Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹41.1 CrAccepted-AOC | ₹41.1 Cr | L1 | Accepted-AOC accept |
| 2 | L2₹44.1 CrRejected-AOC | ₹44.1 Cr | L2 | Rejected-AOC accept |
| 3 | L3₹45.5 CrRejected-AOC | ₹45.5 Cr | L3 | Rejected-AOC accept |
| 4 | Rejected-Technical | - | - | Rejected-Technical Reject |
Tender Value
₹41.5 Cr
EMD Value
₹20.8 L
Closing Date
7 Nov 2022, 6:55 pmClosed
Executive Engineer, PWD Nanded, Dist.Nanded
Sneh Nagar, Behind Govt. Rest House
CONSTRUCTION OF 100 BEDDED HOSPITAL BUILDING AT WADI (BK) TQ AND DIST. NANDED
2022_PWR_840038_1
PWD/NANDED/2022-23/SBD/ENo.28
Open Tender
Civil Works - Buildings
730 days
NANDED
Please refer Tender documents.
5 documents required · 5 mandatory
₹3,000
₹20.8 L
Chief Engineer, Public Works Region, Nanded
16 Mar 2023
3 Oct 2022
10 Nov 2022
3 Oct 2022
7 Nov 2022
3 Oct 2022
17 Oct 2022
Amount
Part A Work Portion
Excavation for foundation in earth, soil of all types, sand, gravel and soft murum, including removing the excavated material up to a distance of 50 m. beyond the building area and stacking and spreading as directed, dewatering, preparing the bed for the foundation and necessary back filling, ramming, watering including shoring and strutting etc. complete. (Lift upto 1.5 m.) By Mechanical Means
Excavation for foundation in earth, soilsHrd Murum including removing the excavated material upto a distance of 50 metres beyond the building area and stacking and spreading as directed, dewatering, preparing the bed for the foundation and necessary back filling, ramming, watering including shoring and strutting etc. complete. (Lift from 1.5m ) By Mechanical Means
Excavation for foundation in Hard murum including removing the excavated material upto a distance of 50 metres beyond the building area and stacking and spreading as directed, dewatering, preparing the bed for the foundation and necessary back filling, ramming, watering including shoring and strutting etc. complete. (Lift from 1.5 to 3.0m.) By Mechanical Means
Excavation for foundation in Hard murum and boulders including removing the excavated material upto a distance of 50 metres, beyond the building area and stacking and spreading as directed, dewatering, preparing the bed for the foundation and necessary back filling, ramming, watering including shoring and strutting etc. complete. (Lift from 1.5 m to 3.0 m.) By Mechanical Means
Conveying materials obtained from road cutting including all lifts, laying in layers of 20cm to 30cm. breaking clods, dressing to the required lines, curves, grades and section, watering and compacting to not less than 97% of standard Proctor density for a lead of over 50m. to 300m. inclusive from the site of excavation to the site of deposition as directed.
Providing soling using 80 mm size trap metal in 15 cm. layer including filling voids with Crushed sand/grit, ramming, watering etc. complete.
Providing and laying Cast in situ/Ready Mix cement concrete in M-10 of trap/ granite/ quartzite/ gneiss metal for foundation and bedding including bailing out water, Steel centering, formwork, laying/pumping, compacting, roughening them if special finish is to be provided, finishing if required and curing complete, with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade)
Providing and laying Cast in situ/Ready Mix cement concrete in M15 of trap/ granite/quartzite/gneiss metal for plain or molded sills, cornice, jambs, block in course, or architraves of required size and shapes including steel centering, formwork, laying/ pumping, compacting, roughening them if special finish is to be provided,finishing uneven and honeycombed surface and curing etc. complete. The Cement Mortar 1:3 plaster is considered for rendering uneven and honeycombed surface only. Newly laid concrete shall be covered by gunny bag, plastic, tarpaulin etc. (Wooden centering will not be allowed.) with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade)
Providing and laying Cast in situ/Ready Mix cement concrete M-25 of trap / granite/quartzite/ gneiss metal for R.C.C. work in foundations like raft, strip foundations, grillage and footings of R.C.C. columns and steel stanchions etc. including bailing out water, Steel centering, formwork ,cover blocks, laying/pumping, compaction and curing roughening the surface if special finish is to be provided (Excluding reinforcement and structural steel) etc. complete, with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade)
Providing and laying Cast in situ/Ready Mix cement concrete M-25 of trap / granite /quartzite/ gneiss metal for R.C.C. columns as per detailed designs and drawings or as directed including steel centering, formwork, cover blocks, laying/pumping, compaction finishing the formed surfaces with cement mortar 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening if special finish is to be provided and curing etc. complete,(Excluding reinforcement and structural steel).with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade)
First Floor
Second Floor
Providing and laying Cast in situ/Ready Mix cement concrete in M-25 of trap/ granite/ quartzite/ gneiss metal for R.C.C. beams and lintels as per detailed designs and drawings or as directed including steel centering, formwork, cover blocks, laying/pumping, compactionand roughening the surface if special finish is to be provided and curing etc. complete. (Excluding reinforcement and structural steel).with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade)
First Floor
Second Floor
Providing and laying Cast in situ/Ready Mix cement concrete M-25 of trap/ granite / quartzite/ gneiss metal for R.C.C. slabs and landings as per detailed designs and drawings including steel centering, formwork, cover blocks, laying/pumping, compaction finishing the formed surfaces with cement mortar 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening if special finish is to be provided and curing etc. complete,(Excluding reinforcement and structural steel).with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade)
First Floor
Second Floor
Providing and laying Cast in situ/Ready Mixcement concrete M-25 of trap/ granite/ quartzite/ gneiss metal for R.C.C. chajja as per detailed design and drawings including steel centering, formwork, cover blocks, laying/pumping, compacting and roughening the surface if special finish is to be provided and curing complete. (Excluding reinforcement and structural steel). with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade)
First Floor
Second Floor
Providing and laying Cast in situ/Ready Mix cement concrete in M-25 of trap/ granite/ quartzite/ gneiss metal for R.C.C. pardi of required thickness including steel centering, formwork, cover blocks, laying/pumping, compacting and roughening them if special finish is to be provided and curing complete. (Excluding reinforcement and structural steel).with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade)
First Floor
Second Floor
Providing and laying Cast in situ/Ready Mix cement concrete in M-25 of trap / quartzite/granite /gneiss metal for R.C.C. Waist slab, and steps of staircases as per detailed design and drawings or as directed including steel centering, plywood/ steel formwork, steel props, laying/pumping, compaction, finishing uneven and honeycombed surface with C.M. 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening the surface if special finish is to be provided and curing etc. complete. (Excluding einforcement, including cover block).(Newly laid concrete shall be covered by gunny bag, plastic, tarpaulin etc.) with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade)
First Floor
Second Floor
Providing and laying Cast in situ/Ready Mix cement concrete M-25 of trap / granite / quartzite / gneiss metal for R.C.C. canopy as per detailed designs and drawings including steel centering, formwork, laying/pumping, compacting and roughening the surface if special finish is to be provided and curing etc. complete (excluding reinforcement). with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade)
Providing and laying Cast in situ/Ready Mix cement concrete in M-20 of trap/ granite/ quartzite/ gneiss metal for R.C.C.coping to plinth or parapet and sill of doors and windows moulded as per detailed drawings or chamfered as approved by the Engineer including steel centering, formwork, cover blocks, laying/pumping, compacting , curing , finishing and roughening them if special finish is to be provided and curing complete. (Excluding reinforcement and structural steel).with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade)
Second Floor
Providing and applying two coats of protective membrane over the cured concrete surface like R.C.C. footings, columns, plinth beams etc. which will be submerged under soil so as to protect the same. Apply two pack coal tar epoxy system of Sunepoxy Coaltar of approved make & approved by Engineer in charge, having solid content ranges from 80-100%, Tack free time 4-6 hrs. Recoat after 16-24 hrs. Mix Part A and Part B of Sunepoxy Coaltar of approved make & approved by Engineer in charge in 1:1 ratio with slow speed stirrer and apply the same on a clean R.C.C. surface by brush. Allow to set for 8-10 hours and apply the second coat. The rate to include for application at all levels to various RCC elements to the satisfaction of the EIC etc. complete.
Providing and fixing in position TMT - FE - 500 bar reinforcement of various diameters for R.C.C. pile caps, footings, foundations, slabs, beams columns, canopies, staircase, newels, chajjas, lintels pardis, copings, fins, arches etc. as per detailed designs, drawings and schedules. including cutting, bending, hooking the bars, binding with wires or tack welding and supporting as required complete.
First Floor
Second Floor
Filling in plinth and floors with approved excavated material in 15cm. to 20cm. Layers including watering and compacting etc. complete.
Filling in plinth and floors with contractors material/brought from outside and approved by Engineer incharge in layers of 15 cm to 20 cm including watering and compaction etc. complete.
Providing expansion joints in R.C.C. framed structure (at floor level) with premoulded filler 25 mm thick and 3 mm thick aluminium plate as required, bitumen poured filler and fixing T.W. battens on rear faces etc. complete as directed.
First Floor
Providing expansion joints in R.C.C. framed structure (at terrace level) with premoulded filler 25 mm thick and 3 mm thick aluminium plate as required, bituminous poured filler, fixing lead, flashing on upper side and T.W. battens on inner face finishing etc. Complete as directed.
Providing expansion joints in reinforced cement concrete framed structure (interior columns) with plain premoulded filler with confirming to IS 1838,1961, 25 mm thick with 75 mm wide and 1 mm thick stainless steel plate finishing etc. complete as directed
First Floor
Second Floor
Providing expansion joints in R.C.C. framed structure (exterior column) with plain premoulded filler 25 mm thick with 75 mm wide and 1 mm thick stainless steel plate and finishing etc. complete.
First Floor
Second Floor
Providing fly ash brick masonry with conventional / I.S. type fly ash bricks in C.M. 1:6 in foundation and plinth including bailing out water manually striking joints, racking out joints watering and scaffolding etc. complete.
Providing fly ash brick masonry with conventional/ I.S. type bricks in cement mortar 1:6 in superstructure including striking joints, raking out joints, watering and scaffolding etc. Complete
First Floor
Second Floor
Providing Second class fly ash brick masonry with conventional / I.S. type bricks in cement mortar 1:4 in half brick thick wall including mild steel longitudinal reinforcement of two bars of 6 mm diameter / two hoop iron strips 25 mm x 1.60 mm at every third course, properly bent and bounded at ends scaffolding raking out joints and watering etc. complete.
First Floor
Second Floor
Providing patti/ band 75mm wide on plastered surface 12 mm to 15 mm thick in C.M. 1:3 line and level including neat finishing scaffolding curing etc. complete.
First Floor
Second Floor
Providing patti/ band 100mm wide on plastered surface 12 mm to 15 mm thick in C.M. 1:3 line and level including neat finishing scaffolding curing etc. complete.
First Floor
Second Floor
Providing and fixing chicken mesh of 22 gauge, with about 30 cm. width at the junction of R.C.C members and brick work, of approved quality including fixing mesh in position by necessary drilling in concrete /B.B.masonry and or tying by binding wire etc. complete.
First Floor
Second Floor
Providing internal cement plaster 20mm thick in a single coat using Ready to use wall plaster to concrete, brick surfaces in all positions including scaffolding and curing. Providing groove at joint of B.B.Masonry and concrete members complete. b) cement mortar 1:4 With Prior Approval of Concerned S.E.
First Floor
Second Floor
Providing sand faced plaster externally in cement mortar using approved screened sand, in all positions including base coat of 15 mm thick in cement mortar 1:4 using waterproofing compound at 1Kilogramper cement bag curing the same for not less than 2 days and keeping the surface of the base coat rough to receive the sand faced treatment 6 to 8 mm thick in cement mortar 1:4 finishing the surface by taking out grains and curing for fourteen days scaffolding etc.complete.
First Floor
Second Floor
Boring/drilling bore well of 300mm dia for casing/ strainer pipe, by suitable method prescribed in IS: 2800 (part I), including collecting samples from different strata, preparing and submitting strata chart/ bore log, including hire & running charges of all equipments, tools, plants & machinery required for the job, all complete as per direction of Engineer in charge, upto 90m depth below ground level.
Providing and fixing mild steel grill work for windows, ventilators etc. 20 Kilogram/ One Square Metre as per drawing including fixtures, necessary welding and painting with one coats of anticorrosive paint and two coats of oil painting complete.
First Floor
Second Floor
Providing and fixing mild steel grill work for windows, ventilators, etc. 15 Kilogram/ One Square Metre as per drawing including fixtures necessary welding and painting with one coat of anticorrosive paint and two coats of oil painting complete.
First Floor
Second Floor
Providing and fixing mild steel grill gate with angle iron frame 65mm x 65mm x 10mm with iron bars at 150mm C/C and diagonal flats as per the detailed drawing including hinges, pivot block locking arrangement, welding riveting and oil painting of three coats of approved shade Weight of gate 35 Kilogram/Smt.
Providing and fixing bituminous pad 25mm thick for expansion joints in retaining wall, compound wall etc. complete.
Providing and applying plaster with plaster of paris in 6mm thickness to previously plaster surface in all position including preparing the surface scaffolding etc. complete.
First Floor
Second Floor
Providing and applying Two coats of wall care Putty on plastered surface and Ceiling and Walls to prepare surface even and smooth of approved make, etc complete.
First Floor
Second Floor
Providing & Fixing in position, Acoustical Panelling made from Gypsum plain 12mm panels on, 50 x 50 mm Sal-wood frame of 600 x 600 c to c having wooden supports from wall of required length, in front of 1000 Gsm synthetic wool 50 mm thick with chicken mesh on wall side, including cost of required Cut-Outs, decorative mouldings / finishing-items / paint & Scaffolding, as per Architectural & Acoustical Design & Instructions & Complete in all aspects. including all materials labour,finishing etc complete
First Floor
Second Floor
Waterproofing Treatment to new Toilet/bathroom by using Polymeric Cementitious Membrane as approved by Engineer in charge, followed by 112mm thick brick bat coba covered with 20 mm mortar finish. If there are cracks on the bare slab, open the crack in V Groove and fill it with ready to use repair polymer modified mortar based on special cements, aldehyde based polymers with thixotropy modifying agents. If there are lots of honeycombs and identified bad patches of concrete the same should be grouted as per the instructions of site incharge. (The grouting shall be paid separately). Clean the entire surface thoroughly and over this prepared surface, apply three coats of polymeric Cementitious waterproofing coating having a non-toxic, 2-(methoxycarbonyl)-1-propene-Butyl-2 propenoate (MPBP) based polymeric waterproofing solution as approved by Engineer in charge. Provide and lay 112 mm average thicknes of brick bat coba in cement mortar 1:5 over 12mm thick CM 1:3 bedding with one pouch of 330 grams of thorough blend of special cements, aldehyde based polymers, shrinkage compensating agents as approved by Engineer in charge per 50 Kg bag of cement and finishing with 20 mm thick cement plaster in cement mortar 1:3 by mixing one 330 grams pouch of above admixture per 50 Kg bag of cement, including all lead, lifts and laid to proper slope to drain off water entirely preparing bell mouth including watta, beveled or champhered portion at the junction of wall and work up to a height of 300 mm or as directed and including finishing the top layer of waterproofing treatement with false marking of 30 cm x 30 cm or as directed, curing and covering the whole treatment. MPBP Polymeric Waterproofing Coating for Concrete and Masonry should have following minimum properties:1) Elongation % (ASTM D412-2016): @ 100% 2) Tensile Strength N/mm2 (ASTM D412-2016): 3.3 3) Specific Gravity: 1.02 ± 0.02 4) Total Solids (ASTM D1644-2012): 43.98 5) Hardness Shore A (ASTM D2240-2015): 82
First Floor
Second Floor
Providing waterproof plaster in W.C. and bath 20 mm thick for dado in cement mortar 1:3 with neat finishing, floating using waterproofing compound at the rate of 1 Kilogram. per bag of cement of approved make and manufacturer and curing (and filling joints of Nahani trap and any outlet by properly) etc. complete.
First Floor
Second Floor
Providing water proof bedding for flooring of Bath and WC 25 mm thick in C.M. 1:3 including using approved water proofing compound in specified proportion as per manufacturers specifications for per bag of cement including leveling, curing and covering 10 years guarantee on court fee stamp paper of Rs.500/- including ponding test etc. complete.
Providing waterproof plaster in W.C. and bath 12 mm thick for dado in cement mortar 1:3 with neat finishing, floating using waterproofing compound at the rate of 1 Kilogram. per bag of cement of approved make and manufacturer and curing etc. complete. (Excluding Tiles) (As directed by Engineer in Charge)
Providing and fixing H.D.P container one piece moulded water tank made out of low density polythyler and built corrugation including of delivery up to destination hoisting and fixing of accessories such as inlet, outlet overflow of all tanks capacity above 1000 to 20,000 litres
Providing and fixing H.D.P container one piece moulded water tank made out of low density polythyler and built corrugation including of delivery up to destination hoisting and fixing of accessories such as inlet, outlet overflow of all tanks capacity above 1000 to 20,000 litres
Providing and fixing 40 mm. dia Ball cock medium type with PVC float including sockets and necessary fittings and tested as per municipal requirements etc. complete.
Providing and fixing 40 mm. dia Ball cock medium type with PVC float including sockets and necessary fittings and tested as per municipal requirements etc. complete.
Providing and fixing on walls/ ceiling/ floor 15 mm dia. CPVC pipe with necessary fittings, remaking good the demolished portion etc. complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etc. complete.
First Floor
Second Floor
Providing and fixing on walls/ceiling/floor 20 mm dia. CPVC pipe with necessary fittings, remaking good the demolished portion etc. complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etc. complete.
First Floor
Second Floor
Providing and fixing on walls/ ceiling/ floor 25 mm dia. CPVC pipe with necessary fittings, remaking good the demolished portion etc. complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etc. complete.
First Floor
Second Floor
Providing and fixing on walls/ ceiling/ floor 32 mm dia. CPVC pipe with necessary fittings, remaking good the demolished portion etc. complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etc. complete.
First Floor
Second Floor
Providing and fixing on walls /ceiling/ floor 40 mm dia. CPVC pipe with necessary fittings, remaking good the demolished portion etc. complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etc. complete.
First Floor
Second Floor
Providing and fixing on walls/ ceiling/ floor 50 mm dia. CPVC pipe with necessary fittings, remaking good the demolished portion etc. complete.
First Floor
Second Floor
Providing and fixing 15 cm rigid PVC Nahani trap including PVC grating ,bend,connectingpiece of UPVC pipe up to the outside face of wall ,making the good damaged surface and testing etc. complete ( Prior approval of sample and brand by Ex. Engr. is necessary before use)
First Floor
Second Floor
Providing and laying in trenches 40mm dai. CPVC pipe including necessary excavation, fittings. Refilling trenches etc. complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etc. complete.
Providing and laying in trenches 50mm dai. CPVC pipe including necessary excavation, fittings. Refilling trenches etc. complete. Including removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etc. complete.
Providing and fixing 100 mm dia stabiliser pipe/ P.V.C. soil vent/waste pipe and with necessary fixtures and fitting such as bends, tees, single junctions, slotted vent, clamps etc. complete.
First Floor
Second Floor
Providing and fixing in position UPVC ultra violet stabilized 110 mm outer diameter cowl dome confirming to I.S.-4985 including making joints with solvent cement etc. complete
Providing and fixing in position UPVC ultra violet stabilized 110 mm outer diameter cowl dome confirming to I.S.-4985 including making joints with solvent cement etc. complete
First Floor
Second Floor
Providing and fixing C.P. 2 Way BIB cock with wall flange of approved make including necessary sockets/ union nut etc. complete as directed by Engineer in charge.
First Floor
Second Floor
Providing and fixing C.P. BIB cock with wall flange of approved make including necessary sockets/ union nut etc. complete as directed by Engineer in charge.
First Floor
Second Floor
Providing and fixing white Opal series European type wall-hung, of size 400 mm x 370 mm x 575mm with approved make flush valve including soil pipe, vent pipe upto outside face of wall, 100mm dia C.I. plug bend inlet pipe all fittings, cutting & making good walls, floors etc as directed by Engineer in charge.
First Floor
Second Floor
Providing and fixing Orissa Pan of size 580x445x260 mm with approved make flush valve including trap, C.I. soil and vent pipe upto outside face of wall including 100mm dia. C.I. plug, bend and necessary pipe connection, etc complete. As directed by Engineer in charge.
First Floor
Second Floor
Providing and fixing white european type wall-hung, Size 360mm x 360mm x 575 mm with flush valve having flow rate up to 6.0 Litr/Minute of Jaquar/Cera/Hindware /Perryware or equivalent make including PVC soil pipe, vent pipe upto outside face of wall, 100mm dia PVC plug bend inlet pipe all fittings,cutting & making good walls, floors etc as directed by Engineer in charge.( Make shall conform to manufacturer's Green product and shall got approved from the Engineer In Charge.)
First Floor
Second Floor
Providing and fixing Table top white wash basin of size 120x635x405mm rubber plugs and brass chain, with pillar cock, C.P.Angular stop cock long thread, continental including S.S. bottle trap of approved make having necessary pipe connection up to theoutside face of the wall.etc complete as directed by Engineer in charge.
First Floor
Second Floor
Providing and fixing Oval Type Under Counter Wash Hand Basin of 420 x 590 x 195mm size with pillar cock, C.P.Angular stop cock, long thread of approved make continental including SS bottle trap of necessary pipe connection up to the outside face of the wall, having Telephonic Black / Colour Granite of 180 mm thick fixed on Black Kadappa Framework, etc. Complete as directed by Engineer in charge.
Providing and fixing stainless steel sink of size 600 x 510 x 200 mm incluidng coupling, outlet pipe, elbow and other necessary fitting, finishing etc. complete.
First Floor
Second Floor
Providing and fixing sink cock with regular swinging spout (Wall / floor Mounted Model) with wall flange having flow rate up to 6.0 Litr/Minute of Jaquar/Cera/Hindware /Perryware or equivalent make incluidng other necessary fitting, etc. complete as directed by Engineer in charge.( Make shall conform to manufacturer's Green product and shall got approved from the Engineer In Charge.)
Providing and fixing C.P. sink cock with raised J" shaped swinging casted spout ofapproved make including necessary sockets/ union nut etc. complete."
First Floor
Second Floor
Providing and fixing white glazed urinal with Pressmatic auto closing valve having flow rate up to 4.0 Litr/Minute of Jaquar/Cera/Hindware /Perryware or equivalent make with P.V.C. waste pipe with fitting arrangement etc.complete as directed by Engineer in charge.( Make shall conform to manufacturer's Green product and shall got approved from the Engineer In Charge.)
Providing and fixing wall mixer with overhead shower,shower arm,hand shower with wall bracket having flow rate up to 12 liters/minutes of Jaquar/Cera/Hindware /Perryware or equivalent make including all necessary pipes,fittings etc.complete as directed by Engineer In Charge.( Make shall conform to manufacturer's Green product and shall got approved from the Engineer In Charge.)
Providing and fixing 450mm x 550mm size superior type Belgium mirror with 16mm dia. nickel plated towel rod etc. complete.
First Floor
Second Floor
Providing and fixing chromium plated towel rod 16 mm dia and 75 cm. in length including all accessories complete.
First Floor
Second Floor
Providing and fixing Glass self 125 mm wide and 600 mm long with necessary chromium plated brackets providing T.W.gutties etc. complete
First Floor
Second Floor
Providing supplying in standard length (PE material) HDPE Double wall corrugated pipe for non pressure underground drainage and sewerage with smooth internal & corrugated external surface confirming to IS 16098:Part-2 2013 with spigot or plain end with necessary jointing material coupler including transportation and freight charges, inspection charges, loading and unloading charges, conveyance to departmental store and stacking the same in closed shade duly protecting from direct sun ray and rains excluding GST levied by Gol and GoM in all respect, etc. complete.(250 mm Dia)
Providing supplying in standard length (PE material) HDPE Double wall corrugated pipe for non pressure underground drainage and sewerage with smooth internal & corrugated external surface confirming to IS 16098:Part-2 2013 with spigot or plain end with necessary jointing material coupler including transportation and freight charges, inspection charges, loading and unloading charges, conveyance to departmental store and stacking the same in closed shade duly protecting from direct sun ray and rains excluding GST levied by Gol and GoM in all respect, etc. complete.(300 mm Dia)
Lowering, Laying and Jointing (PE material) HDPE double wall corrugated pipe for non pressure underground by heating to the ends of pipes with the help of tefflon coated electric heater to the required temparature and then pressing the ends together against each other, to form a monolithic & leak proof joint by thermosetting process. The pressing may be required to be done with Jacks/ Hydraulic Jacks/Butt fusion machine etc. complete with all materials labours as directed by Engineer - in - charge. including (250 mm Dia)
Lowering, Laying and Jointing (PE material) HDPE double wall corrugated pipe for non pressure underground by heating to the ends of pipes with the help of tefflon coated electric heater to the required temparature and then pressing the ends together against each other, to form a monolithic & leak proof joint by thermosetting process. The pressing may be required to be done with Jacks/ Hydraulic Jacks/Butt fusion machine etc. complete with all materials labours as directed by Engineer - in - charge. including (300 mm Dia)
Providing supplying in standard length (PE material) HDPE Double wall corrugated pipe for non pressure underground drainage and sewerage with smooth internal & corrugated external surface confirming to IS 16098:Part-2 2013 with spigot or plain end with necessary jointing material coupler including transportation and freight charges, inspection charges, loading and unloading charges, conveyance to departmental store and stacking the same in closed shade duly protecting from direct sun ray and rains excluding GST levied by Gol and GoM in all respect, etc. complete.(200 mm Dia)
Lowering, Laying and Jointing (PE material) HDPE double wall corrugated pipe for non pressure underground by heating to the ends of pipes with the help of tefflon coated electric heater to the required temparature and then pressing the ends together against each other, to form a monolithic & leak proof joint by thermosetting process. The pressing may be required to be done with Jacks/ Hydraulic Jacks/Butt fusion machine etc. complete with all materials labours as directed by Engineer - in - charge. including (200 mm Dia)
Providing , constructing and fixing 450 mm dia. Inspection chamber made up of Polypropylene / polyethylene material of thickness 3.5 mm and height of 388 mm with 160 or 200 mm main inlet (s) outlet and 110 and / or 160 mm branch inlets, with 450 mm dia. Ultra shaft pipe of HDPE material having height of 460 mm, having R.C.C. cover and frame fixing in 150 mm thick in c.c.1:2:4, having crushed sand bed of 150 mm thick of size 750 mm dia. Including excavation and refilling the sides of chamber by sand crushed cushioning 150 mm thickness, connecting all required UPVC fittings with rubber lubricant etc. complete.
Providing , constructing and fixing 600 mm dia. Inspection chamber made up of Polypropylene / polyethylene material Having 315 mm diameter inlet(s)/outlets and with eccentric reducers as per requirement to connect 160 mm and 200 mm pipes having thickness of 5 mm and 600 mm in height, with inbuilt shaft achieve the invert depth as per site condition of wall thickness of 5 mm having R.C.C. cover and frame fixing in 150 mm thick in c.c.1:2:4, having crushed sand bed of 150 mm thick of size 750 mm dia. Including excavation and refilling the sides of chamber by ?sand crushed cushioning 150 mm thickness, connecting all required UPVC fittings with rubber lubricant etc.complete.
Providing and laying vitrified matt fininsh tiles having size 590 mm to 605 mm x to 605 mm of 8 to 10 mm thickness and confirming IS. 15622-2006 (Group Bla) of approved make, shade and pattern for flooring in required position laid on a bed of 1:4 cement morar including neat cement float, filling joints, curing and cleaning etc. complete.
First Floor
Second Floor
Providing and laying vitrified matt finish tiles having size 590 mm to 605 mm x to 605 mm of 8 to 10 mm thickness and confirming IS. 15622-2006 (Group Bla) of approved make, shade and pattern for dado and skirting in required position fixed in 1:4 cement mortar including neat cement float, filling joints, curing and cleaning etc. complete.
First Floor
Second Floor
Providing and laying vitrified matt fininsh tiles having size 590 mm to 605 mm x to 605 mm of 15 to 20 mm thickness and confirming IS. 15622-2006 (Group Bla) of approved make, shade and pattern for flooring in required position laid on a bed of 1:4 cement morar including neat cement float, filling joints, curing and cleaning etc. complete.
First Floor
Second Floor
Providing and laying vitrified mirror / glossy finish tiles decorative type having size 590 mm to 605 mm x 590 mm to 605 mm of 8 to 10 mm thickness and confirming to IS. 15622-2006 ( group Bla) of approved make, shade and pattern for flooring in required position laid on a bed of 1:4 cement mortar including neat cement float, filling joints, curing and clearing etc. complete.
Providing and laying vitrified mirror / glossy finish tiles having size 590 mm to 605 mm x 590 mm to 605 mm of 8 to 10 mm thickness and confirming to IS. 15622-2006 ( group Bla) of approved make, shade and pattern for dado and skirting in required position fixed in 1:4 cement mortar including neat cement float, filling joints, curing and clearing etc. complete
Providing and laying polished hand cut Kotah Stone flooring 25mm to 30mm thick and 45cm to 55cm wide in plain/diamond pattern on a bed of 1:6 C.M. including cement float, filling joints with neat cement slurry, curing, polishing and cleaning complete.
Providing and laying 18 mm thick ADONI BROWN LEATHER FINISH stone for flooring, machine cut in required size, approved shade, color and texture laid using white cement slurry over 20 mm (average) thick base of cement mortar 1:4 followed by laying, fixing and jointed with white cement slurry mixed with matching pigment, including rubbing and curing moulding and polishing to edge to give high gloss finish etc complete. The application rate for tile adhesives shall be as per manufacturer's recommendations. as per detail drawing. The rate shall be inclusive of all labour, material, wastage, scaffolding, transportation, taxes, including all leads, lifts at all levels and as directed by Engineer in charge. Complete. a) Flooring
Providing and laying machine cut machine Polished Kota stone flooring 25mm to 30mm thick and required width in plain/ diamond pattern on bed of 1:6 C. M. including cement float, filling joints with neat cement slurry, curing, polishing and cleaning etc. complete.
Providing 25 mm to 30 mm thick partition of polished black kadappa stone slab of approved quality including giving required size and shape etc. Fixing in cement mortar 1:3 curing and cement etc. complete. b) Both side polish
First Floor
Second Floor
Providing and constructing granite kitchen platform with fixing of stainless steel sink 600 mm x 450 mm size as per detailed drawing including vertical both side polished kadappah stone 25 to 30 mm thick supports with kadappah top 35 to 40 mm thick and polished granite 16 to 20 mm top with side strips of granite at front and both sides of platform raised with two vertical granite supports 15 cm height and top granite of 75 x 40 cm including cutting, opening for sink of required size in kadappah as well as granite etc. complete. (Platform top size 5.00 m x 0.60 m and height is 0.75 m)
First Floor
Second Floor
Providing and laying 18 mm thick ADONI BROWN LEATHER FINISH stone for flooring, machine cut in required size, approved shade, color and texture laid using white cement slurry over 20 mm (average) thick base of cement mortar 1:4 followed by laying, fixing and jointed with white cement slurry mixed with matching pigment, including rubbing and curing moulding and polishing to edge to give high gloss finish etc complete. The application rate for tile adhesives shall be as per manufacturer's recommendations. as per detail drawing. The rate shall be inclusive of all labour, material, wastage, scaffolding, transportation, taxes, including all leads, lifts at all levels and as directed by Engineer in charge. Complete. a) Skirting
First Floor
Second Floor
Providing and fixing machine cut machine polished 18 mm to 20 mm thick telephone black / Amba White / Cat bary brown / RBI red / Ocean Brown granite stone for treads and risers of steps and staircases of approved colour and shade with full moulding and three grooved line for the treads on bed of 1:4 Cement mortar including float filling joints with neat cement slurry curing polishing and cleaning etc. complete.
First Floor
Second Floor
Providing and fixing machine cut mirror polished 18 mm to 20 mm thick telephone black granite / Amba White / Cat bary brown / RBI red / Ocean Brown granite stone partition with full moulding the edges etc. complete . Both side polish
First Floor
Second Floor
Providing and laying telephone black / Amba White / Cadburybrown / Ruby red / Ocean Brown granite stone of 18 to 20 mm thick for door frame/ dado/ window boxing etc. On C.M. 1:6 including filling joints with polymer base filler nosing/moulding the sharp edges wherever necessary, curing, etc. complete.
First Floor
Second Floor
Providing and fixing factory made Hydraulically pressed Mechanically vibrated and compacted precast inter locking cement concrete paving blocks 100MM thick in M-50 grade of approved size and shape for City streets and roads with high volume/ heavy traffice as specified and as per IS 15658:2006 including cost of all materials, manufacturing, curing, transportation of blocks to work site including loading, unloading and stacking as directed, laying paving blocks in position over prepared bed of natural sand / crushed sand of 50 mm thickness including necessary excavation in all stratas, spreading blindge of fine sand over the prepared bed, compacting blocks by plate vibrator etc. complete.
Providing and fixing M40 grade thick vibrated pull cast or similar type concrete frame with chamfer conforming to I.S. 65241983 having 6 mm dia bars 3 Nos. And strips @250 mm c/c and fixing in wall with 6 Nos. of hold fast of 12 mm dia bars 500 mm long including primer and oil painting etc, complete) frame size 60 mm x 125 mm
Providing and fixing in position, Double shuttered aluminium extruded powder coated openable door of specified size with aluminium door frame of powder coated section 101.60 x 44.75mm , 3.18 mm thick and shutter comprising of powder coated section having bottom and lock rail of size 150 mm x 44.5 mm x 3.00 mm thick top rails 47.62 x 44.45 mm x 3.00 mm thick , vertical style 47.62 x 44.45 mm, 3.00 mm thick and for shutter plain glass panes 5 mm thick for top panels and 12mm thick both side laminated phenol bonded particle board panels for bottom panels etc. , I.S.I. mark , heavy duty, Hydraulic floor spring of 150Kilogramcapacity , having heavy duty concealed lock, necessary beading, glazing clips, PVC gaskets, 250mm length aluminium tower bolts, 150mm dia. pad handle, etc. as per detailed design and drawing or as directed by engineer in charge including all materials , labours, and equipment etc.complete
First Floor
Second Floor
Providing & fixing factory-made Aluminum windows of aluminum alloy HE 9WP (6063 T5/T6), powder coating of jotun/AkzoNobel of 60 micron thickness a.) Glass: 5mm thick clear float of Saint Gobain / Asahi make b.) Mesh of SS Type 304 grade of .22 mm thickness c.) Accessories: EPDM (Ethylene Propylene Diene Monomer) Gasket , SS Screws , Aluminum cleats , Roller , Push handle , Fly mesh handle , Anti lifter , U guide glass and mesh shutter complete
Providing and fixing reinforced cement concrete cover of size 90 cm x 45 cm with frame over inspection chamber etc. complete. Heavy duty (225 Kilogram)
Providing and fixing on walls/ ceiling/ floors, 25 mm dia. heavy grade having embossed as ISI Mark galvanised iron pipes weight of 3.01 Kilogram/meter with necessary fittings . remaking good the demolished portion and applying primer of anti-corrosive oil paint 2 coats Including necessary scaffolding and removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etc. complete.
Providing and fixing on walls/ ceiling/ floors, 32 mm dia. heavy grade having embossed as ISI Mark galvanised iron pipes weight of 3.89 Kilogram/meter with necessary fittings . remaking good the demolished portion and applying primer of anti-corrosive oil paint 2 coats Including necessary scaffolding and removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etc. complete.
Providing and fixing on walls/ ceiling/ floors, 40 mm dia. heavy grade having embossed as ISI Mark galvanised iron pipes weight of 4.49 Kilogram/meter with necessary fittings and remaking good the demolished portion and applying primer of anti-corrosive oil paint 2 coats Including necessary scaffolding and removing existing pipe line if necessary and conveying and stacking the same in PWD chowky or as directed etc. complete.
Providing of Lead Lined Door system with 120x60 mm Hardwood Frames, interlayered with 3mm lead and 44mm Solid core flush door shutters conforming to the I.S. specification 2202-1991 (specification for wooden flush door shutter – solid core type), interlayered with 3mm lead with prior approval of concerned Superitending Engineer. b) Shutter: Supplying of ' 44mm Solid core flush door shutters conforming to the I.S. specification 2202-1991 (specification for wooden flush door shutter – solid core type). 32mm Wooden structure of 1st class Hardwood or Pinewood of at least 50mm width, top and bottom rails of 75mm width, with filler material without any gap of 1st Class Hardwood, or pine wood, all chemically treated for termite and borer resistance as per IS 401:2001 under minimum 150 PSI pressure, and seasoned as per IS 1141: 1993 upto desired moisture level as per IS 287, with one side 3mm HDF & other side 3mm lead & 6mm BWP ply; all hot-pressed with Phenol Formaldehyde resin, internally lipped with hardwood beading, and pasted in Hydraulic Press under 50 tonnes pressure, spray quoted with 2 coats of enamel paint of minimum 300 micron. with prior approval of concerned Superitending Engineer.
First Floor
Second Floor
Providing and fixing solid core flush door shutter in double leaf 32 mm thick decorative type of exterior grade as per detailed drawings approved face veneers 3 mm thick on both faces or as directed, all necessary beads, mouldings and lipping, wrought iron hold fasts, chromium plated fixtures and fastenings, with brass mortise lock, chromium plated handles on both sides, and finishing with French Polish etc. complete.
First Floor
Second Floor
Providing and fixing solid core flush door shutter in single leaf 32 mm thick decorative type of exterior grade as per detailed drawings approved face veneers 3 mm thick on both faces or as directed, all necessary beads, mouldings and lipping, wrought iron hold fasts, chromium plated fixtures and fastenings, with brass mortise lock, chromium plated handles on both sides, and finishing with French Polish etc. complete.
First Floor
Second Floor
Providing and fixing mild steel grill gate as per the detailed drawing including hinges, locking arrangements and painting in three coats of oil paint of approved colour and shade etc. complete.(weight 18 Kilogram. to 20 Kilogram. Per Sq.m.) Spec.One Number: As directed by Engineer- in-charge.
First Floor
Second Floor
Providing and fixing 34 mm thick moulded door shutter consisting of solid core single leaf flush door of 30 mm thickness lipped with 15 mm ( 5mm x 3) thick x 30 mm width on one style and top rail and 10 mm (5mm x 2) thick x 30 mm width on other style and bottom rails. The inner panels laminated with 2 mm thick termite proof, water proof and fire resistant moulded PVC sheet with 2,4,6 design in different plain and /or prelim colours on one side after routing the moulded design on flush doors and 2 mm plain and /or pre lam PVC on other side using rubber adhesive on flush door and solvent cement adhesive on the PVC lipping etc. as per direction of Engineer in charge and manufacturers specification and drawing etc. complete.
First Floor
Second Floor
Solid Core Flush door Single leaf Providing and fixing factory made solid core flush door in single leaf 35 mm thick, decorative types, of exterior grade, as per detailed drawings, conforming to I.S.:2202 - 1962 (Revised) with approved face veneers on both faces with/without glazing and venetians in the positions shown on the drawings or as directed, all necessary beads, moulding and lipping, holdfasts, mat finish stainless steel fixtures fastenings , finishing with french-polish/ waxing complete. (without door frame).(Sample to be got approved from Ex.Engineer before use) Commercial Hard Wood shutter
Providing and fixing of factory made uPVC casement window / Fixed Window & Casement Door (White Colour) comprising uPVC multi-chambered frame, Sash, & Mullion with wall thickness of 2.3mm (+-0.2 mm ), duly reinforced with G.I. section 1.5 mm, wherever required. uPVC window & door profile shall be made in India & shall conform to BS EN 12608 and other standards as mentioned below: S.No. Name of the test Test Method Specified Parameter 1 Tensile Impact Strength ISO 8256 - more than 700Kj/m2 2 Vicat Softening Temperature EN ISO – 306 Shall not be < 750C 3 Charpy Impact Strength EN ISO – 179-2 Shall not be < 20KJ/m2 4 Flexural Modulus Elasticity EN ISO – 178 Shall not be < 2200 N/mm2 5 Mean Breaking Stress for welded corner (a) For the tensile bending test EN – 514 Shall not be < 25 N/mm2 (b) For the compression bending test Shall not be < 30N/mm2 6 Heat Reversion Test IS:4985-2000 Shall not be > 2.0 % 7 Surface Spread of flame BS : 476 - Part 7 Classification 1 8 Ignitability Evaluation BS : 476 - Part 5 'P' Not easily ignitable 9 Tensile modulus ASTM D 638 Shall not be < 35 MPa 10 Shear Modulus ASTM D 732 Shall not be < 220 MPa 11 Tensile Strength EN ISO 527 Shall not be < 30 MPa. All corners of frame and sash will be fusion welded. Mullion shall be welded / screwed. EPDM / TPE Gasket shall be provided in all frame, sash & mullion, wherever necessary.Thereafter, 5 mm Float Annealed glass shall be provided in the sash with the help of uPVC glazing bead and hardware, i.e., friction hinge & single point handle (in window) & 3D Hinges & Multipoint Lock (in door) shall be provided. Window / Door shall be fixed to the wall with 100mm long and 8mm dia. Fasteners and complete in all respect as per direction of Engineer-In-Charge. uPVC Window and Door Profiles are warranted for a period of ten (10) years against non-uniform discoloration, wrapping and rotting under general use. 3 Track 3 / 6 Sash (Big Series) window frame of size 122 x 54 mm & Sash of size 64 x 47 mm
Providing and fixing of factory made uPVC casement window / Fixed Window & Casement Door (White Colour) comprising uPVC multi-chambered frame, Sash, & Mullion with wall thickness of 2.3mm (+-0.2 mm ), duly reinforced with G.I. section 1.5 mm, wherever required. uPVC window & door profile shall be made in India & shall conform to BS EN 12608 and other standards as mentioned below: S.No. Name of the test Test Method Specified Parameter 1 Tensile Impact Strength ISO 8256 - more than 700Kj/m2 2 Vicat Softening Temperature EN ISO – 306 Shall not be < 750C 3 Charpy Impact Strength EN ISO – 179-2 Shall not be < 20KJ/m2 4 Flexural Modulus Elasticity EN ISO – 178 Shall not be < 2200 N/mm2 5 Mean Breaking Stress for welded corner (a) For the tensile bending test EN – 514 Shall not be < 25 N/mm2 (b) For the compression bending test Shall not be < 30N/mm2 6 Heat Reversion Test IS:4985-2000 Shall not be > 2.0 % 7 Surface Spread of flame BS : 476 - Part 7 Classification 1 8 Ignitability Evaluation BS : 476 - Part 5 'P' Not easily ignitable 9 Tensile modulus ASTM D 638 Shall not be < 35 MPa 10 Shear Modulus ASTM D 732 Shall not be < 220 MPa 11 Tensile Strength EN ISO 527 Shall not be < 30 MPa. All corners of frame and sash will be fusion welded. Mullion shall be welded / screwed. EPDM / TPE Gasket shall be provided in all frame, sash & mullion, wherever necessary.Thereafter, 5 mm Float Annealed glass shall be provided in the sash with the help of uPVC glazing bead and hardware, i.e., friction hinge & single point handle (in window) & 3D Hinges & Multipoint Lock (in door) shall be provided. Window / Door shall be fixed to the wall with 100mm long and 8mm dia. Fasteners and complete in all respect as per direction of Engineer-In-Charge. uPVC Window and Door Profiles are warranted for a period of ten (10) years against non-uniform discoloration, wrapping and rotting under general use. 3 Track with Mesh-2 Glass Sash + 1 Mesh Sash (Each sash shall be half of width of window) (Big Series) Window frame of size 122 x 5
First Floor
Second Floor
Providing and fixing in position powder coated aluminium louvered windows / ventilator of various sizes with powder coating as per detailed drawing and specifications including aluminium frames 80 x 38 mm x 1.22 mm box type, 5 mm thick sheet glass louvers, of approved quality etc. complete.
First Floor
Second Floor
Providing and fixing in position anodised (as per IS 1868/1982) Aluminium fixed staggered ( Z Type) Ventilator with aluminium rectangular pipe 63 mm x 38.10 mm x 1.22 mm at weight 0.650 Kilogram/One Running Metre, Aluminium angle of size 15 mm x 15 mm x 1 mm,aluminium channel of 9 mm sizes, S.S.mosquito net of 304 Grade,4 mm thick float glass per detailed drawing and as directed by Engineer in charge etc.complete.
First Floor
Second Floor
Providing and fixing in position after hoisting, precast 1:2 cement mortar reinforced jali 80 mm thick with 3 mm diameter mild steel bar reinforcement, of approved design on both sides, fixing in cement mortar 1:3 and curing etc .complete.
First Floor
Second Floor
Providing and Fixing mat finish stainless steel (of 302 grade ) railing with top pipe of 50 mm dia. and vertical pipe of 38 mm dia at 0.60 m c/c or as required and horizontal pipes of 25 mm dia in three rows, all pipes of 2 mm thick including buffing,fabricating fixtures and fastening including pipe base of appropriate diameter and ball base of 75 mm dia above newel post of 75 mm diameter etc. complete (Prior approval of sample and brand by Ex.Engineer is necessary before use)
First Floor
Second Floor
Supplying, assembling, lowering and fixing in vertical position in bore well, unplasticized PVC medium well-casing pipe of 150mm dia, conforming to IS:12818, including required hire and labour charges, fittings & accessories etc. all complete, for all depths, as per the direction of Engineer in charge.
Providing and fixing 45 cm wide mild steel ladder of 40mm x 6 mm mild steel flat stringers and steps of 18 mm dia. mild steel bar for water tank including fixing it in (1:2:4) M-15 cement concrete block 60cm x 30cm x 30cm and painting the ladder complete. (Anti Corossive Paint)
RWH - Recharge Pit Providing and constructing recharge pit of 2.0m deep and 1.0m dia of pre-cast RCC rings with 6.5" dia x 25m deep borewell at the floor of recharge pit including installation of combination of solid/perforated PVC casing pipe wrapped around with netlon mesh including 300mm thick sidefilling around outside of RCC rings (annular space) with 40mm size boulders including filling of recharge pit up to 0.5m depth with 25-75mm clean washed gravels from bottom up followed by 0.5m depth of 10-25mm of clean washed stones followed by 0.5m of washed river fine aggregate (natural sand/crushed sand VSI grade finely washed etc.) including netlon mesh between each gravel/fine aggregate (natural sand/crushed sand VSI grade finely washed etc.) media layer including covering with RCC slab, manhole frame & cover, PVC rungs, PVC end-caps, fittings etc. including arrangement for inlet & outlet pipe excavation & backfilling as shown in the drawing.The rate shall be inclusive of all labour, material, wastage, scaffolding, transportation, taxes, including all leads, lifts at all levels. All material should be of approved make. All works complete as per the drawing, technical specification and direction of the Engineer in charge.
Providing and installing bio digester unit based on DRDO technology made of fibre reinforced plastic (FRP) having composition and following technical specifications and including necessary pipe and accessories up to 3 meter length, excluding the necessary excavation for installing the bio digester. Percentage of fibre glass (glass content in fibre glass should be minimum 30%): -33.33% Percentage of polyester resin: - 66.67% Water absorption (as per ASTM):-0.30% Flammability as per ASTM Tensile strength:-115 MPA Specific Gravity at 25 degree centigrade 1.45 Izod impact strength:-65KJ/M2 Heat defection/distort temperature:-65deg C Corrosion resistance (Non Corrosive) fitted with Inlet pipe size rigid PVC: -100mm Outlet pipe size rigid PVC:-80mm Gas outlet rigid PVC with Valve: 20mm Bacteria immobilization PVC mattes (on all partition) With DRDO TOT licensee and latest batch certificate(month & year of supply) and capacity as below
Providing and applying impression 24 carrat Luxury paint of approved make & approved brand Emulsion paint to interior walls and ceilings of approved quality, colour and shade to new surface in two coats, including sub surface prparation by Acrylic putty and Acrylic primer coats including scaffolding, preparing the surface. etc. complete (Low VOC).
First Floor
Second Floor
Providing and applying Dazzly Texture paint of approved make & approved brand exterior Emulsion paint of approved quality, colour and shade to old and new surface in two coats, including exterior acrylic primer coat, scaffolding, preparing the surface etc. complete
First Floor
Second Floor
Providing and applying Texture plaster with finishing with texture material of approved make in 3 to 4 millimeter thickness on previously plastered surface, including Plaster Groove 6mm thickness or Tape Grooves 35 to 45 mm thickness or as required, in all position including preparing the surface, scaffolding etc. complete.
Providing and applying antipeel paint of approved make & approved brand exterior Emulsion paint of approved quality, colour and shade to old and new surface in two coats, including exterior acrylic primer coat, scaffolding, preparing the surface etc. complete (Heat Reflective Paint).
Waterproofing Treatment to new terrace by using Polymeric Cementitious Membrane as approved by Engineer in charge, followed by 112mm thick brick bat coba covered with 20 mm mortar finish. If there are cracks on the bare slab, open the crack in V Groove and fill it with ready to use repair polymer modified mortar based on special cements, aldehyde based polymers with thixotropy modifying agents. If there are lots of honeycombs and identified bad patches of concrete the same should be grouted as per the instructions of site incharge. (The grouting shall be paid separately). Clean the entire surface thoroughly and over this prepared surface, apply three coats of polymeric Cementitious waterproofing coating having a non-toxic, 2-(methoxycarbonyl)-1-propene-Butyl-2 propenoate (MPBP) based polymeric waterproofing solution as approved by Engineer in charge. Provide and lay 112 mm average thicknes of brick bat coba in cement mortar 1:5 over 12mm thick CM 1:3 bedding with one pouch of 330 grams of thorough blend of special cements, aldehyde based polymers, shrinkage compensating agents as approved by Engineer in charge per 50 Kg bag of cement and finishing with 20 mm thick cement plaster in cement mortar 1:3 by mixing one 330 grams pouch of above admixture per 50 Kg bag of cement, including all lead, lifts and laid to proper slope to drain off water entirely preparing bell mouth including watta, beveled or champhered portion at the junction of parapet and work up to a height of 300 mm or as directed and including finishing the top layer of waterproofing treatement with false marking of 30 cm x 30 cm or as directed, curing and covering the whole treatment. MPBP Polymeric Waterproofing Coating for Concrete and Masonry should have following minimum properties: (1) Elongation % (ASTM D412-2016): @ 100% (2) Tensile Strength N/mm2 (ASTM D412-2016): 3.3 (3) Specific Gravity: 1.02 ± 0.02 (4) Total Solids (ASTM D1644-2012): 43.98 (5) Hardness Shore A (ASTM D2240-2015): 82
Second Floor
Providing and Fixing Rollar Blinds AMI Make or approved make & shade of 38mm round Aluminium channel with Blackout fabric & telting with chain (Ball) system with all necessary fixtures and fitting etc. complete. (Sample to be final by Engineer In-charge prior execution of work)
First Floor
Second Floor
Kitchen Trolley Providing and Fixing stainless steel kitchen trolley of overall 26 " height and 22" depth,supported on aluminium pipes ,trolley basket made out of 5 mm stainless steel rod fitted on telescopic channel of size 1.5 " x 20 " x 22 " on both sides of trolley of 12 " or above size, panel having 40Kilogramload bearing capacity of trolley made out of 20 mm PUC coated plywood and colour combination as directed by E-I-C.Inner side of panel covered by white mica ,100 mm s.s. decorative handle.(The width and height of individual compartments shall be kept as directed by Engineer-in-charge)
First Floor
Supplying hard murum/ kankar at the road site, including conveying and stacking complete.
Spreading hard murum/ soft murrum/ gravel or kankar for side width complete
Compacting the hard murum side widths including laying in layers on each side with vibratory roller including artificial watering etc. complete.
Providing,aupplying,fabricating and fixing panel of aluminium composite panel cladding in approved shape made out of 4 mm thick ACP sheet material consisting of 3mm thick FR grade mineral core following NBC part IV Fire and life safety (having 2 hours fire resistance in accordance to ASTM E119-12 and BS476 part 6 and 7 class O) sandwitched between two aluminium sheets (each 0.5 mm thick of AA 5005/AA3105 grade) The aluminium composite panel cladding sheet shall be coil coated with kynar 500 based PVDF/Lumiflon based fluropolymer resin (having 70:30 ratio of PVDF and acrylic) coating of approved colour and sg=hade on top face and polymer (service) coating of bottom face as specified using stainless steel screws, nuts, bolts, washers, cleats ,weather silicon sealent,backer rods etc .overall weight of the ACP shall not be less than 7.5 Kilogram/ One Square Metre)
First Floor
Second Floor
Providing and fixing 6mm Toughned Glass panelling with ST series green reflective cool glass on frame aluminium section 70 mm X 53 mm For Green Building Concept and additional frame work for fixing aluminium frame etc. complete as directed by Engineer In-Charge
First Floor
Second Floor
Hyper Structure-Designing Supply,Fabrication and Erection of Tensile Fabric Shed with PVC/ Both Side PVDF coated Polyster Membrane of Serage Farrari make with 950 GSM, 100 % waterproof with 15 Years Warranty and Mehire Makewith 900 GSM F1 100 % waterproof with 15 yeras of warranty from Manufacturer, rates including design, supply Fabrication, Erection and Epoxy Paint and Primer
Providing the consultancy services for GRIHA/IGBC certification of the building, including all related expenses in achieving Green certification, including all taxes, excluding GST, including conducting all awareness programme during inspection till the receipt of the GRIHA/GBC certification and even during 2-year defect liability period; including the fees for training programme, excluding the fees for statuary requirement and GRIHA/IGBC certification fees which will be paid by P.W. Dept. and site visits paid by the consultant, including all related to the achievement of the GRIHA/IGBC certification, etc (Rate approved by SE PWC Nanded)
Providing and Fixing Double Skin type PUF for Modular OT insulated 40mm thick Air handling Unit (AHU) made out of 24G GI inside and outside powder coated sheet, comprising of mixing box, Pre filter section for fixing 10µ,5 filter including filters , 6-row cooling coil section , SS insulated drain tray with pipe connection, fan section with DIDW backward curved centrifugal fan belt driven by suitable non flame proof TEFC squirrel cage induction motor and complete with anti vibration mounts,5µ filter including filters, inlet and outlet connections complete with service doors and outlet and fresh air dampers. [30% Fresh Air & 70% re-circulatory). MOTOR- 5HP, KRUGER-BLOWER. NICOTRA , RDH400. ( AS PER NABH NORMS) 3500 CFM AHU CONSISITING :- MOTOR, BLOWER, COOLING COIL, FILTER TRAYS, FILTERS, DRAIN TANK, CANVAS, ALUMIUM CHANNELS, SUPPLY AND RETURN DAMPERS, FRESH AIR DAMPER AND PREVENTER INCLUDES INSTALLATION, CEMENT BASE, SHED) including all leads and lifts Etc. Complete and as Directed By Engineer In-Charge
Providing and Fixing , Testing & Commissioning for Modular OT of Air Cooled DX Type For Modular OT,Condensing unit of normal cooling capacity 5.5 TR fitted with scroll compressor , air cooled condenser and propeller axial gas with refrigerent gas and oil installation Testing and Commmissioning of the following sizes of seam less and Eddy Current Tested 16 Guage Hard Bdrawn Copper Insulated referigerent Piping shall be pressure tested at 550PSIG WITH NITROGEN. MAKE: BLUE STAR / DAIKIN / CARRIER. WARRANTY :- 1 YEAR FROM THE DATE OF INSTALLATION including all Leads and Lifts Etc. Complete and as Directed By Engineer In-Charge
Providing and Fixing DUCTING For Modular OT :- 24 G ALUMINIUM ducting with required clamps for connection to air purification unit, supporting accessories etc. All joints shall be sealed with silicon to maintain 0% leakage. (Return & Supply ducting will run above the ceiling pannels in the OT area) 24 G GI Ducting from 4 Corners of Modular O.T. till AHU placement Aluminium Insulation Foil for the above ducting with control Dampers including all Leads and Lifts Etc. Complete and as Directed By Engineer In-Charge
Providing and Fixing HEPA- FILTERS For Modular OT of planar ceiling system with Unconditional air flow . Plenum unit, Holding structure & Top Plenum are made of G.I. sheet 1.6 mm thick with Aluminium Extrusion frame and sealed gasket confirming to DIN 4799 standards for their Air distribution Systems with HEPA filters HAVINF Efficiency 99.97 % Down to 0.3 MICRON. Laminar flow systems shall have such designs that it provides STYPE HEPA FILTER MODULES ,including all Leads and Lifts Etc. Complete and as Directed By Engineer In-Charge
Providing and Fixing 50mm Thick Modular SS-304 Ceiling Panels for Modular OT With PUF with 40 density Insulated 0.8 mm SS-304 plain Sheet on one side and 0.6 mm GI sheet on the other side , vertical and horizontal joints shall be sealed with silicon sealant ,including all Leads and Lifts Etc. Complete and as Directed By Engineer In-Charge
Providing and Fixing SS-304 WALL PANNELS Modular OT :- 50mm Thick Modular SS WALL Panels With PUF with 40 density Insulated 0.8 mm SS-304 plain Sheet on one side and 0.6 mm GI sheet on the other side, vertical and horizontal joints shall be sealed with silicon sealant ,including Intallation with all Leads and Lifts Etc. Complete and as Directed By Engineer In-Charge
Providing and Fixing SS-304 SCIENTIFIC DOOR :- Double Leaf Modular SS-304 door. With honeycomb insulated between the panels, stainless steel hardware i.e:- door closer, door lock, door caps, door handle, push plates, tower bolt and required size view glass and finished with silicon sealant to avoid sharp edges of glass . SS-304 Scientific Door Size:-1.5 m X 2.1 m 1500 MM X 2100MM X 100 MM ( Equal door or Unequal Door) including all Leads and Lifts Etc. Complete and as Directed By Engineer In-Charge
Providing and Fixing Coaving for Modular OT :- Wall to ceiling and wall to flooring coaving made of alluminium profiles with SS powder coating shall be used to avoid sharp corners. 3D, 2D Corners & D section profiles , C Channels, Z Profiles & L- Angles will be used including all Leads and Lifts Etc. Complete and as Directed By Engineer In-Charge
Providing and Fixing EPOXY / PVC VYNYL FLOORING in Modular OT :- Flooring: self-level epoxy flooring on existing Floor by 2mm base screed & 1mm Epoxy Or Imported PVC/VINAYL with 2mm thickness . EPOXY WILL BE 3 MM THICK, VYNYL WILL BE 2 MM THICK including all Leads and Lifts Etc. Complete and as Directed By Engineer In-Charge
Providing and Fixing SCIENTIFIC WIPRO DAY LIGHTS for Modular OT :- • Includes: Slim Panel Light • Wattage: 40 watts • Warranty: 2 years on product from date of invoice • LM 80 tested LED technology • Soft glare free light with LGP optics • Withstand wide voltage range 100-277V AC • Driver with surge and short circuit protection • SIZE:- 0.6 m X 0.6 m 6 LIGHTS IN O.T including all Leads and Lifts Etc. Complete and as Directed By Engineer In-Charge
Providing and Fixing VFD CONTROL for Modular OT :- VFD stands for Variable Frequency Drive used for controlling the speed of an AC motor also used for ramping up a motor for a smooth startup, or to prevent a heavy load from straining the motor on startup. ... VFDs allow the operator to control the flow of the pump manually or automatically with a PLC including all Leads and Lifts Etc. Complete and as Directed By Engineer In-Charge
Providing and Fixing O.T LIGHT for Modular OT:- Intensity 1,30,000 Lux ±10% Size of Light Field 12-30 cm Colour Temperature 4000-5000 K Colour Reduction Index 93 RA LED Life >50000 Hrs. Number of LED 84 Diameter of Light 600mm Brightness Control Capacitive Touch Panel Power Supply 220V/50Hz AC Colour of LED White & Yellow (Double Colour) including all Leads and Lifts Etc. Complete and as Directed By Engineer In-Charge
Providing and Fixing WRITING BOARD for Modular OT :- 5 FEET X 2 FEET White Writing Board . It shall be concealded into the panels. Joints shall be covered with Silicon sealent including all Leads and Lifts Etc. Complete and as Directed By Engineer In-Charge
Providing and Fixing DOUBLE FILM X-RAY BOX for Modular OT:- • Viewing Area (Inch) : 28 x 17, External Dimension (mm) : 866 x 512 x 45 • Color Temperature : 7000K, Light Source : LED, Brightness: 15,000 LUX • Lamp Life Approx. : 100,000 Hours, Power : AC 100-270 V (47-53 HZ) • Power Supply: 80 W, Available for desk and wall mounting, effective use of space including all Leads and Lifts Etc. Complete and as Directed By Engineer In-Charge
Providing and Fixing ELECTRICAL WORKS for Modular OT :- Wiring for Entire O.T. WITH 10 NO’S 6 MODULE BOARDS and 1 NO 12 MODULE BOARD . Wiring of ceiling for 2 Ft. X 2 Ft. LIGHTS and Centre O.T. Lights. Wiring from Main Panel Board to Control Panel Board placed at O.T.and Armour Cable run through the same panel Board to the AHU . 1.5 Sq.mm wire shall be used for internally in OT 4 Sq.mm Armour cable will be used for AHU TO Control Pannel. with providing 10 nos. of 6 Module and 1 no. of 12 Module Board including all Labour Work with all Leads and Lifts Etc. Complete and as Directed By Engineer In-Charge
Providing and Fixing GAS PIPE LINE WORKS for Modular OT:- Supply Installation Testing and Commissioning of COPPER PIPE LINE OF 28 mm Dia size for Distribution of O2, Vaccume and Medical gas to OT room.After Installtion Pipe shall be Pinted with synthetic Enamel Paint with Colour Code. Pipe line shall be connected to nearest point existing besides the O.T. They will be pressure tested for 1 day to check if any leaks in the pipes. 1’’Copper Pipe lines are used at @ 30 Nos. Gas Outlets@ 8 NO’S Comissinning , Breezing, Paint, Pressure Test ETC including all Leads and Lifts Etc. Complete and as Directed By Engineer In-Charge
Providing and Fixing SS304 SS Scrub Rectangular in Shape Polished Finishing SS 304 Material Grade Wall Mounted including all leads and Lifts Etc. Complete and as Directed by Engineer In-Charge
COMPREHENSIVE TYPE ANNUAL MAINTENANCE CONTRACT FOR PERIOD OF Three YEAR THE CONTRACT SHALL START AFTER THE COMPLETION OF DEFECT LIABILITY PERIOD OF ONE YEARS. The contract shall be of comprehensive type complete with all required tools tackles, equipments, spares, all consumables including with refrigerent gas and oil to operate & maintain the ac plant in most efficient & trouble free manner. The contarct shall cover all reqd. Quarterly & yealry preventive maintenanace schedlues. The contract shall also cover attending all break down calls within 12 hours & Rectifying the problem within 24 hours with Fittings and refittings including all Lead and Lifts and as Directed by Engineer In-Charge
Third Year
Executive's Table @ 1800Lx900Dx750HT Providing & Fixing of Table @ 1800Lx900Dx750HT - TOP & GABLE END to be made of Membrane finish with soft water fall edges & curved panel & Decorated Anodized section MODESTY PANEL to be made of 18 mm thick Prelaminated particle board with PVC edge band as per drawing
First Floor
Second Floor
Pedestal Unit @ 420Lx450Dx650HT Providing & Fixing of PEDESTAL @ 420Lx450Dx650HT :- To be made out of Complete Membrane consist of three Drawers as per drawing.
First Floor
Second Floor
Credestal @ 1200Lx450Lx650HT Providing & Fixing of LOW HEIGHT CREDESTAL @ 1200L X 450D X 650H :- To be made out of Membrane Finish ( 2 Openable Shutter & 3 Drawer Pedestal in between )as per drawing.
First Floor
Second Floor
Executive Table @ 2250Lx2100Dx750HT including Low Height Credestal @ 1200Lx450Dx650HT Providing & Fixing of Table @ 2250Lx2100Dx750HT TOP & GABLE END to be made of Membrane finish with soft water fall edges & curved panel & Decorated Anodized section MODESTY PANEL to be made of 18 mm thick Prelaminated particle board with PVC edge band. INCLUDING CREDESTAL @ 1200L X 450D X 650H :- To be made out of Membrane Finish ( 2 Openable Shutter & 3 Drawer Pedestal in between ) as per drawing.
First Floor
Second Floor
12 Seater Reading Table for Library @ 3600Lx1200Dx750HT Providing and Fixing 12 Seater Reading Table for Liberary @ 3600Lx1200Dx750HT Top: made from 25 mm Prelaminated Particle board. All edges are covered by 2 mm. Thk. PVC edge bands glued by hot melt glue applied by auto edge banding machine. Gable Ends : made from 25 mm Prelaminated Particle board. All edges are covered by 2 mm. Thk. PVC edge bands glued by hot melt glue applied by auto edge banding machine. Modesty panel : Made from 18mm both side prelaminated particle boards.All edges are covered by 0.8mm PVC edge bands glued by hot melt glue applied by auto edge banding machine.
Second Floor
Book Case with Glass Shutter @ 825Lx300Dx1650HT Providing & Fixing of Book Case with Glass Shutter @ 825Lx300Dx1650HT:- To be made out of complete body & in 0.7mm thick CRCA & Shutter in 1.2mm thick CRCA with glass pannel in Powder coating finish as per drawing.
First Floor
Second Floor
Providing & Arrangemnt of High Back, Synchronized Mechanism with Multiple Locking, Adjustable Armrest, Gaslift for Seat height adjustment, Standard 5-prong P/Nylon Base with Leatherite Upholstery
First Floor
Second Floor
Providing & Arrangemnt of MId Back, Normal Syncro Mechanism , Fixed Armrest , Gaslift for Seat height adjustment, Standard 5-prong/Nylon Base with Leather Upholstery
First Floor
Second Floor
Public Seating Chair. - 3 Seater Providing and Fixing 3 seater Public seating chair made of complete metal with Legs in Crome finish and seates in silver powder coating finish.
First Floor
Second Floor
Double Faced Mobile Unit for Compactor 2150mmH x 2745mmW x 900mmD Providing and fixing Double Faced Mobile Unit for Compactor 2150mmH x 2745mmW x 900mmD - BASE FRAME : Base Frame shall be fabricated in channel Type from minimum 2.5 mm thick MS Sheet Size of Channel 25mm x 100mm x 45mm. GUIDE RAILS : The guide rails shall be made out of 28mm Bright bar placed on 1.2 mm thick M.S. Plate which will be above the floor and are as per the international standard of safety. SUPER STRUCTURE : Super structure of the Mobile storage system will consist of knock down type panels. All the components such as shelves, front panel, end panel, vertical rear panel, central partition etc. Will act as an integral member of the Unit. SHELVES : Shelves made of 22SWG thick Prime Quality C.R.C.A. having 10 folds each will be provided each designed to carry a U.D.L. of 70 Kilograms. VERTICAL PANEL : Vertical panel consists of the front, Centre & rear panel shall be made out of 20SWG thick C.R.C.A. Prime quality Mild Steel & designed to take the load of shelves. DRIVE COVER PANEL : Made out of 22SWG thick C. R.C. A. prime quality Steel to cover the entire drive mechanism. CENTRE PARTITION : The Centre partition will comprise of a full C.R.C.A. prime quality Mild Steel 22SWG Sheet. LOCKING : System will be provided with individual rack locking as well as centralised locking arrangement on the last unit when all units are brought together, central lock when operated gets locked with the floor & does not allow access to the units. DRIVE MECHANISM : Driving Mechanism will be provided externally supported on special grade anti-friction bearing to have smooth & effortless movement. Entire mechanism or gear & sprockets shall be incorporated within the front panel provided in the front of the unit within an area of 1000mm x 200mm x 60mm. DRIVING WHEEL : Fully Powder Coated three pronged drive wheel for better torque & free movement of the rack over the guide rail. INDEXING ARRANGEMENT : Acrylic card holders provided on the front panel for easy identification & retrieval. FINAL FINISH : Powder Coating (8 tanks process with 70 microns).
First Floor
Second Floor
Sofa Set 3+1+1 Providing & fixing Sofa Set 3+1+1 Brown and Cream leather DIMENSION Length: 182.5 (cms) Breadth (cms): 100 (cms)Height (cms): 100 (cms) Weight (Kilograms): 66 (Kilogram) Seating Capacity: Five Seat
First Floor
Second Floor
Tea Table 900mm X 750mm X 450mm for m.s. ante chamber Providing And Fixing Of Tea Table 900mm X 750mm X 450mm With 12mm Thick Colour Eitched Tempered Glass With Bevelled Drawing Made Out Of 18mm Thick Waterproofing Ply. The Outer Laces To Be Finished With High Quality 4 Mm Thik Veneer Or 1 Mm Thik Mica Etc.
First Floor
Second Floor
Single Bed @ 2025LX 1000DX 650H Providing and fixing Single Bed of Size 2025Lx1000Dx650H with matress and pillow. Understructure: - The legs are made of Square tube of size 25 x 25mm made out of MS with a thickness of 1.2 mm. The legs should have corner brackets welded to it at two levels. The corner brackets are made of 2mm thick CRCA having a L shaped structure to join the side panels and headboard to the leg. Three nos. of Horizontal stiffeners are provided at equal intervals. The stiffeners are made of Square tube of size 25 x 25mm made out of MS with a thickness of 1.2mm. The middle Horizontal Stiffener has a leg attached to it to transfer the load to the ground and add to the strength and stability of the complete structure. This leg is also made of Square tube of size 25 x 25mm made out of MS with a thickness of 1.2mm. All Metal components to undergo 7 tank treatment process and should be powder coated to the thickness of minimum 50 Microns DFT.Side Panel: - The side panels are made up of 18mm thick Prelam Particle Board with both side decorative laminate. All exposed edges are sealed with 2mm thick PVC edge Banding. The overall width of the side panel is 150mm. The side panels have 18mm thick prelam particle board Baton running for required length to add rigidity to the structure. Head Board :- The head board is made up of 18mm thick Prelam Particle Board with both side decorative laminate. All exposed edges are sealed with 2mm thick PVC edge Banding. The head board size to be considered as 1000 x 650mm. Foot Board :- The foot board is made up of 18mm thick Prelam Particle Board with both side decorative laminate. All exposed edges are sealed with 2mm thick PVC edge Banding. The head board size to be considered as 1000 x 450mm. Bed Base: - The Bed Base is made up of 12mm thick Prelam Particle Board with both side White laminate.
First Floor
Second Floor
Full Height Steel Storage @ 750Lx450Dx2100HT Providing and fixing Openable Steel Storage of 750 x 450 x 2100Ht, with 4 adjustable shelves, Complete body & shutter made in 0.8 mm thick & Top in 2 mm thick CRCA, 4 Shutter to be mounted with the help of cup hinges, and 4 adjustable levelers, enitre storage in powder coated finish with 60 to 80 microns as as per drawing.
First Floor
Second Floor
First Floor
Excavation for roadway in earth, soil of all sorts, sand, gravel or soft murum including dressing section to the required grade, camber and side slopes and conveying the excavated materials with all lifts upto a lead of 50m. and spreading for embankment or stacking as directed.
Wet Mix Macadam -- Providing, laying, spreading and compacting graded stone aggregate to wet mix macadam specification including premixing the Material with water at OMC in mechanical mix plant carriage of mixed Material by tipper to site, laying in uniform layers with paver in sub- base / base course on well prepared surface and compacting with vibratory roller to achieve the desired density. Laying By Grader/Paver.
Construction of dry lean cement concrete Sub- base over a prepared sub-grade with coarse and fine aggregate ( natural sand/ VSI grade finely washed crushed sand) conforming to IS: 383, the size of coarse aggregate not exceeding 25 mm, , cement content not to be less than 150 kg/ cum, optimum moisture content to be determined during trial length construction, concrete strength not to be less than 10 Mpa at 7 days, mixed in a batching plant/ Weigh batch mixer, transported to site with all leads and lifts, laid with a paver with electronic sensor /by suitable means as approved by Engineer-in-charge , compacting with vibratory roller, finishing, curing and including preparation of sub-grade surface if required etc. complete. with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete.
Providing and laying in situ cement concrete M -30 with tremix treatment for 200 mm thickness for Concrete Road is including laying plastic sheet for 125 micron thickness with groove cutting of 4 mm wide and 20 mm deep with necessary refilling with polysuphide sealent (Pouring grade) confirming to BS : 5212 - 1989 into sawed groove widened at top for sealent reservoir of specified size and shape as per detailed drawing including fixing Polyethylene foam backer rod of required diameter ( excluding reinforcement) with coarsen and fine aggregate Using V.S.I.Quality Artifitial Sand etc. complete with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete.
Providing and fixing in position TMT FE 500, tie bars precoated with anticorrosive epoxy paint of 12 mm dia. 70 cms.long and at 30.00 cm. C/C and wherever directed including handling, straightening wrapping with paper of approved quality for half length, necessary cutting, handling, straightening , supported by assembly of TMT FE 500, chairs with proper alignment etc. complete.
Providing and fixing in position TMT FE 500, 25mm dia dowel bars precoated with anticorrosive epoxy paint of required Dia. 60 cms. Long and at 30.00 cm. C/C and wherever directed including handling, straightening, necessary cutting supported by TMT FE 500, chairs with proper alignment by using properly designed assembly of Bulkheads lubricating half length with bituminous paint as directed etc. complete.
Providing and Laying hot applied thermoplastic road marking strip on Bituminous Surface of specified shade/ colour of 2.5 mm thick including 1.5 Refractive index reflectorizing glass beads @ 250gm/sqm .Thickness of 2.5 mm is exclusive of surface applied glass beads as per IRC 35:2015. Initial Dry reflectivity RL shall be > 250 mcd/sqm/lux measured in the initial 7 days and sustained reflectivity RL of 100 mcd/sqm/ lux and Qd of 100 mcd/sqm/ lux measured at the end of 2 years by means of a Standard Reflectometer of Zehntner, Easylux, Delta make capable of measuring RL & QD both according to IRC 35:2015 clause 15.5. The finished surface to be level, uniform, and free from streaks and holes complete as per direction of Engineer-in-charge and in accordance with applicable specifications.(Refer MORTH Clause 803 for technical Specification and Performance for IRC 35:2015).
Supplying and Fixing of Molded Shank Raised Pavement Markers / Cat's Eye made of polycarbonate and ABS moulded body and reflective panels with micro prismatic lens capable of providing total internal reflection of the light entering the lens face and shall support a load of 16000 kg tested in accordance to ASTM D 4280 Type H and complying to Specifications of Category A of MORTH Circular No RW/NH/33023/10-97 DO III Dt 11.06. 1997. The height, width and length shall not exceed 50 mm, 100 mm and 102 +/- 2 mm and with minimum reflective area of 13 Sqcm on each side and the slope to the base shall be 35 +/- 5 degree. The strength of detachment of the integrated cylindrical shanks, (of diameter not less than 19 +/- 2 mm and height not less than 30+/- 2 mm) from the body is to be a minimum value of 500 Kg. Fixing will be by drilling holes on the road for the shanks to go inside, without nails and using epoxy resin based adhesive as per manufacturer's recommendation and complete as directed by the engineer.The contractor shall submit a two year warranty for satisfactory field performance including stipulated retro-reflectance of the reflecting panel, to the Engineer.
Fixing in position Road Junction/ Informatory Sign Board in ground with C.C.1:4:8 block of 60cm x 60cm x 75cm size including all leads complete.
Providing and fixing Mandatory/Regulatory sign boards in circular shape of ___mm dia made out of ____mm aluminum sheet bonded with white retro reflective sheeting of Class C ( Type XI Micro prismatic grade sheeting) having pressure sensitive/heat activated adhesive retoreflective specified back ground, border and back side retoreflctive symbols, letters, numerals, arrow as per IRC:67-2012 Table No 8.3 Supported with back support frame 25mm x 25mm x 3mm, duly painted on back side with grey stove enamel paint and supported on one no. of M. S. angle iron post of size 65 mm X 65 mm X 6 mm, 3.45 m long, duly painted with with flat oil paint having alternate black and white bands of 25 cm width including G.I. fixtures etc; fixing the boards in M25 grade concrete block of size 60cm X 60cm X 75cm including transportation etc; complete. Class C ( Type XI Micro prismatic grade sheeting) shall have 10 years written warranty from the manufacturer and authorised distributor/convertor issued for field performance including the screen printed areas and cut-out sheeting and cut-out durable transparent overlay film and this warranty certificate in original should be submitted to the Engineer in charge by the contractor/supplier. 600 mm dia made out of 1.5mm aluminum sheet
Providing cast in situ / ready mix M20 grade cement concrete for head walls of CD work / retaining walls etc. including necessary form work, compaction, finishing and curing etc. complete. (with reversible drum type mixer/ concrete batch mix plant (pan mixer) with SCADA
Providing and laying Cast in situ/Ready Mix cement concrete M-20 of trap/ granite / quartzite/ gneiss metal for R.C.C. slabs and landings as per detailed designs and drawings including steel centering, formwork, cover blocks, laying/pumping, compaction finishing the formed surfaces with cement mortar 1:3 of sufficient minimum thickness to give a smooth and even surface or roughening if special finish is to be provided and curing etc. complete,(Excluding reinforcement and structural steel).with fully automatic micro processor based PLC with SCADA enabled reversible Drum Type mixer/ concrete Batch mix plant (Pan mixer) etc. complete. With fine aggregate (Crushed sand VSI Grade)
Providing and laying weep holes of 100 mm diameter PVC pipes as per drawing for abutment returns, return walls etc. Complete.
Providing and casting in situ or precast tapering R.C.C. M-20 Barrier type Kerb without gutter ( as per IRC 86 1983) embedded 125mm below ground level over M-10 PCC finished neatly with C.M. 1:2, setting the same in C.M. 1:2, including the required excavation in any strata and removing the excavated stuff any where in city and redoing the surface as specified and directed by Engineering In-charge. Using Concrete Batching and Mixing Plant
Design, supply, fabrication & erection tensile dome structure included supply of MS Structure with fabric with white colour translucent tensile polyester fabric of Serge Ferrari Cloth Type-702, 750 gsm both side coated with PVDF coating lacquer system on both sides, titanium dioxide front side primer, low-wick, protected against microbial and fungal attack, UV-protected top coat of membrane type - 2 grade of required colour and shape and design including necessary accessories. Structure will be painted with one coat of primer and two coats of enamel paint including all leads and lifts and as directed by engineer in-charge, excluding GST. (Fabric has manufacturers Warrenty of 15 Years - Warrenty certificate shall be provided).
Supplying and erecting 25 mm dia. corrugated flexible polypropylene conduit
Supplying and erecting HMS PVC conduit FRLS grade 25 mm dia. with necessary accessories in wall/floor with chiselling appropriately
Supplying and laying HMS PVC conduit FRLS grade 25 mm dia with necessary accessories in RCC work/false ceiling/false flooring
Supplying and erecting HMS PVC conduit FRLS grade 32 mm dia. with necessary accessories in wall/floor with chiselling appropriately
Supplying and laying HMS PVC conduit FRLS grade 32mm dia. with necessary accessories in RCC work/false ceiling/false flooring
Supplying and erecting PVC trunking (PVC casing-n-capping) of size 25 mm with accessories on wall/ceiling as per specification No: WG-MA/CON.
Supplying and erecting mains with 2x1.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places
Supplying and erecting mains with 1x1.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places
Supplying and erecting mains with 2x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW
Supplying and erecting mains with 1x2.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places.
Supplying and erecting mains with 2x4 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW
Supplying and erecting mains with 1x4 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW
Supplying and erecting mains with 2x6 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW
Supplying and erecting mains with 1x6 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW
Supplying and erecting mains with 4x4 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW
Supplying and erecting mains with 4x6 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places. as per specification No: WG-MA/BW
Supplying and erecting modular type switch 6A / 10A duly erected on provided plate and box with wiring connections complete.
Supplying and erecting modular type switch 16A duly erected on provided plate and box with wiring connections complete.
Supplying and erecting modular type 3 pin 6A multi socket with safety shutter, duly erected on provided plate and box with wiring connections complete.
Supplying and erecting modular type 3 pin 6 / 16A multi socket with safety shutter, duly erected on provided plate and box with wiring connections complete.
Supplying and erecting modular type telephone socket one gang with safety shutter, duly erected on provided plate and box with wiring connections complete.
Supplying and erecting modular type (two module) electronic step regulator for fan, duly erected on provided plate and box with wiring connections complete.
Supplying and erecting modular type blanking plate one module, duly erected on provided plate & box.
Supplying and erecting PVC Surface modular switch box with double mounting plate for 2 module duly erected.
Supplying and erecting PVC Surface modular switch box with double mounting plate for 3 module duly erected.
Supplying and erecting PVC Surface modular switch box with double mounting plate for 6 module duly erected.
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 1 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background.
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 2 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background.
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 3 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background.
Supplying and erecting unbreakable concealed type modular switch box with double mounting plate for 12 module duly erected flush to wall with required chiselling and finishing with cement mortar / POP as per required to match the background.
Supplying and erecting 16 / 20 / 25 A starter (modular range) 2 module for AC unit on provided box complete & duly concealed with necessary material and connected.
Point wiring for light/bell concealed type in min 20 mm FRLS grade HMS PVC conduit with 1.5 sq.mm. (2+1E) FRLSH grade copper wires, modular type switch, earthing and required accessories as per specification No: WG-PW/CW
Point wiring for ceiling fan concealed type in min 20 mm FRLS grade HMS PVC conduit with 1.5 sq.mm. (2+1E) FRLSH grade copper wires, modular type switch, earthing and required accessories as per specification No: WG-PW/CW
Point wiring for light/bell hybrid type (Surface type under false ceiling and concealed type for drops & switch boards on walls) in min 20 mm PVC conduit / casing n capping with 1.5 sq.mm. (2+1E) FRLSH grade copper wires, modular type switch, earthing and required accessories as per specification No: WG-PW/HW
Point wiring for ceiling fan (Surface type under false ceiling and concealed type for drops & switch boards on walls) in min 20 mm PVC conduit / casing n capping with 1.5 sq.mm. (2+1E) FRLSH grade copper wires, modular type switch, earthing and required accessories as per specification No: WG-PW/HW
Wiring for plug on board with Switch socket surface/concealed type, copper wiring and earthing and with modular accessories as per specification No: WG-PW/CW
Point wiring for light/bell/exhaust fan in PVC trunking (casing-capping) with 1.5 sq.mm (2+1E) FRLSH grade copper wire, modular type switch, earthing and required accessories as per specification No: WG-PW/SW
Supplying & erecting 2 pair telephone copper cable 0.5 mm dia. with high density polyethylene insulation, polyester taped, Nylon Rip Cord & grey colour sheathed with FR PVC, conforming to ITD specification S/WS 113C laid in provided PVC casing capping/conduit as per specification No. WG-TW
Supplying and installing cat-6 cable suitable for networking as per specification no. WG-COC/NC
Supplying and erecting LED square / circular Max. 18 W down lighter/ Panel Light having pressure die-cast aluminium housing, polystyrene diffuser having system lumens output of Min. 2000 Lumens, min. efficacy of 110 lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg., max. ripple of 5%, THD<10%, p.f. >0.95, operating range of 120-270V, surge protection of 2.5 kV, Life class of 50,000 Hrs. at L70B50, including driver, having mounting arrangement with board for surface type or spring loaded mounting clips complete with 3 years warranty.
Supplying and erecting LED Panel Light(600mm X 600mm) Max. 30 W having CRCA powder coated housing, polystyrene diffuser having system lumens output of Min. 3600 Lumens, min. efficacy of 120 lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg., max. ripple of 5%, THD<10%, p.f. >0.95, operating range of 120-270V, surge protection of 2.5 kV, Life class of 50,000 Hrs. at L70B50 including driver, having mounting arrangement with board for surface type or spring loaded mounting clips complete with 3 years warranty.
Supplying and erecting CRCA powder coated corridor/passage light LED fitting (4 feet) Max. 17W with high transitivity diffuser with system lumens output of Min. 2000 lumens , min. efficacy of 120 lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg., Ripple<5%, THD<10%, p.f. >0.95, operating range of 120-270V, surge protection of 4 kV, Life class of 50,000 Hrs. at L70B50, including driver, with end caps on provided PVC Block / wooden board with 3 years warranty.
Supplying and erecting ding dong / electronic musical type call bell with heavy duty coil suitable to operate on 230V A.C. supply erected on polished double wooden block/sunmica block of suitable size.
Supplying and erecting integrated LED street light fitting 40 to 50W IP65 & IK08 class having single piece pressure die-cast aluminium housing, having system lumens output of Min. 4400 Lumens, min. efficacy of 110 lumen/W, CRI>70, CCT upto 6500K,THD<10%, p.f. >0.95, operating range of 140-270V, inbuilt surge protection of 10 kV, Life class of 50,000 Hrs. at L70B50, including driver complete with 3 Years warranty as per specification No FG-ODF/FLS2.
Supplying and erecting street light Wall bracket made from 25 mm. dia ‘ G.I. pipe 1.2 m. in total length complete as per specification no. FG-BKT/WB
Supplying & erecting 5W-7W, 230V integral type LED Lamp suitable for B-22 / E-27 base.
Supplying and erecting anodized aluminium corridor / passage / mirror light LED fitting (2 feet) Max. 12W with high transitivity diffuser with min. system lumens output of 1200 lumens, min. efficacy of 100 lumen/W, CRI>80, CCT upto 6000K, Beam Angle of 110 deg., Ripple<5%, THD<10%, p.f. >0.95, operating range of 200-270V, surge protection of 2 kV, Life class of 50,000 Hrs. at L70B50, including driver with end caps on provided PVC Block / wooden board with 3 years warranty.
Supplying and erecting fresh air cum exhaust fan of light duty 250 V A.C. 50 cycles 225mm. 1400 RPM rust proof body & blades, wire mesh, duly erected, complete.
Supplying and erecting Energy Saving BLDC Ceiling fan 230 V A.C. 50 cycles 1200 mm, max. energy consumption of 28W having service ratio (CMM/W) of Min. 8 , PF>0.9, THD<10% without IR remote control/compatible speed regulator, Temperature Rise of Max. 40 deg. C, having external mounted control PCB completely erected in position as per specification no. FG-FN/CF
Supplying and erecting fan hook box of 10 mm M.S. round bar bounded to the R.C.C. bars upto 50 mm length each side and pierced through a 16 S.W.G. thick aluminium/M.S. Bowl 100 mm dia. or equivalent square size and having depth upto 75 mm complete erected with duly painted by one coat of red oxide paint and two coats of paint erected in position and without any leakage of slurry of cement concrete on either side of the box and positioned to the bottom level of the slab.
Supplying and erecting ‘B’ class G.I .pipe / M.S. pipe down rod duly painted for fan complete erected with PVC three core flexible cable 1 sq. mm copper PVC wire.
Supplying, erecting & marking SPMCB 6A to 32A, C-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB
Supplying, erecting & marking SPMCB 6A to 32A, B-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB
Supplying, erecting & marking TPMCB 6A to 32A, with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB
Supplying, erecting & marking TPMCB 40A to 63A, with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB
Supplying & erecting triple pole and neutral distribution board (TPNDB), SPMCB of 4 ways/phase (12 poles), with door, 1.2mm thickness, surface/flush mounted, IP 43 protection on iron/GI frame (horizontal busbar type)
Supplying & erecting triple pole and neutral distribution board (TPNDB), SP/TP MCBs total 4 ways /12 Poles, with door, 1.2mm thickness surface/flush mounted, IP 43 Protection on iron/GI frame (vertical busbar type)
Supplying & erecting triple pole and neutral distribution board (TPNDB), 3 pole/4 pole MCCB as incomer & outgoing SP MCB (24 poles) or TP MCB of 8 ways (24 poles), with door, 1.2mm thickness, surface/flush mounted, on iron/GI frame (vertical busbar type) as per specification no. SW-SWR/MCBDB1
Providing & erecting 4 Pole MCCB, 415 V, 100A, rated short-circuit breaking capacity 25 kA (Ics=100% of Icu), adjustable thermal (overload) setting and fixed magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact. MCCB with phase barriers on both sides, insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB
Providing & erecting 4 Pole MCCB 415V, 250A, rated short-circuit breaking capacity 36 kA (Ics=100% of Icu) adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact and MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB
Providing & erecting 3 Pole MCCB, 415 V, 100A, rated short-circuit breaking capacity 25 kA (Ics=100% of Icu), adjustable thermal (overload) setting and fixed magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact. MCCB with phase barriers on both sides, insulation withstand capacity 800V, no line-load bias in provided enclosure/panel
Providing & erecting 4 Pole MCCB 415V, 400A, rated short-circuit breaking capacity 36 kA (Ics=100% of Icu), adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/ UV/ trip alarm contact and MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure /panel as per specification no. SW-SWR/MCCB
Providing & erecting 4 Pole MCCB 415V, 630A, rated short-circuit breaking capacity 36 kA (Ics=100% of Icu), adjustable thermal (overload) setting and adjustable magnetic setting with provided leads, provision for installation of shunt/UV/trip alarm contact and MCCB should have phase barriers both sides, with insulation withstand capacity 800V, no line-load bias in provided enclosure/panel as per specification no. SW-SWR/MCCB
Supplying, erecting & commissioning 4 pole RCCB 40A, electromagnetic type with 30/100/300 mA sensitivity with earth leakage trip indication complete as per specification no. SW-RCCB/RCCB
Supplying, erecting & commissioning 4 pole RCCB 63A, electromagnetic type with 30/100/300 mA sensitivity with earth leakage trip indication complete as per specification no. SW-RCCB/RCCB
Providing & erecting floor/wall mounting, MCCB panel board, with door, suitable for four pole incoming 250A, 8 ways Four pole outgoing, up to 100 A MCCBs on iron frame, as per specification no SW-SWR/MCCBPB. (Excluding MCCBs)
Providing & erecting floor/wall mounting, MCCB panel board, with door, suitable for four pole incoming 400A, 8 ways four pole outgoing, up to 100 A MCCBs on iron frame, as per specification no. SW-SWR/MCCBPB. (Excluding MCCBs)
Providing & erecting incoming and outgoing cable alleys suitable for MCCB panel board with door, 250A incoming and 8 way outgoing or 400A incoming and 6 way outgoing made from CRCA sheet 1.6 mm thick duly powder coated and having vertical insulated partition for shielding between the shared face of cableway and DB.
Providing & erecting incoming and outgoing cable alleys suitable for MCCB panel board with door, 250A incoming and 12 way outgoing or 400A incoming and 6/8 way outgoing made from CRCA sheet 1.6 mm thick duly powder coated and having vertical insulated partition for shielding between the shared face of cableway and DB.
Providing & erecting prewired meter module suitable for MCCB panel board with CTs and emfs VIF meter.
Supplying and erecting SS enclosure for MCCB suitable for up to 100A MCCB.
Supplying and erecting metal work in CRCA sheet including Iron work for supports with fabrication of boxes, panel boards, etc. including cutting, bending, drilling, welding, riveting, treated with anti-rust treatment and duly powder coated or painted with one coat of red lead paint and 2 coats of enamel paint complete.
Supplying and erecting iron work, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars, MS pipes, etc. for panel board or any other purpose with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority.
Supplying & erecting of required size electrolyte copper flexible braided bus patti or bar in bus bar chamber/in panel or any other purpose, suitable for 500 volt with required capacity having thermal conductivity of 400W per meter with composition Pure copper 99.9% & Trillium 0.001 % & Current density 1.8 with fixing arrangement (like lug or bottle type lug) to both the end with high grade polyolefin insulation sleeve complete as per specification no. BCP-BB
Supplying, erecting & terminating XL-HFFR insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 35 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating XL-HFFR insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 70 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating XL-HFFR insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½ core 185 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating XL-HFFR insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 3½core 400 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating XL-HFFR insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 16 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Providng earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm complete with all materials, testing & recording the results as per specification no. EA-EP
Part - B
Supplying and laying HMS PVC conduit FRLS grade 25 mm dia with necessary accessories in RCC work/false ceiling/false flooring
Carrying out core cutting of size 3" to 5" dia x 15" length in the C.C./rock/stone wall with the help of specialized core cutting machine in proper manner and finishing the site as original.
Supplying and erecting iron work, sheet metal work consisting of CRCA sheets, various sections of iron, plates, chequered plates, rods, bars, MS pipes, etc. for panel board or any other purpose with bending, cutting, drilling and welding complete erected at the position with necessary materials duly painted with one coat of red oxide and two coats of enamel paint to match the switchgears or as per directions by the authority.
Providng earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm complete with all materials, testing & recording the results as per specification no. EA-EP
Supplying and erecting GI strip of high purity required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint with joints required. As per specification no EA-EP.
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 6 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 50 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 95 sq. mm. aluminium conductor complete erected with glands & lugs, on wall/ trusses/pole or laid in provided trench/ pipe as per specification no. CB-LT/AL
Providing & erecting hot dipped galvanised ladder type cable tray manufactured from 16 SWG (1.6 mm thick) GI sheet of 150 mm width & 75 mm height complete with necessary coupler plates & hardware.
Providng earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm complete with all materials, testing & recording the results as per specification no. EA-EP
Supplying and erecting GI strip of high purity required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint with joints required. As per specification no EA-EP.
Supplying, installation, testing and commissioning of main fire pump (MFP /EP) suitable for water discharge of 1600 to 1800 LPM at 70 to 55 m head driven by electric motor 415 volts, 3 phase 50 Hz, AC supply of 30kW or of suitable kW capacity for manual/automatic operation and consisting of following: (a) Horizontal type, single stage, centrifugal/split casing pump of cast iron body & bronze impeller with stainless steel shaft (SS410 grade), mechanical seal conforming to IS 1520. (b) Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325. (c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required. (d) Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, as per specification no. FF-MFP/SSC/EP
Supplying, installation, testing and commissioning of jockey fire pump (JP) suitable for water discharge of 180 to 240 LPM at 70 to 50 m head driven by electric motor 415 volts, 3 phase 50 Hz, AC supply of 5.5 kW or of suitable kW capacity for manual/automatic operation and consisting of following : (a) Horizontal/vertical type, multi stage, centrifugal casing pump of cast iron body & bronze impeller with stainless steel shaft (SS410 grade), mechanical seal conforming to IS 1520. (b) Squirrel cage induction motor, TEFC, synchronous speed 3000 RPM, suitable for operation with IP 55 protection for enclosure, horizontal foot mounted type with Class-'F' insulation, conforming to IS-325. (c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required. (d) Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003)complete, as per specification no. FF-MFP/JP
Supplying, installation, testing and commissioning of main fire pump (MFP/DP) suitable for water discharge of 1600 to 1800 LPM at 70 to 50 m head driven by 45 HP or suitable HP capacity diesel engine at required working speed suitable for manual/automatic operation and consisting of following : (a) Horizontal type, single stage, centrifugal casing pump of cast iron body & bronze impeller with stainless steel shaft (SS410 grade), mechanical seal conforming to IS 1520. (b) Water cooled with radiator, diesel engine conforming to relevant IS standard complete with auto starting mechanism, 12/24 volts DC electric starting equipment with battery of required AH capacity with necessary charger suitable to work on 230v, 50Hz AC supply, diesel tank of minimum 150ltr capacity with first filling of diesel up to 100% level with necessary piping with valves up to engine, exhaust pipe extended up to 10 m outside pump house duly insulated with 50 mm thick glass wool with 1.0 mm thick aluminium sheet cladding, residential silencer, instruments and protection as per standard specification, stop solenoid for auto stop in the event of fault with audio indications etc. as required. (c) M.S. fabricated common base plate, coupling, coupling guard, foundation bolts etc. as required. (d) Erected on provided suitable size cement concrete foundation duly plastered with anti vibration pads with perfect aligning, proper levelling complete pump set with engine assembly and accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003) complete, as per specification no. FF-MFP/SSC/DP
Supplying, erecting, testing & commissioning of fire pump control panel (FCP) of cubical construction, floor mounted type, fabricated from minimum 2 mm thick CRCA sheet, compartmentalised with hinged lockable doors, with enclosure protection class IP54, duly powder coated or painted with accessories duly painted with two coats of synthetic enamel paint of fire red colour over a coat of primer (ISC code 536 as per IS 2932 of 2003), cable alley, interconnection with suitable size solid copper busbar strip of adequate size for all power connections having switchgears and accessories, mountings and internal wiring with adequate size copper conductor cable, earth terminals, numbering etc. complete in all respect, suitable for satisfactory operation of main fire pump and jockey (pressurisation) pumps (1working+1standby) with necessary accessories, wiring & cabling along with allied accessories with following incoming and outgoings, suitable for automatic & manual operation on 415V, 3 phase, 50Hz ac supply as per specifications the capacity of electric motor driven pump are as follows a. Main fire pump(MFP) having capacity of 22kW 1no (1 working) b. Jockey pump(JP) capacity of suitable capacity 2 nos(1 working +1 standby, alternate run per start in auto mode) comprises of the following features & switchgears: 1. Main incomer FP SFU having rotary handle with HRC fuses of suitable rating. 2. Electrolytic grade copper strips for busbar of suitable sizes for main incomer and branches to motor SFU's, starters & outgoing terminals with necessary accessories like stainless steel nut bolts with spring washers for connections, mounted on required no of epoxy or porcelain support insulators of suitable ratings etc.
Supplying and erecting G.I. pipe ‘C’ class ERW 25 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe ‘C’ class ERW 50 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe ‘C’ class ERW 65 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe ‘C’ class ERW 75/80 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe ‘C’ class ERW 100 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe ‘C’ class ERW 150 mm dia with necessary fittings complete as per specification no. FF-PP
Supplying and erecting G.I. pipe ‘C’ class ERW 200 mm dia with necessary fittings complete as per specification no. FF-PP
Providing coating of bitumen paint & 4mm thick wrapping for underground 100 mm ring main of fire fighting system.
Providing coating of bitumen paint & 4mm thick wrapping for underground 150 mm ring main of fire fighting system.
Supplying and erecting 80 mm dia cast iron foot valve ball type/flap type with strainer for negative suction complete as per specification no. FF-VL/FV
Supplying and erecting 150 mm dia cast iron foot valve ball type/flap type with strainer for negative suction complete as per specification no. FF-VL/FV
Supplying and erecting 50 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV
Supplying and erecting 75/80 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV
Supplying and erecting 100 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV
Supplying and erecting 150 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV
Supplying and erecting 200 mm dia. cast iron double flange butterfly valve of size complete with PN16 pressure rating, as per specification no. FF-VL/BFV
Supplying and erecting 75/80 mm dia cast iron double flange NRV complete with PN16 pressure rating, as per specification no. FF-VL/NRV
Supplying and erecting 150 mm dia cast iron double flange NRV complete with PN16 pressure rating, as per specification no. FF-VL/NRV
Supplying and erecting 200 mm dia cast iron double flange NRV complete with PN16 pressure rating, as per specification no. FF-VL/NRV
Supplying and erecting 25 mm dia gun metal gate valve complete with PN16 pressure rating, as per specification no. FF-VL/GV
Supplying and erecting stainless steel single outlet hydrant valve fitted with necessary accessories complete as per specification no. FF-VL/HV
Supplying and installing one piece moulded HDPE / fibre water tank for negative suction only, having capacity 1000 litres fitted with necessary accessories complete as per specification no. FF-FFA/PT
Supplying and installing wall mounting swinging hose reel drum fitted with 19 mm dia. 30m long high pressure polypropylene (Polyhose) along with necessary accessories complete as per specification no. FF-FFA/HV
Supplying and erecting 63mm dia, reinforced rubber lined (R.R.L.) hose pipe, 15m in length, fitted with necessary accessories complete as per specification no. FF-FFA/RRL
Supplying and erecting stainless steel branch pipe 63 mm dia fitted with 20 mm dia detachable hexagonal nozzle complete as per specifications no. FF-FFA/NZ
Supplying and erecting 150 mm dia fire brigade header suitable for supplying water in fire tank complete as per specification no. FF-FA/FBC
Supplying and erecting fire brigade header ( Siamese connection )of 150 mm dia, for supplying water in fire tank complete as per specification no. FF-FA/FMC
Supplying and erecting 300 mm dia 1.5m in height air vessel / tank fabricated from min 5mm thick M.S. sheet complete as per specification no. FF-FFA/ACT
Supplying and erecting 20/25mm dia gun metal air release cock, with necessary G.I. coupling to be fitted on top of air vessel or on wet riser complete as per specification no. FF-FFA/ARV
Supplying and erecting 100 mm dia. pressure gauge , 0-300 PSI or 0-14 kg per cm square fitted with 12/15 mm dia. pad cock valve, erected with provided G.I. pipe, elbow etc. complete as per specification no. FF-FFA/PG
Supplying and erecting 12/15 mm dia pressure switch with provided isolation valve, G.I. nipple, elbow, etc complete as per specification no. FF-FFA/PS
Supplying and erecting brass orifice plate having 6 mm. thickness, 160 mm outer dia with required diameter of inner hole at every double outlet hydrant valve as per specification no. FF-FFA/OP
Supplying and erecting M.S./CRCA cabinet for housing Floor Hydrant valve, hose pipe, hose reel and branch pipe (size 1000 x 736 x 736 mm.) made from 16 SWG sheet and angle iron 25 x 25 x 4 mm. having front doors with viewing glass (8"x6") and locking arrangement with necessary fixing material such as rubber bidding etc. duly painted in post box red colour( Code 538 of IS 5)
Supplying, installing, testing and commissioning of intelligent addressable thermal/heat detector with rate of rise cum fixed temperature thermistor complete with base as required, suitable for temperature variations from -20°C to 38°C for fixed-heat and rate-of-rise type detectors and 0°C to 66°C for high heat type detectors, in built isolation mode, suitable for offices/ceiling cable trenches/less ventilation area's etc. with 3 years equipment replacement warranty IS : 2175 - 1988 reaffirmed 2000, IS 15908:2021 standards FF-AFAS/SD.
Supplying, installing, testing and commissioning of addressable optical smoke detector, single/twin LED’s with 360 degree view, suitable for low voltage 15 to 32 V DC two wires supply, in-built locking mechanism to check the removal and pilferage of the detector, in built isolation mode, start up current 300µA and alarm condition current shall be maximum 6.5 mA, operating temperature 0°C to 50°C, humidity 0-95% RH, IP 41, conforming to IS 2189: 2008, 11360_1985_Reff2020 EN 54 or UL Approved with 3 years equipment replacement warranty FF AFAS/SD
Supplying, installing, testing and commissioning of addressable manual call points ( break glass type/pull station type), made of addressable break glass plastic square in shape surface/flush mounted with "Break Glass" massage embedded on the glass, complete erected with mounting base and required accessories conforming to EN 54 or UL listed with 3 years equipment replacement warranty FF-AFAS/MCP.
Supplying, installing, testing and commissioning of addressable horn cum strobe sound/ hooter, output frequency 500 to 1000 Hz with dB as per Chart given in IS 15908:2021, with flashing at 1 Hz over the strobe’s entire operating voltage range EN 54, conforming to IS 2189: 2008, IS 15908:2021 standards with 3 years equipment replacement warranty FF-AFAS/SSH.
Supplying, installing, testing and commissioning remote response indicators suitable to operate on 5 - 28 V dc supply having FR Polymer ABS Housing complete as per specification no. FF-FAAS/RRI
Supplying, installing, testing and commissioning FRLS, XLPE armoured cable 2 core 1.5 sq.mm. copper conductor complete erected on wall/ ceiling complete as per specification no. CB-LT/CU
Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the 4 loop capacity and capable of supporting upto 250 devices and detectors per loop, with on-board LCD display with min 16 lines of text, operating at 230 V 50 HZ - AC with inbuilt Battery Backup of a minimum 24 hours in normal condition and 30 min in alarm condition, suitable provision for network connectivity, interfacing with third party equipment via a MODBUS/ OPC/ L-ON interface etc. conforming to IS 15908:2021, ,IS 2189: 2008, EN 54 & VDS / FM/ UL 864 (10th edition) with 3 years replacement warranty FF-AFAS/CP.
Supplying, erecting, testing and commissioning 120 W amplifier suitable to operate on 230 Volts A.C. / 12 Volts D.C. supply complete as per specification no. FF-PA/AFR
Supplying, erecting, testing and commissioning 15 to 30 Watts sound column or ceiling mounted complete as per specification no. FF-PA/SOC
Supplying, erecting, testing and commissioning stand mounted/handheld type wired microphone having 2 mV/Pa sensitivity, impedance level limit 300 ohms and 50 - 16000 Hz suitable to operate in -10 deg C to +55 deg C with min. 7 metre shielded cable and 3 Pin Professional XLR Connector, stereo jack complete as per specification no. FF-PA/MIC
Supplying, erecting, testing and commissioning rust free microphone floor stand of chrome plating/powder coating or S.S. material , 500 mm to 1500 mm height and sturdy mechanism ensuring trouble free movement complete.
Supplying, erecting, testing and commissioning of 1.5 sq. mm speaker wire complete.
Supplying, erecting, testing and commissioning of quartzoid bulb sprinkler, 15 mm (½") dia. NBCM Body chrome finished, 68º C fixed temperature rating with deflector disc of conventional construction complete as per specification no. FF-SPR.
Supplying, erecting, testing and commissioning vane type water flow detector 75/80 mm dia. with 1) Visual switch activation 2) Rugged switch assembly 3) Heavy duty aluminium pipe saddles 4)Durable metal enclosure 5) Steel U bolts for secure mounting 6) Two SPDT ( Single pole double track ) synchronised switches 7) serviceable without draining pipes.
Supplying and erecting fire resistant mortar (20 kg) with fire resistance class S90 as per National Electrical Code (NEC) SP30-2011 suitable to seal the openings of all kinds of cables, pipes and cable support system in steel, aluminium and plastic profiles ( except hollow core conductors). The residual openings shall be closed with filler, as per specification no FF-FRM.
Supplying & erecting Carbon Dioxide (CO2) fire extinguisher of 4.5 kg. capacity cartridge type conform to IS 2878 /15683 complete erected with necessary clamp made from 50 x 6 mm. M. S. flat with nut & bolts routed in wall complete.
Excavating hard Rock or bituminous road by chiselling for preparing pit for pole / stay/earth plate / for laying cable/ pipe & clearing the site by removing debris & making the site as required complete.
Excavating hard murum / stone metal road by chiselling for preparing pit for poles stay or earth plates or for laying cables, pipes & clearing the site by removing debris & making the site as required complete.
Making cement concrete foundation in 1:2:4 cement concrete with foundation bolts and nuts complete. (cost of wooden box is included) (for pumps).
Supplying and erecting ISI mark GI pipe 32 mm. dia ‘C” class at position with accessories complete. Specification no. CW-PLB/GP.
Supplying and erecting ISI mark GI pipe 40 mm. dia ‘C” class at position with accessories complete. Specification no. CW-PLB/GP.
Supplying and installing auto glow (Viewing up to 15 mtr length) fire signages in PVC/Vinyl 4/6mm thick sheet or as per sample approved by client viz fire hydrant,fire hydrant,fire extinguishers,fire exists,fire door,fire hose box,fire & Electrical & safety etc size 300mm* 100 mm (Rates are taken from previously sanctioned estimate OW/1655/2021-2022 Latur subdivision vide letter no 107/2022 dt 21.01.2022)
Supplying and installing auto glow (Viewing up to 15 mtr length) fire signages viz fire hydrant,fire hydrant,fire extinguishers,fire exists,fire door,fire hose box,fire & Electrical & safety etc size 450mm* 150 mm (Rates are taken from previously sanctioned estimate OW/1655/2021-2022 Latur subdivision vide letter no 107/2022 dt 21.01.2022)
Supply & Eracting 1000 mm long, 25 mm dia. Stainless steel corrugated flexible pipe (hose)nfor dropping sprinkler below false ceiling, pipe shall have 16 bar rating and with union/reducer coller, clamps etc. as required (Rates are taken from previously sanctioned estimate OW/1655/2021-2022 Latur subdivision vide letter no 107/2022 dt 21.01.2022)
Rossette Plate powder coated in white/off white colour with 25 mm dia. Hole. (Rates are taken from previously sanctioned estimate OW/1655/2021-2022 Latur subdivision vide letter no 107/2022 dt 21.01.2022)
PART-III
Supplying and erecting 20mm dia. corrugated flexible polypropylene conduit
Supplying and erecting PVC trunking (PVC casing-n-capping) of size 25 mm with accessories on wall/ceiling as per specification No: WG-MA/CON.
Supplying and erecting mains with 2x1.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW
Supplying and erecting mains with 2x1.5 sq.mm FRLSH copper PVC insulated wire laid in provided conduit/trunking/inside pole/Bus bars or any other places as per specification No: WG-MA/BW
Supplying and erecting Ceiling rose / Batten holder / Slanting holder / hanging cord switch / hanging bell push / pendant holder bakelite base 6A. erected on filled polypropylene board or polished double wooden block/ PVC junction box.
Supplying and erecting modular type switch 6A / 10A duly erected on provided plate and box with wiring connections complete.
Supplying and erecting modular type 3 pin 6A multi socket with safety shutter, duly erected on provided plate and box with wiring connections complete.
Supplying and erecting modular type (two module) electronic step regulator for fan, duly erected on provided plate and box with wiring connections complete.
Supplying and erecting PVC Surface modular switch box with double mounting plate for 4 module duly erected.
Wiring for plug on board with Switch socket surface/concealed type, copper wiring and earthing and with modular accessories as per specification No: WG-PW/CW
Point wiring for light/bell/exhaust fan in PVC trunking (casing-capping) with 1.5 sq.mm (2+1E) FRLSH grade copper wire, modular type switch, earthing and required accessories as per specification No: WG-PW/SW
Point wiring for ceiling fan in PVC trunking (casing-capping) with 1.5 sq.mm (2+1E) FRLSH grade copper wire, modular type switch, earthing and required accessories as per specification No: WG-PW/SW
Supplying and erecting CRCA powder coated corridor/passage light LED fitting (4 feet) Max. 17W with high transitivity diffuser with system lumens output of Min. 2000 lumens , min. efficacy of 120 lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg., Ripple<5%, THD<10%, p.f. >0.95, operating range of 120-270V, surge protection of 4 kV, Life class of 50,000 Hrs. at L70B50, including driver, with end caps on provided PVC Block / wooden board with 3 years warranty.
Supplying and erecting bulk head LED fitting max. 10W with high transitivity diffuser with system lumens output of min. 1100 lumens, min. efficacy of 110 lumen/W, CRI>80, CCT upto 6500K, Beam Angle of 120 deg., THD<10%, p.f. >0.95, operating range of 140-260V, in built surge protection of 2.5 kV, Life class of 50,000 Hrs. at L70B50, including driver, IP66, IK09 rated on provided PVC Block / wooden board with 3 years warranty.
Supplying and erecting fresh air cum exhaust fan of light duty 250 V A.C. 50 cycles 225mm. 1400 RPM rust proof body & blades, wire mesh, duly erected, complete.
Supplying and erecting Energy Saving BLDC Ceiling fan 230 V A.C. 50 cycles 1200 mm, max. energy consumption of 28W having service ratio (CMM/W) of Min. 8 , PF>0.9, THD<10% without IR remote control/compatible speed regulator, Temperature Rise of Max. 40 deg. C, having external mounted control PCB completely erected in position as per specification no. FG-FN/CF
Supplying, erecting & marking SPMCB 6A to 32A, B-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB
Supplying, erecting & marking DPMCB 6 A to 32 A, B-series with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB
Supplying, erecting & marking TPMCB 40A to 63A, with rated short - circuit breaking capacity (Icn) 10kA in provided distribution board as per specification no. SW-SWR/MCB
Supplying, erecting and marking four pole isolators only switch version of miniature circuit breakers of 40A in provided distribution board.
Supplying and erecting single pole and neutral distribution board (SPNDB), with 2 ways for incoming and 2 ways (2 poles) for outgoing SP MCBs, with door, 1.2mm thickness surface / flush mounted, IP 43 Protection on iron / GI frame as per specification no. SW-SWR/MCBDB
Supplying & erecting CRCA sheet metal one way enclosures of 1.2mm thickness suitable for DP MCB /TP MCB/FP MCB/RCCB/RCBO complete erected on angle iron/GI frame.
Providing, erecting & commissioning 4 pole RCCB 40A, with added immunity to avoid DC pulse tripping with 30/100/300 mA sensitivity complete as per specification no. SW-RCCB/RCCB
Supplying, fixing and commissioning 2 pole, RCBO 6/10/16/20/25A, with overcurrent, rated short-circuit breaking capacity (10 kA) and earth leakage protection, with 30/100/300 mA sensitivity and short circuit and earth leakage trip indication as per specification no SW-RCCB/RCBO
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 2 core 2.5 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Supplying, erecting & terminating FR XLPE insulated, galvanised steel formed wire armoured (strip) cable 1100 V, 4 core 10 sq. mm. copper conductor complete erected with glands & lugs, on wall/ trusses/ pole or laid in provided trench/ pipe as per specification no. CB-LT/CU
Providng earthing with galvanized iron earth plate size 60 x 60 x 0.6 cm complete with all materials, testing & recording the results as per specification no. EA-EP
Supplying and erecting GI strip of high purity required size used for earthing on wall and/or any other purpose with necessary GI clamps fixed on wall painted with bituminous paint with joints required. As per specification no EA-EP.
SITC of Electric Traction Passenger Lift with
Rated capacity :- 10 Passenger/680Kg • Floors :- G+3 floor (4 Stops/4 Landings) • Travel :- 3 to 4.2 mtrs • Location of Lift Machine:- MR/MRL • Rated speed :- 1.0mps VS • Car/Landing door clear opening of 800 mm wide x 2000 mm high • Clear Car size of 1300mm wide x 1350mm deep x 2250mm high • Lift shaft available having clear size of 3000mm wide x 1800mm deep, 1500mm Pit depth,4200mm Overhead. • Doors type :- COPO/TOPO Doors with frame made from SS 304 grade solid(non-cladded) sheet of 1.5mm thick in hairline finish for car and all landing doors with SS door architraves/frames The lift doors shall have minimum 1 hour fire rating (with submission of necessary valid test certificate issued by NABL accredited or Independent test laboratory). • Lift car enclosure made from SS 304 grade solid (non-cladded) sheet of 1.5mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safety factor of 5, with Toe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS chequered plate flooring, handrails, mirror, emergency light etc. The lift car interior design shall be done as per the directions of engineer in charge.
• COP with SS face plate having metallic push buttons with Braille code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with / without attendant key switch, OWD with audio-visual alarm, VAS in Marathi, Hindi & English with intercom system with telephone instrument in Lift car, LMR & FCC/ground floor. • LOP with SS face plate having recess/surface push button box for all landings with scrolling UP/DN LED indicator having metallic push buttons with Braille code & luminous indicator around button with CPI, Lift car arrival & next travel direction audio-visual indication at all landings. • Lift controller based on microprocessor/ PLC with VVVF Drive having closed loop control system, with IBMS compatible having necessary port. The controller shall have necessary protections such as overcurrent, overvoltage, over speed, overheat for all devices including lift motor and travel direction protection, protection for phase loss at input or output etc. various operation modes such as maintenance, change direction by attendant, full load bypass, VIP call operation, self levelling operation, call cancel facility, auto return to home landing, fireman evacuation operation, earthquake operation, door open/close operation from COP etc. The system can
record information for minimum 30 latest faults, with real-time clock management and handheld keypad with LCD screen for view and setting of parameters. The control panel duly wired with proper size & strength, copper wire for power & control circuit, with provision for addition of floor/control card & allied accessories control panel having enclosure of 1.5mm CRCA sheet with powder coating with IP54 Protection class. • ARD complete with necessary SMF VRLA batteries. • Fireman controller having fireman switch at fire Landing. • CCTV surveillance system comprises of 2 nos minimum 2.0MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCC with HDR data backup for min. 90 days with min.18” FHD TV monitor, to be kept in FCC/LMR as directed by Engineer In Charge. • Lift Machine of Gearless PMSM of suitable kW with duty cycle of minimum 120 starts/hr (with submission of necessary valid test certificate issued by NABL accredited or Independent test laboratory), with Traction pulley, OSG, electromagnetic brakes, entire assembly mounted on adequate size girders duly fixed on LMR floor/ shaft walls complete with main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength.
• Other mechanical parts such as 'T' section adequate size guide rails for car & counter weight with brackets fasteners, counter weight frame with necessary blocks, buffers with necessary support arrangement, MS pit ladder etc. erected with necessary steel work. • Minor civil work such as alteration work if any necessary for erection of landing door frames and it's accessories e.g. sill, header, hole pass etc complete with plaster finish, civil work for erection buffers, erection of lift machinery, adequate size core cuts if required & scaffolding for erecting guide rails, providing and fixing steel girders/RCC work having adequate strength for mounting and hoisting lift machine etc. complete as per specification no. LFT. • General: - Job includes entire procedure of obtaining all necessary erection permissions & "License to Work the Lift" from Electrical Inspector(Lifts) with submission to the Engineer In Charge. • The above rate includes Fully Comprehensive AMC for one year from the date of commissioning.
· General: - Job includes entire procedure of obtaining all necessary erection permissions & "License to Work the Lift" from Electrical Inspector(Lifts) with submission to the Engineer In Charge. · The above rate includes Fully Comprehensive AMC for one year from the date of commissioning.
For Lift having 800mm wide x 2000mm high clear entrance in 1.5mm thick SS 304 grade solid (non-cladded) landing door [Two panel], this includes all necessary accessories like LOP's with UP/DN buttons-arrows-indicators, extension of guide rails, shaft wiring with trunking, traveling cables, main hoisting ropes/belts, & OSG rope landing doors with all accessories etc. necessary for the normal safe functioning of lift installation complete.
Full collective control system
For additional 2MP Camera along with necessary accessories at Home Landing, add as given.
SITC of Electric Traction Passenger cum Stretcher/Hospital Lift with
Rated capacity :- 20 Passenger/1360Kg • Floors :- G+3 floor (4 Stops/4 Landings) • Travel :- 3 to 4.2 mtrs • Location of Lift Machine:- MR/MRL • Rated speed :- 1.0mps VS • Car/Landing door clear opening of 1100/1200 mm wide x 2000 mm high • Clear Car size of 1300mm wide x 2400mm deep x 2250mm high • Lift shaft available having clear size of 3000mm wide x 2200mm deep, 1500mm Pit depth,4200mm Overhead. • Doors type :- COPO/TOPO Doors with frame made from SS 304 grade solid(non-cladded) sheet of 1.5mm thick in hairline finish for car and all landing doors with SS door architraves/frames The lift doors shall have minimum 1 hour fire rating (with submission of necessary valid test certificate issued by NABL accredited or Independent test laboratory) • Lift car enclosure made from SS 304 grade solid (non-cladded) sheet of 1.5mm, thick with hairline finish with frame made from MS girders, bracing of adequate size with minimum safety factor of 5, with Toe Guard Apron, with necessary false ceiling with adequate LED lights, blower/fan for ventilation & SS chequered plate flooring, handrails, mirror, emergency light etc. The lift car interior design shall be done as per the directions of engineer in charge.
• COP with SS face plate having metallic push buttons with Braille code & luminous indicator around button with FPI, scrolling UP/DN LED indicator & with / without attendant key switch, OWD with audio-visual alarm, VAS in Marathi, Hindi & English with intercom system with telephone instrument in Lift car, LMR & FCC/ground floor. • LOP with SS face plate having recess/surface push button box for all landings with scrolling UP/DN LED indicator having metallic push buttons with Braille code & luminous indicator around button with CPI, Lift car arrival & next travel direction audio-visual indication at all landings. • Lift controller based on microprocessor/ PLC with VVVF Drive having closed loop control system, with IBMS compatible having necessary port. The controller shall have necessary protections such as overcurrent, overvoltage, over speed, overheat for all devices including lift motor and travel direction protection, protection for phase loss at input or output etc. various operation modes such as maintenance, change direction by attendant, full load bypass, VIP call operation, self levelling operation, call cancel facility, auto return to home landing, fireman evacuation operation, earthquake operation, door open/close operation from COP etc. The system can record information for minimum 30 latest faults, with real-time clock management and handheld keypad with LCD screen for view and setting of parameters, The control panel duly wired with proper size & strength, copper wire for power & control circuit, with provision for addition of floor/control card & allied accessories control panel having enclosure of 1.5mm CRCA sheet with powder coating with IP54 Protection class.
• ARD complete with necessary SMF VRLA batteries. • Fireman controller having fireman switch at fire Landing. • CCTV surveillance system comprises of 2nos minimum 2.0MP FHD IP based vandal proof Dome camera in lift car & in LMR/inside lift shaft top aimed on Lift machinery & controller with NVR kept in LMR/FCC with HDR data backup for min. 90 days with min. 20" FHD TV monitor, to be kept in FCC/LMR as directed by Engineer In Charge. • Lift Machine of Gearless PMSM of suitable kW with duty cycle of minimum 120 starts/hr (with submission of necessary valid test certificate issued by NABL accredited or Independent test laboratory), with Traction pulley, OSG, electromagnetic brakes, entire assembly mounted on adequate size girders duly fixed on LMR floor/ shaft walls complete with main/diverter traction sheaves, suspension wire ropes/belts of adequate size & strength. • Other mechanical parts such as 'T' section adequate size guide rails for car & counter weight with brackets fasteners, counter weight frame with necessary blocks, buffers with necessary support arrangement, MS pit ladder etc. erected with necessary steel work. • Minor civil work such as alteration work if any necessary for erection of landing door frames and it's accessories e.g. sill, header, hole pass etc complete with plaster finish, civil work for erection buffers, erection of lift machinery, adequate size core cuts if required & scaffolding for erecting guide rails, providing and fixing steel girders/RCC work having adequate strength for mounting and hoisting lift machine etc. complete as per specification no. LFT.
• General: - Job includes entire procedure of obtaining all necessary erection permissions & "License to Work the Lift" from Electrical Inspector(Lifts) with submission to the Engineer In Charge. • The above rate includes Fully Comprehensive AMC for one year from the date of commissioning.
For Lift having 800mm wide x 2000mm high clear entrance in 1.5mm thick SS 304 grade solid (non-cladded) landing door [Two panel], this includes all necessary accessories like LOP's with UP/DN buttons-arrows-indicators, extension of guide rails, shaft wiring with trunking, traveling cables, main hoisting ropes/belts, & OSG rope landing doors with all accessories etc. necessary for the normal safe functioning of lift installation complete.
Full collective control system
For additional 2MP Camera along with necessary accessories at Home Landing, add as given.
Mohini Buildwell Pvt. Ltd.
Atal Realtech Ltd
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid