DGM(PJ-CONTRACTS)
Indian Oil Corporation Limited (Pipelines Division) A-1, Udyog Marg, Sector-1, NOIDA (UP) 201 301, INDIA
DESIGN, SUPPLY, INSTALLATION AND COMMISSIONING OF INSTRUMENTATION, PLC BASED CONTROL SYSTEM, FIRE ALARM AND DETECTION SYSTEM INCLUDING UPGRADATION OF EXISTING PLC BASED CONTROL SYSTEM AND FIRE ALARM AND DETECTION SYSTEM, SIL 3 SAFETY PLC SYSTEM FOR P
2019_PLHO_96862_1
PLCC/HBPL/TI/19043
Open Tender
Instrumentation - All
Works
240 days
in state of Odisha, WB, Bihar
Please refer Tender documents.
4 documents required · 4 mandatory
₹2.7 L
Yes
PLHO,NOIDA
20 Jan 2020
15 May 2019
18 Jul 2019
15 May 2019
17 Jul 2019
1 Jun 2019
20 May 2019
Amount
Control System Works - Odissa-Supply
Supply of CPU & NIU units as replacement to existing PLC system along with supply of additional IO racks complete with /O modules, Serial interface, Relay Modules, interconnecting cables, data cables & Marshalling Panels, rack power supply (dual redundant), interrogation power supplies (dual-redundant), system software , diagnostics, firmware and all installation materials etc. so as to make the system complete in all respects as per system configuration, I/O list / table and Tender specifications. The supplied CPU (single) system shall replace the existing CPUs & supplied NIU's shall replace the existing NIUs to upgrade the processor and communication from existing genius bus to proficy bus. The new CPU shall interface with existing IOs and new IOs supplied by the vendor. CPU, IOs, NIU and associated modules shall be of GE make and compatible with existing system
Paradip
Zener Barriers
For DI
For AI
For AO
For RTD
Surge Protection Devices
For RS 232/485 signals
For LAN application
1 Phase 2 / 3 wire (230 V)
IT HARDWARE AND NETWORKING - SUPPLY
Industrial Grade L2 Ethernet switch (having 8 Nos. of 10/100/1000 MBPS ports and optical interface) with cables & connectors etc. complete in all respects as per tender specifications (1 Set Comprises of 2 switches)
Supply & installation of industrial grade serial to ethernet converter with required connectors, cables, power supply etc. as per tender specifications. (1 Set Comprises 02 converters)
Supply & installation of industrial grade Optical to Ethernet converter with required connectors, cables, power supply etc. as per tender specifications. (1 Set Comprises 02 converters)
FIELD INSTRUMENTS complete with cable glands, fittings, accessories and other installation materials etc.,complete as per tender specifications.
Pressure Transmitters with Cable glands Range max (-1 to 5 kg/cm2); Smart type; accuracy 0.075% or better Installation: 2" Pipe Mounted
Pressure Transmitters with Cable glands Range max (0 - 20 kg/cm2); Smart type; accuracy 0.075% or better Installation: 2" Pipe Mounted
Pressure Transmitters with Cable glands Range max (0-160 kg/cm2); Smart type; accuracy 0.075% or better Installation: 2" Pipe Mounted
Pressure switches with junction box & cable glands suitable for low pressure side, set point 1 Kg/cm2 to 10 Kg/cm2. Proof Pressure: 200 Kg/cm2.
Differential Pressure Transmitter with manifold valves and Cable Glands.Range max (0 to 3 kg/cm2).Smart type; accuracy 0.1% or better
CABLES AND MISCELLANEOUS MATERIAL
Supply of CAT6 Cable (Armoured)
Supply of CAT6 Cable (Unarmoured)
Supply of Armoured Power cable (3Cx2.5 sqmm.)
Industrial Grade Networking & Optical fibre accessories including LIU, network termination boxes/ fibremanagement system, pig tails, patchcords, connectors for the complete control System as per tender specifications.
UPS (Online) as per Tender Specification
5 KVA with 1 phase input & 1 phase output UPS in (1+1) parallel redundant equal load sharing configuration excluding battery as per the tender specifications (for T&I requirement)
Sealed maintenance free 2V VRLA battery in dual string for 1 hrs backup considering aging, temperature & capacity factors complete with all interconnecting cables, glands, battery cables, battery stands, AC distribution boxes, connectors & lugs etc as per the tender specifications for 5 KVA UPS (for Electrical requirement)
Spares
Control system Spares
PLC Processor Module
PLC Processor power supply
Communication Module
Rack power supply
Digital input module
Digital output module
Analog input module
RTD Module
UPS Spares
PCB's, one of each type for 5 KVA UPS
FIRE AND GAS DETECTION SYSTEM - SUPPLY
2 loop, Addressable, Intelligent Fire Detection and Alarm Panel with FM-200 release facilities for automatic fire detection & annunciation of alarms for various types of detectors installed like multi sensor, heat detectors, response indicators, loop isolators, manual call points, hooters etc installed in plant area and various buildings.
DETECTORS
IR Based explosion proof & weather proof (Point type) Hydrocarbon detectors along with all mounting & other accessories as per tenderspecifications.
IR Based explosion proof & weather proof (Open Path type) Hydrocarbon detectors along with all mounting & other accessories as per tenderspecifications.
UV / IR Flame Detectors explosion proof & weather proof along with allmounting & other accessories as per the tender specifications.
Intrinsically safe Rate of Rise Heat Detectors for hazardous areas alongwith all mounting & other accessories as per the tender specifications
Multi sensor detectors (addressable type) along with all mounting & other accessories as per the tender specifications.
Addressable Manual Call Point (for safe area) along with all mounting & other accessories as per the tender specifications.
Manual Call Point (Explosion Proof & Weather Proof) for hazardous areas along with all mounting & other accessories as per the tender specifications.
Isolators for isolating of signalling loop in case of any fault alongwith all mounting & other accessories as per the tender specifications.
Response Indicators along with all mounting & other accessories as per the tender specifications.
Beacons for safe area along with all mounting & other accessories & instructions sign as per the tender specifications.
Hooters / Horn / Strobe (for safe area) along with all mounting & other accessories as per the tender specifications.
Explosion Proof / Weather Proof Hooters (for hazardous area) along with all mounting & other accessories as per the tender specifications.
Explosion Proof / Weather Proof Beacon (for hazardous area) along with all mounting & other accessories as per the tender specifications.
Monitor modules along with all mounting & other accessories for third party interface as per the tender specifications.
Cables & Junction Boxes
2 Pair x 1.5 Sq. mm, unarmoured FRLS cable complaint to BS: EN 50288-7 as per the tender specifications for indoor applications to be laid through PVC/Metalic conduits..
Supply of flame proof and weather proof junction boxes including supply of EP/WP double compression cable glands, plugs for unused cable entries including EP/WP certificates as per the tender specifications for UV/IR flame detectors, Hydrocarbon detectors, IS ROR etc. in hazardous areas.
Supply of weather proof junction boxes including supply of cable glands, plugs for unused cable entries including WP certificates as per the tender specifications for various detectors inside buildings.
Control System Works - Odissa-Services
CONTROL SYSTEM SERVICES
Supervison of erection of new panels and performing upgradation of CPU, NIU etc., testing & commissioning of new CPU along with additional/Remote IO panels for existing PLC based control system at PARADIP stations including supervision for termination of control/signal cables, installation and commissiong of additional/Remote IO panels , integration of same with existing PLC system and control systems along with support for interfacing with SCADA system and field instrumentation systems including supplied hardware/ software with station on remote & auto including development of control logics, database, data panel screen, networking equipments etc. making all jobs complete as per drawings / specifications and acceptance of system by Owner. Wherever the interfacing is to be done with the existing system, all services including interfacing with the existing system, changes in the existing system, upgradtion in the existing system is in scope of vendor. This include supply of all labour, consumables, tools, services rendered etc.
Modifications/Creation in the Control System HMI graphics & logic for the Control System including development/modification of new database, tags, PLC logic and all related jobs for inclusion of upcoming facilities at respective stations. Work includes Modification/Development of MMI graphics and uploading of the same in the existing workstations, engineering cum programming terminal etc. as per the scope of the work and specifications to complete the job in all respects for incorporation of upcoming facilities as per the specifications, drawings and directions of the Site Engineer and submission of "As built" documentation. The work also includes providing data to the SCADA vendor and assisting the same for incorporation of the changes in the SCADA.
Paradip
FIRE AND GAS DETECTION SYSTEM SERVICES
Modifications/Creation in the HMI graphics & logic for the exsiting Safety PLC including development/modification of new database, tags, PLC logic and all related jobs for inclusion of upcoming facilities at respective stations. Work includes Modification/Development of MMI graphics and uploading of the same in the existing workstations, engineering cum programming terminal etc. as per the scope of the work and specifications to complete the job in all respects for incorporation of upcoming facilities as per the specifications, drawings and directions of the Site Engineer and submission of "As built" documentation. The work shall also include the Supervison for termination of cables, looptesting, and commissiong of completesystems along with support for interfacing of field detectors/hooter etc. This shall include commissioning of the system complete as per drawings / specifications and acceptance of system by Owner. Supply of all labour, consumables, tools, services rendered etc. shall be in the contractors's scope.
Paradip
Erection, testing & commissioning of 2 Loop Fire Alarm & Detection System comprising of addressable Fire Alarm Panel, addressable detectors of various types such as multisensor detectors, rate of rise heat detectors, manual call points, hooters, etc including gas release system for arease such as MCC room, transformer room, VFD room, control room and other office /equipment room etc. and pumping sheds, piping area, including laying of cables (as per scope), energizing & testing of the complete system with simulation and also demonstration of working of the complete system,commissioning of the complete system including the cost of allmaterials, labour, consumables, equipments tools & tackles on lump sum basis as per the specifications & instructions of Site Engineer / EIC.
"Splicing of the owner supplied 24 fiber cable with the control system (using vendor supplied optical accessories) for interfacing of RIO panels/Remote panels/Sub-system etc. with main PLC/control system etc. along with tesing of Fiber with OTDR including the cost of all materials, labour, consumables, equipments tools & tackles as per the specifications & instructions of Site Engineer / EIC. Each Set shall comprise of splicing of 24 fibers at one end. In case 12 fiber optical cable is provided by the owner, 0.5 times of the quoted rates shall be paid. "
Control System Works - Odissa-Composite
FIRE AND GAS DETECTION SYSTEM
"FM 200 based clean agent Fire suppression system Supply, installation, testing & commissioning of FM 200 gas based clean agent Fire Suppression System complete as per NFPA 2001 ( latest edition) with Gas release panel, cylinders, piping, nozzles, cylinder racks, collecting manifold with pressure hoses & interconnecting hoses, non-return valves, manual release switch, manual override switch, warning signs, accessories for support and installation of clean agent piping, electrical & pneumatic actuators, pressure switches, etc for release of clean agent gas in the area such as equipment room, VFD room and cable ducts, cable trenches using multi sensor detectors, rate of rise heat detectors and clean agent flooding system on receiving of alarm in area etc along with erection of clean agent cylinders in racks, manifolds with pressure hoses and interconnecting hoses, erection of clean agent piping with discharge nozzles in cable trenches & ducts and all accessories like weighing devices, actuating valves, pressure switches, release switch, abort switch, warning lables etc including accessories for support, junction boxes etc. as per the approved scheme, hooking of the clean agent system with fire alarm system for actuation on detection of smoke/fire,automatic actuation and total flooding of clean agent in the area covered such as cable ducts, cable trenches to complete the work in all respects inclusive of supply of all consumables , cost of all materials, labour, painting services, carriages etc. as per specifications, drawings, International Standard practices and the directions of Site Engineer/EIC."
FM 200 based clean agent cylinders (80 l capacity) in configuration of set of banks (1 set = 1-main & 1 -standby cyliner) complete with safety valve and all accessories.
FM 200 based clean agent cylinders (40/50 L capacity) in configuration of set of banks (1 set = 1-main & 1 -standby cyliner) complete with safety valve and all accessories.
FM 200 based clean agent filled in cylinders
All sizes of piping for clean agent dispersion complete with nozzles, manifold , all type of hoses, etc to complete the work in all respect
Supply , installation & interfacing of Gas release panel with Fire alarm panel to achieve the functionality of clean agent dispersion
Installation of explosion proof / weather proof junction boxes for marshalling of control / signalling cables, terminating the cables at field and control panel end, mounting the junction boxes, connecting to earthing grid by supplying and installing all the required materials such as supporting structure, cement concrete, painting, GI wire etc.(excluding supply of the Junction Boxes) complete in all respects as per specifications, approved drawings and direction of EIC / Site Engineerincluding all labour, tools, materials, glanding, ferruling etc.complete in all respects.
Installation, testing & commissioning of various types of detectors for integration of detectors with Fire Alarm panel including supply & installation of all mounting accessories for support, junction boxes, termination of cables etc. as per the approved scheme to complete the work in all respects inclusive of supply of all consumables ,cost of all materials, labour, painting services, carriages etc. as per specifications, drawings, International Standard practices and the directions of Site Engineer/EIC. Job includesinstallation of all types of detectors, material etc.
Multi Sensor Detectors & isolators
Response Indicators & monitor modules
Manual Call Point (for safe area)
Beacons / Hooters / Horn / Strobe (for safe area)
Explosion Proof / Weather Proof Hooters (for hazardous area)
Explosion Proof / Weather Proof Beacons (for hazardous area)
Supply & installation of 25 mm ISI marked (as per IS-9537 part 2) metallic conduit along with all fittings & fixtures like Tees, bends, junction boxes, etc for installation detectors in building as per specifications. Clamping / fixing of GI pipe on wall/roof/trenches/ducts etc. in various building for laying of cable.
Laying of unarmoured/armoured signal cable through GI pipe / tray etc for interfacing of various type of detectors e.g. multi sensor, ROR, response indicator, hooters, beacons etc
Control System Works -West Bengal-Supply
IT HARDWARE AND NETWORKING - SUPPLY
Supply & installation of industrial grade Optical to Ethernet converter with required connectors, cables, power supply etc. as per tender specifications. (1 Set Comprises 02 converters)
FIELD INSTRUMENTS complete with cable glands, fittings, accessories and other installation materials etc.,complete as per tender specifications.
Pressure Transmitters with Cable glands Range max (0 - 20 kg/cm2); Smart type; accuracy 0.075% or better Installation: 2" Pipe Mounted
Pressure Transmitters with Cable glands Range max (0-160 kg/cm2); Smart type; accuracy 0.075% or better Installation: 2" Pipe Mounted
Temperature Transmitter with duplex RTD, Thermowell & Cable glands, Range max (0 to 100 deg C ) Smart type; accuracy 0.1% or better Installation: Transmitter 2" pipe mounted; RTD in thermowell on process pipe above ground installation.
Temperature Transmitter with surface mounted duplex RTD, Weld pad and dual sensors & Cable glands, Range max (0 to 100 oC); Smart type; accuracy 0.1% or better Installation: Transmitter 2" pipe mounted ; RTD in weldpad welded to process pipe surface for below ground installation.
Pressure switches with junction box & cable glands suitable for low pressure side, set point 1 Kg/cm2 to 10 Kg/cm2. Proof Pressure: 200 Kg/cm2.
Pressure switches with junction box & cable glands suitable for High pressure side, set point 65 Kg/cm2 to 160 Kg/cm2. Proof Pressure: 200 Kg/cm2.
Differential Pressure Transmitter with manifold valves and Cable Glands.Range max (0 to 3 kg/cm2).Smart type; accuracy 0.1% or better
Density Cum Viscosity Meter along with all the accessories like weldolet, pitot scoop, isolation & drain valve, tees blind etc. as per tender specifications & installation drawing.
Flow Switch, Thermal dispersion sensor type, Body material: Cast Aluminium, Sensing element: Stainless Steel, process connection: 1" threaded suitable for 16IN 150# Line complete with flameproof cable gland and stopper plug.
Flow Computer complete with software for meter proving and tables as per API for petroleum products, turbine / mass flow meter / UFM inputs, Density meter inputs etc as per the tender specifications & data sheet.
CABLES AND MISCELLANEOUS MATERIAL
Supply of CAT6 Cable (Armoured)
Supply of CAT6 Cable (Unarmoured)
Supply of Armoured Power cable (3Cx2.5 sqmm.)
Industrial Grade Networking & Optical fibre accessories including LIU, network termination boxes/ fibremanagement system, pig tails, patchcords, connectors for the complete control System as per tender specifications.
UPS (Online) as per Tender Specification
10 KVA with 3 phase input & 1 phase output UPS in (1+1) parallel redundant equal load sharing configuration excluding battery as per the tender specifications (for Electrical requirement)
Sealed maintenance free 2V VRLA battery in dual string for 1 hrs backup considering aging, temperature & capacity factors complete with all interconnecting cables, glands, battery cables, battery stands, AC distribution boxes, connectors & lugs etc as per the tender specifications for 10 KVA UPS (for Electrical requirement)
Spares
UPS Spares
PCB's, one of each type for 10 KVA UPS
FIRE AND GAS DETECTION SYSTEM - SUPPLY
DETECTORS
IR Based explosion proof & weather proof (Point type) Hydrocarbon detectors along with all mounting & other accessories as per tenderspecifications.
Multi sensor detectors (addressable type) along with all mounting & other accessories as per the tender specifications.
Addressable Manual Call Point (for safe area) along with all mounting & other accessories as per the tender specifications.
Manual Call Point (Explosion Proof & Weather Proof) for hazardous areas along with all mounting & other accessories as per the tender specifications.
Isolators for isolating of signalling loop in case of any fault alongwith all mounting & other accessories as per the tender specifications.
Response Indicators along with all mounting & other accessories as per the tender specifications.
Beacons for safe area along with all mounting & other accessories & instructions sign as per the tender specifications.
Hooters / Horn / Strobe (for safe area) along with all mounting & other accessories as per the tender specifications.
Explosion Proof / Weather Proof Hooters (for hazardous area) along with all mounting & other accessories as per the tender specifications.
Explosion Proof / Weather Proof Beacon (for hazardous area) along with all mounting & other accessories as per the tender specifications.
Monitor modules along with all mounting & other accessories for third party interface as per the tender specifications.
Cables & Junction Boxes
2 Pair x 1.5 Sq. mm, unarmoured FRLS cable complaint to BS: EN 50288-7 as per the tender specifications for indoor applications to be laid through PVC/Metalic conduits..
Supply of flame proof and weather proof junction boxes including supply of EP/WP double compression cable glands, plugs for unused cable entries including EP/WP certificates as per the tender specifications for UV/IR flame detectors, Hydrocarbon detectors, IS ROR etc. in hazardous areas.
Supply of weather proof junction boxes including supply of cable glands, plugs for unused cable entries including WP certificates as per the tender specifications for various detectors inside buildings.
Control System Works West Bengal-Service
CONTROL SYSTEM SERVICES
Modifications/Creation in the Control System HMI graphics & logic for the Control System including development/modification of new database, tags, PLC logic and all related jobs for inclusion of upcoming facilities at respective stations. Work includes Modification/Development of MMI graphics and uploading of the same in the existing workstations, engineering cum programming terminal etc. as per the scope of the work and specifications to complete the job in all respects for incorporation of upcoming facilities as per the specifications, drawings and directions of the Site Engineer and submission of "As built" documentation. The work also includes providing data to the SCADA vendor and assisting the same for incorporation of the changes in the SCADA.
Haldia
Bolpur
Supervison for termination of control cables/signal cables, looptesting, and commissiong of complete control systems along with support for interfacing of field instrumentation systems for operation of station facilities in remote & auto mode. This shall include commissioning of the system complete as per drawings / specifications and acceptance of system by Owner. Supply of all labour, consumables, tools, services rendered etc. shall be in the contractors's scope.
Haldia
Bolpur
FIRE AND GAS DETECTION SYSTEM SERVICES
Modifications/Creation in the HMI graphics & logic for the exsiting Safety PLC including development/modification of new database, tags, PLC logic and all related jobs for inclusion of upcoming facilities at respective stations. Work includes Modification/Development of MMI graphics and uploading of the same in the existing workstations, engineering cum programming terminal etc. as per the scope of the work and specifications to complete the job in all respects for incorporation of upcoming facilities as per the specifications, drawings and directions of the Site Engineer and submission of "As built" documentation. The work shall also include the Supervison for termination of cables, looptesting, and commissiong of completesystems along with support for interfacing of field detectors/hooter etc. This shall include commissioning of the system complete as per drawings / specifications and acceptance of system by Owner. Supply of all labour, consumables, tools, services rendered etc. shall be in the contractors's scope.
Haldia
Bolpur
Integration of existing fire alram panel with new addressable detectors of various types such as multisensor detectors, rate of rise heat detectors, manual call points, hooters, etc including gas release system for areas such as MCC room, transformer room, VFD room, control room and other office /equipment room etc. and pumping sheds, piping area, including laying of cables (as per scope), energizing & testing of the complete system with simulation and also demonstration of working of the complete system,commissioning of the complete system including the cost of allmaterials, labour, consumables, equipments tools & tackles on lump sum basis as per the specifications & instructions of Site Engineer / EIC.
"Splicing of the owner supplied 24 fiber cable with the control system (using vendor supplied optical accessories) for interfacing of RIO panels/Remote panels/Sub-system etc. with main PLC/control system etc. along with tesing of Fiber with OTDR including the cost of all materials, labour, consumables, equipments tools & tackles as per the specifications & instructions of Site Engineer / EIC. Each Set shall comprise of splicing of 24 fibers at one end. In case 12 fiber optical cable is provided by the owner, 0.5 times of the quoted rates shall be paid. "
Control System Works West Bengal-Composi
"Supply, Installation and termination of IO cards/modules (AI / DI / DO / AO / RTD / PULSE / Serial Interafce / Other Cards) inside the existing Panels of GE make PLC. Installation of suppied IO card shall include its wiring from the I/O card/base plate to the terminal block including supply of base plate, relay panel, fuses, terminal blocks, etc with all the installation material required for wiring of the field instrumentation. Installation work also include the configuraiton of the new IO cards in the system, modification of logic and HMI graphic screens to complete the job in all respect. Bidder to note same rates shall also be used as rate refference in case requirement of wiring/termination additional I/O cards arrises at later stage at any of the locations. IO and associated modules shall be of same make and model (or compatible model) as that of existing IO and associated modbules. Exact requirement shall be worked out during detailed engineering. "
Rack power supply
Digital input module
Digital output module
Analog input module
FIRE AND GAS DETECTION SYSTEM
"FM 200 based clean agent Fire suppression system Supply, installation, testing & commissioning of FM 200 gas based clean agent Fire Suppression System complete as per NFPA 2001 ( latest edition) with Gas release panel, cylinders, piping, nozzles, cylinder racks, collecting manifold with pressure hoses & interconnecting hoses, non-return valves, manual release switch, manual override switch, warning signs, accessories for support and installation of clean agent piping, electrical & pneumatic actuators, pressure switches, etc for release of clean agent gas in the area such as equipment room, VFD room and cable ducts, cable trenches using multi sensor detectors, rate of rise heat detectors and clean agent flooding system on receiving of alarm in area etc along with erection of clean agent cylinders in racks, manifolds with pressure hoses and interconnecting hoses, erection of clean agent piping with discharge nozzles in cable trenches & ducts and all accessories like weighing devices, actuating valves, pressure switches, release switch, abort switch, warning lables etc including accessories for support, junction boxes etc. as per the approved scheme, hooking of the clean agent system with fire alarm system for actuation on detection of smoke/fire,automatic actuation and total flooding of clean agent in the area covered such as cable ducts, cable trenches to complete the work in all respects inclusive of supply of all consumables , cost of all materials, labour, painting services, carriages etc. as per specifications, drawings, International Standard practices and the directions of Site Engineer/EIC."
FM 200 based clean agent cylinders (80 l capacity) in configuration of set of banks (1 set = 1-main & 1 -standby cyliner) complete with safety valve and all accessories.
FM 200 based clean agent cylinders (40/50 L capacity) in configuration of set of banks (1 set = 1-main & 1 -standby cyliner) complete with safety valve and all accessories.
FM 200 based clean agent cylinders (40/50 L capacity) in configuration of set of banks (1 set = 1-main & 1 -standby cyliner) complete with safety valve and all accessories. FM 200 based clean agent filled in cylinders
All sizes of piping for clean agent dispersion complete with nozzles, manifold , all type of hoses, etc to complete the work in all respect
Supply , installation & interfacing of Gas release panel with Fire alarm panel to achieve the functionality of clean agent dispersion
Installation of explosion proof / weather proof junction boxes for marshalling of control / signalling cables, terminating the cables at field and control panel end, mounting the junction boxes, connecting to earthing grid by supplying and installing all the required materials such as supporting structure, cement concrete, painting, GI wire etc.(excluding supply of the Junction Boxes) complete in all respects as per specifications, approved drawings and direction of EIC / Site Engineerincluding all labour, tools, materials, glanding, ferruling etc.complete in all respects.
Installation, testing & commissioning of various types of detectors for integration of detectors with Fire Alarm panel including supply & installation of all mounting accessories for support, junction boxes, termination of cables etc. as per the approved scheme to complete the work in all respects inclusive of supply of all consumables ,cost of all materials, labour, painting services, carriages etc. as per specifications, drawings, International Standard practices and the directions of Site Engineer/EIC. Job includesinstallation of all types of detectors, material etc.
Multi Sensor Detectors & isolators
Response Indicators & monitor modules
Manual Call Point (for safe area)
Beacons / Hooters / Horn / Strobe (for safe area)
Explosion Proof / Weather Proof Hooters (for hazardous area)
Explosion Proof / Weather Proof Beacons (for hazardous area)
Supply & installation of 25 mm ISI marked (as per IS-9537 part 2) metallic conduit along with all fittings & fixtures like Tees, bends, junction boxes, etc for installation detectors in building as per specifications. Clamping / fixing of GI pipe on wall/roof/trenches/ducts etc. in various building for laying of cable.
Laying of unarmoured/armoured signal cable through GI pipe / tray etc for interfacing of various type of detectors e.g. multi sensor, ROR, response indicator, hooters, beacons etc
Control System Works - Bihar-Supply
Surge Protection Devices
For LAN application
1 Phase 2 / 3 wire (230 V)
IT HARDWARE AND NETWORKING - SUPPLY
Industrial Grade L2 Ethernet switch (having 8 Nos. of 10/100/1000 MBPS ports and optical interface) with cables & connectors etc. complete in all respects as per tender specifications (1 Set Comprises of 2 switches)
Supply & installation of industrial grade Optical to Ethernet converter with required connectors, cables, power supply etc. as per tender specifications. (1 Set Comprises 02 converters)
FIELD INSTRUMENTS complete with cable glands, fittings, accessories and other installation materials etc.,complete as per tender specifications.
Pressure Transmitters with Cable glands Range max (0 - 20 kg/cm2); Smart type; accuracy 0.075% or better Installation: 2" Pipe Mounted
Pressure Transmitters with Cable glands Range max (0-160 kg/cm2); Smart type; accuracy 0.075% or better Installation: 2" Pipe Mounted
Temperature Transmitter with duplex RTD, Thermowell & Cable glands, Range max (0 to 100 deg C ) Smart type; accuracy 0.1% or better Installation: Transmitter 2" pipe mounted; RTD in thermowell on process pipe above ground installation.
Temperature Transmitter with surface mounted duplex RTD, Weld pad and dual sensors & Cable glands, Range max (0 to 100 oC); Smart type; accuracy 0.1% or better Installation: Transmitter 2" pipe mounted ; RTD in weldpad welded to process pipe surface for below ground installation.
Pressure switches with junction box & cable glands suitable for low pressure side, set point 1 Kg/cm2 to 10 Kg/cm2. Proof Pressure: 200 Kg/cm2.
Differential Pressure Transmitter with manifold valves and Cable Glands.Range max (0 to 3 kg/cm2).Smart type; accuracy 0.1% or better
Density Cum Viscosity Meter along with all the accessories like weldolet, pitot scoop, isolation & drain valve, tees blind etc. as per tender specifications & installation drawing.
Flow Switch, Thermal dispersion sensor type, Body material: Cast Aluminium, Sensing element: Stainless Steel, process connection: 1" threaded suitable for 3 IN/ 4 IN 150# Line complete with flameproof cable gland and stopper plug.
Flow Switch, Thermal dispersion sensor type, Body material: Cast Aluminium, Sensing element: Stainless Steel, process connection: 1" threaded suitable for 16IN 150# Line complete with flameproof cable gland and stopper plug.
CABLES AND MISCELLANEOUS MATERIAL
Supply of CAT6 Cable (Armoured)
Supply of CAT6 Cable (Unarmoured)
Supply of Armoured Power cable (3Cx2.5 sqmm.)
Industrial Grade Networking & Optical fibre accessories including LIU, network termination boxes/ fibremanagement system, pig tails, patchcords, connectors for the complete control System as per tender specifications.
FIRE AND GAS DETECTION SYSTEM - SUPPLY
DETECTORS
IR Based explosion proof & weather proof (Point type) Hydrocarbon detectors along with all mounting & other accessories as per tenderspecifications.
Multi sensor detectors (addressable type) along with all mounting & other accessories as per the tender specifications.
Addressable Manual Call Point (for safe area) along with all mounting & other accessories as per the tender specifications.
Manual Call Point (Explosion Proof & Weather Proof) for hazardous areas along with all mounting & other accessories as per the tender specifications.
Isolators for isolating of signalling loop in case of any fault alongwith all mounting & other accessories as per the tender specifications.
Response Indicators along with all mounting & other accessories as per the tender specifications.
Beacons for safe area along with all mounting & other accessories & instructions sign as per the tender specifications.
Hooters / Horn / Strobe (for safe area) along with all mounting & other accessories as per the tender specifications.
Explosion Proof / Weather Proof Hooters (for hazardous area) along with all mounting & other accessories as per the tender specifications.
Explosion Proof / Weather Proof Beacon (for hazardous area) along with all mounting & other accessories as per the tender specifications.
Monitor modules along with all mounting & other accessories for third party interface as per the tender specifications.
Cables & Junction Boxes
2 Pair x 1.5 Sq. mm, unarmoured FRLS cable complaint to BS: EN 50288-7 as per the tender specifications for indoor applications to be laid through PVC/Metalic conduits..
Supply of flame proof and weather proof junction boxes including supply of EP/WP double compression cable glands, plugs for unused cable entries including EP/WP certificates as per the tender specifications for UV/IR flame detectors, Hydrocarbon detectors, IS ROR etc. in hazardous areas.
Supply of weather proof junction boxes including supply of cable glands, plugs for unused cable entries including WP certificates as per the tender specifications for various detectors inside buildings.
Control System Works - Bihar-Services
CONTROL SYSTEM SERVICES
Modifications/Creation in the Control System HMI graphics & logic for the Control System including development/modification of new database, tags, PLC logic and all related jobs for inclusion of upcoming facilities at respective stations. Work includes Modification/Development of MMI graphics and uploading of the same in the existing workstations, engineering cum programming terminal etc. as per the scope of the work and specifications to complete the job in all respects for incorporation of upcoming facilities as per the specifications, drawings and directions of the Site Engineer and submission of "As built" documentation. The work also includes providing data to the SCADA vendor and assisting the same for incorporation of the changes in the SCADA.
Barauni
Supervison for termination of control cables/signal cables, looptesting, and commissiong of complete control systems along with support for interfacing of field instrumentation systems for operation of station facilities in remote & auto mode. This shall include commissioning of the system complete as per drawings / specifications and acceptance of system by Owner. Supply of all labour, consumables, tools, services rendered etc. shall be in the contractors's scope.
Barauni
FIRE AND GAS DETECTION SYSTEM SERVICES
Modifications/Creation in the HMI graphics & logic for the exsiting Safety PLC including development/modification of new database, tags, PLC logic and all related jobs for inclusion of upcoming facilities at respective stations. Work includes Modification/Development of MMI graphics and uploading of the same in the existing workstations, engineering cum programming terminal etc. as per the scope of the work and specifications to complete the job in all respects for incorporation of upcoming facilities as per the specifications, drawings and directions of the Site Engineer and submission of "As built" documentation. The work shall also include the Supervison for termination of cables, looptesting, and commissiong of completesystems along with support for interfacing of field detectors/hooter etc. This shall include commissioning of the system complete as per drawings / specifications and acceptance of system by Owner. Supply of all labour, consumables, tools, services rendered etc. shall be in the contractors's scope.
Barauni
Integration of existing fire alram panel with new addressable detectors of various types such as multisensor detectors, rate of rise heat detectors, manual call points, hooters, etc including gas release system for areas such as MCC room, transformer room, VFD room, control room and other office /equipment room etc. and pumping sheds, piping area, including laying of cables (as per scope), energizing & testing of the complete system with simulation and also demonstration of working of the complete system,commissioning of the complete system including the cost of allmaterials, labour, consumables, equipments tools & tackles on lump sum basis as per the specifications & instructions of Site Engineer / EIC.
"Splicing of the owner supplied 24 fiber cable with the control system (using vendor supplied optical accessories) for interfacing of RIO panels/Remote panels/Sub-system etc. with main PLC/control system etc. along with tesing of Fiber with OTDR including the cost of all materials, labour, consumables, equipments tools & tackles as per the specifications & instructions of Site Engineer / EIC. Each Set shall comprise of splicing of 24 fibers at one end. In case 12 fiber optical cable is provided by the owner, 0.5 times of the quoted rates shall be paid. "
Control System Works - Bihar-Composite
"Supply, Installation and termination of IO cards/modules (AI / DI / DO / AO / RTD / PULSE / Serial Interafce / Other Cards) inside the existing Panels of GE make PLC. Installation of suppied IO card shall include its wiring from the I/O card/base plate to the terminal block including supply of base plate, relay panel, fuses, terminal blocks, etc with all the installation material required for wiring of the field instrumentation. Installation work also include the configuraiton of the new IO cards in the system, modification of logic and HMI graphic screens to complete the job in all respect. Bidder to note same rates shall also be used as rate refference in case requirement of wiring/termination additional I/O cards arrises at later stage at any of the locations. IO and associated modules shall be of same make and model (or compatible model) as that of existing IO and associated modbules. Exact requirement shall be worked out during detailed engineering. "
Rack power supply
Digital input module
Digital output module
Analog input module
FIRE AND GAS DETECTION SYSTEM
"FM 200 based clean agent Fire suppression system Supply, installation, testing & commissioning of FM 200 gas based clean agent Fire Suppression System complete as per NFPA 2001 ( latest edition) with Gas release panel, cylinders, piping, nozzles, cylinder racks, collecting manifold with pressure hoses & interconnecting hoses, non-return valves, manual release switch, manual override switch, warning signs, accessories for support and installation of clean agent piping, electrical & pneumatic actuators, pressure switches, etc for release of clean agent gas in the area such as equipment room, VFD room and cable ducts, cable trenches using multi sensor detectors, rate of rise heat detectors and clean agent flooding system on receiving of alarm in area etc along with erection of clean agent cylinders in racks, manifolds with pressure hoses and interconnecting hoses, erection of clean agent piping with discharge nozzles in cable trenches & ducts and all accessories like weighing devices, actuating valves, pressure switches, release switch, abort switch, warning lables etc including accessories for support, junction boxes etc. as per the approved scheme, hooking of the clean agent system with fire alarm system for actuation on detection of smoke/fire,automatic actuation and total flooding of clean agent in the area covered such as cable ducts, cable trenches to complete the work in all respects inclusive of supply of all consumables , cost of all materials, labour, painting services, carriages etc. as per specifications, drawings, International Standard practices and the directions of Site Engineer/EIC."
FM 200 based clean agent cylinders (80 l capacity) in configuration of set of banks (1 set = 1-main & 1 -standby cyliner) complete with safety valve and all accessories.
FM 200 based clean agent cylinders (40/50 L capacity) in configuration of set of banks (1 set = 1-main & 1 -standby cyliner) complete with safety valve and all accessories.
FM 200 based clean agent filled in cylinders
All sizes of piping for clean agent dispersion complete with nozzles, manifold , all type of hoses, etc to complete the work in all respect
Supply , installation & interfacing of Gas release panel with Fire alarm panel to achieve the functionality of clean agent dispersion
Installation of explosion proof / weather proof junction boxes for marshalling of control / signalling cables, terminating the cables at field and control panel end, mounting the junction boxes, connecting to earthing grid by supplying and installing all the required materials such as supporting structure, cement concrete, painting, GI wire etc.(excluding supply of the Junction Boxes) complete in all respects as per specifications, approved drawings and direction of EIC / Site Engineerincluding all labour, tools, materials, glanding, ferruling etc.complete in all respects.
Installation, testing & commissioning of various types of detectors for integration of detectors with Fire Alarm panel including supply & installation of all mounting accessories for support, junction boxes, termination of cables etc. as per the approved scheme to complete the work in all respects inclusive of supply of all consumables ,cost of all materials, labour, painting services, carriages etc. as per specifications, drawings, International Standard practices and the directions of Site Engineer/EIC. Job includesinstallation of all types of detectors, material etc.
Multi Sensor Detectors & isolators
Response Indicators & monitor modules
Manual Call Point (for safe area)
Beacons / Hooters / Horn / Strobe (for s
Explosion Proof / Weather Proof Hooters (for hazardous area)
Explosion Proof / Weather Proof Beacons (for hazardous area)
Supply & installation of 25 mm ISI marked (as per IS-9537 part 2) metallic conduit along with all fittings & fixtures like Tees, bends, junction boxes, etc for installation detectors in building as per specifications. Clamping / fixing of GI pipe on wall/roof/trenches/ducts etc. in various building for laying of cable.
Supply & installation of 25 mm ISI marked (as per IS-9537 part 2) metallic conduit along with all fittings & fixtures like Tees, bends, junction boxes, etc for installation detectors in building as per specifications. Clamping / fixing of GI pipe on wall/roof/trenches/ducts etc. in various building for laying of cable. Laying of unarmoured/armoured signal cable through GI pipe / tray etc for interfacing of various type of detectors e.g. multi sensor, ROR, response indicator, hooters, beacons etc
Yokogawa India Limited
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .