Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹1.1 CrAccepted-Finance 23A 1 SHAKTI VIHAR TANKI ROAD BADARPUR NEW DELHI 110 044 | SOUTH EAST | DELHI | 110044 | ₹1.1 Cr | L-1 | Accepted-Finance AOC is being Awarded to the lowest bidder |
| 2 | L-2₹1.1 Cr+₹1.3 L (1.16%)Rejected-Finance F 03 FIRST FLOOR PLOT NO 166 BEHIND TOKAS PLAZA AMVERHAI EXT SECTOR 19B DWARKA DELHI 110075 | DELHI | SOUTH WEST DELHI | DELHI | 110075 | ₹1.1 Cr+₹1.3 L (1.16%) | L-2 | Rejected-Finance Rejected for being other than lowest |
| 3 | L-3₹1.4 Cr+₹27.0 L (24.4%)Rejected-Finance | ₹1.4 Cr+₹27.0 L (24.4%) | L-3 | Rejected-Finance Rejected for being other than lowest |
| 4 | Rejected-Technical 301 VARDHAMAN CHAMBER II VIKASPURI NEW DELHI 110018 | WEST | DELHI | 110018 | - | - | Rejected-Technical EMD submitted in the form of DD, which is not in acceptable mode of submission EMD as per Para 1(g) and 3(a) of NIT. EMD is valid for 90 days instead of bid validity of 120 days as per para 1(g) and 3(a) of NIT. Hence not accepted in Technical Evalua |
| 5 | Rejected-Technical | - | - | Rejected-Technical EMD submitted in the form of DD, which is not in acceptable mode of submission EMD as per Para 1(g) and 3(a) of NIT. EMD is valid for 90 days instead of bid validity of 120 days as per para 1(g) and 3(a) of NIT. Hence not accepted in Technical Evalua |
Tender Value
₹1.3 Cr
EMD Value
₹2.6 L
Closing Date
8 Jun 2026, 3:00 pmClosed
CCE R N D ESTATES NORTH CHANDIGARH
CCE R N D ESTATES NORTH M-1026 Sector- 29A, Chandigarh - 160030
REPLACEMENT OF WORN OUT 2X50 TR CENTRAL AC PLANT AND 1X50 TR STAND BY CENTRAL AC PLANT INSTALLED AT TECHNICAL AREA AT ADRDE AGRA
2026_DRDO_908603_1
CCE(RD)EN/PMG-II/DEL/ AC PLANT-AGRA/1032/26-27
Open Tender
Miscellaneous Works
Percentage
180 days
ADRDE Agra
All agencies enlisted DCWnE under Composite Class-III, Class-II, Class-I, Class-I(A), Class-I(AA), Class-I(AAA), Class-I(Super) and Estate Management and Maintenance (DRDO - 2024) BIM-III, BIM-II, BIM-I class are eligible as per Appx A of NIT
4 documents required · 4 mandatory
₹0
₹2.6 L
Yes
CCE R N D ESTATES NORTH
6 Aug 2026
13 May 2026
11 Jun 2026
13 May 2026
8 Jun 2026
21 May 2026
18 May 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | WATER COOLED CHILLER
Supply, installation, testing & commissioning of Fix speed SCROLL AHRI CERTIFIED, factory designed, pre-fabricated and floor-mounted hermetically sealed scroll type water cooled chiller machine of at least 50 TR as mentioned nominal capacity and complete with scroll compressors, water-cooled type condenser, horizontal flooded type evaporator with MS shell and seamless copper tubes with elastomeric insulation, suitable numbers of hermetically sealed, lubrication system as per manufacturer's design required for smooth and trouble-free operation of the chiller package, common base frame, interconnected copper refrigerant piping along with elastomeric insulation, fittings, valves, expansion valves and accessories to interconnect compressor, condenser, chiller Ozone friendly, CFC-free refrigerant R- 410A/R407A complete all as specified and directed by the Engineer-in-Charge and accessories complete to maintain inside condition as under:
Necessary civil work viz. foundation for placement of chillers etc. shall be deemed to be included in the scope of work.
The chiller shall conform to the following requirements / specifications:
[i] Chilled water inlet / outlet temperature: 12/7˚C
[ii] Evaporator fouling factor: 0.000018 ⁰Fft²hr/Btu
[iii] Condenser water inlet / outlet temperature: 32/37˚C
[iv] Condenser fouling factor: 0.000044 ⁰Fft²hr/Btu
[v] Refrigerant (Ozone friendly type): R410A/R407C
[vi] Test standard: In accordance with ISEER / AHRI / ARI / As per OEM. | 3 | Set | 15,65,819 | ₹46,97,457 |
| 1.01 | Cooling Tower
Supplying, Installation, testing and commissioning of Induced Draft counterflow cooling Towers(CTI approved). The Cooling Tower shall be of Fiber Reinforced Plastic (FRP) Construction. The casing, basin/sump, fan deck and fan cylinder shall be of FRP,
with direct driven fans, Galvanised hardware complete with sump and drain connection with suitable valve, PVC Honey comb fill, louvers, drift eliminator complete with spray nozzle having self rotating sprinklers, steel ladder, Isolating switch and other accessories to make it fully operational and maintaince National
Accreditation Board for Testing and Calibration Laboratories (NABL) & positioning of cooling tower at Terrace of Building. Propeller Type Fan, weather proof IP 55 and Direct driven.The fan motor shall be premium efficiency IE3 class , as per IS 12615 The Cooling tower shall be capable to communicate effectively with Building Management System (BMS). Range of CT: 6 0C. Designed Duty Conditions :- EWT, LWT , D/WBT Complete as per CPWD specification/drawings and as directed by Engineer-incharge. ( Note - Cooling tower size depends on the
ambient temperature conditions , contractor must check the required design temperature). | 3 | Each | 4,25,000 | ₹12,75,000 |
| 2 | PRIMARY CHILLED WATER PUMPS
Supply, installation, testing and commissioning of PN16 rated Vertical Inline single stage centrifugal pump each capable of delivering the specified flow rate comprising the following and complete as per specifications. Casing (Volute) - Cast Iron.
Impeller - SS/Bronze - Statically and Dynamically Balanced
Casing Gasket - Confined Non Asbestos Fiber
Pump Shaft - SS 416.
Flush Line - Braided Stainless Steel
Motor Type - TEFC Squirrel Cage, Efficiency Class - IE3, Insulation - Class F, 415V ± 10% , 50Hz ± 5%, 3Ø AC Power Supply
Triple duty valve and suction Guide to be supplied along with Pumps
(2Working +1 Stand By)
Capacity of each pump (LPM) 600
Pump Head (Mt) 15
Maximum Permissible Speed 1450 RPM
Pump Efficiency Not less than 75% | 3 | Set | 47,548 | ₹1,42,644 |
| 3 | SECONDARY CHILLED WATER PUMPS
Supply, installation, testing and commissioning of PN16 rated Vertical Inline single stage centrifugal pump each capable of delivering the specified flow rate comprising the following and complete as per specifications. Casing (Volute) - Cast Iron.
Impeller - SS/Bronze - Statically and Dynamically Balanced
Casing Gasket - Confined Non Asbestos Fiber
Pump Shaft - SS 416.
Flush Line - Braided Stainless Steel
Motor Type - TEFC Squirrel Cage, Efficiency Class - IE3, Insulation - Class F, 415V ± 10% , 50Hz ± 5%, 3Ø AC Power Supply
Triple duty valve and suction Guide to be supplied along with Pumps
(2Working +1 Stand By)
Capacity of each pump (LPM) 600
Pump Head (Mt) 45
Maximum Permissible Speed 1450 RPM
Pump Efficiency Not less than 75% | 3 | Set | 62,563 | ₹1,87,689 |
| 4 | MICROBUBBLE AIR & DIRT SEPRATOR WITH INBUILT STRAINER
Supply, installation,testing & commissioning of Micro bubble Air & Dirt Separator capability,automatic air purging arrangement etc.The shell shall be constructed of mild steel with coalescence. It shall work on the principle of coalescence.The water velocity the shall not Exceed 1.5m/sec.The M.S shall to be fabricated or other similar standard.The inlet and outlet connections shall be flanged. It shall be provided with a high capacity auto air vent at the to and a drain valve at the bottom.Matching flanges, high tensile bolts & nuts and gasket shall be also provided By the manufacturer.
it shall be duly insulated 32mm thick class O Nitrile rubber insulation as per specifications complete as per specifications.The design parameters for the air separator of efficiency 96-98 % should be as follows with Safety working pressure:3.5 bar (32mm thick insulation) Line Size:400 mm diameter
Line Size: 100 mm diameter;
Design Flow: 1250 LPM | 1 | Set | 47,200 | ₹47,200 |
| 5 | Variable Pumping System Controller (For CHWPS)
Design, Manufacture, Supplying, installation, testing and cmmissioning of variable pumping system controller having VFD along with controller for secondary pumping for above pumps and change over star delta starter with total controls fitted in single console,sequential operation etc. complete along with (2+1) sets of Differential pressure transmitter of range 0-6 bar for process feed back and set point variable to operate the pumps along with connectivity to the central monitoring system.The Panel shall house other than the Drive Input MCCB/MPCB for each drive , star delta bypass circuit for individual pumps, start, stop and reset push buttons and serial communication to BMS port.
One main Incoming Protection circuit breaker with O/C, S/C & E/F Protections
Auto manual selector switch for local and remote operation.
Interfacing amongst all components and compatibility of I/O signals etc Should be Modbus RTU/ BACnet enabled for communicating with BMS & RS-485 serial communication with Pump VFD
Display: Minimum 4.3" backlit LCD
Remote or local start/stop mode of operation.
The VFD of required capacity shall be provided one each for secondry pumps installed(VFD panel Separately Provided).
All the VFD should display the dynamic head & flow rate of the pump using inputs from ultrasonic flow meter and digital pressure gauge or using sensorless algorithms,( 1 Ultrasonic flow meter and 2 pressure gauges to be supplied for each VFD driven pump).
Ultrasonic flow meter and digital pressure gauges along with the pumps supplied. | 1 | Set | 2,22,447 | ₹2,22,447 |
| 6 | PRESSURISED EXPANSION TANK
Supply, installation, testing and commissioning of pressurised chilled water Expansion Tank of capacity as given below made of MS Sheet & finished with epoxy enamel, having interchangeable butile - EPDM membrane, operating pressure 10 Kg/cm², overall height of the tank shall be limited to 2.4 meter & the tank shall be complete with necessary controls as required. Size of tank is for guidance only & AC Contractor to quote as per actual requirement
Capacity of the pressurised tank - 100 Liters | 1 | Set | 73,686 | ₹73,686 |
| 7AIR HANDLING UNITS Supply, Installation, Testing and Commissioning of factory built Air Handling Units with 40+2mm Thick Panel of density not less than 40Kg/CuM having outer sheet of Precoated GI in 0.8mm thickness & inner sheet with 0.8mm having thermal break profile. The air handling units shall be complete with pre-filter (MERV-8), High efficiency medical contamination filtration with dia-electric media with efficency not less than <90 % of PM .1 micron alongwith <95 % of gases contamination removal with 350 mm depth (CBR- Certification IACS for filteration efficiency, Green Pro, ISO, FDA & RoHS - refer details specifcation for CBR Filter for compliance) in the AHU along with necessary frames, Air Decontamination Chamber in the supply air/ plenum comprising of nanoX coating plasmOX having EPA approved metallic compound of five metals targeted on Alumninum matrix cell duly enclosed by a poly quartz casing tube with the capability to produce ionized Hydroxyl oxidizers having following wattage for different CFM's, refer details specification for Air Decontamination System for compliance with the following certification CE, ROHS, ISO, FDA, Green Pro, CCMB, FICCI, TUV & Human Epithelial test By IIT Guwahati)Note: The AHUs should be supplied with a pair of pre-commissioning filters which will be replaced by the actual filters during commissioning Fine Filter Section:The AHU shall be provided Fine filter section containing Synthetic 300 mm Bag, class F7, equivalent to EU7 (MERV 13) of ASHRAE 52.2 1999 .The efficiency of the filters shall be 95% down to particle size of 5 microns as per EN 779. Differential pressure measuring port to check filter efficiency all complete as required Coil Section: Chilled water Cooling coil of 6 row copper tube with Factory Fitted UL Tested 60335 Lamps with D90 certification lamps as per ISO, coil section with multi-rows deep chilled water cooling coil of copper tube & aluminium fin with hydrophilic coating with SS-304 end plates, Fan section with High Efficiency SISW Plug fan Airfoil blades with AC Motor, motor suitable for operation on 415±10% Volts, 50 Hz, 3 Phase AC power supply, insulated SS drain pan, copper header with "Copper to MS" adopter, with Celdeck pad along with reciculation pumps, vibration isolation pads etc. all complete as per the specifications. AHUs shall be selected for a maximum face velocity of 525 FPM (2.5 MPS). Unit outlet velocity shall not exceed 2000 FPM (10.2 MPS). The unit shall be provided mixing box having access doors/ panels for fresh air and return air duct termination as per "Approved for Construction" - Shop Drawings. | |||||
| 7.01 | Mechanical performance of AHU casing shall be tested as per EUROVENT 1886 should meet the following characteristics: As per EUROVENT 1886
Mechanical Strength-D1
Thermal Bridging-TB2
Thermal Transmittance-T2
Air Leakage-L1
Cooling Coil Section:
SS-304 construction end plates with Hydrophilic costing on Fins to be provided.
Fan Section:
Fan section shall be equipped with a Single Inlet Centrifugal Impeller with High Efficiency Backward curved airfoil blades and AC motor, energy optimized for operation without spiral housing for high efficiency and favorable acoustic behavior.
The minimum efficiency class of the motor shall be equivalent to IE4 suitable for continuous operation. The speed of the motor shall be varied with variable frequency drive. The fan in totality shall be of most efficient type so that the power Consumption and noise level is minimal. The motor shall be minimum IP54 protection class.
Fan Static Indicated are tentative for external ducting work only, however internal static pressure of AHU shall be as per OEM Standards. Contractor shall submit fan static calculations based on approved shop drawings & as per actual site condition before ordering the unit. Any rise in static required shall be offer by contractor without any additional cost. | - | - | - | - |
| 7.02 | FM AHU 1x 10000 CFM/14 TR/65 MM STATIC/6RD with CHW and HWC/Sound less than 40 Db | 2 | Set | 4,86,603 | ₹9,73,206 |
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.38 MB
BOQ_954954.xls
BOQ • 0.47 MB
GCC2023.pdf
Additional Documents • 5.89 MB
NITFinal.pdf
Tender Documents • 1.36 MB
1.pdf
PDF • 0.51 MB
1032AgraCorrigendum.pdf
PDF • 1.65 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .