space for 19” or 22” Interactive panel with Motorized angle adjustment | Built-in Document Camera and 19” Interactive Panel |Drawer with lock for Document Camera | Shelf for keeping laptop or Documents | Locks for safety | Standard Rack to keep all the equipment and PC | RFID Lock mechanism | 19” Rack for storing equipment | Separate space for Vertical Desktop PC | Two Door system – One for Rack and other for PC | PC door with smal window for On/Off. | Front Door for Servicing | For placement of extra laptop or Document to show through Inbuilt Document Camera and for Presenter with Internal Lock. Lock Mechanism : 3 options in lock- Manual key, RFID and Biometric (finger) for better security and ease of use. Ease of Use : The single sliding wooden shelf covers and hide all 3 equipment’s - Interactive Monitor, Document camera and multimedia contro ler. Have door locks. Document Camera is installed and placed next to the interactive monitor for ease of use of both the items.
SPEAKER CABLE
Supply installation testing and commissioningof High flexible speaker cable for power amplifiers up to 2750 watts, Must Have Jacket PVC,Plenum rated polyvinyl chloride Wall thickness: 0.011" | 0.28mm Diameter: 0.112" | 2.85mm, black and red Conductor Stranded bare copper wires, 19‐strand annealed bare copper conductors Diameter: 0.090" | 2.29mm DC resistance: 1.68 Ω / 1000' | 5.51 Ω/KM Mutual capacitance: 41.6 pF/FT | 136.45 pF/M Impedance: 50 Ω Inductance: 0.14µH/FT | 0.46µH/M Velocity of Propagation: 55% Voltage rating: 300V Maximum current: 12A@25˚Cded bare copper wires, 19‐strand annealed bare copper conductors Diameter: 0.090" | 2.29mm DC resistance: 1.68 Ω / 1000' | 5.51 Ω/KM Mutual capacitance: 41.6 pF/FT | 136.45 pF/M Impedance: 50 Ω Inductance: 0.14µH/FT | 0.46µH/M Velocity of Propagation: 55% Voltage rating: 300V Maximum current: 12A@25˚C. Bidder Shall Submitted oem authorization along with technical bid
supply installation testing and commissioningof High flexible speaker cable for power amplifiers up to 1550 watts, 14 AWG 19-strand annealed bare copper conductors Diameter: 0.073" | 1.85mm. Must Have Jacket PVC,Plenum rated polyvinyl chloride Wall thickness: 0.011" | 0.28mm Diameter: 0.112" | 2.85mm, black and red Conductor DC resistance: 2.66 Ω / 1000' | 8.72 Ω/KM Mutual capacitance: 40.06 pF/FT | 131.40 pF/M Impedance: 51 Ω Inductance: 0.15µH/FT | 0.49µH/M Velocity of Propagation: 55% Voltage rating: 300V Maximum current: 8A@25˚C. Bidder Shall Submitted oem authorization along with technical bid
3 CORE MICROPHONE / AUDIO SIGNAL CABLE
supply installation testing and commissioningof high Quality Signal Cable Jacket PVC,22 AWG 7-strand annealed bare copper conductors Diameter: 0.029" | 0.74mm . Semi-rigid polyvinyl chloride Wall thickness: 0.008" | 0.20mm Diameter: 0.045" | 1.14mm. DC resistance: 16.4 Ω / 1000' | 53.79 Ω/KM Mutual capacitance: 39.7 pF/FT | 130.22 pF/M Impedance: 47 Ω Velocity of Propagation: 55% Voltage rating: 300V Maximum current: 2.8A@25˚C. Bidder Shall Submitted oem authorization along with technical bid
Subtotal
Lump sum price worked out by the tenderer for “SITE CLEARANCE & DEVELOPMENT AND EARTHWORK" as listed in Schedule ‘A’ Part - XII
Schedule ‘A’ Part -XII (SITE CLEARANCE & DEVELOPMENT AND EARTHWORK)
Subtotal
Lump sum price worked out by the tenderer for “FIRE FIGHTING ARRANGEMENT" as listed in Schedule ‘A’ Part - XIII
Schedule ‘A’ Part -XIII (FIRE FIGHTING ARRANGEMENT)
M & L for low smoke zero halogen (LS0H) fire survival control cable with circuit integrity, conforming to BS 7846 and rated for 600 V, having plain annealed stranded copper conductor with fire-resistant mica tapes covered by an extruded layer of cross-linked polyethylene, extruded layer of thermoplastic low smoke zero halogen (LS0H) compound, single layer of galvanized steel wires and thermoplastic LS0H compound sheath, suitable for operating temperature range -40 ˚C to +90 ˚C and minimum bending radius being 12 times the overall cable diameter, including laying, clamping, termination and ferruling complete as specified and directed by the engineer-in-charge.
2 core, 2.5 mm² (for instrumentation)
3 core, 2.5 mm² (for auto start/stop panel)
12 core, 2.5 mm² (for diesel engine pump)
M & L for 1.1 kV grade fire survival cable with fire rating FS (950/FWS) conforming to IS 17505-1: 2021, and having electrolytic annealed plain / tinned copper (Class 1/2) conductor conforming to IS 8130: 2013, mica tape layer (s) primary insulation, cross linked PE (XLPE) / cross linked HFFR secondary insulation, thermoplastic HFFR inner sheath, glass fibre heat barrier tape, galvanized round wire armour, thermoplastic HFFR (HFS-TP 90) / Cross Linked HFFR (HSF-XL 90) outer sheath including necessary clamping / dressing with cable ties and termination complete as all specified and directed by engineer- in- charge.
3 core, 35 mm² FS (950/FWS) Cable
3 core, 4 mm² FS (950/FWS) Cable
S & F of perforated hot dipped galvanized iron cable tray having galvanization thickness not less than 50 microns and perforation not more than 17.5% including fittigs viz. joints, bends, tees, etc. in convenient sections of length complete including cable tray supports supports and associated accessories, all as specified and directed by the engineer-in-charge.
300 mm X 50 mm X 1.6 mm
150 mm X 50 mm X 1.6 mm
100 mm X 50 mm X 1.6 mm
M & L for ISI marked MS ERW pipes conforming to IS: 1239 (Part 1 & 2) with all accessories like all fittings including tees, elbows, reducers, union, flanges, rubber gaskets, GI nuts bolts, washer, including supporting/fixing the pipe on floor / wall / ceiling with clamps, hangers, angles, channels (using anchor fasteners) with painting of one coat primer and 2 or more coats of synthetic enamel paint complete as specified and directed by the engineer-in-charge.
NOTES:
[i] Standard MS fittings with welded joint shall be used on pipes.
[ii] All hangers, clamps, brackets etc. shall be of galvanized iron.
[iii] Welding of any kind on the galvanised support / hanger shall not be permitted.
[iv] The pipe size 150 mm NB & below shall be MS 'C' class as per IS 1239 (Part- 1): 2004 & IS 1239 (Part- 2): 2011.
[v] The pipe size above 150 mm NB shall be welded black steel pipe heavy class as per IS 3589: 2001.
[v] Pipes of size more than 50 mm NB shall be butt welded with fittings of equal or higher thickness whereas pipes below 50 mm NB size shall be socket welded.
M & L for ISI marked MS ERW pipes conforming to IS: 1239 (Part 1 & 2) with painting of one coat primer and 2 or more coats of synthetic enamel paint, accessories like all fittings including tees, elbows, reducers, union, flanges, rubber gaskets, GI nuts bolts, washer, including supporting / fixing the pipe in ground including welding, excavation & providing cement concrete blocks as supports, anticorrosive treatment with coal tar / asphalt tape as per IS 10221, refilling the trench etc. complete as specified and directed by the engineer-in-charge.
NOTES:
[i] Standard MS fittings with welded joint shall be used on pipes.
[ii] All hangers, clamps, brackets etc. shall be of galvanized iron.
[iii] Welding of any kind on the galvanised support / hanger shall not be permitted.
[iv] The pipe size 150 mm NB & below shall be MS 'C' class as per IS 1239 (Part- 1): 2004 & IS 1239 (Part- 2): 2011.
[v] The pipe size above 150 mm NB shall be welded black steel pipe heavy class as per IS 3589: 2001.
[v] Pipes of size more than 50 mm NB shall be butt welded with fittings of equal or higher thickness whereas pipes below 50 mm NB size shall be socket welded.
M & L for PN 1.6 rated 200 mm NB polypropylene Vortex inhibitor suction lift, conforming to BS 4504 with stainless wire mesh, bolts, nuts and washers, etc. complete all as specified and directed by the engineer-in-charge.
M & L for FM approved and UL listed, PN 1.6 rated lever operated, wafer type CI Butterfly valve, conforming to IS 13095: 1991,fitted with visual indicator & temper switch, having Cast iron (CI) body with ductile iron EPDM coated disc, SS431 stub shaft, PTFE bushing, flange drilling standard end connection conforming to IS: 1538- 1993 along with necessary accessories complete as specified and directed by the engineer-in-charge (for Zone control valve assembly).
S & F of CL 150 # rated ball valve, designed & manufactured as per IS: 9890 (1981) and tested as per BS 6755 Part- I, having floating type three piece design, CS body, SS- 304 ball, PTFE seal / packing / gasket, CS fastners and lever and screwed/socket weld end connection, etc. with accessories complete all as specified and directed.
M & L for PN 1.6 rated GI Puddle Flange designed & manufactured as per BS 1560-3.1 & BS 4504 for suction of fire pumps from water tank all complete all as specified and directed by the engineer-in-charge.
S & F of orifice plate made out of 6 mm thick SS 304 with orifice of required size to be fitted between flange and landing valve of external and internal hydrants to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as specified and directed by the engineer-in-charge.
S & F non-percolating rubber reinforced lined RRL hose type-B 15 m long fire hose of 63 mm NB size, conforming to IS 636: 1988, rated for bursting pressure of 35.7 kg/cm² complete with gunmetal male & female coupling conforming to IS: 903- 1993, bound and rivetted to the hose pipe with copper rivets and 1.5 mm² copper wire complete as specified and directed by the engineer-in-charge.
Supply, installation, testing and commissioning of automatic air-vent valve with 20 mm end connections, brass body and cover, plastic float, brass cap etc. suitable for maximum operating pressure of 16 bar and maximum operating temperature 100 °C respectively, installed on all high points in the water piping system to automatically remove the trapped air complete all as specified and directed.
Supply, installation, testing and commissioning of FM approved and UL listed addressable relay module to provide FACP a dry-contact output for activating a variety of auxiliary devices, viz. fans, dampers, control equipment, etc. having built-in type identification, integral LED indicators, high noise immunity, SMES screws with clamping plates for wiring ease, direct-dial entry of address, etc. complete all as specified and directed by engineer-in-charge.
M & L flame retardant, low smoke & low halogen fire alarm armoured cable having stranded class 2 copper conductor conforming to EN 60228, insulated with XLPE type GP8 conforming to BS 7655-1.3, extruded inner sheath with PVC conforming to BS 5467, armoured with galvanised steel round wire and sheathed with extruded FRPL PVC conforming to BS 5467, suitable for voltage rating 600/1000 V, maximum operation temperature 90 °C, maximum conductor temperature at short-circuit 250 °C, RED in colour, including laying, termination and ferruling complete all as specified and directed by engineer-in-charge.
2 core, 1.5 mm²
2 core, 2.5 mm²
Supply, installation, testing and commissioning of FM approved and UL listed (fire fighter's) Telephone Jack with Addressable Module mounted to a single-gang electrical back box with suitable interface module for two way communication with abvoe INTEGRATED FACP having FFT feature complete all as specified and directed by engineer-in-charge.
Supply, installation, testing and commissioning of FM approved and UL listed Fire Fighter's Telephone Handset for two way communication with the with abvoe INTEGRATED FACP having FFT feature complete all as specified and directed by engineer-in-charge.
M & L for transparent FR PVC insulated, twin core copper conductor flexible Speaker cable having stranded annealed tinned copper conductor, PVC insulated cores twisted to form pairs, shielded for interference rejection, unarmoured PVC sheathed 1.1 kV grade in conductor size 2 X 1.0 mm2 including laying, termination and ferruling complete all as specified and directed by engineer-in-charge.
S & F 6 kg capacity dry chemical powder (ABC) type fire extinguisher, conforming to IS 15683: 2006, with initial filling in brand new cylinder with powder coated finish, fitted in gunmetal union, high pressure CO2 gas cartridge, discharge hose, wall mounting bracket / floor trolley mounting accessories along with suitable signage, etc. complete all as specified and directed by the engineer-in-charge.
S & F of 4.5 kg light-weight squeeze grip CO2 type fire extinguisher, conforming to IS 15683: 2006, with CO2 gas filled in brand new seamless cylinder with powder coated finish, made out of Manganese steel with wheel type valve, discharge nozzle, bend & horn, wall mounting bracket / floor trolley mounting accessories along with suitable signage complete all as specified and directed by the engineer-in-charge.
S & F of 9 litre Mechanical Foam type fire extinguisher, conforming to IS 15683: 2006, with initial filling in brand new cylinder with powder coated finish, fitted with gunmetal union, high pressure CO2 gas cartridge, hose and ABS type branch pipe and wall mounting bracket / floor trolley mounting accessories along with suitable signage complete all as specified and directed by the engineer-in-charge. (In Parking Area)
Make: Kanex, Minimax, Aim-EX, Safeguard, coffco, Variex
[i] Test Pressure: 250 kgf / Sq. cm
[ii] Operating temperature : -300C to + 550C
[iii] Locking pin and wire seal should be provided to indicate that the extinguisher has not been use.
[iv] Every Extinguisher should be supplied with an operating manual.
S & F 6 kg capacity dry chemical powder (ABC) type fire extinguisher, conforming to IS 15683: 2006, with initial filling in brand new cylinder with powder coated finish, fitted in gunmetal union, high pressure CO2 gas cartridge, discharge hose, wall mounting bracket / floor trolley mounting accessories along with suitable signage, etc. complete all as specified and directed by the engineer-in-charge.
S & F of 4.5 kg light-weight squeeze grip CO2 type fire extinguisher, conforming to IS 15683: 2006, with CO2 gas filled in brand new seamless cylinder with powder coated finish, made out of Manganese steel with wheel type valve, discharge nozzle, bend & horn, wall mounting bracket / floor trolley mounting accessories along with suitable signage complete all as specified and directed by the engineer-in-charge.
S & F of 9 litre Mechanical Foam type fire extinguisher, conforming to IS 15683: 2006, with initial filling in brand new cylinder with powder coated finish, fitted with gunmetal union, high pressure CO2 gas cartridge, hose and ABS type branch pipe and wall mounting bracket / floor trolley mounting accessories along with suitable signage complete all as specified and directed by the engineer-in-charge. (In Parking Area)
Subtotal
Schedule ‘A’ Part -XIV (FURNITURE)
Sofs set 4 seater with cushion (1 long piece of 3 seat and one single piece) timber shall be Ist class teakwood(MP Teak) used throughout. All faces of timber shall be wrought. Seat and back shall be 100mm thick PU foam make "Sleep Well/Kurlon or MM Foam 40 density covered with tapestry cloth of approved quality (as approved by GE).All wooden surfaces exposed to view shall be French polished to high gloss finish. Rest all as shown on drawing FD/MAP-II/02
Sofa Single seat of size 86 cm length x90.50 cm depth x85.50 cm height x 45 cm seat height in M/s Godrej interio Or equilent moled in Methodex.
Sofa Three seater of size 206 cm length x90.50 cm depth x85.50 cm height x 45 cm seat height in M/s Godrej interio Or equilent moled in Methodex.
Push back Chair Auditorium High Back having central distance (centre to centre clearance) shall be height 103.50 cm height back chair with cupholder, depth 71.50 cm and length 64 cm, multiple color black, fabric upholistery material, mild steel of frame material, suitable head support and fixed seat through chemical+ nut bolt. All expose parts shall be spray painted. M/s Godrej interio Or equilent model No : AUDI-04 in Methodex, Allied etc. Note : The chair shall be installed and fixed with chamical and nut-bolt heavy duty.
Push back Chair Auditorium Mid Back having central distance (centre to centre clearance) shall be height 95 cm height back chair with cupholder, depth 71.50 cm and length 64 cm, multiple color black, fabric upholistery material, mild steel of frame material, suitable head support and fixed seat through chemical+ nut bolt. All expose parts shall be spray painted. M/s Godrej interio Or equilent model No : AUDI-01 in Methodex, Allied etc. Note : The chair shall be installed and fixed with chamical and nut-bolt heavy duty.
Fixing charges / chair ( Chemical fixing + bolt)
Subtotal
Lump sum price worked out by the tenderer for “ARBORICULTURE WORKS" as listed in Schedule ‘A’ Part - XV
Schedule ‘A’ Part -XV (ARBORICULTURE WORKS)
Supply and stacking of good earth at site brought from outside MD land including royalty and carriage for all leads and lifts all as specified and directed byEngineer-in-Charge. Note :- For the purpose of payment the stack measurement shall be reduced by 20% for voids.
Supply and stacking of well decomposed Cow dung/ meegni manure including royalty, loading, unloading, transportation and stacking etc at site. Note:- For the purpose of payment the stack measurement shall be reduced by 10% for voids.(338Cum for Lawns and 49 Cum for trees and shrubs)
Supply and stacking of Regent/ DCM agronil to improve the soil quality complete all as specified and directed by Engineer-in-Charge.
Supply and stacking of gypsum 50 kg bag complete all as specified and directed by Engineer-in-Charge.
PITS FOR TREEES :Preparation of pit for trees by excavating in ordinary soft/ loose soil of size 60cm X 60cm X 60cm deep, getting out, returning , filling in the same with the excavated earth (after removal of rubbish) mixed with manure in the ratio of 2:1 by volume (2 part of stacked volume of earth after reduction by 20% and 1 part of stacked volume of manure after reduction by 10%) flooding with water, dressing and removing surplus soil to a distance n exc 50m including spreading & levelling complete all as specified and directed by Engineer-in-Charge. Note- (i) Cost of manure, Pesticide or extra good earth if needed to be paid for separately.
Supplying & Planting of "Neem" trees as approved by GE of 6 feet height with poly bag in pits (Holes) as prepared here-in -before and complete maintenance of trees during currency of contract including mortality replacement with same height of plant complete all as specified and directed by Engineer-in-Charge.
Supplying & Planting of "Mango" trees as approved by GE of 6 feet height with poly bag in pits (Holes) as prepared here-in -before and complete maintenance of trees during currency of contract including mortality replacement with same height of plant complete all as specified and directed by Engineer-in-Charge.
Supplying & Planting of "Keenu" trees as approved by GE of 6 feet height with poly bag in pits (Holes) as prepared here-in -before and complete maintenance of trees during currency of contract including mortality replacement with same height of plant complete all as specified and directed by Engineer-in-Charge.
Supplying & Planting of "Gulmohar" trees as approved by GE of 6 feet height with poly bag in pits (Holes) as prepared here-in -before and complete maintenance of trees during currency of contract including mortality replacement with same height of plant complete all as specified and directed by Engineer-in-Charge.
Supplying & Planting of "Palm" trees as approved by GE of 6 feet height with poly bag in pits (Holes) as prepared here-in -before and complete maintenance of trees during currency of contract including mortality replacement with same height of plant complete all as specified and directed by Engineer-in-Charge.
PITS FOR SHRUBS : Preparation of pit for shrubs by excavating in ordinary soft/ loose soil of size 30cm X 30cm X 45cm deep, getting out, returning , filling in the same with the excavated earth (after removal of rubbish) mixed with manure in the ratio of 3:1 by volume (3 part of stacked volume of earth after reduction by 20% and 1 part of stacked volume of manure after reduction by 10%) flooding with water, dressing and removing surplus soil to a distance n exc 50m including spreading & levelling complete all as specified and directed by Engineer-in-Charge. Note- (i) Cost of manure, Pesticide or extra good earth if needed to be paid for separately.
Supplying & Planting of "Ashoka Regional" shrubs as approved by GE of 1 to 1.50 feet height in poly bag in pits (Holes) as prepared here-in -before and complete maintenance of trees during currency of contract including mortality replacement with same height of plant complete all as specified and directed by Engineer-in-Charge.
Supplying & Planting of "Bougen Villa" shrubs as approved by GE of 1 to 1.50 feet height in poly bag in pits (Holes) as prepared here-in -before and complete maintenance of trees during currency of contract including mortality replacement with same height of plant complete all as specified and directed by Engineer-in-Charge.
Supplying & Planting of "Benjamin" shrubs as approved by GE of 1 to 1.50 feet height in poly bag in pits (Holes) as prepared here-in -before and complete maintenance of trees during currency of contract including mortality replacement with same height of plant complete all as specified and directed by Engineer-in-Charge.
Supplying & Planting of "More Pankh" shrubs as approved by GE of 1 to 1.50 feet height in poly bag in pits (Holes) as prepared here-in -before and complete maintenance of trees during currency of contract including mortality replacement with same height of plant complete all as specified and directed by Engineer-in-Charge.
Supplying & Planting of "Hedge" shrubs as approved by GE of 1 to 1.50 feet height in poly bag in pits (Holes) as prepared here-in -before and complete maintenance of trees during currency of contract including mortality replacement with same height of plant complete all as specified and directed by Engineer-in-Charge.
Supplying & Planting of "Rose" shrubs as approved by GE of 1 to 1.50 feet height in poly bag in pits (Holes) as prepared here-in -before and complete maintenance of trees during currency of contract including mortality replacement with same height of plant complete all as specified and directed by Engineer-in-Charge.
Supplying & Planting of "Hibiscus" shrubs as approved by GE of 1 to 1.50 feet height in poly bag in pits (Holes) as prepared here-in -before and complete maintenance of trees during currency of contract including mortality replacement with same height of plant complete all as specified and directed by Engineer-in-Charge.
Supplying & Planting of "Marigold" shrubs as approved by GE of 1 to 1.50 feet height in poly bag in pits (Holes) as prepared here-in -before and complete maintenance of trees during currency of contract including mortality replacement with same height of plant complete all as specified and directed by Engineer-in-Charge.
TREE GUARDS :Supplying & fixing of tree guards 60 CM in plan and 1.5 Mtrs high from groung level made of 30mm x 30mm x 3mm angel iron frame and 30mm x 3mm flat iron welded wire mesh of size 32mm x 32mm x 3mm and vertical angle with shoe shall be embedded in the round firmly tree guard as shownn in drawing (Drg No : CWE/SGNR/SD/158/15 Sheet-1/1 revised dt 13 Sep 2019) with number plaque and writing nae of tree complee all as specified and directed by Enginner-in-Charge Note: Tree guard shall be painted two coat of synthetic enamel paint over of red oxide primer complete in all respect.
Subtotal
Lump sum price worked out by the tenderer for “SPL ITEMS WORKS (MISC)" as listed in Schedule ‘A’ Part - XVI
Schedule ‘A’ Part -XVI (SPL ITEMS WORKS (MISC))
Water Closet wall hung Make : Jaguar(continental) Code CNS WHT 353SPPZ Size (mm) 770 X 375 X 620
Wash Basin with full pedestal size (mm) 565x440x210mm Make : Jaguar Code FLS-WHT-5801 + FLS-WHT-5301
Wash Basin oval shape Make : Jaguar Code CNS-WHT-705 Size (mm) 595 x 420 x 200
Urinal with sensor size (mm) 475x315x715 Make :Jaguar Code URS-WHT-13259 (Rs 7690.00) for urinal and SNR-CHR-51097 (Rs 8400.00) for sensor Kit
Urinal partition wall Make : Jaguar Code JSE-CHR-810UC 450X 1810 UC
Single lever basin mixer Make : Jaguar (Lyric) Code LYR 38001B without popup waste
CP Bib cock with wall flange Make : Jaguar Code LYR 38037
Angular stop cock with wall flange Make : Jaguar Code LYR 38053
Bottle trap (with internal partition) 32 mm size with 250 mm wall connection ,pipe and wall flange. Code ALD-CHR-769L250X190
450 mm long braided hoses Make : Jaguar Code ALD 805 B
Toilet roll holder with flap Make : Jaguar Code AKP-CHR-35753PS
Towel rail 600 mm long Make : Jaguar Code AKP-CHR-35711PS
WC brush holder Make: Jaguar Code AKP-CHR-35743P
Soap dispensor Make: Jaguar Code AKP-CHR-35735P
Waste coupling full thread Make : Jaguar Code ALD 709L130
Hand drier Make OPTIMA (Jaguar ) Code HDR-SAP-M99ACS 304 SS ,Finish Satin
Painting with texture paint,natural grit regular in Two pack system(stone chips and binder 2mm thick) (one complete pack contains 25 kgs stone chips and 5 Ltr binder)
Aluminium door and frame with side hung shutters including hardware fittings size 44x135x2.00mm thick and style and rails beading and rubber gasket with fittings such as butt hinges 100 mm long (06 Nos) ,pivot,aluminium sections used door shall be powder coated.
Subtotal
SOM BUILDERS (BID ID -3503830)
M/s Khanna Enterprises (BID ID -3503044)
M/S Shiv Shakti Enterprises (BID ID -3503343)
NAFREF ENGINEERS PVT LTD (BID ID -3496852)
Pooja Singla Builders And Engineers Pvt Ltd (BID ID -3496540)
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.28 MB
CEBT5004HVAC.pdf
Tender Documents • 35.75 MB
archdrwngs.pdf
Tender Documents • 17.20 MB
TenderDocumentsCEBZ84528.pdf
Tender Documents • 2.53 MB
SOFDRWINGS.pdf
Tender Documents • 2.65 MB
strl01.pdf
Tender Documents • 18.77 MB
strl02.pdf
Tender Documents • 20.02 MB
TD.rar
Tender Documents • 34.91 MB
prepricedschedules.pdf
Tender Documents • 0.79 MB
BOQ_829826.xls
BOQ • 0.87 MB
Download all tender documents and submit your bid