Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹27.7 LAccepted-AOC | L1 | Accepted-AOC Lowest | |
| 2 | L2₹30.7 L+₹3.0 L (10.9%)Rejected-Finance | L2 | Rejected-Finance Not Lowest | |
| 3 | L3₹39.5 L+₹11.9 L (42.8%)Rejected-Finance SHOP NO 259 LOHOGAON ROAD KALWAD KHANDVE NAGAR PUNE 411032 | PUNE | MAHARASHTRA | 411032 | L3 | Rejected-Finance Not Lowest |
Tender Value
₹38 L
EMD Value
₹76,000
Closing Date
28 Oct 2021, 6:00 pmClosed
GE NORTH PUNE
Garrison Engineer North General Cariappa Marg Camp Pune 411001
GE (N) P/TOKEN- 45 OF 2021-2022REPAIRS/ MAINTENANCE/SERVICING OF DG SETS AND AMF PANELS INCLUDING DG PANEL CONTROLS, CONTACTORS AND ALLIED WORKS IN THE AREA OF AGE E/M (NORTH) UNDER GE (NORTH) PUNE
2021_MES_479213_1
GE (N) P/TOKEN- 45 OF 2021-2022
Open Tender
Electrical and Maintenance Works
Item Rate
334 days
GE NORTH PUNE
Refer tender documents.
8 documents required · 8 mandatory
₹500
GE NORTH PUNE
₹76,000
Yes
2 Feb 2022
1 Oct 2021
30 Oct 2021
1 Oct 2021
28 Oct 2021
16 Oct 2021
Amount
Maintenance and servicing to DG set once in a month including attending faults on call basis for normal repairs including replacement of defective and worn out minor parts like filters gaskets, V- belts, Engine oil, rubber hoses, worm drive clamps, nuts, bolts and cleaning of alternator with vaccum cleaner and attending faults of AMF panels etc, tappet settings if required and greasing of bearings of engine and alternator, checking of batteries, applying petroleum jelly to battery terminals, adding distilled water, checking the oil, coolent levels of capacity 380 KVA DG set installed at Southern Command Signal Centre complete all as directed by Engr- in- Charge. Note:- (i) Spares required for maintenance will be measured and paid seprately under relevant items. (ii) Servicing to be carried out as per manufacturer’s specifications/ instructions (iii) The work of maintenance shall be carried out through respective authorized dealer whose certificate shall be produced to Engineer - in - charge (iv) Proper record & test results of the same shall be maintained as directed (v) Work shall be carried out at site at different location
All as per serial item No.1.00 here-in-before but capacity 200 KVA DG set installed at PCDA Southern Command.
All as per serial item No.1.00 here-in-before but capacity 200 KVA DG set installed at Old Telephone Exchange.
All as per serial item No.1.00 here-in-before but capacity 200 KVA DG set installed at SC Signal Centre.
All as per serial item No.1.00 here-in-before but capacity 200 KVA DG set installed at Sewage Treatment Plant.
All as per serial item No.1.00 here-in-before but capacity 160 KVA DG set installed at PCDA Pump House.
All as per serial item No.1.00 here-in-before but capacity 125 KVA DG set installed at SCOM Pump House.
All as per serial item No.1.00 here-in-before but capacity 125 KVA DG set installed at Star Auditorium.
All as per serial item No.1.00 here-in-before but capacity 125 KVA DG set installed at Old telephone exchange.
All as per serial item No.1.00 here-in-before but capacity 110 KVA DG set installed at Old telephone exchange.
All as per serial item No.1.00 here-in-before but capacity 110 KVA DG set installed at Old telephone exchange.
All as per serial item No.1.00 here-in-before but capacity 100 KVA DG set installed at Old telephone exchange.
All as per serial item No.1.00 here-in-before but capacity 82.50 KVA DG set installed at Old telephone exchange.
All as per serial item No.1.00 here-in-before but capacity 70 KVA DG set installed at CE PZ Pump House.
All as per serial item No.1.00 here-in-before but capacity 63 KVA DG set at Old telephone Exchange.
All as per serial item No.1.00 here-in-before but capacity 62.50 KVA DG set installed at MES IB.
All as per serial item No.1.00 here-in-before but capacity 62.50 KVA DG set installed at Victoria Road Pump House.
All as per serial item No.1.00 here-in-before but capacity 62.50 KVA DG set installed at 64 Pump House.
All as per serial item No.1.00 here-in-before but capacity 50 KVA DG set installed at Sport Complex (Milka singh) Pump House.
All as per serial item No.1.00 here-in-before but capacity 50 KVA DG set installed at MAP JCOs Race Course Pump House.
All as per serial item No.1.00 here-in-before but capacity 50 KVA DG set installed at RSI Swimming pool.
All as per serial item No.1.00 here-in-before but capacity 50 KVA DG set installed at Parbatali Auditorium.
All as per serial item No.1.00 here-in-before but capacity 50 KVA DG set installed at Victoria Road Pump House.
All as per serial item No.1.00 here-in-before but capacity 50 KVA DG set installed at Ghorpadi No 1 Pump House.
All as per serial item No.1.00 here-in-before but capacity 25 KVA DG set installed at MES colony Pump House.
All as per serial item No. 1.00 here-in-before but capacity 20 KVA DG set installed at Shanti Vihar Pump House.
All as per serial item No.1.00 here-in-before but capacity 15 KVA DG set installed at Children School Pump House.
All as per serial item No.1.00 here-in-before but capacity 15 KVA DG set installed at Nirman Vihar Pump House.
All as per serial item No.1.00 here-in-before but capacity 15 KVA DG set installed at HQ SWAC.
All as per serial item No.1.00 here-in-before but capacity 15 KVA DG set installed at 64 Pump House.
All as per serial item No.1.00 here-in-before but capacity 7.5 KVA DG set installed at HQ SWAC.
Supply only diesel filter element with 'O' ring suitable for 380/250 KVA DG set complete all as specified.
Supply only diesel filter element with 'O' ring suitable for 200/160/150 KVA DG set complete all as specified.
Supply only diesel filter element with 'O' ring suitable for 125 KVA DG set complete all as specified.
Supply only diesel filter element with 'O' ring suitable for 110/100 KVA DG set complete all as specified..
Supply only diesel filter element with 'O' ring suitable for capacity 82.50/70 KVA DG set complete all as specified.
Supply only diesel filter element with 'O' ring suitable for capacity 63/62.50 KVA DG set complete all as specified.
Supply only diesel filter element with 'O' ring suitable for capacity 50 KVA DG set complete all as specified.
Supply only diesel filter element with 'O' ring suitable for capacity 25/20 KVA DG set complete all as specified.
Supply only diesel filter element with 'O' ring suitable for capacity 15 KVA DG set complete all as specified.
Supply only spin on filter element for lubricanting oil with 'O' ring suitable for 380/250 KVA DG set complete all as specified.
Supply only spin on filter element for lubricanting oil with 'O' ring suitable for 200/160/150 KVA DG set complete all as specified.
Supply only spin on filter element for lubricanting oil with 'O' ring suitable for 125 KVA DG set complete all as specified.
Supply only spin on filter element for lubricanting oil with 'O' ring suitable for 110/100 KVA DG set complete all as specified.
Supply only spin on filter element for lubricanting oil with 'O' ring suitable for capacity 82.50/70 KVA DG set complete all as specified.
Supply only spin on filter element for lubricanting oil with 'O' ring suitable for capacity 63/62.50 KVA DG set complete all as specified.
Supply only spin on filter element for lubricanting oil with 'O' ring suitable for capacity 50 KVA DG set complete all as specified.
Supply only spin on filter element for lubricanting oil with 'O' ring suitable for capacity 25/20 KVA DG set complete all as specified.
Supply only spin on filter element for lubricanting oil with 'O' ring suitable for capacity 15 KVA DG set complete all as specified.
Supply only by pass filter element with 'O' ring suitable for 380/250 KVA DG set complete all as specified.
Supply only by pass filter element with 'O' ring suitable for 200 to150 KVA DG set complete all as specified.
Supply only by pass filter element with 'O' ring suitable for 125 KVA DG set complete all as specified.
Supply only by pass filter element with 'O' ring suitable for 110/100 KVA DG set complete all as specified.
Supply only by pass filter element with 'O' ring suitable for capacity 82.50/70 KVA DG set compete all as specified.
Supply only by pass filter element with 'O' ring suitable for capacity 63/62.50 KVA DG set complete all as specified.
Supply only by pass filter element with 'O' ring suitable for capacity 50 KVA DG set complete all as specified.
Supply only by pass filter element with 'O' ring suitable for capacity 25/20 KVA DG set complete all as specified.
Supply only by pass filter element with 'O' ring suitable for capacity 15 KVA DG set complete all as specified..
Supply only air filter element suitable for 380/250 KVA DG set complete all as specified.
Supply only air filter element suitable for 200 to 150 KVA DG set complete all as specified.
Supply only air filter element suitable for 125 KVA DG set complete all as specified.
Supply only air filter element suitable for 110/100 KVA DG set complete all as specified.
Supply only air filter element suitable for capacity 82.50/70 KVA DG set complete all as specified.
Supply only air filter element suitable for capacity 63/62.50 KVA DG set complete all as specified.
Supply only air filter element suitable for capacity 50 KVA DG set complete all as specified.
Supply only air filter element suitable for capacity 25/20 KVA DG set complete all as specified.
Supply only air filter element suitable for capacity 15 KVA DG set complete all as specified.
Supply only fan belt complete suitable for 380/250 KVA DG set complete all as specified. Make: Fenner/ Dunlop.
Supply only fan belt complete suitable for 200 to 150 KVA DG set compete all as specified. Make : Fenner/ Dunlop.
Supply only fan belt complete suitable for 125 KVA DG set complete all as specified. Make : Fenner/ Dunlop.
Supply only fan belt complete suitable for 110/100 KVA DG set complete all as specified. Make : Fenner/ Dunlop.
Supply only fan belt complete suitable for capacity 82.50/70 KVA DG set complete all as specified. Make : Fenner/ Dunlop.
Supply only fan belt complete suitable for capacity 63/62.50 KVA DG set complete all as specified. Make : Fenner/ Dunlop.
Supply only fan belt complete suitable for capacity 50 KVA DG set complete all as specified. Make : Fenner/ Dunlop.
Supply only fan belt complete suitable for capacity 25/20 KVA DG set compete all as specified. Make : Fenner/ Dunlop.
Supply only fan belt complete suitable for capacity 15 KVA DG set complete all as specified. Make : Fenner/ Dunlop.
Supply only belt for battery charging alternator complete suitable for 380/250 KVA DG set complete all as specified. Make : Fenner/ Dunlop.
Supply only belt for battery charging alternator complete suitable for 200 to 150 KVA DG set complete all as specified. Make : Fenner/ Dunlop.
Supply only belt for battery charging alternator complete suitable for 125 KVA DG set complete all as specified. Make : Fenner/ Dunlop.
Supply only belt for battery charging alternator complete suitable for 110/100 KVA DG set complete all as specified. Make : Fenner/ Dunlop.
Supply only belt for battery charging alternator complete suitable for capacity 82.50/70 KVA DG set complete all as specified. Make : Fenner/ Dunlop.
Supply only belt for battery charging alternator complete suitable for capacity 63/62.50 KVA DG set complete all as specified. Make : Fenner/ Dunlop.
Supply only belt for battery charging alternator complete suitable for capacity 50 KVA DG set complete all as specified. Make : Fenner/ Dunlop.
Supply only belt for battery charging alternator complete suitable for capacity 25/20 KVA DG set complete all as specified. Make : Fenner/ Dunlop.
Supply only belt for battery charging alternator complete suitable for capacity 15 KVA DG set complete all as specified. Make : Fenner/ Dunlop.
Supply only rubber hose pipe set for water circuit with clamps complete suitable for 380/250 KVA DG set complete all as specified.
Supply only rubber hose pipe set for water circuit with clamps complete suitable for 200/160 KVA DG set complete all as specified.
Supply only rubber hose pipe set for water circuit with clamps complete suitable for 125 KVA DG set complete all as specified.
Supply only rubber hose pipe set for water circuit with clamps complete suitable for 110/100 KVA DG set complete all as specified.
Supply only rubber hose pipe set for water circuit with clamps complete suitable for capacity 82.50/ 70 KVA DG set complete all as specified.
Supply only rubber hose pipe set for water circuit with clamps complete suitable for capacity 63/62.50 KVA DG set complete all as specified.
Supply only rubber hose pipe set for water circuit with clamps complete suitable for capacity 50 KVA DG set complete all as specified.
Supply only rubber hose pipe set for water circuit with clamps complete suitable for capacity 25/20 KVA DG set complete all as specified.
Supply only rubber hose pipe set for water circuit with clamps complete suitable for capacity 15 KVA DG set complete all as specified.
Supply only Engine oil, multi grade premium Genuine oil 15W/ 40 as per manufacturer recommendations in DG sets complete all as specified. Make : Indian oil/ Hindustan Petrolium/ Castrol/ BPCL.
Supply and applying for petrolium Jelly (01 Kg plastic sealed container) complete all as specified and as directed. Make : Indian oil/ Hindustan Petrolium/ Castrol/ BPCL.
Supply and fill for distilled water for topping up in lead acid batteries complete all as specified and as directed.
Supply and fill for electrolyte of suitable specific gravity for lead acid batteries in sealed container complete all as specified and as directed.
Supply and fill for genuine coolant in 5 litres plastic sealed container for topping up in Radiator of DG set located at different locations complete all as specified and as directed.
Material and labour for battery leads of PVC insulated, multistranded, copper conductor of size 70 Sqmm of 1.25 metres long each duly fixed with brass clamps, copper lugs suitable for DG set batteries installed at different locations including removal of existing unserviceable one complete all as specified and as directed.
Material and labour for battery teriminal brass clamps including removal of existing unserviceable one compete all as specified and as directed.
Material and labour for disconnecting all electrical connections from DG set alternator of any capacity from base plate by opening nuts & bolts keeping aside the alternator for inspection and taking out to work shop for rewinding including testing and commissioning complete all as specified and as directed.
Rewinding of alternator field coil with super enamelled copper winding wire of class 'F' insullation as per existing size and gauge including heating, varnishing and testing for capacity 7.50 KVA DG set to 15.00 KVA DG set.
All as per serial item No.103.00 here-in-before but for capacity 20.00 KVA DG set to 25.00 KVA DG set.
All as per serial item No.103.00 here-in-before but for capacity 50.00 KVA DG set to 82.50 KVA DG set.
All as per serial item No.103.00 here-in-before but for capacity 100.00 KVA DG set to 125.00 KVA DG set.
All as per serial item No.103.00 here-in-before but for capacity 150.00 KVA DG set to 200.00 KVA DG set.
All as per serial item No.103.00 here-in-before but for capacity 250 KVA DG set to 380 KVA DG set.
Material and labour for water temperature guage including sensor and cable complete as per sample including removal of existing unserviceable one complete all as specified and as directed.
Material and labour for dismantaling the radiator and taking to work shop for overhauling & cleaning, de-scaling with acid, removal of leakage including soldering and welding, brazing as required and renewal of gaskets, nuts, bolts, mounting pads,hoses,clips, etc and refixing in its original position for capacity of 7.50 KVA to 15.00 KVA DG set complete all as specified and as directed
All as per serial item No.110 here-in-befor but for capacity 20.00 KVA to 25.00 KVA DG set
All as per serial item No.110 here-in-befor but for capacity 40.00 KVA to 50.00 KVA DG set
All as per serial item No.110 here-in-befor but for capacity 62.50 KVA to 83.00 KVA DG set
All as per serial item No.110 here-in-befor but for capacity 100.00 KVA DG set to 125.00 KVA DG set
All as per serial item No.110 here-in-befor but for capacity 150.00 KVA to 200.00 KVA DG set
All as per serial item No.110 here-in-befor but for capacity 250.00 KVA to 380.00 KVA DG set
Material and labour for repair and calibration of FIP and injectors from authorised dealer for petty repairs to make the FIP functional as per standard calibration procedure and norms including replacement of minor spares, gasket etc for smooth functioning of FIP and refixing in its original position including testing at site for capacity 7.50 KVA to 15.00 KVA DG set complete all as specified and as directed. Note :- A certificate to the effect that the calibration and repairs has been carried out by the authorised dealer shall be submitted by the contractor.
All as per serial item No.117.00 herer-in-before but for 20.00 KVA to 25.00 KVA DG set
All as per serial item No.117.00 herer-in-before but for 40.00 KVA to 50.00 KVA DG set
All as per serial item No.117.00 herer-in-before but for 62.50 KVA to 83.00 KVA DG set
All as per serial item No.117.00 herer-in-before but for 100.00 KVA to 125.00 KVA DG set
All as per serial item No.117.00 herer-in-before but for 150.00 KVA to 200.00 KVA DG set
All as per serial item No.117.00 herer-in-before but for 250.00 KVA to 380.00 KVA DG set
Material and labour for repair/ overhauling of self starting system of DG set including replacement of carbon brushes, bearings, bushes, rewinding of armature and field coil etc and varnishing of capacity 24 volts with necessary connections incluing testing and commissioing complete all as specified and as directed.
Material and labour for repair/ overhauling of self starting system of DG set including replacement of carbon brushes, bearings, bushes, rewinding of armature and field coil etc and varnishing of capacity 12 volts with necessary connections incluing testing and commissioing complete all as specified and as directed.
Material and labour for repairing of battery charging alternator engine mounted with replacement of any of the unserviceable part such as rectifier with voltage regulator, diode plate, carbon brushes of capacity 24 volts including testing and commissioing complete all as specified and as directed.
Material and labour for repairing of battery charging alternator engine mounted with replacement of any of the unserviceable part such as rectifier with voltage regulator, diode plate, carbon brushes of capacity 12 volts including testing and commissioing complete all as specified and as directed.
Material and labour for AVR (automatic voltage regulator) control unit assembly suitable for 7.5 KVA to 82.5 KVA DG set including removal of existing unserviceable one compete all as specified and as directed.
Material and labour for AVR (automatic voltage regulator) control unit assembly suitable for 100 KVA to 380 KVA DG set including removal of exsting unserviceable one compete all as specified and as directed.
Material and labour for fuel steel braided pipe with benjo bolts and washers etc of length 30 cm long including removal of existing unserviceable one compete all as specified and as directed.
Material nad labour for fuel steel braided pipe with benjo bolts and washers etc of length 45 cm long including removal of existing unserviceable one compete all as specified and as directed.
Material and labour for fuel steel braided pipe with benjo bolts and washers etc of length 60 cm long including removal of existing unserviceable one compete all as specified and as directed.
Material and labour for canopy hinges for aquastic doors with suitable bolts and nuts of DG set including removal of existing unserviceable one compete all as specified and as directed.
Material and labour for anti vibration pads with suitable bolts and washers including removal of existing unserviceable one compete all as specified and as directed.
Material and labour for carrying out repairs to AMF panel of 15 KVA to 200 KVA DG set at various installation inclduing study, tracing out circuit, testing, replacing all defective parts, rewinding existing power and control wiring with same cables including testing and commissioning complete all as specified and as directed. (Note: Spares like Volt meter, CT, power contactor required for repair will be measured and paid seperately under relevant items.
Supply only for digital type frequency meter 96 x 96 mm flush/ square pattern compete all as specified. Make: L&T/ AE or equivalent.
Supply only for LED indicator lamps R, Y, B with holder 15 mm screw type compete all as specified. Make: Rishab/ L&T/AE/ Legrand or equivalent
Supply only for CT cast resin type of ratio 400/5 Amps of suitable VA burden compete all as specified. Make: AE/ L&T/ Nutech/ Amol
Supply only for CT cast resin type of ratio 200/5 Amps of suitable VA burden compete all as specified. Make: AE/ L&T/ Nutech/ Amol
Supply and fix for CT cast resin type of ratio 100/5 Amps of suitable VA burden compete all as specified and as directed. Make: AE/ L&T/ Nutech/ Amol
Supply and fix for Power Contactor 415 Volt, 50 Hz AC suitable for DG set control panel/ AMF panel for capacity of 7.50 KVA to 15.00 KVA DG set including removal of existing unserviceable one compete all as specified and as directed. Make: Simens/ L&T/ ABB/ C&S/ Schneider.
All as per serial item No.147 here-in-before but for capacity of 20.00 KVA to 25.00 KVA DG set.
All as per serial item No.147 here-in-before but for capacity of 40.00 KVA to 50.00 KVA DG set.
All as per serial item No.147 here-in-before but for capacity of 62.50 KVA to 83.00 KVA DG set.
All as per serial item No.147 here-in-before but for capacity of 100.00 KVA to 125.00 KVA DG set.
All as per serial item No.147 here-in-before but for capacity of 150.00 KVA to 200.00 KVA DG set .
All as per serial item No.147 here-in-before but for capacity of 250.00 KVA to 380.00 KVA DG set .
Supply and fix for time delay relay suitable for 7.50 KVA to 83.00 KVA DG set including removal of existing unserviceable one compete all as specified and as directed. Make:- Simens/ L&T/ ABB/ C & S
Supply and fix for time delay relay suitable for 100.00 KVA to 380.00 KVA DG set including removal of extg unserviceable one compete all as specified and as directed. Make: Simens/ L&T/ ABB/ C & S.
Material and labour for solinoid switch assembly 24 volts suitable for 100 KVA to 380 KVA DG set including removal of existing unserviceable one compete all as specified and as directed.
Material and labour for solinoid switch assembly 12 volts suitable for 7.5 KVA to 83 KVA DG set including removal of existing unserviceable one compete all as specified and as directed.
Material and labour for self starter assembly 12 volts complete suitable for 7.50 KVA to 83 KVA DG set including removal of existing unserviceable one complete all as specified and as directed. Make: Lucas/ TVS.
Material and labour for self starter assembly 24 volts complete suitable for 100 KVA to 380 KVA DG set including removal of existing unserviceable one complete all as specified and as directed.
Material and labour for DC alternator assembly 24 volts suitable for 100 KVA to 380 KVA DG set including removal of existing unserviceable one compete all as specified and as directed.
Material and labour for DC alternator assembly 12 volts suitable for 7.50 KVA to 83 KVA DG set including removal of existing unserviceable one compete all as specified and as directed.
Material and labour for electronic speed control unit assembly 12 volts suitable for 7.50 KVA to 83 KVA DG set including removal of existing unserviceable one compete all as specified and as directed.
Material and labour for electronic speed control unit assembly 24 volts suitable for 100 KVA to 380 KVA DG set including removal of existing unserviceable one compete all as specified and as directed .
Material and labour fo SMPS (system main power supply) type control unit assembly suitable for 12 volts battery charger including removal of extg unserviceable one compete all as specified .
Material and labour for SMPS (system main power supply) type control unit assembly suitable for 24 volts battery charger including removal of existing unserviceable one compete all as specified and as directed .
Supply and fix for single phase preventer suitable for operation on 415 Volts 50 Hz AC supply including removal of existing unserviceable one compete all as specified and as directed. Make : L&T/ Minilec.
Supply and fix for three phase preventer suitable for operation on 415 Volts 50 Hz AC supply including removal of existing unserviceable one compete all as specified and as directed. Make : L&T/ Minilec.
Supply and fix for battery low maintenance lead acid of capacity 12 volts 180 AH with initial charging including removal of existing unserviceable one and hand over to store yard compete all as specified and as directed. Make: Exide/ AMCO/ Amaron.
Supply and fix for battery low maintenance lead acid of capacity 12 volts 150 AH with initial charging including removal of existing unserviceable one and hand over to store yard compete all as specified and as directed. Make: Exide/ AMCO/ Amaron.
Supply and fix for battery low maintenance lead acid of capacity 12 volts 135 AH with initial charging including removal of exsting unserviceable one and hand over to store yard compete all as specified and as directed. Make: Exide/ AMCO/ Amaron.
Supply and fix for battery low maintenance lead acid of capacity 12 volts 100 AH with initial charging including removal of extg unserviceable one and hand over to store yard compete all as specified and as directed by Engr-in charge. Make:- Exide/ AMCO/ Amaron
Supply and fix for battery low maintenance lead acid of capacity 12 volts 65 AH with initial charging including removal of existing unserviceable one and hand over to store yard compete all as specified and as directed. Make:- Exide/ AMCO/ Amaron.
Material and labour for welding MS pipe heavy duty 100 mm dia suitable for exhaust manifold of DG set with necessary scraping cutting to size as required and painting with two coats silver paint over a coat of redoxide primer including removal of existing unserviceable one compete all as specified and as directed.
Material and labour for control wiring of the DG set upto 125 KVA complete with provision of additional auto cables heavy duty suitable for generator set applications including removal of existing unserviceable one compete all as specified and as directed.
Material and labour for control wiring of the DG set above 125 KVA to 380 KVA complete with provision of additional auto cables heavy duty suitable for generator set applications including removal of existing unserviceable one compete all as specified and as directed.
Material and labour for overhauling of top only of DG set of Kirloskar/ Cummins/ Crompton Greaves make including replacement of gaskets and Oil sump packing set etc, testing on full load upto entire satisfaction of Engineer-in-Charge for capacity of 7.50 KVA to 15.00 KVA DG set complete all specified and as directed.
All as per serial item No.176 here-in-before but capacity of 20.00 KVA to 25.00 KVA DG set
All as per serial item No.176 here-in-before but capacity of 40.00 KVA to 50.00 KVA DG set
All as per serial item No.176 here-in-before but capacity of 62.50 KVA to 83.00 KVA DG set
All as per serial item No.176 here-in-before but capacity of 100.00 KVA to 125.00 KVA DG set
All as per serial item No.176 here-in-before but capacity of 150.00 KVA to 200.00 KVA DG set
All as per serial item No.176 here-in-before but capacity of 250.00 KVA to 380.00 KVA DG set
Supply and fix for solenoid valve suitable for capacity of 7.50 KVA to 15.00 KVA DG set for smooth function of DG sets including removal of existing unserviceable one complete all specified and as directed .
All as per serial item No.183 here-in-before but capacity of 20.00 KVA to 25.00 KVA DG set.
All as per serial item No.183 here-in-before but capacity of 40.00 KVA to 50.00 KVA DG set.
All as per serial item No.183 here-in-before but capacity of 62.50 KVA to 83.00 KVA DG set.
All as per serial item No.183 here-in-before but capacity of 100.00 KVA to 125.00 KVA DG set.
All as per serial item No.183 here-in-before but capacity of 150.00 KVA to 200.00 KVA DG set .
All as per serial item No.183 here-in-before but capacity of 250.00 KVA to 380.00 KVA DG set .
Material and labour for overhauling engine complete of DG set capacity 125 KVA to capacity 200 KVA of Kirloskar/ Crompton Greaves makes, by opening the top cover including dismantling the engine head, cylinder liner and piston assembly, crank shaft assembly, radiator fan belt and radiator fan, gear assembly complete removing of engine aside for repair/ replacement of parts i.e gasket, washer, 'O' ring all types etc including grinding polishing of crank shaft , head repairing and overhauling valve seat cutting and replacing, valve tapping, head assemble and testing of DG set after necessary repair with an authorised dealer, fixing at site reassembling of DG set and testing on full load upto entire satisfaction of Engineer in Charge complete all as specified and directed (Note : Spare parts will be measured and paid seperately as supply only under relevent items)
Supply only piston assembly
Supply only piston ring set
Supply only full engine gasket
Supply only main bearing set
Supply only main cylinder liner
Supply only main cylinder head copper sleeves
Supply only lock nut
Supply only big end bearing
Supply only timing belt
Supply only benjo bolt
Supply only timing belt tension adjuster
Supply only inlet valve
Supply only exhaust valve
Supply only head gasket
Supply only oil pump assembly
Supply only thrust washer
Supply only crank case gasket
Supply only head nozzle plug set
Material and labour for overhauling engine complete of DG set capacity 82.50 KVA to capacity 110 KVA of Kirloskar/ Crompton Greaves makes by opening the top cover complete including dismatling the engine head, cylinder liner and piston assembly, crank shaft assembly, radiator fan belt and radiator fan, gear assembly complete removing of engine side for repair/ replacement of parts i.e gasket, washer, 'O' ring all types etc including grinding polishing of crank shaft , head repairing and overhauling valve seat cutting and replacing, valve tapping, head assemble and testing of DG set after necessary repair with and authorised dealer fix at site reassembling of DG set and testing on full load upto entire satisfaction of Engineer in Charge complete all as directed (Note : Spare parts will be measured and paid seperately as supply only under relevent items)
Supply only piston assembly
Supply only piston ring set
Supply only full engine gasket
Supply only main bearing set
Supply only main cylinder liner
Supply only main cylinder head copper sleeves
Supply only lock nut
Supply only big end bearing
Supply only timing belt
Supply only benjo bolt
Supply only timing belt tension adjuster
Supply only inlet valve
Supply only exhaust valve
Supply only head gasket
Supply only oil pump assembly
Supply only thrust washer
Supply only crank case gasket
Supply only head nozzle plug set
Supply and fix for pressure gauge 0 to 7 Kg/ sqcm along with sensor and cables for DG set including removal of existing unserviceable one complete all as specified and as directed.
Supply and fix for microprocessor based multifunction controller suitable for DG sets operation of any capacity and showing the various parameters such as volt, ampere, frequency, RPM etc complete as per manufacturer of DG set with site requirment including removal of existing unserviceable one complete all specified and as directed.
Material and labour for chart/ diagram/ name plates/ details of DG sets made out of bakelite hylem sheet, ISI marked, 3 mm thick , cutting to shape/ size including fixing of adhesive transparent filament of red/ blue colour including cutting of filament of letters/ figures/ diagrams/ details of suitable size/ type including fixing to the wall by wooden screws and PVC hold fast etc. complete all as specified and as directed. Note : Sise of matter/ figure/ chart/ diagrams/ letter shall be give by the Engineer- in- Charge.
Supply, connecting and testing for MCCB in existing DG set panel of capacity 4 pole 63 Amps with thermal magnetic release breaking capacity 16 KA, Ics=100% Icu , suitable for 415 volts, 50 Hz, with extended terminals type, inter locked to prevent opening when the Switch is in ON position, connecting and testing complete including removal of existing unserviceable complete all as specified and as directed. Make: L&T/ ABB/ Siemens/ Schneider as approved.
All as per serial item No.231.00 but capacity of 4 pole 100 Amps with thermal magnetic release breaking capacity 25 KA, Ics=100% Icu.
All as per serial item No.231.00 but capacity of 4 pole 125 Amps with thermal magnetic release breaking capacity 25 KA, Ics=100% Icu.
All as per serial item No.231.00 but capacity of 4 pole 160 Amps with thermal magnetic release breaking capacity 25 KA, Ics=100% Icu.
All as per serial item No.231.00 but capacity of4 pole 200 Amps with thermal magnetic release breaking capacity 25 KA, Ics=100% Icu.
All as per serial item No.231.00 but capacity of 4 pole 250 Amps with thermal magnetic release breaking capacity 36 KA, Ics=100% Icu.
All as per serial item No.231.00 but capacity of 4 pole 400 Amps with thermal magnetic release breaking capacity 36 KA, Ics=100% Icu.
Supply, connecting and testing open execution on load change over switch in existing DG set panel of capacity of 4 pole 63 Amps, suitable for 415 volts, 50 Hz, with extended terminals type, interlocked to prevent opening when the switch is in ON position, connecting and testing complete including taking down of existing unserviceable one complete all as specified and as directed. Make: ABB/ Siemens/ Schneider/ Legrand as approved.
All as per serial item No.238.00 but capacity of 4 pole 100 Amps.
All as per serial item No.238.00 but capacity of 4 pole 125 Amps.
All as per serial item No.238.00 but capacity of 4 pole 160 Amps.
All as per serial item No.238.00 but capacity of 4 pole 200 Amps.
All as per serial item No.238.00 but capacity of 4 pole 200 Amps.
Supply and install cubical outdoor type, weather type, weather proof IP-54 AMF Control panel fabricated out of 3.0 mm thick CRCA MS sheet for outer panel and 1.6 mm MS sheet for internal compartments, powder coated incorporating the following items including control wiring etc. :- Mechanically and electrically interlocked 2 Nos 4 pole power contactors of suitable rating mounted side-by-side on a base plate for changeover of engine and main supply, 2 Nos of 400A 35 KA 4 pole MCCB with overload relay range of appropriate rating for incoming mains supply and engine alternator set supply control, Static battery charger of suitable rating with auto cut off facility for charging the battery from mains including AC and DC wiring, Microprocessor based Gen set controller and monitoring unit for Mains and DG set supply with AMF with all required standard controls, relays, protective systems, digital type ammeter with suitable CTs and volt meter with display, indicator lamps for various functions suitable for 200 KVA DG set complete all as specified and as directed including dismantling existing unserviceable panel. Note: a) Suitable PCC plinth for mounting the AMF panel not less than 500 mm height from the ground with adequate space not less than 600 mm in front of the panel for smooth operation shall be provided by the contractor for fixing the panel b) Adequate space shall be provided for cable entry and exit.
Supply, laying and testing in replacement of cable XLPE insulated screened, PVC bedded galvanized steel strip or wire armoured electric power cable (heavy duty) with aluminium conductor 1100 Volts grade cross sectional area 3.5 core x 400 Sq mm. complete all as specified and as directed.
Supply, laying and testing in replacement of cable XLPE insulated screened, PVC bedded galvanized steel strip or wire armoured electric power cable (heavy duty) with aluminium conductor 1100 Volts grade cross sectional area 3.5 core x 240 Sq mm. complete all as specified and as directed. Notes for item No. 245 and 246 : (i) Provision of suitable double crimpped lugs and glands deemed to be included in quoted rates. (ii) Excavation, earth work and cable protection shall be measured and paid separately under relevant items.
S&F on load change over switch in steel metal enclosure of size 400 Amps , 415 Volts, AC, 50 Hz with bus bar for connecting both incoming and outgoing cables with suitables connections with suitable size of glands etc including taking down of existing unserviceable one complete including testing & commissioning all as specified and as directed by Engineer - in - Charge. Note: Any modifications needed for fixing the open execution awitch in the panel is deemed to be included in the rates quoted and no extra payment will be done on this account.
Supply and fix Hot dipped Galvanized CABLOFIL wire mesh cable trays should comply Standard EN ISO 1461, manufactured with a longitudinal 'T - welded' safety edge, constructed with 50 X 100 mm mesh configuration including couplers, covers with clips and wall mounting accessories as per site requirement. Supports, brackets or hangers, covers designed loading capacities of the brackets and the hanger torques must be tested in accordance with the standard IEC 61537 of size 200mm width and 54mm height including taking down existing cable tary complete all as specified and as directed. Make: Legrand, C&S
M & L for cutting of Hard Standing/ Bituman Road/ taking out interlocking tiles of any size for Laying of cable through GI tubing and making good in PCC 1:2:4 type B-1 using 20 mm graded stone aggregate/ refixing of removed interlocking tiles complete all as specified and as directed. Note : GI Tubing and UG cable shall be measured and paid separatly.
Excavation in trenches n exc 1.5 wide and n exc 1.5 m in depth for foundation etc or for laying cable etc n exc 10 Sqm on plan and n exc 1.5 m in depth and getting out in soft/loose soil complete all as specified and as directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm in hard and dense soil, complete all as specified and as directed.
Removing excavated material n.exc. 50 m and depositing where directed at a level n.exc. 1.5 m above the starting point, complete all as specified and as directed.
Supply and laying 77mm outer dia, double walled corrugated (DWC) HDPE duct pipe conforming to IS-:16205 part 24 2017, PE 63 of pressure rate 4 Kg/sq.cm with antirodent and non flame propogating properties of approved colour complete with fittings for cable protection complete all as specified and as directed.
Supply and laying 90mm outer dia, double walled corrugated (DWC) HDPE duct pipe conforming to IS-:16205 part 24 2017, PE 63 of pressure rate 4 Kg/sq.cm with antirodent and non flame propogating properties of approved colour complete with fittings for cable protection complete all as specified and as directed.
S&F of GI tubing light grade of size 150 mm for protection of cable in trenches/on pole including taking down existing tubing complete all as directed by Engr-in-charge.
S & F ACB (air circuit breaker) manual draw out type of rating 1600 Amps 4 pole, 50 KA, O/L, S/C, micro processor based release and cassette mounted horizontal draw out type fully interlocked cassette door automatic safety shutters, mechanical on and off indicators, service/test/isolated position with position indicators, provision of castell lock, with O/L, S/C with 3 CT's of standard ratings 4 blocks of 6 way sliding type LT disconnectors, error prevention plug, racking handle, safety shutters and painted with finished light grey shade as per IS:631 and as per IS 13947-2-1993 inclusive suitable length of bus bars including taking complete all as specified and as directed.
Supply & Installation of Maintenance Free Earthing System consisting of a Copper bonded steel rod shall have 17.2 mm dia. & min. 10 feet length as per UL 467. The material shall have low carbon, high tensile steel molecularly bonded with 99.99% pure electrolytic grade copper thickness of minimum 250 microns with an exothermically welded Cu Busbar of (50X6X200mm) both tested by CPRI at 25 kA Fault Current carrying capacity. Copper Bonded Rod shall be UL listed. The manufacturer shall be RDSO approved to ensure the manufacturing capacity & capability along with the quality of the earthing rod. Along with a sealed bag of minimum 30 kg (10 kg Bag x 3) RoHS tested Earth Enhancement Compound tested by NABL accredited lab in compliance to IEC 62561-7 with a resistivity of not more than 1.0 ohm-m. It shall be a carbon based material and shall be free from bentonite and other hazardous substances. It shall be a permanent, non-corrosive material and will not leach any chemicals into the ground. It shall retain moisture even in high soil resistivity areas. It shall lower an earth resistance value and shall offer a constant desirable performance, including an Earth Pit cover made of Poly plastic tested at 7.5 ton load for covering of earth including taking out existing earthing complete all as specified and as directed.
S&F Earth conitnuity Copper clad steel conductor or main earthing lead fixed to wall on batten or reccess or chases or burried in ground or drawn in conduit/pipe or fixed to pole or any other indicated situation for loop earthing etc as required 8 mm dia after taking down the old one any type complete all as specified and as directed.
Note : 1. Rerformance security:- Refer Condition 22 of Special Conditions. 2. Quoted Contract Sum shall be arrived at after deducting the amount of Credit Schedule (refer Schedule of Credit in pdf form for quantity, rate and amount etc.) for old unserviceable materials retrieved from site.
PURVA ELECTRICALS AND ENGINEERS
Rama Electricals
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .