Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹14.6 LAccepted-AOC SR NO 331 2B PLOT NO 43 R H NO 02 BALDEWA RAO BUNGLOW NEWA NMC WATER TANK PATHARDI SHIVAR NASHIK 422 009 INDEX NO E 84CWE AF LOHEGAON PUNE | NASHIK | MAHARASHTRA | 422009 | L1 | Accepted-AOC BeingL1 | |
| 2 | L2₹15.7 L+₹71,552.80 (4.78%)Rejected-Finance | L2 | Rejected-Finance BEING NOT L1 | |
| 3 | L3₹15.7 L+₹72,581.80 (4.85%)Rejected-Finance | L3 | Rejected-Finance BEING NOT L1 | |
| 4 | L4₹15.7 L+₹74,991.80 (5.01%)Rejected-Finance | L4 | Rejected-Finance BEING NOT L1 | |
| 5 | L5₹15.8 L+₹80,619.30 (5.38%)Rejected-Finance | L5 | Rejected-Finance BEING NOT L1 |
Tender Value
₹15 L
EMD Value
₹30,000
Closing Date
17 Jan 2023, 6:00 pmClosed
GE AF OJHAR
GE AF OJHAR
Repair Replacement and maintenance of various capacity DG Sets and connected items in AF station Deolal
2022_MES_570575_1
8956/E8
Open Tender
Electrical and Maintenance Works
Item Rate
335 days
DEOLALI
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE AF OJHAR
₹30,000
Yes
11 Apr 2023
22 Dec 2022
19 Jan 2023
23 Dec 2022
17 Jan 2023
5 Jan 2023
Amount
M&L for preventive checks/breakdown maintenance of DG set by deputing skilled service mechanic to attend the DG set as per the requirement for carrying out scheduled preventive checks/breakdown maintenance for smooth functioning of DG set of any make all as directed by engineer-in Charge of cap 15 to 25KVA DG Set.
All as per item no-1 but capacity of DG set 40 KVA
All as per item no-1 but capacity of DG set 62.5KVA
All as per item no-1 but capacity of DG set 100KVA
All as per item no-1 but capacity of DG set 200KVA
All as per item no-1 but capacity of DG set 250KVA
All as per item no-1 but capacity of DG set 320KVA
Supply and fix in repalcement of following spares for DG Set of capacity 15 KVA to 40 KVA
Diesel fuel filter
Lub Oil Filter
Air filter(Inner and Outer)
Hose pipe Set
V belt set
Supply and fix in repalcement ogf following spares for DG Set of capacity 62.5 KVA to 100 KVA
Diesel fuel filter
Lub Oil Filter
Air filter(Inner and Outer)
Hose pipe Set
V belt set
Supply and fix in repalcement ogf following spares for DG Set of capacity 200 KVA to 320 KVA
Diesel fuel filter
Lub Oil Filter
Air filter(Inner and Outer)
Hose pipe Set
V belt set
M& L for draining out old engine Oil from Chamber of the DG Set Of any capacity ,cleaning of chamber thoroghly and filling new engine oil of grade 20W40 Complet all as specified and directed
Calibration of FIP from authorised service centre for matching the RPM of DG set and output voltage complete all as per manufacturer's instructions and as directed..
Supply and fix in repair high pressure fuel line with end coupler complete from FIP to injector with new high pressure line fixed properly (without any leakage) to the engine complete all as per manufacturer's instructions and as directed.
Supply and fix in repair Alternator Assembly for battery charging of 24 Volts complete all as per manufacturer's instructions and as directed. Make: Lucas or equivalent as approved by GE.
Supply and fix in repair radiator fan belt of suitable size complete all as per manufacturer's instructions and as directed..
M& L for cleaning and descaling of radiator assembly by using suitable chemical and blower fan ,injecting water with high pressure in water tubings so as to remove all dirts in the fins, taking down the copper bottom portion of tank for welding / brazing and refit the same after replacing the unserviceable and damaged fins tank cap rubber bush and refix the same at the engine of DG sets complete all as per manufacturer's instructions and as directed..
Opening of the above mentioned DG set alternator of capacity 62.5 KVA TO 320 KVA and taking out the worn out parts ,lifting, loading and transportation of DG set/Alternator to the work shop for rewinding/lathe work and taking back to MES store yard /installation after repair work, re-assembling of DG sets including testing complete all as per manufacturer's instructions and as directed. Note:- Worn out parts which are to be replaced shall be measured under Ser item No.2.09 to 2.14 here in below.
Supply and fix in repair rectifier /Diode plate all as per manufacturer's instructions and as directed.
S & F in repair internal wiring with suitable gauge of copper wire all as specified and as directed.
Cleaning of rotor slots all as per manufacturer's instructions and as directed..
S&F in repair carbon brush set all as per manufacturer's instructions and as directed..
S&F in repair slip rings all as per manufacturer's instructions and as directed..
S&F in repair copper terminal lead ( 95 sqmm) heavy duty for battery (length 1.5m) connection with suitable size of copper lugs on one side, brass lead on other end all as per manufacturer's instructions and as directed..
Repair to DG SET 40 KVA to 100 KVA:- Disconnect the electrical connection of DG sets ,situated at site ,opening of the engine head cover, remove the cylinder head , Supply and fix in replacement of piston , piston rings and replacement of fuel injector, complete overhauling of Engine by removal of carbon accumulation from cylinder inner layer and piston , replacement of oil and water seal etc all as directed by Engg-in-charge. Make: Kirloskar/Cummins (Notes:- (i)Tenderer's quoted rate is deemed to be inclusive of disconnecting /dismantling /opening of DG Set, and repair/ replacement of items described above etc., as directed. (ii)The other repair / replacement works as described below which are essential for proper functioning of DG set shall be measured and paid separately vide item No.3.01 to 3.16 here in below and the cost of these items of repair works shall not be included in the unit rate quoted for item No.3.00
Calibration of fuel line/ fuel pump and fuel injector from authorised service centre for matching the RPM of DG set and output voltage complete all as per manufactures instruction and as directed.
S & F in repair high pressure fuel line with end coupler complete from FIP to injector with new high pressure line fixed properly (without of any leakage) to the engine all as per manufacturer's instructions and as directed..
Remove and refix radiator assembly by brazing / welding if any leakage complete of suitable dimension with cleaning of copper fins by high pressure jet of air / water including connecting ,testing complete all as per manufacturer's instructions and as directed..
S&F in repair anti vibration pad Make : Dunlop or equivalent as approved by GE complete all as specified and as directed.
S&F in repair bottom chamber with nuts and bolts all as specified and as directed.
S&F in repair fuel flexible pipe of suitable length and size as per existing complete all specified and as directed.
S&F in repair water hose pipe of suitable size and length complete all as specified and as directed.
S&F in repair fuel filter Assembly complete all as per manufacturer's instructions and as directed.
Opening of the DG set pf capacity 15 KVA to 40 KVA alternator and taking out the worn out parts, lifting, loading and transportation of DG set/ Alternator to the work shop for rewinding/lathe work and taking back to MES store yard/ installation after repair work, re-assembling of DG sets including testing complete all as per manufacturer's instructions and as directed.
S&F in repair carbon bushes complete all as per manufacturer's instructions and as directed.
Cleaning the rotor slots complete all as per manufacturer's instructions and as directed.
Disconnect the self starter from the engine ,loading and shifting motor to work shop for repair to starter by change of carbon bushes , solinoid switch and change of slip rings etc. taking back to MES store and connect to engine including ,commissioning and testing complete all as directed.
S&F in repair ignition switch assembly complete with nuts and bolts on DG set including all electrical connection by using suitable gauge of copper wire and testing complete all as specified and directed.
S & F In repair rubber coupling, bush with rubber ring nuts and bolts of plate type or round in shape as per sample complete all as specified and directed.
S&F in repair copper terminal heavy duty for battery (length 1.5m ) connection with suitable size of copper lugs on one side and brass lead at other end all as directed.
S&F in repair AVR of Suitable capacity applicable for 40 to 100KVA DG Set all as specified and as directed.
M&L for cleaning and descaling of radiator assembly of any size situated at site by using suitable chemical and blower fan ,injecting water with high pressure in water tubings so as to remove all dirts in the fins, taking down the copper bottom portion of tank for welding / brazing and refit the same after replacing the unserviceable and damaged fins, tank cap, rubber bush and refix the same at the engine of DG sets complete all as per manufacturer's instructions and as directed.
S&F in repair asbestos rope on exhaust pipe of DG sets of any capacity complete as per existing and as directed
Dismantling the exhaust pipe of DG sets at site, carry out necessary repair by necessary welding works and refix the exhaust pipe at the same location all as directed by Engineer-in-charge. (Note: The rate quoted by the contractor shall be deemed to be include any additional cabling work/ interconnection of AMF panel to DG set/ DG set to existing panel if required all as directed).
Supply and fill coolant of standard specification for top up in radiator of Diesel Engine of any size all as specified and directed.
M&L for painting to the entire body of DG sets including canopy enclosure by scrapping out (and flames if necessary) the old paints , denting, spray painting to the entire body of DG set with minimum two coats of synthetic enamel paint to achieve bright finish of military green colour over a coat of primer and writing of MES/SM No of DG set all as directed. of capacity Above 25 KVA up to 63 KVA DG sets
All as per item no-60 above but above 100 KVA
All as per item no-60 above but Up to 25 KVA
Opening of the AMF panel by unscrewing screws, nuts bolts etc after removing all connection to DG sets and LT panel and reassemble the AMF panel after repair / replacement of worn out parts including fixing only the serviceable parts/ new parts complete including all connection, commissioning and testing complete all as specified and directed. Note:-Supply only requisite spare parts shall be measured and paid separately vide item No.10.00 here in under.
Supply in replacement only the following spare parts of AMF panel as per existing capacity and make:-
Control relay
OD DC timer
Line voltage monitor
Announciator
EF relay
Power contactor ,heavy duty ,4 pole of any capacity.
Current Transformer
Repairs to broken disconnected door of DG Set by welding with new hinges, of suitable sizes , supply and fix new door locks as per existing complete all as directed for smooth opening and closing of door .
Lifting, loading and transportation of lead acid battery to work shop and repair to lead acid battery of 12 volt of 90/130/180 AH by filling up of distilled water, change of worn out cells, changing of unserviceable electrode/ electrolyte and changing of unserviceable terminal and taking back to MES store yard refixing for its original position etc complete all directed .
M&L for rewinding of main stator (Field) with suitable gauge of super enamelled copper wire duly varnished, insulated all as specified and directed for 15 KVA up to 40 KVA
All as per item no-76 above but Above 62.5 KVA up to 100KVA
Removing of main rotor from stator assembly by dismantling alternator from engine after disconnection of electric connection and rewinding of main rotor with suitable gauge of super enamelled copper wire with 'F' class insulation complete all as per manufacturer's instructions and as directed for 15 KVA up to 40 KVA
All as per item no-78 above but Above 62.5 KVA up to 100KVA
Supply only distilled water in packed PVC container for lead acid battery complete all as directed.
Material and labour for earthing complete with galvanized steel earth plate electrode of size 60cm x 60 cm x 6 mm thick buried directly in ground ( earth pit not less than 2.25 mtr deep below ground level) with top edge of earth plate not less than 1.5 mtr below ground level connected to galvanized iron strip 25 x 4 mm by means of of galvanized iron nuts & bolts or as directed at site by Engineer -in-Charge protected by GI Pipe 40 mm dia light grade and connected to test point and further connected to equipment, mcachinery, electrical panel or any other as directed by Engineer-in-Charge, which to be earthed, all as shown in electrical plate No 3 of SSR Part I including providion of concrete earth pit constructed in PCC 1:3:6 type C-1 as earth pit and PCC 1:2:4 type B-1 for cover slab with necessary reinforcement with handle for lifting also including provision of funnel with wiremesh with 20 mm GI pipe medium grade for watering, charcoal and salt in alternative layers of 15 cm thick all around the electrode , including necessary excavation and earth work , testing and commissioning complete all as directed at site.
All as per item No.81 above but by using with copper earth plate electrode of size 60cm x 60 cm x 3.0 mm thick and copper strip 20 x 3 mm as earth continuity conductor complete all as directed by Engineer-in-Charge.
SHRI SULAI ELECTRICALS
M/s.NIKI ENTERPRISES
K R Electricals
Datar Electrical and Engg Services
United Enterprises
LOKMANYA ENTERPRISES
SIDDHIVINAYAK ENTERPRISES
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .