| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹93.8 LAccepted-AOC 24 A RAGHBIR MARG NEAR 22 NO PHATAK PATIALA 147001 PB | PATIALA | PATIALA | PUNJAB | 147001 | ₹93.8 L Quoted ₹93.9 L | L1 | Accepted-AOC AOC |
| 2 | L2₹97.4 LRejected-Finance A 3 257 JANAKPURI NEW DELHI 110058 | WEST DELHI | DELHI | 110058 | ₹97.4 L | L2 | Rejected-Finance Rejected due to bidder not L1 |
| 3 | L3₹1.2 CrRejected-Finance NO 9 BYRAVESHWARA INDUSTRIAL ESTATE ANDRAHALLI MAIN ROAD NEAR PEENYA 2ND STAGE BENGALURU 560 091 | BENGALURU URBAN | KARNATAKA | 560091 | ₹1.2 Cr | L3 | Rejected-Finance Rejected due to bidder not L1 |
| Sl No | Description | Qty | Unit | MAHESH KUMAR SINGLA CONTRACTOR L1 | Vijay Electricals L3 | M/S ADHIKARI CONSTRUCTION CO. L2 |
|---|---|---|---|---|---|---|
| 1.00 | Supplying, installing, testing and commissioning of 33kV, 630A, 25KA /3 -sec, IAC, AFLR, Gas-Insulated Panel making arrangement IP 4X Indoor suitable, floor-mounted, complying to IEC 62271-200 for design, manufacturing and type-tested, including Internal Arc for operator safety (IAC 25kA/1-sec), having 01 Bus coupler+with 01 bus raiser as a extension with existing GIS Panel (ABB) all inside Gas-Insulated IP65 (partition class : partition of metal) SS 304 grade SS tank (2.5 mm thickness) copper bus bar, flush-front mechanism having lockable access door with mounted bay-protection and control scheme, including LEDs, mimic etc. as prescribed below , also SCADA complying to IEC 61850 :- | 1 | Each Job | 47,00,000 ₹47 L | 63,00,000 ₹63 L | 51,49,999 ₹51.5 L |
| 1.01(i) Rated voltage/maximum operating voltage - 36 KV, (ii) Rated power frquency withstand voltage 70 KV(RMS) (iii) Rated lighting impulse withstand voltage 170 KV(Peak) (iv) Rated frequency 50 Hz, (v) Rated short circuit making current 62.5 KA, (vi) Rated short time withstand current 25 KA, (vii) Rated duration of short circuit 3 Sec, (viii) Rated opening time ≤ 45 m sec, (ix) Rated break time ≤ 60 m sec, (x) Rated auxiliary voltage 110 V DC.(xi) GIS vaccum Interruter main numerical relays & meters must be same make for better life cycle optimization. (xii) Each VCB shall comprises of 02 Nos tripping coil. | ||||||
| 1.02(A) 01 x Bus Coupler 33 KV GIS Panel (i) 33 kV, 630 Amp, 25 KA /3-sec, Vacuum Circuit Breaker as per IEC-62271-100 Vacuum Circuit Breaker having 03nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (110V DC). (ii) Current Transformers 33 KV 400/200/1-1 amp, Core2: Class 0.5, 5VA, Core1: Class 5P20 - Set of 03 Nos per breaker (iii) Main Protection Relay shall be a Numerical Drawout IED Relay ( Should be GIS manufacturers own make) communicable on IEC 61850 GOOSE platform over double /Redundant RJ-45/USB/FO port and HSR complaint with programmable min 14 digital input, min 10 digital outputs, 11 front LED ,large dynamic display | ||||||
| 1.03,microprocessor based protection scheme for detecting, indicating and tripping the breaker on various faults like (a) over current+ earth fault protection for HT/LT side. The Relay shall have complete bay control features incl. displaying Feeder SLD (position indication), integrated ON/OFF control function, three phase current measurement, disturbance recorder, event log and fault record with non-volatile memory, self-supervision. The relay shall have sufficient binary inputs and outputs to receive and issue external commands as listed separately. However more DI & DO may be provided in order to fulfill the scheme requirement for SCADA compatibilty.The relay shall be fully integrated with the feeder, internally capturing feeder statuses incl. Breaker On/Off/Spring.Chrgd, Line-Current, SF6 Gas Pressure Low (Busbar compartment), SF6 Gas Pressure Low (Breaker Compartment), Master Trip, Trip Circuit Failure (from TCS relay) and display locally on a built-in back-lit LCD screen as a Single-Line-Diagram with parameters as advised (i) Manometer in each gas chamber. | ||||||
| 1.04(ii) LED Indications - Breaker ON/OFF/TRIP/Spring-Charged, R-Y-B, Disconnector-ON/OFF/EARTH, DC Available (iii) 16-Window Annunciator with Ackn/Test/Reset push button and Hooter to indicate following alarms :- (a) SF6 Gas Pressure Low (Busbar compartment), (b) SF6 Gas Pressure Low (Breaker Compartment), (c) Local Master Trip, (d) Trip Circuit Failure, (iv) Control Equipment incl. 01 x TNC Switch, MCBs for AC/DC isolation as required (v) Other accessories incl. Space Heater with thermostat for LV panel and cable chamber, 3-Pin socket with switch, LED lamp (vi) Soft ware for relay and cable. (vii) Panel shall be offered with digital Ammeter and selector switch (viii) Vaccuum interrupter and GIS panel should be of same make. | ||||||
| 1.05(ix) Metering Equipment incl. 01 x Digital Ammeter (Acc.Cl.0.5), 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port | ||||||
| 1.06Supplying, installing, testing and commissioning of 33kV, 630A, 25KA /3 -sec, IAC, AFLR, Gas-Insulated Panel making arrangement IP 4X Indoor suitable, floor-mounted, complying to IEC 62271-200 for design, manufacturing and type-tested, including Internal | ||||||
| 2.00 | Supplying, installing, testing and commissioning of 33kV, 630A, 25KA /3 -sec, IAC, AFLR, Gas-Insulated Panel making arrangement IP 4X Indoor suitable, floor-mounted, complying to IEC 62271-200 for design, manufacturing and type-tested, including Internal Arc for operator safety (IAC 25kA/1-sec), having 01 x Incomming as a extension with existing GIS panel (ABB) all inside Gas-Insulated IP65 (partition class : partition of metal) SS 304 grade SS tank (2.5 mm thickness) coppeer bus bar 630 amp flush-front mechanism having lockable access door with mounted bay-protection and control scheme, including LEDs, mimic etc. as prescribed below , also SCADA complying to IEC 61850 :- | 1 | Each Job | 45,00,000 ₹45 L | 55,00,000 ₹55 L | 44,99,999 ₹45.0 L |
| 2.01(i) Rated voltage/maximum operating voltage - 36 KV, (ii) Rated power frquency withstand voltage 70 KV (RMS) (iii) Rated lighting impulse withstand voltage 170 KV(Peak) (iv) Rated frequency 50 Hz, (v) Rated short circuit making current 62.5 KA, (vi) Rated short time withstand current 25 KA, (vii) Rated duration of short circuit 3 Sec, (viii) Rated opening time ≤ 45 m sec, (ix) Rated break time ≤ 60 m sec, (x) Rated auxiliary voltage 110 V DC.(xi) GIS vaccum Interruter main numerical relays & meters must be same make for better life cycle optimization. (xii) Each VCB shall 02 Nos tripping coil. | ||||||
| 2.02(i) 33 kV, 630 Amp, 25KA /3 -sec,Vacuum Circuit Breaker as per IEC-62271-100 with roll on floor type Vacuum Circuit Breaker having 03 Nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (110V DC). | ||||||
Updated dates
Tender Value
₹77.3 L
EMD Value
₹1.4 L
Closing Date
30 Apr 2026, 6:00 pmClosed
HQ CWE (U) Delhi Cantt-110010
HQ CWE (U) Delhi Cantt-110010
PROVN OF 33 KV GIS HT BUS COUPLER PANEL AT HQ NSB-II SUB STN AND AUGMENTATION OF EXISTING 33 KV NETWORK WITH CONNECTED ITEMS UNDER GE(U) ELECT SUPPLY DELHI CANTT -10
2025_MES_701834_4
CWE (U)/D-48/2024-25
Open Tender
Civil Works
120 days
HQ CWE (U) Delhi Cantt
As per tender pages
9 documents required · 9 mandatory
₹1,000
GE (U) Elect Supply
₹1.4 L
Yes
19 Jun 2026
10 Apr 2026
7 May 2026
10 Apr 2026
30 Apr 2026
17 Apr 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
Supplying, installing, testing and commissioning of 33kV, 630A, 25KA /3 -sec, IAC, AFLR, Gas-Insulated Panel making arrangement IP 4X Indoor suitable, floor-mounted, complying to IEC 62271-200 for design, manufacturing and type-tested, including Internal Arc for operator safety (IAC 25kA/1-sec), having 01 Bus coupler+with 01 bus raiser as a extension with existing GIS Panel (ABB) all inside Gas-Insulated IP65 (partition class : partition of metal) SS 304 grade SS tank (2.5 mm thickness) copper bus bar, flush-front mechanism having lockable access door with mounted bay-protection and control scheme, including LEDs, mimic etc. as prescribed below , also SCADA complying to IEC 61850 :- | - | Each Job | - | - | |
(i) Rated voltage/maximum operating voltage - 36 KV, (ii) Rated power frquency withstand voltage 70 KV(RMS) (iii) Rated lighting impulse withstand voltage 170 KV(Peak) (iv) Rated frequency 50 Hz, (v) Rated short circuit making current 62.5 KA, (vi) Rated short time withstand current 25 KA, (vii) Rated duration of short circuit 3 Sec, (viii) Rated opening time ≤ 45 m sec, (ix) Rated break time ≤ 60 m sec, (x) Rated auxiliary voltage 110 V DC.(xi) GIS vaccum Interruter main numerical relays & meters must be same make for better life cycle optimization. (xii) Each VCB shall comprises of 02 Nos tripping coil. | - | - | - | - | |
(A) 01 x Bus Coupler 33 KV GIS Panel (i) 33 kV, 630 Amp, 25 KA /3-sec, Vacuum Circuit Breaker as per IEC-62271-100 Vacuum Circuit Breaker having 03nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (110V DC).
(ii) Current Transformers 33 KV 400/200/1-1 amp, Core2: Class 0.5, 5VA, Core1: Class 5P20 - Set of 03 Nos per breaker
(iii) Main Protection Relay shall be a Numerical Drawout IED Relay ( Should be GIS manufacturers own make) communicable on IEC 61850 GOOSE platform over double /Redundant RJ-45/USB/FO port and HSR complaint with programmable min 14 digital input, min 10 digital outputs, 11 front LED ,large dynamic display | - | - | - | - | |
,microprocessor based protection scheme for detecting, indicating and tripping the breaker on various faults like (a) over current+ earth fault protection for HT/LT side. The Relay shall have complete bay control features incl. displaying Feeder SLD (position indication), integrated ON/OFF control function, three phase current measurement, disturbance recorder, event log and fault record with non-volatile memory, self-supervision. The relay shall have sufficient binary inputs and outputs to receive and issue external commands as listed separately. However more DI & DO may be provided in order to fulfill the scheme requirement for SCADA compatibilty.The relay shall be fully integrated with the feeder, internally capturing feeder statuses incl. Breaker On/Off/Spring.Chrgd, Line-Current, SF6 Gas Pressure Low (Busbar compartment), SF6 Gas Pressure Low (Breaker Compartment), Master Trip, Trip Circuit Failure (from TCS relay) and display locally on a built-in back-lit LCD screen as a Single-Line-Diagram with parameters as advised (i) Manometer in each gas chamber. | - | - | - | - | |
(ii) LED Indications - Breaker ON/OFF/TRIP/Spring-Charged, R-Y-B, Disconnector-ON/OFF/EARTH, DC Available
(iii) 16-Window Annunciator with Ackn/Test/Reset push button and Hooter to indicate following alarms :- (a) SF6 Gas Pressure Low (Busbar compartment), (b) SF6 Gas Pressure Low (Breaker Compartment), (c) Local Master Trip, (d) Trip Circuit Failure,
(iv) Control Equipment incl. 01 x TNC Switch, MCBs for AC/DC isolation as required
(v) Other accessories incl. Space Heater with thermostat for LV panel and cable chamber, 3-Pin socket with switch, LED lamp
(vi) Soft ware for relay and cable. (vii) Panel shall be offered with digital Ammeter and selector switch (viii) Vaccuum interrupter and GIS panel should be of same make. | - | - | - | - | |
(ix) Metering Equipment incl. 01 x Digital Ammeter (Acc.Cl.0.5), 01no. Multi-Function-Meter (Acc.Cl.0.5) shall be provided with LCD display for measuring current, voltage, power, power-factor and energy-parameters, Total Harmonic Distortion and Max. Demand Indication, same shall be communicable on ModBus via RS485 port | - | - | - | - | |
Supplying, installing, testing and commissioning of 33kV, 630A, 25KA /3 -sec, IAC, AFLR, Gas-Insulated Panel making arrangement IP 4X Indoor suitable, floor-mounted, complying to IEC 62271-200 for design, manufacturing and type-tested, including Internal | - | - | - | - | |
Supplying, installing, testing and commissioning of 33kV, 630A, 25KA /3 -sec, IAC, AFLR, Gas-Insulated Panel making arrangement IP 4X Indoor suitable, floor-mounted, complying to IEC 62271-200 for design, manufacturing and type-tested, including Internal Arc for operator safety (IAC 25kA/1-sec), having 01 x Incomming as a extension with existing GIS panel (ABB) all inside Gas-Insulated IP65 (partition class : partition of metal) SS 304 grade SS tank (2.5 mm thickness) coppeer bus bar 630 amp flush-front mechanism having lockable access door with mounted bay-protection and control scheme, including LEDs, mimic etc. as prescribed below , also SCADA complying to IEC 61850 :- | - | Each Job | - | - | |
(i) Rated voltage/maximum operating voltage - 36 KV, (ii) Rated power frquency withstand voltage 70 KV (RMS) (iii) Rated lighting impulse withstand voltage 170 KV(Peak) (iv) Rated frequency 50 Hz, (v) Rated short circuit making current 62.5 KA, (vi) Rated short time withstand current 25 KA, (vii) Rated duration of short circuit 3 Sec, (viii) Rated opening time ≤ 45 m sec, (ix) Rated break time ≤ 60 m sec, (x) Rated auxiliary voltage 110 V DC.(xi) GIS vaccum Interruter main numerical relays & meters must be same make for better life cycle optimization. (xii) Each VCB shall 02 Nos tripping coil. | - | - | - | - | |
(i) 33 kV, 630 Amp, 25KA /3 -sec,Vacuum Circuit Breaker as per IEC-62271-100 with roll on floor type Vacuum Circuit Breaker having 03 Nos. vacuum bottles of same make as of circuit breaker and panel, motorized spring charging mechanism (230VAC) with integral spring charging handle for manual charging, associated push-buttons, anti-pumping feature, and associated Shunt Trip/Close Coils (110V DC). | - | - | - | - |
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.60 MB
BOQ_851209.xls
BOQ • 1.16 MB
D48TP.pdf
Tender Documents • 1.32 MB
Download all tender documents and submit your bid