Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.8 LAccepted-AOC | L1 | Accepted-AOC AOC | |
| 2 | L2₹9.0 L+₹11,939.25 (1.35%)Rejected-Finance | L2 | Rejected-Finance being other then L1. | |
| 3 | L3₹10.4 L+₹1.6 L (17.7%)Rejected-Finance | L3 | Rejected-Finance being other then L1. |
| Sl No | Description | Qty | Unit | FIRST SOLAR L3 | M/S INDIA ENTERPRISES L2 | AYANSH ASSOCIATES L1 |
|---|---|---|---|---|---|---|
| 1.00 | Disconnecting HT & LT side cables of following indoor/ outdoor transformer and earth strip from body and neutral of transformer mounted on plinth base/two pole/four pole structure/staging and taking down the transformer manually/using mechanical, for overhauling and general maintenance of transformer with removing of top cover and draining out existing transformer oil, lifting of core, cleaning of oil tank, using chemicals, cleaning of core of capacity of transformer for 160 KVA complete all as specified and as directed. | 1 | Each Job | 12,000 ₹12,000 | 8,900 ₹8,900 Lowest | 9,000 ₹9,000 |
| 2.00 | Ditto- all as per above items No 1.00 but 315 KVA. | 2 | Each Job | 1,700 ₹3,400 Lowest | 13,900 ₹27,800 | 16,000 ₹32,000 |
| 3.00 | Ditto- all as per above items No 1.00 but 1.6 MVA. | 1 | Each Job | 25,000 ₹25,000 Lowest | 27,200 ₹27,200 | 28,000 ₹28,000 |
| 4.00 | M&L for replacement of insulation material such as gasket(cork sheet for top cover), LT terminal box, LV & HV bushing washer, paper insulation for coil for 160 to 315 KVA transformer complete all as specified and as directed. | 3 | Each Job | 2,200 ₹6,600 | 1,750 ₹5,250 Lowest | 1,850 ₹5,550 |
| 5.00 | Ditto- all as per above items No 4.00 but 1.6 MVA. | 1 | Each Job | 3,300 ₹3,300 | 2,930 ₹2,930 Lowest | 3,000 ₹3,000 |
| 6.00 | M&L for reconnecting the following transformer after complete overhauling including installation & testing the transformer as per relevant IS provisions for 160 KVA complete all as specified and directed. | 1 | Each Job | 6,800 ₹6,800 | 4,000 ₹4,000 Lowest | 5,000 ₹5,000 |
| 7.00 | Ditto- all as per above items No 6.00 but 315 KVA. | 2 | Each Job | 11,300 ₹22,600 | 8,000 ₹16,000 Lowest | 9,500 ₹19,000 |
| 8.00 | Ditto- all as per above items No 6.00 but 1.6 MVA. | 1 | Each Job | 17,600 ₹17,600 | 15,230 ₹15,230 | 15,000 ₹15,000 Lowest |
| 9.00 | M & L for 315 to 1600 KVA transformer loading and tranportation from MES store yard/sub station/ site to workshop for repairs of any type and coil rewinding of HT/LT coil any type/material, dehydration of transformer oil re-connecting after repair etc re-assembling with core varnishing heating and bringing back the same and installed after repairs to the same point complete all as specified and directed by Engr-in-Charge. | 1 | Each Job | 1,15,000 ₹1,15,000 | 98,000 ₹98,000 Lowest | 1,07,000 ₹1,07,000 |
| 10.00 | Supply and filling/ Topup of fresh transformer oil confirming to IS 335 having di electric strength not less than 50 KV of one minute in existing transformers installed at different locations complete all as specified and directed by Engineer-in-Charge.
Make : Sheetal N-68/Power oil/Castrol with test certificate. | 548 | Ltr | 220 ₹1,20,560 | 185 ₹1,01,380 | 130 ₹71,240 Lowest |
Tender Value
₹9.5 L
EMD Value
₹19,500
Closing Date
19 Jul 2025, 6:00 pmClosed
AGE (I) Naya Raipur
AGE (I) Naya Raipur, Military Engineer Services, C/O HQ COSA, Near International Cricket Stadium, Atal Nagar, Raipur (CG) - 492101
As per BOQ
2025_MES_716100_1
8400/425/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
AGE (I) Naya Raipur
As per NIT
7 documents required · 7 mandatory
₹500
AGE (I) Naya Raipur
₹19,500
27 Sept 2025
21 Jun 2025
21 Jul 2025
21 Jun 2025
19 Jul 2025
5 Jul 2025
Amount
Disconnecting HT & LT side cables of following indoor/ outdoor transformer and earth strip from body and neutral of transformer mounted on plinth base/two pole/four pole structure/staging and taking down the transformer manually/using mechanical, for overhauling and general maintenance of transformer with removing of top cover and draining out existing transformer oil, lifting of core, cleaning of oil tank, using chemicals, cleaning of core of capacity of transformer for 160 KVA complete all as specified and as directed.
Ditto- all as per above items No 1.00 but 315 KVA.
Ditto- all as per above items No 1.00 but 1.6 MVA.
M&L for replacement of insulation material such as gasket(cork sheet for top cover), LT terminal box, LV & HV bushing washer, paper insulation for coil for 160 to 315 KVA transformer complete all as specified and as directed.
Ditto- all as per above items No 4.00 but 1.6 MVA.
M&L for reconnecting the following transformer after complete overhauling including installation & testing the transformer as per relevant IS provisions for 160 KVA complete all as specified and directed.
Ditto- all as per above items No 6.00 but 315 KVA.
Ditto- all as per above items No 6.00 but 1.6 MVA.
M & L for 315 to 1600 KVA transformer loading and tranportation from MES store yard/sub station/ site to workshop for repairs of any type and coil rewinding of HT/LT coil any type/material, dehydration of transformer oil re-connecting after repair etc re-assembling with core varnishing heating and bringing back the same and installed after repairs to the same point complete all as specified and directed by Engr-in-Charge.
Supply and filling/ Topup of fresh transformer oil confirming to IS 335 having di electric strength not less than 50 KV of one minute in existing transformers installed at different locations complete all as specified and directed by Engineer-in-Charge. Make : Sheetal N-68/Power oil/Castrol with test certificate.
S & F in replacement of transformer bushing of HT side (set of 03) with porcelain, brass rod, bolts, washers and packing sheet suitable for 315 to 1600 KVA transformer complete all as specified and directed by Engineer-in-Charge.
Supply & fixing in replacement of transformer bushing of LT side (Set of 04) with porcelain, brass rod bolts washers and packing sheet suitable for 160 to 315 KVA transformer complete all as specified and directed by Engineer-in-Charge.
Dehydration and filtration of existing transformer oil using centrifugal plant to eliminate foreign particles and to improve di-electric strength not less than 40 KV in 25mm electrode gap and to bring the acidity within the permissible limit complete all as specified and directed by Engineer - in - Charge.
M & L for preparation of existing painted external surface of transformer of 315 KVA and applying two coats of synthetic enamel paint complete all as specified and directed by Engineer-in-Charge.
Taking out existing silica gel and providing new silica gel complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in replacement of Air breather asembly with silica gel for transformer ranging from 100 KVA to 1600KVA complete all as specified and directed by Engineer-in-Charge.
Supply and fixing in replacement of transformer temperature gauge heavy duty 0-150 degre centigrade of size 96mm dial type for 100 KVA to 1600 KVA transformer having brass sensor complete all as specified and directed by Engineer-in-Charge. Make : Scientific/H Guru/Tapan.
Supplying, jointing and testing cold shrinkable type, end termination cable jointing kit, outdoor type, suitable for 33/11KV under ground earthed system 3 core XLPE cable of size 120 to 300 Sqmm including making connections complete all as specified and directed by Engr-in-Charge. Make : Raychem / M Seal / 3M.
Supplying, jointing and testing cold shrinkable type, end termination cable jointing kit, outdoor type, suitable for 33/11KV under ground earthed system 3 core XLPE cable of size 50 ot 95 Sqmm including making connections complete all as specified and directed by Engr-in-Charge. Make : Raychem / M Seal / 3M.
M&L for earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6.0mm thick burried directly in ground vertically to a depth not less than 2.25 metre below ground level with top edge of earth plate at a depth not less than 1.5 metre below ground level, earth plate surrounded by 15cm thick packed layer of charcoal dust and common salt, connected to galvanized iron strip 32mm x 6mm thick as earth lead by means of bolts, nuts and washers of galvanised iron or steel and thimbles and other end of the earth strip connected to earthing test point/equipment and protected by galvanised iron pipe light grade 40mm dia upto earthing test point/equipment fixed with required number of mild steel clamp made out of 32mm x 6mm flat iron and perforated water pipe 20mm dia GI medium grade of length 2.25 metre and top with socket & plug and bottom connected to earth plate by slit and two bolts/nuts/washers, PCC chamber in cement concrete (1:2:4) type B-1 and 40mmthick pre-cast RCC (1:2:4) type B-0 cover with 40mm x 40mm x 6mm MS angle iron frame, excavation & earth work complete all as shown in electrical plate No. 3 of MES Schedule Part-I of SSR-2009. complete all as specified and directed by Engr-in-charge. Notes :- (i) GI strip upto earth test point/equipment is included in this item. (ii) Outer edge of earth pit chamber shall be 1.5 metre away from the outer edge of PCC chamber. (iii) Minimum weight of reinforcement shall be 1 kg for each earth pit cover.
Supply, laying, jointing testing and commissioning in replacement of XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with multistranded aluminum conductors, 11 KV grade of cross-sectional area 240 Sqmm, 3 core, IS 7098 marked, suitable for HT 11 KV(E) system , laid in trenches / ducts / encased in GI pipe / fixed to pole complete all as specified and directed by Engineer-in-Charge.
Supply, laying, jointing testing and commissioning in replacement of XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with multistranded aluminum conductors, 11 KV grade of cross-sectional area 95 Sqmm, 3 core, IS 7098 marked, suitable for HT 11 KV(E) system , laid in trenches / ducts / encased in GI pipe / fixed to pole complete all as specified and directed by Engineer-in-Charge.
Excavation in trenches, not exc 1.5 m wide and n. exc 1.5 m depth; or n exc 10 Sqm on plan and n exc 1.5 m in depth for foundations of poles, struts, stays etc. or laying underground cable etc. in soft/loose soil, & getting out complete all as specified and directed by Engineer-in-Charge.
Returning, filling in, including spreading, levelling, watering and well ramming in layers n.exc 25cm thick complete all as specified and directed by Engineer-in-Charge
Removal of excavated surplus soil to a distance n.exc 50m and depositing where directed at level not exceeding 1.5 m above the starting point complete all as specified & directed by Engineer-in-charge .
M & L for sand cushioning with dry coarse sand to under ground cable below and around after laying the cable jently punning down complete all as specified and directed by Engineer-in-Charge. Note : Thickness after punning shall be considered for payment.
Supplying and laying un-reinforced precast concrete cable cover, class EHV ,type 1 with peak, size 450mm x 230mm x 50mm complete all as specified and directed by engr-in-charge.
Supply and fixing of Sealed Maintenance free VRLA battery 2 Volt 100AH dry type complete with inter cell cooper connector , SS nut and bolt , MS powder coated stand in factory charge condition all as per Engr-in-Charge. Make : Amra Raja, Exide etc
Disconecting electric supply and strip open/dismantling carefully the existing 11 KV (VCBs) Vaccum circuit Brekers carefully and equipment calibration testing segregating serviceble and unserviceable spare parts setting aside for re-use. After that regular servicing/ maintenance and rectification of error and equipment calibration testing of the HT panel comparising of protection and control wiring test, and indicating instrument, earthing, over current, short circuit, insulation resistance and heater etc, replacement of worn out wiring including bus bar insulation, applying protective kits complete all as specified and directed by Engineer-in-Charge. Note:- (i) The new spare parts required for replacement shall be measured and paid separately as Supply only. (ii) Relevent T&P and testing equipments/tools and minor accessories are arranged by the contractor and included in the unit rate of item. Make of VCB : Siemens
Disconecting electric supply and strip open/dismantling carefully the existing 11 KV indoor Bus-Bar general servicing and mainttenance carefully. After that regular servicing/ maintenance and rectification of error and equipment calibration testing of the above mentioned items comparising of protection and control wiring test, and indicating instrument, earthing, over current, short circuit, insulation resistance etc, replacement of worn out wiring including bus bar insulation, applying protective kits complete all as specified and directed by Engineer-in-Charge. Note:- (i) The new spare parts required for replacement shall be measured and paid separately as Supply only. (ii) Relevent T&P and testing equipments/tools and minor accessories are arranged by the contractor and included in the unit rate of item. Make of VCB : Siemens
Disconecting electric supply and strip open/dismantling carefully the existing 33 KV (VCBs) Vaccum circuit Brekers carefully and equipment calibration testing segregating serviceble and unserviceable spare parts setting aside for re-use. After that regular servicing/ maintenance and rectification of error and equipment calibration testing of the HT panel comparising of protection and control wiring test, and indicating instrument, earthing, over current, short circuit, insulation resistance and heater etc, replacement of worn out wiring including bus bar insulation, applying protective kits complete all as specified and directed by Engineer-in-Charge. Note:- (i) The new spare parts required for replacement shall be measured and paid separately as Supply only. (ii) Relevent T&P and testing equipments/tools and minor accessories are arranged by the contractor and included in the unit rate of item. Make of VCB : Siemens
Disconecting electric supply and strip open/dismantling carefully the existing 33 KV indoor Bus-Bar general servicing and mainttenance carefully. After that regular servicing/ maintenance and rectification of error and equipment calibration testing of the above mentioned items comparising of protection and control wiring test, and indicating instrument, earthing, over current, short circuit, insulation resistance etc, replacement of worn out wiring including bus bar insulation, applying protective kits complete all as specified and directed by Engineer-in-Charge. Note:- (i) The new spare parts required for replacement shall be measured and paid separately as Supply only. (ii) Relevent T&P and testing equipments/tools and minor accessories are arranged by the contractor and included in the unit rate of item. Make of VCB : Siemens
Regular servicing/maintanance current transformer CT Ratio 200-100/-5/5A suitable for 33KV, 12/15/20VA, class of accurancy 0.5/5P10. complete all as specified and directed by Engineer-in-Charge
Regular servicing/maintanance current transformer CT Ratio 200-100/-5/5A suitable for 11KV, 12/15/20VA, class of accurancy 0.5/5P10. complete all as specified and directed by Engineer-in-Charge
Regular servicing/maintanance potential transformer PT Ratio 11KV/110V suitable for 33KV, 50VA, class of accurancy 0.5/3P. complete all as specified and directed by Engineer-in-Charge
Regular servicing/maintanance potential transformer PT Ratio 11KV/110V suitable for 11KV, 50VA, class of accurancy 0.5/3P. complete all as specified and directed by Engineer-in-Charge
Supply & Fixing TNC Switch , three position switch , as per size suitable for 33/11 KV complete taking down old unsv all as specified and directed by Engineer-in-Charge. Make: Areva / CG / Schnieder or equivelent
Disconnecting and taking out DG set electric connection from both side incoming and out going electric and DG set supply of 30 KVA DG Set and servicing the DG set with authotrised dealer/rep of dealer (kirloskar) and make it complete with all respect as servicing, connecting including replacement of necessary minor spares for the engine and alternator, repair machining of cylinder head for the optimum performance of the machine and overhauling of FIP and injectors with necessary calibration etc all as specified and as directed testing etc with duly change of Unserviceable Parts of DG Set same shall be paid separately and checking the battery terminals, apply necessary vesline on it and fresh connection complete all as specified and directed. Note : (i) Rate deemed to included the T&P used for this purpose bring by the contractor and If again any fault occur of same nature of repair during the Contract period is rectified by the contractor at free of cost. (ii) Supply only spares required for repairs shall be measured and paid separately under Sch 'A' item No 39.00 to 52.00 herein after.
Supply only Set of fuel filter elements for replacement during the process of overhaul repair of the generating set vide serial items No 38.00 here in before.
Ditto - all as per above item No 38 but Set of oil filter elements.
Ditto - all as per above item No 38 but Air filter elements.
Ditto - all as per above item No 38 but Set of hose pipes with kits.
Ditto - all as per above item No 38 but Oil temperature gauge with sensor.
Ditto - all as per above item No 38 but Cylinder liner.
Ditto - all as per above item No 38 but Piston.
Ditto - all as per above item No 38 but Set of upper engine gasket.
Ditto - all as per above item No 38 but CR bearing.
Ditto - all as per above item No 38 but Oil pan gasket.
Ditto - all as per above item No 38. but Cylinder head repair kit complete including valve and valve seat grinding springs collects and sleeves.
Ditto - all as per above item No 38 but Barrel plunger and cup.
Ditto - all as per above item No 38 but Set of Lower engine gasket.
Ditto - all as per above item No 38 but Solonide switch.
Supply & filling changing in replacement of old Unserviceable Oil with of Kirloskar Engine Oil as per prescribed grade of Kirloskar complete all as specified and directed by engr-in-charge
S&F in replcement of coolant of DG set as per existing complete all as specified and directed by engr-in-charge.
Disconnecting and taking out DG set electric connection from both side incoming and out going electric and DG set supply of 62.5/63 KVA DG Set and serving the DG set with authotrised dealer/rep of dealer (kirloskar) and make it complete with all respect as servicing, connecting , including replacement of necessary minor spares for the engine and alternator, repair machining of cylinder head for the optimum performance of the machine and overhauling of FIP and injectors with necessary calibration etc complete all as specified and as directed. testing etc with duly change of US Parts of DG Set same shall be paid separately and checking the battery terminals, apply necessary vesline on it and fresh connection complete all as specified and directed. Note : (i) Rate deemed to included the T&P used for this purpose bring by the contractor and If again any fault occur of same nature of repair during the contact period is rectified by the contractor at free of cost. (ii) Supply only spares required for repairs shall be measured and paid separately under Sch 'A' item No 56.00 to 69.00 herein after.
Supply only Set of fuel filter elements for replacement during the process of overhaul repair of the generating set vide serial items No 55.00 here in before :-
Ditto - all as per above item No 55 but Set of oil filter elements.
Ditto - all as per above item No 55 but Air filter elements.
Ditto - all as per above item No 55 but Set of hose pipes with kits.
Ditto - all as per above item No 55 but Oil temperature gauge with senser.
Ditto - all as per above item No 55 but Cylinder liner.
Ditto - all as per above item No 55 but Piston.
Ditto - all as per above item No 55 but Set of upper engine gasket.
Ditto - all as per above item No 55 but CR Bearing.
Ditto - all as per above item No 55 but Oil pan gasket.
Ditto - all as per above item No 55 but Cylinder head repair kit complete including valve and valve seat grinding springs collects and sleeves.
Ditto - all as per above item No 55 but Barrel plunger and cup.
Ditto - all as per above item No 55 but Set of Lower engine gasket.
Ditto - all as per above item No 55 but Solonide switch.
S&F in replacement of battery terminal brass suitable for 12 volt 150 Ah battery of DG set complete all as specified and directed by engr-in-charge
S & F for onload change over switch (four pole) TPN 40 Amps capacity complete in sheet steel enclosure type FN (TPN) suitable for DIN fuse link and removing existing unserviceable one complete all as specified and directed by Engr-in-Chage.
Ditto - all as per above item No 71 but TPN 63 Amps.
Ditto - all as per above item No 71 but TPN 100 Amps.
Taking down MCCB of any type and any capacity all as specified and directed by engr-in-charge
Supply and fixing MCCBs 4 pole 415 volt adjustable type 250 amps, 36 KA three pole, incl necessary cable connection complete all as specified and directed by Engr-in-charge
Supply and fixing MCCBs 4 pole 415 volt fixed type 63 amps, 16 KA three pole, incl necessary cable connection complete all as specified and directed by Engr-in-charge
Supply and fixing MCCBs 4 pole 415 volt fixed type 100 amps, 16 KA three pole, incl necessary cable connection complete all as specified and directed by Engr-in-charge
Supply and fixing MCCBs 4 pole 415 volt fixed type 125 amps, 16 KA three pole, incl necessary cable connection complete all as specified and directed by Engr-in-charge
Supply and fixing MCCBs 4 pole 415 volt fixed type 200 amps, 36 KA three pole, incl necessary cable connection complete all as specified and directed by Engr-in-charge
Supply and fix in repair Battery 12V 100AH Make-Exide
Supply and fix electrical materials for repairs of LT pannel/DG set pannel boards situated at various installation including making copper cable connections with lugs, connectors,ferrule,glands of suitable size Combined Voltmeter & Ammeter digital type, square as per requirement etc complete all as directed.
Ditto - all as per above item No 81 but Push button with NC.
Ditto - all as per above item No 81 but Indicating light.
Ditto - all as per above item No 81 but Main contactor 100 Amps Make L&T. model MCX 22
Ditto - all as per above item No 81 but Main contactor 130 Amps MCX23 Make L&T. model MCX 23
Ditto - all as per above item No 81 but Main contactor 50 Amps Make L&T. model MCX 11
Ditto - all as per above item No 81 but Main contactor 63 Amps Make L&T. model MCX 12
Ditto - all as per above item No 81 but Main contactor 80 Amps Make L&T. model MCX 13.
Ditto - all as per above item No 81 but Relay Contact with specification 250VAc 10A(NO) , 5A(NC) , 3 NO + 1 NC , PF 0.41 (As per sample).
Total contract sum shall be calculated after deduction of schedule of credit amount of Rs. 5,765.00
M/S INDIA ENTERPRISES (BID ID -3364032)
FIRST SOLAR (BID ID -3353139)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .