| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹14.0 LAccepted-Finance | ₹14.0 L | L1 | Accepted-Finance Financial Bid in Order |
| 2 | L2₹14.9 LAccepted-Finance | ₹14.9 L | L2 | Accepted-Finance Financial Bid in Order |
| Sl No | Description | Qty | Unit | EASHWAR ELECTRICALS L2 | SRIRAM ELECTRICALS L1 |
|---|---|---|---|---|---|
| 1.00 | Material & Labour for Servicing HT VCB panel cum breaker 1250/800/630A 13.1KA rating Indoor type make of SEIMENS/CROMPTON/SCHINDER after taking proper shut down and disconnecting the cables from panel draw out VCB breakers, earth fault relay, checking alignment of VCB isolating contact, servicing of operating mechanism including tripping and closing system of the breakers, dehydrating, decarburizing of panel, bus bar section & circuit section including incoming/ outgoing cables, provide necessary HT insulation at joints. Removing perished monoplus compound cleaning and re-insulating with HT taps wherever necessary, with and including replacement of worn-out/defective spares like tension springs, torsion springs, nut bolts, washers of suitable size, lingers and de-carbonizing all joints, bus bar, CTs, PTs spout metal parts and making VCB perfect operation in manual and electric mode including all routine and preventive maintenance of breaker under the supervision of authorized dealer /representative and reconnecting the panel/breaker in its original position and testing all as specified and directed.
Note: - (i) The rate quoted inclusive of all minor spares and consumables etc. required at site.
(ii) Spares parts required other than mentioned here-in-after shall be deemed to be included in the quoted rate. | 10 | Each Job | 12,600 ₹1,26,000 | 7,000 ₹70,000 Lowest |
| 2.00 | Supply and fix in replacement of shunt trip coil 220/110 or 30 Volts DC complete all as specified and directed. | 1 | Each | 4,500 ₹4,500 Lowest | 5,000 ₹5,000 |
| 3.00 | Supply and fix in replacement of closing trip coil 220/110 or 30 Volts DC complete all as specified and directed . | 1 | Each | 4,500 ₹4,500 Lowest | 5,000 ₹5,000 |
| 4.00 | Supply & Fix in repair fuse element 20A-50A at 2/4pole 11KV structure unit complete all as specified and directed | 3 | Each | 360 ₹1,080 Lowest | 500 ₹1,500 |
| 5.00 | Supply & Fix in repair new vacuum interrupter 800/630A 11KV rating suitable for HT breaker of approved make or Brand complete all as directed and directed by Engr-In-Charge. | 1 | Each | 45,000 ₹45,000 Lowest | 55,000 ₹55,000 |
| 6.00 | Supply & Fix in repair LED Indication lamps suitable for HT/LT breakers complete all as specified and directed. | 6 | Each | 180 ₹1,080 Lowest | 300 ₹1,800 |
| 7.00 | Supply & Fix in repair air ventilation fan with wiring of existing panel and taking down unserviceable ventilation fan with wiring complete all as specified and directed by Engg-in-Charge. | 2 | Each Job | 1,800 ₹3,600 Lowest | 6,000 ₹12,000 |
| 8.00 | Supply & Fix in repairs air ventilation louver arrangement for existing VCB Panel including and taking down Unserviceable air ventilation louver all as specified and directed | 2 | Each Job | 2,700 ₹5,400 Lowest | 4,000 ₹8,000 |
| 9.00 | Supply & Fix in repairs 200 watt space heater for existing panel complete all as specified and directed | 2 | Each Job | 1,800 ₹3,600 Lowest | 2,500 ₹5,000 |
| 10.00 | Material & Labour for Inspecting electronic relay (over current relay and earth fault relay) from the 11 KV, VCB and calibrating the relay with the help of secondary injection kit and proper setting of relays and refixing back in existing position testing of proper tripping/ functioning system complete all as specified and as directed. | 4 | Each Job | 27,000 ₹1,08,000 | 3,500 ₹14,000 Lowest |
Tender Value
₹15 L
EMD Value
₹30,000
Closing Date
1 Jul 2026, 6:00 pmClosed
AGE (I) R D AVADI
AGE I R D AVADI CHENNAI 600 054
REPAIRS AND MAINTENANCE OF HT DISTRIBUTION NETWORK INCLUDING REPAIRS TO VCBs TRANSFORMERS, HT UG CABLES ETC AND CONNECTED WORKS AT CVRDE AVADI
2026_MES_769035_1
8761/E8
Open Tender
Electrical and Maintenance Works
Item Rate
240 days
Avadi
as per tender documents
6 documents required · 6 mandatory
₹500
AGE (I) R D AVADI
₹30,000
Yes
24 Aug 2026
1 Jun 2026
6 Jul 2026
1 Jun 2026
1 Jul 2026
14 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Material & Labour for Servicing HT VCB panel cum breaker 1250/800/630A 13.1KA rating Indoor type make of SEIMENS/CROMPTON/SCHINDER after taking proper shut down and disconnecting the cables from panel draw out VCB breakers, earth fault relay, checking alignment of VCB isolating contact, servicing of operating mechanism including tripping and closing system of the breakers, dehydrating, decarburizing of panel, bus bar section & circuit section including incoming/ outgoing cables, provide necessary HT insulation at joints. Removing perished monoplus compound cleaning and re-insulating with HT taps wherever necessary, with and including replacement of worn-out/defective spares like tension springs, torsion springs, nut bolts, washers of suitable size, lingers and de-carbonizing all joints, bus bar, CTs, PTs spout metal parts and making VCB perfect operation in manual and electric mode including all routine and preventive maintenance of breaker under the supervision of authorized dealer /representative and reconnecting the panel/breaker in its original position and testing all as specified and directed.
Note: - (i) The rate quoted inclusive of all minor spares and consumables etc. required at site.
(ii) Spares parts required other than mentioned here-in-after shall be deemed to be included in the quoted rate. | 10 | Each Job | 1.25 | ₹12.5 |
| 2 | Supply and fix in replacement of shunt trip coil 220/110 or 30 Volts DC complete all as specified and directed. | 1 | Each | 1.25 | ₹1.25 |
| 3 | Supply and fix in replacement of closing trip coil 220/110 or 30 Volts DC complete all as specified and directed . | 1 | Each | 1.25 | ₹1.25 |
| 4 | Supply & Fix in repair fuse element 20A-50A at 2/4pole 11KV structure unit complete all as specified and directed | 3 | Each | 1.25 | ₹3.75 |
| 5 | Supply & Fix in repair new vacuum interrupter 800/630A 11KV rating suitable for HT breaker of approved make or Brand complete all as directed and directed by Engr-In-Charge. | 1 | Each | 1.25 | ₹1.25 |
| 6 | Supply & Fix in repair LED Indication lamps suitable for HT/LT breakers complete all as specified and directed. | 6 | Each | 1.25 | ₹7.5 |
| 7 | Supply & Fix in repair air ventilation fan with wiring of existing panel and taking down unserviceable ventilation fan with wiring complete all as specified and directed by Engg-in-Charge. | 2 | Each Job | 1.25 | ₹2.5 |
| 8 | Supply & Fix in repairs air ventilation louver arrangement for existing VCB Panel including and taking down Unserviceable air ventilation louver all as specified and directed | 2 | Each Job | 1.25 | ₹2.5 |
| 9 | Supply & Fix in repairs 200 watt space heater for existing panel complete all as specified and directed | 2 | Each Job | 1.25 | ₹2.5 |
| 10 | Material & Labour for Inspecting electronic relay (over current relay and earth fault relay) from the 11 KV, VCB and calibrating the relay with the help of secondary injection kit and proper setting of relays and refixing back in existing position testing of proper tripping/ functioning system complete all as specified and as directed. | 4 | Each Job | 1.25 | ₹5 |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.60 MB
8761TD.pdf
Tender Documents • 1.53 MB
BOQ_861252.xls
BOQ • 0.31 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].