Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.5 CrAccepted-AOC NAVI MUMBAI | THANE | MAHARASHTRA | 400601 | ₹8.5 Cr | L1 | Accepted-AOC LOWEST BID |
Tender Value
₹9.1 Cr
EMD Value
₹9.1 L
Closing Date
12 Feb 2025, 5:00 pmClosed
GM(Civil)/HoD, WCL
Office of GM(Civil), 10th Floor, Civil Department, WCL HQ, Nagpur-440001
Planning, Design, Engineering, Construction, Fabrication, Erection, Supply, Installation, Testing, Trial Run and Comm of CHP consisting of Truck Loading Station with 2x100 te RCC Surface Hoppers etc on Turnkey Basis at Sharda UG Proj (2nd call)
2025_WCL_324730_1
wcl-hq-gmciv-e12-2024-25
Turnkey
Civil Works - Others
Item Rate
2280 days
Kanhan Area
Please refer Tender documents.
6 documents required · 6 mandatory
₹9.1 L
Through Video Conferencing as per NIT
30 Jun 2025
2 Jan 2025
14 Feb 2025
3 Jan 2025
12 Feb 2025
17 Jan 2025
3 Jan 2025 - 1 Feb 2025
10 Jan 2025
Amount
PART - A (WORKS & SERVICES)
SURVEY, SOIL TESTING & DESIGN ENGINEERING COST
Detailed survey & soil investigation of the area within battery limit and submission of report
Design engineering cost (P&M)
Design engineering cost for Civil & Structural works
CIVIL AND STRUCTURAL WORKS
MAIN COMPONENTS OF CHP
Conveyor Gantry (As per NIT and system requirement)
Truck Loading Hopper with Lift Tower,Staircase and Pavement (As per NIT and system requirement)
Transfer house (As per NIT and system requirement)
SERVICE BUILDINGS
CHP Office with Rest room, Pantry and Switch Yard Room (As per NIT and system requirement)
Security Room (As per NIT and system requirement)
LMV Parking Shed and Scooter Parking Shed (As per NIT and system requirement)
Cement Concrete Road 3.75 Metre with 1.5 metre wide shoulders on both sides (As per NIT and system requirement)
RCC Drains of size 60cmx90cm with covers all around TLS and one side of Service Road (As per NIT and system requirement, minimum legth to be provided 200 metres)
Water reservoir,Water supply & pipe line (As per NIT and system requirement)
Pump house (As per NIT and system requirement)
Cable Trenches (As per NIT and system requirement)
Items/installations/structures not specifically mentioned but needed for CHP
PART- B (SUPPLY OF PLANT & MACHINERY, ERECTION, INSTALLATION & COMMISSIONING INCLUDING DLP PERIOD FOR MAINTENANCE FOR A PERIOD OF 60 CALENDAR MONTHS) (Electrical and Mechanical P&M items)
Mechanical Equipments
Surface Belt conveyor C1, 1200 mm wide, Minimum 70 m long or as required, 400tph nominal capacity, 1.5 m/sec. Speed, 1 x 55 kW drive, Horizontal/vertical gravity loop take up, electrical items suitable for operation at 415 V, 50 Hz, 3 phase supply including scrappers, two way transfer chutes, brakes, idlers, coveyor structures, tail-end, loading points, switches, impact guard, skirt plate, decking plates, D-3500 PVC belting, interlocking & controls, Traction type fluid coupling etc. all complete. (As per NIT)
Hydraulic Sector Gates, 400tph +20% capacity, suitable for (-)150mm lumps alongwith electricals suitable for 415/550V, 3 phase, 50Hz AC Supply will be installed below 2x100te overhead RCC hoppers. (As per NIT)
Lifting tackles (As per Appendix- C) (As per NIT) Elec.Hoist blocks 3T capacity - 2 Nos or as required. Chain pulley blocks 2 T capacity - 1 No or as required. All complete
Dust suppression system consisting of nozzles, pumps, piping, valves, dust extraction system etc. all complete as per specifications
1) For Fire fighting a) 4 electric pump ( 2 working and 2 standby) with 4 jockey pumps, 2 diesel engine operated pump, additional pump (if required), pipes, stand post type fire hydrant points, landing valves, fire hose reels, fire hoses, cabinets, branch pipes, nozzles, fire detection and alarming system (consisting of linear heat sensing devices, smoke detectors), back up power arrangement (UPS), pipes, bends etc. All complete b) Fire extinguishers Dry chemical powder type, 5 kg cap (as required) c) Fire extinguishers CO2, 5 lit. capacity(As required) d) Sand buckets, 9 lit capacity (As required e) MS stand along with hooks to hang the sand buckets (As required f) Any other items as required All complete 2) Plant cleaning and drinking water system consisting of pumps, piping, hoses, nozzles, Compressors etc. , all complete
Misc. 1. Condition monitoring system consisting of sensors for temperature, vibration and noise level, out stations, microprocessor based central station, cables etc., and others as required complete. 2. Ventilation, safety equipments, Air compressors, slurry pumps, for hopper low level/ high level indicators, temperature/thermal sensors, etc. and others as required, all complete
Any other item(s) not included in the above list but necessary for efficient operation of the entire plant (items to be specified), all complete including dovetailing of belt conveyor TB1 and C1 at Transfer House-1.
ELECTRICAL EQUIPMENT
415 V Sectionalizer Motor Control Centre (MCC) at all substations comprising of: - 1 No. of Incomer ACBs - 1No. of Outgoing ACBs for Conveyor C1 Motor - 1No. of Outgoing ACBs as lighting load - Required nos. of outgoing Feeders for supply of power to LT Motors (of equipment like Hydraulic sector gates, Electrical Hoists etc. as per the requirement) (As per NIT)
Power Cables
1.1kV grade, XLPE insulated, PVC sheathed single wire armoured aluminium conductor FRLS cables of different sizes as per technical specification (As per NIT)
Lighting cables
1100 V grade, PVC insulated, PVC sheathed, single wire armoured, Al conductor, FRLS cables of different sizes and 1100V grade and 2 core, PVC insulated with PVC sheathed stranded copper conductors as per technical specification (As per NIT)
Control Cables
1100 V grade, single/multi core PVC insulated and sheathed, copper conductor, FRLS,control and signalling cables of 6 sq. mm cross-section having different no. of cores as per technical specification. (As per NIT)
Cable trays /cable hangers (separate trays shall be used for power and control cables), cable vaults etc as per technical specification. (As per the system Requirement (As per NIT)
Luminaires
Fixed type lighting mast with LED lights (16 m high) (As per NIT)
LED luminaires as per requirement complete with control gears, accessories etc. as per technical specifications for: (i) Transfer house, Drive house etc. (ii) Switch board room, stores, pump house, compressor room, conveyor gantries etc. (As per NIT)
Total impact of GST for the purpose of CTC
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .