Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹28.4 LAccepted-AOC 11 82 GROUND FLOOR BLOCK 11 KALYANPURI EAST DELHI DELHI 110091 | EAST DELHI | DELHI | 110091 | ₹28.4 L Quoted ₹29.2 L | L1 | Accepted-AOC LOWEST BIDDER |
| 2 | L2₹34.9 L+₹5.7 L (19.6%)Rejected-Finance | ₹34.9 L+₹5.7 L (19.6%) | L2 | Rejected-Finance HIGHER BIDDER |
| 3 | L3₹39.0 L+₹9.8 L (33.5%)Rejected-Finance | ₹39.0 L+₹9.8 L (33.5%) | L3 | Rejected-Finance HIGHER BIDDER |
| 4 | L4₹39.8 L+₹10.6 L (36.1%)Rejected-Finance S NO 279 1 1A PLOT NO 113 KUTWAL COLONY SASTHE WASTI LOHEGAON PUNE 411 047 | PUNE | MAHARASHTRA | 411047 | ₹39.8 L+₹10.6 L (36.1%) | L4 | Rejected-Finance HIGHER BIDDER |
| 5 | L5₹39.9 L+₹10.6 L (36.4%)Rejected-Finance | ₹39.9 L+₹10.6 L (36.4%) | L5 | Rejected-Finance HIGHER BIDDER |
Tender Value
₹45 L
EMD Value
₹90,000
Closing Date
5 Oct 2022, 6:00 pmClosed
SHRI BIJENDRA SHARMA IDSE EE
GARRISON ENGINEER (NW) VASCO Opposite KV No.2, School, Shantinagar, Vasco-Da-Gama, Goa-403802
8474/22/E8
2022_MES_551069_1
8474/22/E8
Open Tender
Civil Works
Item Rate
180 days
VASCO
Class D Category b i
9 documents required · 9 mandatory
₹500
Yes
GE NW VASCO
₹90,000
Yes
17 Nov 2022
9 Sept 2022
7 Oct 2022
9 Sept 2022
5 Oct 2022
22 Sept 2022
10 Sept 2022 - 21 Sept 2022
Amount
Taking down old unserviceable LT UG cable from any description (trenches, walls, ceilings, etc) from various locations, Supply laying, testing and commissioning under ground LT Cable XLPE insulated heavy duty armoured sheathed 1100 volts grade of cross sectional area 16 Sq mm, 4 core, with aluminium conductor, ISI marked as per IS : 7098 (Part-1) along with suitable size aluminium cable lugs, gland if required and jointed in any description complete all as specified and directed by Engineer-in-Charge. Note item No 01 to 09 :- (a) Excavation, Concrete cable protection cover, pipe, PCC work for road crossing/hard standing and Sand for cushioning will be measured and paid separately. (b) Cost of glands, aluminium cable lugs (eye lid/barrel/bottle neck type/ ring type or any shape), new nut, bolt and washers of required size/ description are deemed to include in this rate.
All as per item No. 1.00 here in before but of size 4 core 25 sqmm
All as per item No. 1.00 here in before but of size 3 1/2 core 35 sqmm
All as per item No. 1.00 here in before but of size 3 1/2 core 50 sqmm
All as per item No. 1.00 here in before but of size 3 1/2 core 70 sqmm
All as per item No. 1.00 here in before but of size 3 1/2 core 95 sqmm
All as per item No. 1.00 here in before but of size 3 1/2 core 120 sqmm
All as per item No. 1.00 here in before but of size 3 1/2 core 150 sqmm
All as per item No. 1.00 here in before but of size 3 1/2 core 240 sqmm
Excavation in trenches 1.5 Mtr wide and not exc 1.5 Mtr deep in hard/ dense soil getting out and levelling of bottom surface to required level for laying UG cable/errection of poles complete all as specified and directed by Engineer-in-Charge.
Excavation in trenches 1.5 Mtr wide and not exc 1.5 Mtr deep in soft/disintegrated rock getting out and levelling of bottom surface to required level complete all as specified and directed by Engineer-in-Charge.
Excavation in trenches by cutting of road crossing/PCC hard standing, under boundary wall for laying of pipe/cable including making good the existing surface with same finish to match the original finish complete all as specified and directed by Engineer-in-Charge.
Returning filling in, including spreading, leveling, watering and well ramming in layers not exc 25cm thick complete all as specified and directed by Engineer-in-Charge.
Removing excavated material of soils from site to a distance not exc 50 mtr away and depositing where directed not exc 1.5mtr from the starting point complete all as specified and directed by Engineer-in-Charge.
Supply and lay Double walled corrugated pipe (DWC ) confirming to IS 14930 heavy duty 63/50 mm bore for cable protection as a guard pipe including required accessories etc. complete as specified and directed.
Supply and lay Double walled corrugated pipe (DWC) confirming to IS 14930 heavy duty 110/95 mm bore for cable protection as a guard pipe including required accessories etc. complete as specified and directed.
Fixing only bollard light of any capacity complete as required complete all as specified and directed by Engineer-in-Charge. (a) Bolared will be supplied under Sch B items
Fixing only post top lantern light of any capacity complete as required complete all as specified and directed by Engineer-in-Charge. (a) Post top lantern will be supplied under Sch B items
Supply and fix or laying in trenches / on wall / poles / structures as in repairs GI tubing light grade for road crossing/for cable protection/fixing of pigmi lights etc,of the following sizes including necessary provision for cable entry if reqd in pigmi lights pole, fixing screws complete as required complete all as specified and directed by Engineer-in-Charge.
(a) 100 mm dia
(b) 80 mm dia
(c) 50 mm dia
(d) 40 mm dia
S & F in repairs LT heat shrinkable Straight through cable Jointing kit, complete with jointing material and accessories suitable for 2 core XLPE armoured Aluminium conductor cable of size 10 to 16 sqmm complete all as specified and directed by Engineer-in-Charge.
All as per item No 20.00 here in before but of size 4 core 16 to 25 sqmm
All as per item No 20.00 here in before but of size 3.5 core 35 to 50 sqmm
All as per item No 20.00 here in before but of size 3.5 core 70 to 95 sqmm
All as per item No 20.00 here in before but of size 3.5 core 120 to 150 sqmm
Material and labour for fault finding of LT cables of size 35 to 120 sqmm 3.5/4 core and any length with fault detective machine by thumbing method and suitable voltage and all as per manufactures instructions including providing straight through joint and additional cable of same existing size suitable to site requirement complete all as specified and directed by Engineer-in-Charge. Note : Cable joint and cable shall be measured and paid separeatly under relivent item of Sch 'A'
S & F in repairs HT/LT MS cable route indicator 4" dia fixed with two Nos of nut, bolt and washers and provision of PCC 1 : 4 : 8 type D-2 using 40 mm grade stone aggregate of not less than 0.018 cum in each at base buried under the ground incl necessary earth work complete all as specified and directed by Engineer-in-Charge.
Supply and fix in repair changeover swithcs on load changeover switches 4 pole 630 Amps in sheet steel enclosure with inclosure, including necessary spreaders/cable lugs/ gland / nut, bolt and washers if required complete all as specified and directed by Engineer-in-Charge.
All as per item No 27.00 here in before but of capacity 400 A 4 pole 415 Volts.
All as per item No 27.00 here in before but of capacity 320 A 4 pole 415 Volts.
All as per item No 27.00 here in before but of capacity 200 A 4 pole 415 Volts.
Taking out the existing unserviceable MCCB from any description supply and fix MCCB 4 pole 415 volts with adjutable type 125 to160 Amps with breaking capacity 25 KA complete including necessary connection with suitable size aluminum/copper cable lugs complete all as specified and directed by Engineer-in-Charge.
Taking out the existing unserviceable MCCB from any description supply and fix MCCB 4 pole 415 volts with adjutable type 200 Amps with breaking capacity 25 KA complete including necessary connection with suitable size aluminum/copper cable lugs complete all as specified and directed by Engineer-in-Charge.
Taking out the existing unserviceable MCCB from any description supply and fix MCCB 4 pole 415 volts with adjutable type 250 Amps with breaking capacity 25 KA complete including necessary connection with suitable size aluminum/copper cable lugs complete all as specified and directed by Engineer-in-Charge.
Taking out the existing unserviceable MCCB from any description supply and fix MCCB 4 pole 415 volts with adjutable type 400 Amps with breaking capacity 50 KA complete including necessary connection with suitable size aluminum/copper cable lugs complete all as specified and directed by Engineer-in-Charge.
M & L for preparation of old cement coated surface, cleaning the surface of the RCC street light pole (LT) above the ground level to top of the pole incl coping area (if provides) with one coat of ACC exterior Emulsion paint over a coat of cement primer after preparation of surface including 12 cm black paint around the pole and aluminiun paint for Iron cross arms channel/light bracket etc, including writing of pole number (MES........) complete all as specified and directed by Engineer-in-Charge.
M & L for Earthing complete with Galvanised earth plate electrode 600 x 600 x 6 mm thick buried directly in ground earth pit not less than 2.25mtr deep below normal ground level with top edge of the plate not less than 1.5 mtr below normal ground level connected to galvanised earth wire 4 mm dia by mean of nuts/bolts, check nuts and washers of brass as shown in electrical plate No. 5 of SSR Part-I including necessary excavation and earth work, GI Pipe 15 mm bore light grade for watering with Funnel, wire mesh and protection to earth lead shall be provided with GI pipe light grade 20 mm dia up to 7.5 mtr from the earth plate electrode and refilling of soil including adequate quantity of charcoal dust and common salt etc & earth work in any strata, PCC pit chamber in cement mortar 1:3:6 type C-2 with 40 mm thick Precast RCC cover slab 1:2:4 type B with 8 mm dia TMT bar and handle with lifting hooks including testing any type complete all as specified and directed by Engineer-in-Charge.
M & L for Earthing complete with GI earth plate, electrode,600x600x6.0 mm thick burried directly in ground (earth pit not less than 2.25m deep below normal ground level) filled with common salt and charcoal and connected to GI earth strip 32x 6 mm thick dia by means of GI nuts, bolts, & washers as shown in electrical plate No. 5 of SSR Part-I and Connected to earthing test point all as specified and including necessary PCC earth pit chamber of 1:3:6 and chamber cover of 50mm thick PCC 1:2:4 with 6mm dia mild steel reinforcement of 10 cm c/c spacing both ways in lieu of CI cover, watering arrangement shall be made with GI pipe light grade of 20mm dia including funnel and protection to earth lead shall be provided with GI pipe light grade 40 mm dia unto 7.5 from the earth plate electrode & refilling of soil etc including necessary excavation & earth work in any strata and PCC chamber complete all as specified and directed by Engr-in-charge including demolish existing earth pit taking out old materials.
M & L for Earthing complete with copper earth plate electrode 600 x 600 x 3.15 mm thick buried directly in ground earth pit not less than 2.25mtr deep below normal ground level with top edge of the plate not less than 1.5 mtr below normal ground level connected to copper strip size 20 x 3 mm thick by mean of nuts/bolts, check nuts and washers of brass as shown in electrical plate No. 5 of SSR part-I including necessary excavation and earth work, GI Pipe 15 mm bore light grade for watering with Funnel, wire mesh and protection to earthing strip shall be provided with GI pipe light grade 32 mm dia up to 7.5 mtr from the earth plate electrode and refilling of soil including adequate quantity of charcoal dust and common salt etc & earth work in any strata, PCC pit chamber in cement mortar 1:3:6 type C-2 with 40 mm thick Precast RCC cover slab 1:2:4 type B with 8 mm dia TMT bar and handle with lifting hooks including testing any type complete all as specified and directed by Engr-in-charge.
Attending complaints for day to day repair/maint work for outer/inner perimeter/security/street/dispersal/high mast/search lights/any description at INS Hansa area by taking down carefully the existing non operational / unserviceable lights from and description, repair/ replacement of unserviceable spares and re-fixing the same in the existing location after completion of repair work complete all as specified and directed by Engineer-in-Charge.
Note :- (a) All new spares for the above lights will measured and paid seperately under relevent itme of this schedule. (b) The contractor/contractor's supervisor shall be report to AGE E/M- I / INS Hansa maint office in all working days at 0900 AM and collect the complaint slip for defect/ unserviceable lights list at Hansa premises and carrying out and complete the repair work in the same day before 1800 hrs. If the contractor fails to complete the repair work within the 03 working days after receipt of complaint slip necessary recovery @ Rs 100.00 per fittings per day shall be recovered from the actual workdone. For that the register shall be maintained and signed by both the Engineer-in-Charge and contractor. (c) Rate for all Tools and plants, safety equipments, transport including necessary minor spares such as insulation tape, connectors, fixing screws, connecting 2 core wires up to 2 mtr length shall be included in the quoted rates. (d) All defected LED fittings and conventional type security light fittigs partially serviceable are to be deposited to AGE E/M- I Store yard.
Supply and fix in repairs cable junction boxes IP 66 protected “halogen free and weather proof” suitable for out door type (with metric knockouts for cable entry) of size 333 x 233 x 120 mm mm incl necessary suitable size new aluminium bus bar 04 Nos mounted on saddles suitable for 3 phase 4 wire system of suitable length and thickness, provn of new aluminium cable lugs for incoming & out going LT cable connections with junction box fixing clamps made up of GI flat 25 x 3 mm, nut and bolt on poles complete all as specified and directed by Engineer-in-Charge.
Supply and fix in repairs LED post top made in die-cast aluminium housing with decorative clear opal acrylic diffuser with white powder coated aluminium reflector IP-65 protection of 40 watts capacity and including connections service wire with 3 run of 2.5 Sq mm aluminium unsheathed multistranded wire complete all as specified and directed by Engineer-in-Charge.
S & F in repairs Energy efficient LED street Light Luminaire 30 unsheathed wire multistranded from LT over head line to the connector of fitting, connection wires not to be less than 2.5 metre in length duly run through GI bracket complete all as specified and directed by Engineer-in-Charge.
All as per item No 42.00 here in before but of capacity 45 watts complete all as specified and directed by Engineer-in-Charge.
All as per item No 42.00 here in before but of capacity 60 watts complete all as specified and directed by Engineer-in-Charge.
All as per item No 42.00 here in before but of capacity 90 watts complete all as specified and directed by Engineer-in-Charge.
All as per item No 42.00 here in before but of capacity 120 watts complete all as specified and directed by Engineer-in-Charge.
All as per item No 42.00 here in before but of capacity 180 watts complete all as specified and directed by Engineer-in-Charge.
S & F in repairs Street light bracket made out of GI tubing 32/40 mm dia of approx 1.2 mtr length, light grade bend to shape suitable for security / street light / Pigmi light fittings with necessary fixing arrangements by using GI flat of 40 x 6 mm size including nut, bolt, washers etc complete all as specified and directed by Engineer-in-Charge.
S & F in repairs Street light bracket made out of GI tubing 25 mm dia, light grade bend to shape of approx length 1.0 mtr long suitable for security/street light/Pigmi light fittings with necessary fixing arrangements with one coat of red oxide and two coats of synthetic enamel paint including nut, bolt, washers etc complete all as specified and directed by Engineer-in-Charge.
Taking out the existing unserviceable LED street / high bay / security light fittings of any type / make and capacity from any position for carrying out repairs, replacement of spares such as LED panel/driver or PCB of any make and re-fixing the same after repair work including necessary electric connections complete all as specified and directed by Engineer-in-Charge. Note :- New spares will be measured and paid separately as " Supply only " under item Nos 51 to 53 of this schedule
Supply only LED driver with transformer suitable for 45 to 60 watts LED street / Flood / high bay light fitting of complete all as specified and directed by Engineer-in-Charge.
All as per item No. 51.00 here in beforebut of capacity 70 to 90 watts LED fittings complete all as specified and directed by Engineer-in-Charge.
All as per item No. 51.00 here in beforebut of capacity 120 to 150 watts LED fittings complete all as specified and directed by Engineer-in-Charge.
Supply and fix in repairs Galvanised Iron cross arms channel, bracing, support, clamps etc fabricated structured steel, sections, including nuts, bolts, washers etc and cutting to required length beat to any shape drilling holes, fixed on poles or jointed by means of elect welding complete incl taking down / dismantling the old items complete all as specified and directed by Engineer-in-Charge.
Dismantling of existing old unserviceable ACSR of any size from any descritpion, material and labour for providing new ACSR conductor all as specified and directed incl stringing through existing RCC poles, fixing in insulators, jumpers with polythene pipe, aluminium binding wire etc complete of different sizes complete all as specified and directed by Engineer-in-Charge. (Note : Rates for new AAC for binding purpose is included in this rate.)
Dismantling carefully and Re-fixing with re-string of serviceable ACSR conductor of any size with new Aluminium binding wire of suitable size incl taking down the old one for replacement of pole / cross arms etc carefully complete all as specified and directed by Engineer-in-Charge. (Note: Rates for new AAC/Aluminium wire for binding purpose are included in the quoted rate.)
S & F in repairs Pin type porcelain vitreous,brown of white insulator to suit 1100 Volt working pressure of size 100 mm height, 65mm dia, including one galvanised mild steel spindle, two galvanished iron washer and one GI nut complete all as specified and directed by Engineer-in-Charge.
S & F in repairs Shackle type Porcelain, vitreous, white, brown or green insulator including galvanised mild steel straps, washers, insulator bolts, washers and nuts, of height 100 mm and dia 115 mm having working pressure 1100 volts grade complete all as specified and directed by Engineer-in-Charge.
S & F in repairs LT PVC line spacer suitable for existing 3 phase 4 wire OHT system complete all as specified and directed by Engineer-in-Charge.
S & F in repairs LT PVC line spacer suitable for existing single phase 2 wire OHT system complete all as specified and directed by Engineer-in-Charge.
S & F in repair Danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for LT, 20x15cm size complete all as specified and directed by Engineer-in-Charge.
Supply & transporting and erecting in replacement octagonal hot dipped galvanised mild steel pole with grey powder finish 7 meter long complete with top dia of size 70 mm and bottom dia of sie 130 mm including base plate of size 200X200X12 mm, foundation nuts bolts including RCC foundation of suitable size to withstand the said pole and GI bracket for mounting on top of the pole for fixing of 01 Nos of street light complete all as specified and directed by Engineer-in-Charge for street lights. Note :- (a) Cost of Excavation for removing of old RCC pole of requied lenth ,width and depth are deemed to include in this rate. (b) Cost of Excavation for fixing of New octagonal pole of requied lenth, width and depth are deemed to include in this rate.
M & L as in repairs for stay assembly complete with all sections such as stay plate, stay clamps, Stay brackets with 20 mm dia stay rod complete all as shown in electrical plate No. 1 of SSR Part 1 complete. (Note : Loop insulator, excavation and concrete work will be measured and paid separately)
M & L as in repairs for stay strand size 7/3.15 mm all as specified and fixed to stay and pole including lightening complete all as specified and directed by Engineer-in-Charge.
M & L as in repairs loop type insulator vitreous porcelian white, brown or green of size 65x90 mm overall dimension and 16 mm clearance of hole complete all as specified and directed by Engineer-in-Charge.
Supply and fix in repairs cable junction boxes IP 66 protected “halogen free and weather proof” suitable for out door type (with metric knockouts for cable entry) of size 139 x 119 x 70 mm incl necessary suitable size new aluminium busbar single phase with neutral system mounted on saddles - 02 Nos of suitable length and thickness, provn of aluminium cable lugs for incoming & out going LT cable connections with junction box fixing clamps made up of MS flat, nut and bolt on polescomplete all as specified and directed by Engineer-in-Charge.
Taking down the GI / PVC cable protection pipe along with UG cable from pole / wall by disconnecting all incoimg and outgoing connections from the unserviceable street / security light junction boxes and breaking the pole coping, opening the cable loop kept under the pipe / any description by excavation of earth work, cut the damaged portion of UG cable of any size and making new termination arrangement etc,. cut the GI / PVC pipe of required length, fix the same in the existing pole by fixing new GI clamps , provision of new cable junction boxes IP 66 protected “halogen free and weather proof” suitable for out door type (with metric knockouts for cable entry) incl necessary suitable size new aluminium bus bar 04 Nos mounted on saddles suitable for 3 phase 4 wire system of suitable length and thickness, connection of street light connections, re-filling the exavated soils incl making good the damaged coping by providing new PCC 1:3:6 & plastering of existing size complete all as specified and directed by Engineer-in-Charge.
Supply and fix Analogue type timer switch (Daily time switch) including power contactor 25 Amps, three phase, 415 volts and MCB TPN 32 Amps 10 KA 'C' series with arrangement of auto/mannual control switch duly prewired and bypass arrangement and including sheet metal enclosure of 2 mm thick CRCA sheet of adequate size with powder coated for enclosing the time switch with necessary fixing arrangements on PCC pole/wall surface by providing MS flat iron clamps 32x6 mm and nuts,bolts, washers etc complete all as specified and directed by Engineer-in-Charge.
Dismantling carefully the old unserviceable items elect motor, LT panel, elect cables, street light and iron scrap deposited to AGE E/M-I Store yard by using suitable labour, T&P, transports etc. complete all as specified and directed by Engineer-in-Charge. Location INS Hansa Area.
Taking down of existing UNSV flood light fitting of any type, supply and fix LED Flood light fittings 180 Watts incl fixing arrangement and ncluding connections with 3 run of 2.5 Sq mm aluminium unsheathed wire multistranded, necessary connections complete all as specified and directed by Engineer-in-Charge.
Taking down of existing UNSV flood light fitting of any type, supply and fix LED Flood light fittings 200 Watts incl fixing arrangement and ncluding connections with 3 run of 2.5 Sq mm aluminium unsheathed wire multistranded, necessary connections of any hight like high mast pole / LT poles / wall etc. complete all as specified and directed by Engineer-in-Charge.
Taking down of existing UNSV flood light fitting of any type, supply and fix LED Flood light fittings 240 Watts incl fixing arrangement and ncluding connections with 3 run of 2.5 Sq mm aluminium unsheathed wire multistranded, necessary connections of any hight like high mast pole / LT poles / wall etc. complete all as specified and directed by Engineer-in-Charge.
S & F in repairs LED Aviation light comprising of aluminium housing with polycarbonate enclosure, 302 Nos. LED are provided with necessary fixing arrangements & electrical connections complete all as specified and directed by Engineer-in-Charge.
Supply and laying or fixing or passing through pipe, 1100 volts grade heavy duty cable with PVC insulated 3 core stranded aluminium conductor served with an inner sheathing of PVC tape PVC sheathed 4 sqmm nominal cross section in service connection / light connections in poles from juction box to fittings complete all as specified and directed by Engineer-in-Charge.
M & L for removing vegitation, grass, scrubs and bushes or any small tree branches growing in Sub station yard along with fancing, around the pole, under the HT/LT transmission lines, yards or any description by mannually/mechanically and keep the sub station yard neat and clean complete all as specified and directed by Engineer-in-Charge. Note :- Unit rate quoted deemed to include to keep the installation neat and clean through out the period of contract and each cleaning will be measured and paid.)
M & L for Cutting and trimming of tree branches of girth upto 150 mm dia and 3 mtr all around of any size obstructing lumination of street light/perimeter lights and touching LT/HT Over head line incl removing trimmed tree branches complete all as specified and directed by Engineer-in-Charge. Note : Each cut will be measured and paid
M & L for graded coarse aggregate (broken stone or boulders) of size 40 mm in substation yard for laying complete all as specified and directed by Engineer-in-Charge.
star freeze service
D.K. ENTERPRISES
Shree Ram Enterprises
M/S J J ENTERPRISES
Prabha Electricals and Communications
OM SAI ELECTRICALS
M/s. R.S. LAWANDE
M/s J.D. DESAI
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .