Office of the Project Director, FRFCF-NRB, Kalpakkam.
Internal Electrification works for Zone-5, Fuel Fabrication Plant, FRFCF, NRB, BARC, Kalpakkam
2024_BARC_796319_1
BARC/NRB/FRFCF/ELE/ETR045/2024
Open Tender
Electrical Works
Item Rate
366 days
FRFCF, KALPAKKAM
Please refer tender document
8 documents required · 8 mandatory
₹0
₹1.1 L
9 Apr 2024
20 Feb 2024
7 Mar 2024
20 Feb 2024
1 Mar 2024
20 Feb 2024
20 Feb 2024 - 27 Feb 2024
Amount
Supply, installation, testing and commissioning of recessed type LED box indoor fixtures with Min. Lumen output of 3000, colour temperature 6500K, with with all fixuture accessories including accessories required for erection of luminaires in MS Embedded Parts/Brick masonry walls/RCC ceiling/False ceiling with required number and suitable sizes of anchor fasteners, bolts and nuts with washers,safety chain,Scaffolding, safety measures etc., as per the detailed specifications and directed by EIC.
Supply, installation, testing and commissioning of recessed type DALI based,variable CCT LED box fixtures with ,Min. Lumen output of 3300, colour temperature between 4000K to 6500K, with with all fixuture accessories including accessories required for erection of luminaires in MS Embedded Parts/Brick masonry walls/RCC ceiling/False ceiling with required number and suitable sizes of anchor fasteners, bolts and nuts with washers,safety chain,Scaffolding, safety measures etc., as per the detailed specifications and directed by EIC.
Supply, installation, testing and commissioning of recess mounted type LED downlight indoor fixtures with Min.Lumen output of 2200, colour temperature 4000K to 6000K, with all fixuture accessories including d accessories required for erection of luminaires in MS Embedded Parts/Brick masonry walls/RCC ceiling/False ceiling with required number and suitable sizes of anchor fasteners, bolts and nuts with washers,PVC/ GI conduits (Rigid /Flexible as per site requirement),Scaffolding, safety measures etc., as per the detailed specifications and directed by EIC.
Supply, installation, testing and commissioning of surface mounted type LED batten indoor fixtures with ,Min.Lumen output of 3500, colour temperature 4000K, with all fixuture accessories including d accessories required for erection of luminaires in MS Embedded Parts/Brick masonry walls/RCC ceiling/False ceiling with required number and suitable sizes of anchor fasteners, bolts and nuts with washers,PVC/ GI conduits (Rigid /Flexible as per site requirement),Scaffolding, safety measures etc., as per the detailed specifications and directed by EIC.
Supply, installation, testing and commissioning of surface mounted type flame proof LED batten fixtures with Min.Lumen output of 2000, colour temperature 4000K, with all fixuture accessories including d accessories required for erection of luminaires in MS Embedded Parts/Brick masonry walls/RCC ceiling/False ceiling with required number and suitable sizes of anchor fasteners, bolts and nuts with washers,PVC/ GI conduits (Rigid /Flexible as per site requirement),Scaffolding, safety measures etc., as per the detailed specifications and directed by EIC.
Supply, installation, testing and commissioning of bulkhead/decorative type LED indoor fixtures with Min. Lumen output of 1100 , colour temperature 4000K to 6000K, with all fixuture accessories including accessories required for erection of luminaires in MS Embedded Parts/Brick masonry walls/RCC ceiling with required number and suitable sizes of anchor fasteners, bolts and nuts with washers,PVC/ GI conduits (Rigid /Flexible as per site requirement) from nearest control switch,Scaffolding, safety measures etc., as per the detailed specifications and directed by EIC.
Supply, installation, testing and commissioning of surface mounted type ,110V DC LED indoor fixtures with Min. Lumen output of 1000 with all fixuture accessories including d accessories required for erection of luminaires in MS Embedded Parts/Brick masonry walls/RCC ceiling/False ceiling with required number and suitable sizes of anchor fasteners, bolts and nuts with washers,PVC/ GI conduits (Rigid /Flexible as per site requirement),Scaffolding, safety measures etc., as per the detailed specifications and directed by EIC.
Supply, installation, testing and commissioning of Non-Maintained type Self Contained Emergency (SCEL) luminaire with Rechargeable battery with all fixuture accessories including d accessories required for erection of luminaires in MS Embedded Parts/Brick masonry walls/RCC ceiling/False ceiling with required number and suitable sizes of anchor fasteners, bolts and nuts with washers,PVC/ GI conduits (Rigid /Flexible as per site requirement),Scaffolding, safety measures etc., as per the detailed specifications and directed by EIC.
Supply and installation of Surface mounting Powder Coated TPN 250A,3ph,415V,50Hz, distribution board with 1no of I/C-4P, 250A MCCB and 4 no's of O/g's-4P, 80A ,4 no's of O/g's-4P, 100A MCB with all accessories as per the scope of work.
Loading, Transportation, Unloading at site, installation, Testing and Commissioning of 1100 Volts Grade PVC/HRPVC/XLPE insulated, Stranded Aluminium/copper conductor cables of 3/3.5/4core X Upto 25 sqmm sizes in built-in trenches, on walls, poles and through embedded pipes including supply of GI spacer, clamps etc and as per the detailed specification (Note: Cable will be issued free of cost by the department).
Loading, Transportation, Unloading at site, installation, Testing and Commissioning of 1100 Volts Grade PVC/HRPVC/XLPE insulated, Stranded Aluminium/copper conductor cables of 3/3.5/4Core X above 25 & up to 120 sqmm sizes in built-in trenches, on walls, poles and through embedded pipes including supply of GI spacer, clamps etc and as per the detailed specification (Note: Cable will be issued free of cost by the department).
Loading, Transportation, Unloading at site, Laying, Testing and Commissioning of one number PVC/HRPVC/XLPE insulated and PVC sheathed Stranded Aluminium/copper conductor power cable of 1.1 KV grade of 3/3.5/4 Core X above 25 to 3/3.5/4 Core X up to 120 sqmm direct in ground including excavation, sand cushioning, protective covering with chamber burnt/cement bricks on sides & top, refilling the trench and providing RCC route indicator etc as required (Note: Cable will be issued free of cost by the department).
End Termination of 3.5/4 C x16/35 sq.mm of Aluminium Conductor PVC Insulated and sheathed armoured UG Cable using Single Compression, Heavy Duty, Gland connecting the cable to the equipment such as Switches/Panel Boards etc. using Comet or equivalent make Aluminium crimping lugs as directed by Engineer-in-Charge. The rate shall include the cost of supply of Cable Gland and Lugs. The Contractor shall arrange for making holes wherever necessary for fixing cable gland.
End Termination of the 3.5/4C x 50/70 sq.mm of Aluminium Conductor PVC Insulated and sheathed armoured UG Cable using Single Compression, Heavy Duty, Gland connecting the cable to the equipment such as Switches/Panel Boards etc. using Comet or equivalent make Aluminium crimping lugs as directed by Engineer-in-Charge. The rate shall include the cost of supply of Cable Gland and Lugs. The Contractor shall arrange for making holes wherever necessary for fixing cable gland.
Excavation in all types of soil including hard murram for foundations, trenches for cable laying, earthing etc., including refilling with excavated earth and disposing surplus earth at places as directed including neat banking as per the scope of work.
Supply,Fabrication and installation of MS Brackets, Supports, Frame work, Clamps, Base Channels, etc., fabricated out of angle / Channel / Rods etc., The rate quoted shall include the cost of fabrication / welding, cleaning and painting/ galvanising including supply of required, fasteners, nuts, washers, etc.,
Supply,Fabrication and installation of 300 mm width x 100 mm depth x 2.0 mm thickness pre-fabricated, hot dipped galvanized (average weight of zinc coating per unit area - 610 gm/Sq.m and coating thickness minimum of 75 microns) steel (IS:2062 Grade-BR), "Perforated type cable trays with all cable tray accessories" with GI coupler plates, GI L-clips,SS bolts, nuts & washers ,GI covers with thickness of 2.0mm as per drawings, specifications and scope of work.
Supply ,Fabrication and installation of 150 mm width x 100 mm depth x 2.0 mm thickness pre-fabricated, hot dipped galvanized (average weight of zinc coating per unit area - 610 gm/Sq.m and coating thickness minimum of 75 microns) steel (IS:2062 Grade-BR), "Perforated type cable trays with all cable tray accessories" with GI coupler plates, GI L-clips, SS bolts, nuts & washers ,GI covers with thickness of 2.0mm as per drawings, specifications and scope of work.
Supply,Fabrication and installation of 150 mm width x 100 mm depth x 2.0 mm thickness pre-fabricated, hot dipped galvanized (average weight of zinc coating per unit area - 610 gm/Sq.m and coating thickness minimum of 75 microns) steel (IS:2062 Grade-BR), "ladder type cable trays with all cable tray accessories " with GI coupler plates, GI L-clips, SS bolts, nuts & washers ,GI covers with thickness of 2.0mm as per drawings, specifications and scope of work.
Supply,Fabrication and installation of 150 mm width x 100 mm depth x 2.0 mm thickness pre-fabricated, hot dipped galvanized (average weight of zinc coating per unit area - 610 gm/Sq.m and coating thickness minimum of 75 microns) steel (IS:2062 Grade-BR), "Solid type cable trays with all accessories" with GI coupler plates, GI L-clips,SS bolts, nuts & washers ,GI covers with thickness of 2.0mm as per drawings, specifications and scope of work.
Supply, installation and testing of Copper Plate Earth Electrode as per IS: 3043 including excavation, RCC Chamber and RCC cover slab (50 kg each Bentonite & Charcoal shall be provided for each earth pit) as per the specifications and scope of work.
Supply, fabrication and installation of 25 mm x 6 mm Hot dip Galvanised GI Flats in built in trenches on walls, poles, RCC Concrete and through embedded pipes as per the detailed specification.
Supply, fabrication and installation of 25 mm x 6 mm Hot dip Galvanised GI Flats direct in ground including excavation and refilling the trench etc., as required as per the detailed specification.
Supply Embedment Assembling testing and commissioning of 32A 3P+N+E-FP Metra plug and socket DB and 32A FP 30mA sensistivity RCBO type Metra plug and socket DB and RCBO in sheet steel enclosure including chipping and finishing as per the detailed specification. (Refer Sec VI, Clause No.15.4).
Supply Embedment Assembling testing and commissioning of 63A 3P+N+E-FP Metra plug and socket DB and 63A FP 30mA sensistivity RCBO type Metra plug and socket DB and RCBO in sheet steel enclosure including chipping and finishing as per the detailed specification. (Refer Sec VI, Clause No.15.4).
Fabrication, supply, installation of the copper bonded steel round conductor of 16mm size having coating thicness of 250µm in built-in trenches/ walls/column/floor/ slab including clamp and other fixing assessories as per tender specification
Fabrication, supply, installation of the copper bonded steel round conductor of 16mm size having coating thicness of 250µm including excavation and refilling as per tender specification
Fabrication,supply, installation of the copper bonded steel round conductor of 10mm size having coating thicness of 250µm in built-in trenches/ walls/column/floor/ slab including clamp and other fixing assessories as per tender specification
Jointing of 10mm size copper bonded steel round conductors by exothermic welding (CAD welding) of the Straight type Joint complete with all components and accessories as per the scope of work and drawings.
Jointing of 16mm size copper bonded steel round conductors by exothermic welding (CAD welding) of the Straight type Joint complete with all components like mould,contrl unit,powder and accessories as per the scope of work and drawings.
Jointing of CBSC16mm to 185Sqmm Copper conductor by exothermic welding (CAD welding) of the Straight type Joint complete with all components like mould,contrl unit,powder and accessories as per the scope of work and drawings
Jointing of 10 mm size copper bonded steel round conductors by exothermic welding (CAD welding) of the Cross type Joint complete with all components like mould,contrl unit,powder and accessories as per the scope of work and drawings.
Jointing of 16 mm size copper bonded steel round conductors by exothermic welding (CAD welding) of the Cross type Joint complete with all components like mould,contrl unit,powder and accessories as per the scope of work and drawings.
Jointing of 10 mm size copper bonded steel round conductors by exothermic welding (CAD welding) of the T- type Joint complete with all components like mould,contrl unit,powder and accessories as per the scope of work and drawings.
Jointing of 16 mm size copper bonded steel round conductors by exothermic welding (CAD welding) of the T- type Joint complete with all components like mould,contrl unit,powder and accessories as per the scope of work and drawings.
Supply and erection of copper test link for termination of 10mm to 16mm size copper bonded steel conductors at 1500mm above finished ground level as per tender specification
power system
SAS ENTERPRISES
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .