Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.0 LAccepted-AOC | L1 | Accepted-AOC Lowest bidder | |
| 2 | L2₹22.3 L+₹4.7 L (27.1%)Rejected-Finance | L2 | Rejected-Finance Other than lowest | |
| 3 | L3₹22.9 L+₹5.4 L (30.9%)Rejected-Finance 00 A N SINHA ROAD KADAM KUAN PATNA BIHAR 800003 | PATNA | BIHAR | 800003 | L3 | Rejected-Finance Other than lowest | |
| 4 | L4₹25.4 L+₹7.9 L (45.0%)Rejected-Finance | L4 | Rejected-Finance Other than lowest |
Tender Value
Refer Docs
EMD Value
₹60,000
Closing Date
30 Sept 2020, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE BHOPAL
GE Bhopal, Bairagarh, Bhopal
REPAIR/MAINT OF INTERNAL ELECTRIFICATIONS AND FIXTURES IN CERTAIN MD AND OTM ACCN AT SI LINES UNDER GE BHOPAL
2020_MES_374529_1
8713/E8
Open Tender
Electrical and Maintenance Works
Item Rate
274 days
BHOPAL
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
Yes
GE BHOPAL
₹60,000
Yes
19 Nov 2020
3 Sept 2020
2 Oct 2020
3 Sept 2020
30 Sept 2020
17 Sept 2020
60 days
Amount
Taking down carefully existing point wiring (any type viz. aluminum or copper) with wooden batten/surface PVC conduit (with its fittings)/PVC casing-capping or any other type for light, fan, power point (including switch, socket, ceiling rose, etc.) and making good disturbed surface of wall/ceiling to match with existing surface after necessary rewiring complete all as specified and directed.
Taking down unserviceable sub main wiring including service connections, of any size and any description including conduit pipe and making good disturbed surface of wall/ceiling to match with existing surface after necessary rewiring complete all as specified and directed.
Taking down old unserviceable MCB DB of any size and capacity including wooden boards complete all as specified and directed.
M&L for point wiring for one light / fan / bell point with 1.50 sqmm (nominal area) FRLS PVC insulated, unsheathed, multi-stranded copper conductor cable, 1100 volts grade, controlled by one one-way switch, drawn in and including non metallic rigid PVC casing capping/PVC Conduit not less than 25mm base size with all fitting and fixing accessories including one run of 1.5 sqmm copper conductor as earth continuity wire connected to common earth dolly by suitable lugs, sunken sheet steel terminal box made out of 1.20 mm thick GI/MS sheet for mounting of fittings like switches, sockets, fan regulators, etc. with 3mm thick laminated hylum sheet cover complete all as specified and directed. [Make of Cable : Polycab/ Plaza/ Havells/KEI/V-MARC as approved by GE] Note : Wiring to be done as per approved colour code in IE rule.
All as per BOQ item No.4.00 above, but for one light point controlled by two 2 way switches complete all as specified and directed.
All as per BOQ item No.4.00 above, but for 3 pin 5 Amp socket outlet on independent board complete all as specified and directed.
All as per BOQ item No.4.00 above, one 5 Amps socket outlet point controlled by one switch on same board with other switches complete all as specified and directed.
All as per BOQ item No.4.00 above, but wiring with 2.5 Sq mm copper cable for 5/15 amp switch socket combination on or 3 pin socket out let 15 amp independent board and provision of 1.5 Sqmm, FRLS insulated multi-stranded single core earth wire for earth continuity, connected to common earth dolly complete all as specified and directed.
M&L for point wiring for one light / fan / bell point with 1.50 sqmm (nominal area) FRLS PVC insulated, unsheathed, multi-stranded copper conductor cable, 1100 volts grade, controlled by one one-way switch, drawn in & including non metallic rigid PVC conduit (ISI marked) medium grade not less than 20mm diameter with all conduit accessories in concealed wiring system by cutting of walls (brick or stone) and making good disturbed surface of wall in CM 1:3 (except on ceiling for fan point only, surface casing capping will be used in lieu of concealed PVC conduit) including one run of 1.5 sqmm copper conductor as earth continuity wire connected to common earth dolly, sunk sheet steel terminal box made out of 1.20 mm thick GI/MS sheet for mounting of fittings like switches, sockets, fan regulators etc. with 3mm thick laminated hylum sheet cover complete all as specified and directed. [Make of Cable : Polycab/ Plaza/ Havells/KEI/V-MARC as approved by GE] Note : Wiring to be done as per approved colour code in IE rule.
All as per BOQ item No. 9.00 above, but for 3 pin 5 Amp socket outlet on independent board complete all as specified and directed.
All as per BOQ item No. 9.00 above, one 5 Amps socket outlet point controlled by one switch on same board with other switches complete all as specified and directed.
All as per BOQ item No. 9.00 above, but for one light point controlled by two 2 way switches complete all as specified and directed.
All as per BOQ item No. 9.00 above, but wiring with 2.5 Sq mm copper cable for 5/15 amp switch socket combination on or 3 pin socket out let 15 amp independent board and provision of 1.5 Sqmm, FRLS insulated multi-stranded single core earth wire for earth continuity, connected to common earth dolly complete all as specified and directed.
M&L for point wiring for one light / fan / bell point with 1.50 sqmm (nominal area) FRLS PVC insulated, unsheathed, multi-stranded copper conductor cable, 1100 volts grade, controlled by one one-way switch, drawn in existing concealed conduit including one run of 1.5 sqmm copper conductor as earth continuity wire connected to common earth dolly by suitable lugs and 3mm thick laminated hylum sheet cover including taking old point wiring (any type without conduit) complete all as specified and directed. [Make of Cable : Polycab/ Plaza/ Havells/KEI/V-MARC as approved by GE] Note : Wiring to be done as per approved colour code in IE rule.
All as per BOQ item No.14.00 above, but for 3 pin 5 Amp socket outlet on independent board complete all as specified and directed.
All as per BOQ item No.14.00 above, one 5 Amps socket outlet point controlled by one switch on same board with other switches complete all as specified and directed.
All as per BOQ item No.14.00 above, but wiring with 2.5 Sq mm copper cable for 5/15 amp switch socket combination on independent board and provision of 1.5 Sqmm, FRLS insulated multi-stranded single core earth wire for earth continuity, connected to common earth dolly complete all as specified and directed.
All as per BOQ item No.14.00 above, but for one light point controlled by two 2 way switches complete all as specified and directed.
S&F Switch piano, flush type, single pole, one way, 5/6 Amps, 230 volt AC, ISI marked complete all as specified and as directed. [MAKE:-ANCHOR/LEADER/CONA as approved by GE]
S&F Socket outlet multipurpose having provision for 3 pin, 5 Amp and 2 pin, 5 Amp, piano flush type, 230 volt AC complete all as specified and as directed. [MAKE:-ANCHOR/LEADER/CONA as approved by GE]
S&F Switch socket combination, multipurpose, 6 pin, 5-15 Amp, flush type, ISI marked complete all as specified and as directed. [MAKE:-ANCHOR/LEADER/CONA as approved by GE]
S&F Switch socket combination, multipurpose, 2 in 1 , 3 pin, 5/6 Amps flush type, ISI marked complete all as specified and as directed. [MAKE:-ANCHOR/LEADER/CONA as approved by GE]
S&F Ceiling rose surface bakelite, three terminals complete all as specified and as directed. [MAKE:-ANCHOR/LEADER/CONA as approved by GE]
S&F Bell push, flush type, 5 Amp piano type, 230 volt AC ISI marked with valid CML No complete all as specified and as directed. [MAKE:-ANCHOR/LEADER/CONA as approved by GE]
S&F Switch piano, flush type, single pole, two way, 5/6 Amps, 230 volt AC, ISI marked complete all as specified and as directed. [MAKE:-ANCHOR/LEADER/CONA as approved by GE]
S&F Bell, electric, single phase, 230 volt, AC ISI marked with valid CML No complete all as specified and as directed. [MAKE:-ANCHOR/LEADER/CONA as approved by GE]
S&F angle holder PVC/Polycarbonate type complete all as specified and directed. [MAKE FOR HOLDER:-ANCHOR /LEADER/CONA & LAMP : BAJAJ/PHILIPS/SYSKA all as approved by GE]
S&F LED lamp 10 Watt B22 CDL complete all as specified and directed. [MAKE FOR HOLDER:-ANCHOR /LEADER/CONA & LAMP : BAJAJ/PHILIPS/SYSKA all as approved by GE]
S&F ceiling fan regulator electronic step type 240 V, AC 50 Hz single pole, 100 watts flush type, ISI marked complete all as specified and as directed. [MAKE:-ANCHOR/LEADER/CONA as approved by GE]
S&F factory made epoxy powder coated Distribution Board TP & N 4 ways (VTPN MCCB DB) and space for MCCB as In comer, with metal door ( IP-43 protection ) fabricated from CRCA sheet and fixed semi flush to wall and suitable for universal mounting and including 100 Amp copper bus bar for each phase, neutral bar, standard DIN rail, Earth bar and cable ties for cable management, top and bottom removable gland plates with Knockouts including taking down old unsv VTPN DB complete all as specified and as directed. Note:- MCCB shall be measured and paid separately. [MAKE: L&T/ Siemens/ Legrand/HAVELLS as approved by GE]
S&F in replacement MCB DB SPN 240 volts 200 amps rated bus bar, 12 way, double door complete all as specified and as directed. [MAKE:Hegar (L&T)/ Siemens/ Legrand/HAVELLS as approved by GE] NOTE:- MCB shall be measured and paid seperatly.
S&F in replacement MCB DB SPN 240 volts 200 amps rated bus bar, 8 way, double door complete all as specified and as directed. [MAKE:Hegar (L&T)/ Siemens/ Legrand/HAVELLS as approved by GE] NOTE:- MCB shall be measured and paid seperatly.
S&F in replacement MCB DB SPN 240 volts 200 amps rated bus bar, 4 way, double door complete all as specified and as directed. [MAKE:Hegar (L&T)/ Siemens/ Legrand/HAVELLS as approved by GE] NOTE:- MCB shall be measured and paid seperatly.
S&F in repairs MCB SP & N suitable for 240 volts, AC supply 40 to 63 Amps, with over load and short circuit protection and rupturing capacity not less than 10KA complete all as specified and directed. [MAKE:Hegar (L&T)/ Siemens/ Legrand/HAVELLS as approved by GE]
S&F in repairs MCB TP & N suitable for 240 volts, AC supply 40 to 63 Amps, with over load and short circuit protection and rupturing capacity not less than 10KA complete all as specified and directed. [MAKE:Hegar (L&T)/ Siemens/ Legrand/HAVELLS as approved by GE]
S&F MCB SP, 240 volts, 10 KA breaking capacity, 'C' curve, of capacity 5 to 30 amps complete all as specified and directed. [MAKE:Hegar (L&T)/ Siemens/ Legrand/HAVELLS as approved by GE]
S&F MCB SPN, 240 volts, 10 KA breaking capacity, 'C' curve, of capacity 6 to 32 amps complete all as specified and directed. [MAKE:Hegar (L&T)/ Siemens/ Legrand/HAVELLS as approved by GE]
S&F MCB SP, 240 volts, 10 KA breaking capacity, of capacity 40 to 63 amps complete all as specified and directed. [MAKE:Hegar (L&T)/ Siemens/ Legrand/HAVELLS as approved by GE]
S&F in replacement PVC rectangular block for mounting, switches, sockets, fan regulators, etc. with 3 mm thick plastic laminated sheet cover of size 250 mm X 300 mm and 50 mm deep complete all as specified and directed.
M&L for sub main wiring with approved colour coding as per IS (Red, Black and Green for single phase circuits) with two single core PVC insulated FRLS cable 1100V unsheathed with stranded copper conductor of 6.0 sqmm nominal cross section area and drawing into rigid non metallic PVC conduit, ISI marked, medium grade, inclusive of all fittings such as tees, bends, junction boxes, elbows, saddles, pipe hooks, couples, lock outs, etc. 20mm external diameter and PVC insulated stranded copper conductor of 4 sqmm nominal cross section area as earth wire including taking down old unserviceable sub main wiring complete all as specified and directed. [Make of Cable : Polycab/ Plaza/ Havells/KEI/V-MARC as approved by GE] Note: - Two runs of 6.0 sqmm cable, one run of 4.0 sqmm cable of earth continuity conductor & PVC conduit pipe shall be measured as one unit length.
S&F LED tube light complete fitting, surface mounted lumanaires, 1 x 18 W, 240V. Decorative ultra slim round /squar profile LED lighting fixture with extruded polycarbonate body, environmental friendly, energy efficient ready to use pack with bipin holders, LED lamps,connector block, etc. complete with all accessories internally pre-wired and including connecting up with flexible copper conductor cable with suitable size complete all as specified and directed by Engineer in charge . (Make : Havells LHEXBLP7PN1W018 or equivalant in C&G/Bajaj/Surya)
Refixing of tube light fitting any type any make retrieved against item No. 1.00 with connection complete all as specified and directed.
S&F LED tube light complete fitting, surface mounted lumanaires, 1 x 9 W, 240V. Decorative ultra slim round /squar profile LED lighting fixture with extruded polycarbonate , environmental friendly, energy efficient ready to use pack.with bipin holders, LED lamps,connector block, etc. complete with all accessories internally pre-wired and including connecting up with flexible copper conductor cable with suitable size complete all as specified and directed. (Make : Havells LHEXBLP7IN1W009 or equivalant in C&G/Bajaj/Surya)
S&F building security light fitting made up of pressure die cast aluminium housing with high effcient LED as lighting source and PC over having top opening seperate driver compartment with IP-66 protection and impact resistance of IK07 including suitable galvanized iron pipe “light grade” brackets 1 mtr length bent to shape to obtained required shape including clamps, nuts / bots / washers etc connecting with suitable flexible copper wire of size 23/0.0076 complete all as specified and directed. ( Make Havells Cat No ENDURAPEARLSL20WLED757SASYTOPCMP/Bajaj /Surya)
S&F in replacement flexible wire twin core copper conductor of size 23/0.0076 for ceiling fans, light fittings, etc complete all as specified and directed.
M&L MCCB 4 pole,415V, 160 amps with breaking capacity 36 KA complete all as specified and directed. [MAKE: L&T/ Siemens/ Legrand/HAVELLS as approved by GE]
S&F in replacement sheet metal enclosure for MCB DB TPN 440 volts 200 Amps rated bus bar 4 way double door openable recessed mounting all as specified and directed.
S&F in replacement sheet metal enclosures with socket plug top and MCB's with two pin and earth plug and socket complete with one single pole MCB 240 V grade 32 Amp complete all as specified and directed.
S&F PVC Casing & caping of size 20mm complete all as specified and directed.
S&F LED Aesthetically designed recessed mounted panel, ceiling light fitting complete 1 x 20 W, 240V with all accessories internally pre-wired and including connecting up with copper conductor cable with suitable size complete all as specified and directed. (Make : Havells LHEBLEP7IN1W020 or equivalant in C&G/Bajaj/Surya)
S&F 2 x 2' LED recessed mounted environmental frindly , new generation , aesthetically designed, ultra modern recess mounting luminaire with high brightness SMD LEDs as light source , 42 watts complete with all accessories internally pre-wired and including connecting up with copper conductor cable with suitable size complete all as specified and directed. (Make : Havells PLUTONE02X2PLR42WLED840S or equivalant in C&G/Bajaj/Surya)
M&L for Earthing complete with galvanized steel earth plate electrode 600 x 600 x 6 mm thick buried directly in ground (earth pit not less than 2.25 metre deep below ground level) with top edge of plate not less than 1.5 metre below normal ground level connected to galvanized earth lead wire 4 mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical Plate No 3 of MES SSR-2009 Part-I connected to main switch board or main control board all as specified and testing on completion including provision of earth wire protected by 15mm dia light grade GI pipe and watering pipe shall be 20mm bore light grade including all excavation and earth work in any type of soil, PCC pit with pre-cast RCC cover, charcoal/salt, funnel etc complete all as directed. NOTE :- (i) The concrete pit shall be PCC (1:3:6) type C-1, 40 mm thick pre cast cover slab of RCC (1:2:4) type B-1 using 20mm graded stone aggregate reinforced with 8mm TMT bars @ 10 cm C/C on both sides with suitable cast iron handle shall be provided in lieu of cast iron cover shown in electrical plate No 3 of MES SSR Part-I. (ii) The unit rate includes the cost of GI pipe medium grade for protection of earth wire and 4mm dia earh lead wire upto 7.5 M. (iii) PCC pit shall be provided at least 500 mm away from the pit and not on the earth pit itself.
Deduct schedule of credit (calculation will be done off line) Rs.53,900.00
H S ENTERPRISES
UMESH ENTERPRISES
RAJPATI CONSTRUCTION
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .