Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.3 CrAccepted-AOC | ₹1.3 Cr | L1 | Accepted-AOC Accepted |
| 2 | L2₹1.6 Cr+₹28.3 L (21.1%)Rejected-AOC | ₹1.6 Cr+₹28.3 L (21.1%) | L2 | Rejected-AOC Rejected |
| 3 | L3₹1.8 Cr+₹44.9 L (33.5%)Rejected-AOC | ₹1.8 Cr+₹44.9 L (33.5%) | L3 | Rejected-AOC Rejected |
| 4 | Not Admitted-Fee/PreQual/Technical | - | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
₹1.2 Cr
EMD Value
₹1.5 L
Closing Date
27 Jul 2021, 11:00 amClosed
Executive Engineer
JSV Division Rohru
SH C o 1No Percolation well C o Anchor Block Pump House cum attendant quarter Prov Laying jointing of Rising main Supplying errection of pumping machinery Stage 1st Booster stage and Supplying and errection of submersible pumpset alongwith its
2021_HPIPH_49779_1
JSV-RD-AB-Tender 21-3598-3625
Open Tender
Civil Works - Others
Item Rate
180 days
Rohru Town
Tender Document
8 documents required · 8 mandatory
₹1,500
Yes
EE Rohru
₹1.5 L
Yes
24 Nov 2021
12 Jul 2021
27 Jul 2021
12 Jul 2021
27 Jul 2021
12 Jul 2021
Amount
Excavation in foundation, trenches etc., in earth work, lift upto 1.50 mtrs. Stacking the excavated soil not more than 3 mtr. clear from the edge of the excavation and then returning the stacked soil in 15cm. Layers, when required into plinths sides of foundations etc., consolidating each deposited layer by ramming and watering and then disposing of all surplus excavated earth in a lead of 20mtr.(Pick work/Jumper work) within all leads and lifts and as directed by the Engineer-in-charge.
Providing and laying cement concrete 1:3:6 (1cement:3 sand:6 graded aggregates 40mm nominal size) & curing complete excluding cost of form work in foundation & plinth within all leads and lifts and as directed by the Engineer-in-charge
Providing & laying cement concrete 1:1.5:3 (1cement:1.5 sand: 3 graded aggregates 20mm nominal size) & curing complete excluding cost of form work & reinforcement for reinforced concrete work in:
Foundation, footing and bases of columns & the like mass concrete within all leads and lifts and as directed by the Engineer-in-charge.
Walls including attached buttress, pillasters and their caps and string courses etc. upto floor to level within all leads and lifts.
Column, pillars post & struts upto floor two level with in all leads and lifts and as directed by the Engineer-in-charge.
In suspended floor roofs, landing shelves & their support balconies,beams, girders bressumers & contilevers upto floor two level within all leads and lifts and as directed by the Engineer-in-charge.
Stair cases (except spiral stair cases) excluding landing but including preparing of the surfaces & finishing of nosing upto floor two level within all leads and lifts and as directed by the Engineer-in-charge.
Side of beam, beam haunchings, cantilevers, lintels etc. not exceeding 1 mtrs. In depth in all height from floor.
Providing form work with steel plates 3.15mm thick welded with angle iron in frame 30x30x5mm. so as to give a fair finish i/c centering shuttering propping etc. with wooden battens and ballies, height of propping & centring below supporting floor to ceiling not exceeding 4mt. height & removal of samefor in situ reinforcement concrete and plain concrete work in:
Foundation footing bases of columns & mass concrete within all leads and lifts and as directed by the Engineer-in-charge.
Column.pillar & post upto floor two level square, rectangular& polygonal in plan within all leads and lifts and as directed by the Engineer-in-charge.
Beams, cantilever girders& lintals sides & soffits of beams, beams,haunching cantilever bressumers and lintels not exceeding 1mtr. In depth in all heights from floor within all leads and lifts and as directed by the Engineer-in-charge.
Flat surfaces such as soffits of suspended floor roofs landing & like floor etc.,upto 200mm thickness within all leads and lifts and as directed by the Engineer-in-charge.
Vertical surface such as wall(any thickness) partitions and the likeincluding attached pillasters, buttresses, plinth and string cources and thelike within all leads and lifts.
Slopping and battering surfaces i/c folding plates where inclination to horizontal plane not exceeding 30 degrees within all leads and lifts and as directed by the Engineer-in-charge.
Edge of slab and break in floor and wall 20 cm wide within all leads and lifts and as directed by the Engineer-in-charge.
Stair cases with sloping or stepped soffits excluding landing. Beams, cantilever, girders and lintels within all leads and lifts and as directed by the Engineer-in-charge.
Side of beam, beam haunchings, cantilevers, lintels etc. not exceeding 1 mtrs. In depth in all height from floor.
Providing mild steel/tor steel reinforcement i/c bending binding and placing in position complete upto floor two level (Mild steel) within all leads and lifts and as directed by the Engineer-in-charge.
Providing & laying CC 1:2:4 1cement:2 sand 4 graded aggregates 20mm nominal size curing complete excluding cost of form work & reinforcement for RCC work in:- with in all leads and lifts as per the direction of the Engineer in charge.
In suspended floor roofs landing shalves & their support balconies,beams, girders bressumers cantilevers upto floor two level
10 mm thick cement plaster on fair sides of brick/stone masonery convrete walls for interior plastering upto floor two level including arises internal rounded angles not exceeding 80mm girth in CM 1:3 (1cement:3sand) with in all leads and lifts as per the direction of Engineer - In- Charge.
15 mm thick cement plaster on fair sides of brick/stone masonery convrete walls for interior plastering upto floor two level including arises internal rounded angles not exceeding 80mm girth in cm 1:6 (1cement:6sand)within all leads and lifts and as directed by the Engineer-in-charge.
20 mm thick cement plaster on rough sides of brick/stone masonery convrete walls for interior plastering upto floor two level including arises internal rounded angles not exceeding 80mm girth in cm 1:6 (1cement:6sand)within all leads and lifts and as directed by the Engineer-in-charge.
6 mm thick cement plaster in cement concrete 1:3( 1cement 3 sand in roof slabs within all leads and lifts and as directed by the Engineer-in-charge.
Providing and fixing pressed steel doors frames manufactured from commercial mild steel sheet of 1.25mm thickness i/c hinges jump lock jamb, beed and if required angle threshold of mild steel angle of section 50x25mm or base ties of 1.25mm pressed mild steel welded or regidly fixed together by mechanical means, adjustable luge with split and tails to each jamb i/c steel but things 2.5mm thick with guards, lock strike plate and shock as specified and applying a coat of approved steel primer after pretreetment of the surface as directed by the Engineer-in-charge.
Profile-A.
Profile-B.
Profile-C.
Providing and fixing Pannelled and glazed shutters for doors windows and clear storey windows including bright finish black enamel led iron butt hinges with necessary screws 40mm thick: 2nd class deodar wood within all leads and lifts and as directed by the Engineer-in-charge.
P/F wire gause shutters using MS wire gause of IS gause designation 85 G for doors windows clerestorey windows I/c bright finished black enamelled iron hinges with necessary secrews 40 mm thick 2nd class deodar wood within all leads and lifts and as directed by the Engineer-in-charge.
White washing with lime on undecorated wall surfaces(two coats) to give an even shade i/c thoroughly brooming the surface to remove all dust dirt & other foreign matter within all leads and lifts and as directed by the Engineer-in-charge.
Distempering (two coats) with oil bond distemper of approved brand and manufacture and of required shade on undecorated wall surfaceto give an even shade over and including priming coat with distemper primer of approved brand and manufacture after throughly brushing the surface free from mortar dropping and other foreign matter and also including preparing the surface even and sand papered smooth. Priming coat with distemper primer within all leads and lifts and as directed by the Engineer-in-charge.
Finishing wall with water proofing cement paint of approved brand and manufacture and of rerquired shade on undecorated wall surfaces (two coats) to give an even shade after thoroughly brushing the surface to remove all dirt and remains of loose powdered materials within all leads and lifts and as directed by the Engineer-in-charge.
Providing and fixing 10mm thick antiskid water proof stain and impect resitent resistent heavy duty vetrified tiles Nitco or equivalent 600x600mmx10mm manufactured or approved shade and colour in flooring treads of steps and landings laid over (12mm thick cement mortar 1:3)(1Cement:3Sand)jointed with cement slurry mixed with pigment to match the shade of tiles as required complete within all leads and lifts and as directed by the Engineer-in- charge.
Applying priming coat over new wood and wood based surfaces after and including preparing the surface by throughly cleaning oil grease & dirt and other foreigm matter within all leads and lifts and as directed by the Engineer-in-charge.
Painting two coats(excluding priming coat) on new wood and wood based surfaces with ready mixed paint brushing to give even shade including cleaning all dirt, dust and other foreign matters white paint within all leads and lifts and as directed by the Engineer-in-charge.
Painting two coats(excluding priming coat) on new wood and wood based surfaces with ready mixed paint brushing to give even shade including cleaning all dirt, dust and other foreign matters other than white paint within all leads and lifts and as directed by the Engineer-in-charge.
Providing and fixing of MS grill of required patttern in wooden frame of window etc. with MS rounded headed bolts and nuts or by screw: Plain Grill within all leads and lifts and as directed by the Engineer-in-charge.
Stone soling properly hand packed filling interstices with spalls and consolidating with power road roller to the required gradient and camber including spreading watering and rolling of binding materials moorum or earth etc. 100mm spread thickness (finished work including materials and labour) within all leads and lifts and as directed by the Engineer-in-charge.
Providing and fixing anodized aluminium sliding door bolts withnuts and screws complete I) 250mmX16mm within all leads and lifts and as directed by the Engineer-in-charge.
Providing and fixing anodized aiuminium. tower bolts barrel type with screws etc. complete within all leads and lifts and as directed by the Engineer-in-charge.
I) 200mmX10mm
ii) 100mmx10mm
Providing and fixing anodized aluminium .handles with screws etc. complete within all leads and lifts and as directed by the Engineer-in-charge.
I)125mm dia
ii) 100mm dia
Providing 40x3 mm flat iron hold fast 40cm. Long including fixing to frame with 10mm dia metres bolts, nuts and wooden plug and embedding in cement concrete block 30x10x15cm. 1:3:6( 1cement:3sand:6 graded stone att. 20mm nominal size) within all leads and as directed by the Engineer-in-charge.
Providing plinth protection 50mm thick in cement concrete 1:3:6(1cement:3sand:6graded stone agg. 20mm nominal size) i/c finishing the top surface of concrete smooth within all leads and lifts and as directed by the Engineer-in-charge.
Steel work welded in built up sections, trusses and framed work, including cutting, hoisting fixing in postion and applying a priming coat of red lead paint etc.In beams joists channels, angles tes, flats with connection plates or angle cleets as in main and cross beems, hip and jack rafters, purlins connected to common rafter and the like within all leads and lifts and as directed by the Engineer-in-charge.
Providing & Fixing of Finalax pipe 40mm dia. Under floor ( for connection cables) including all req. fitting i.e elbows, sockets etc.
Providing and fixing 0.60mm thick prepainted steel sheet in roofing with hot dipped metallic zinc coated sheet with top coat of regular modified polyster (RNP) organic coating to back coat of polyster of 5microns over 5 micron premier coating including fixing with prepainted iron J or L hooks, bolts and nuts 6mm dia mtr.with prepainted limpet and rubber washers complete with all accessories as required as per the direction of the Engineer-in-charge.
Providing and fixing ridges or hips 60cm over all with 0.60 thick prepainted steel sheet in roofing with bot dipped metallic zinc coated sheet with top coat of regular modified polyster (RNP) organic coating to back coat of polyster of 5 microns over 5 miscron premier coating including fixing with prepainted iron J or L hooks, bolts and nuts 6mm dia mtr.with prepainted limper and rubber washers complete with all accessories as required as per direction of Engineer-in-charge.
Supplying of various material for pump House
Tool Kit for pump house ( 24 items ) with all accessories
Insulation mate ( 6'x4' ) bearing puller, insulation gloves
Poly Chairs, table and stool 1 Nos each for pump house
welding set 1 Nos
Xerox machine & HP Printers for office use
GPS System
Half brick masonry in common burnt clay building brick in cement mortar 1:4(1cement:4sand) 1st.class brick within all leads and lifts and as directed by the Engineer-in-charge.
Dry brick /boulder filling round soak pit 2nd class with in all leads and lifts as per the directions of the Engineer in charge.
Providing and placing horizontal layers filtering media duly graded screened washed and cleaned as specified by the Engineer Incharge with in all leads and lifts.
(i) Prov. Dry Bricks for filter bed/septic tanks
(ii) Coarse sand 3mm to 6mm
Providing and fixing vitreous China wash down water closet (European type. W.C. Pan) with integral 'P' or 'S' trap including jointing the trap with soil pipe in cement mortar 1:1 (1Cement : 1 Sand) (Seat and cover to be measured and paid for separately) Ordinary type.
Providing and fixing Stainless steel kitchen sink with drain board with in all leads and lifts as per the directions of the Engineer in charge. 470X 420X 178MM
Prorviding and fixing vitreous china wash basin with single hole for piller tap with C.I. or M.S. brackets painted white Flat back 630mmx450mm within all leads and lifts and as directed by the Engineer-in-charge.including cutting holes and making good the same but excluding fittings:-with in all leads and lifts as per the directions of the Engineer in charge.
Providing and fixing PTMT Coloured / white high density polyethlylene / poly propylene 10 liters cap. full flush European standard control low level flushing Cistern with fitting and within all leads and lifts and as directed by the Engineer in charge.
P/F C.P. brass waste for wash basin or sink (i)32mm diawith in all leads and lifts as per the directions of the Engineer in charge.
P/F C.P. soap dish with C.P. brass brackets fixed to wooden cleats With C.P. brass screws with in all leads and lifts as per the directions of the Engineer in charge.
P/F C.P. Brass Bib tap with capstan head(15mm dia) with in all leads and lifts as per the directions of the Engineer in charge.
P/F brass full wheel valve with capstan head(15mm dia)within all leads and lifts and as directed by the Engineer-in-charge,
P/F C.P. Angle cock 15mm dia within all leads and lifts as per the directions of the Engineer-in-charge,
P/F of GI Elbow 15mm with in all leads and lifts as per the directions of the Engineer in charge.
P/F of GI Tee15mm with in all leads and lifts as per the directions of the Engineer in charge.
P/F of GI Nipple 15mm with in all leads and lifts as per the directions of the Engineer in charge.
Laying galvanized mild steel tube (heavy class) in wall. Ceiling including with in all leads and lifts as per the directions of the Engineer in charge .15mm dia(fiifteen milimetres)nominal size.(H . C )
Providing and fixing 600mmx450mm bevelled edge miror of superior glass mounted on 6mm thick A.C. sheet or plywood sheet and fixed to wooden plugs with C.P. Brass screws and washers. within all leads and lifts and as directed by the Engineer-in-charge.
Providing and fixing in trenches 10 Kg.f/cum2 working pressure unplasticized P.V.C. pipe (Conforming to IS: 4985-1968) complete fittings (earth work in trenches to be measured and paid for separately):-
110 mm out side diameter.
Elbow 100 mm dia.
Clamps 100mm dia.
. Door Bends
.Plain bends
Collar
.Floor Traps
Wet well sinking in gravel including all pumping shoring etc, within all leads and lifts.
From speing level to 3 mtrs.
From 3mtrs. To 6mtrs.
From 6mtrs. To 9 mtrs.
Lowering steel well curb in the pit and assembling in position
When depth is upto three metres from ground
When depth is more than three metres
R/R masonry/polygonal rubble masonry un-coursed quality in foundation and plinth including leveling by cement concrete 1:6:12(1cement: 6sand:12graded stone at plinth in cement mortar 1:6 (1cement:6sand) within all leads and lifts and as directed by the Engineer-in-charge.
Providing and laying no fine concrete 1:4(1cement:4agg. 40mm nominal size) & curing complete in foundation and plinth excluding cost of form work within all leads and lifts.
Providing 200mm wide cast iron rungs with chequirred ribbed non slip surface including fixing in main holes with 200x20mmx100mm cement concrete 1:3:6(1cement:3sand:6graded stone 20mm nominal size within all leads and lifts.
Square rubble masonry coursed with hard stone of approved quality in Superstructure above plinth including raking out joint in Cement mortar 1:4(1cement:4sand)within all leads and lifts.
Supplying and fixing woven plain GI fencing of mesh 50 to 150mm to any type of standard rails strainging bolts etc. i/c provision of binding wire
20mm cement concrete topping 1:2 to 3 &1cement:2 to 3 stone agg. of size 4.75mm and below, by volume)laid over and finished monolithic with base concrete within all leads and lifts.
Applying mode rent solution on new GI sheet for preparation of surface for painting 5 Ltr. 100 Sqt. Of surface and rubbering the solution with brush i/c throughly brushing cleaning of all dirt dust and all oil, greas etc. within all leads and lifts.
Boulder filling behind retaining wall & crate wall within all leads and lifts and as directed by the Engineer-in-charge.
Stone pitching properly hard packed filling interstices with spalls stone earth etc. within all leads and lifts.
Horizontal
Booster Stage Providing and installation of submersible pump confirming to ISS8034-1976 along with a directy coupled submersible type squrrile cage electric induction motor suitable for operation on 400/-+10% volts 3 phase 50 cycles AC supply water iubericated bearing i/c Supply and fixing of control panel complete with sheet and angle iron fabricvated dully painted and complete with intermal wiring and comprising of air break starter main switch of suitable amperage T.P. Volt meter an meter phase indicate , Supply and fixing of submersible cable sets 6mmsqmt( 50m length ) Providing and fixing of reputed make of 50mm cast Steel double flanged cast steel reflux valve 1 no of various dia. with req. accessaries in 50 mm dia,rope wire 4mm dia suitable to bear the wight of submersible motor pump set and GI pipe etc including entire carriage of material and supporting clamps submersible set including entire carriage of material upto all leads and lifts. 2set of 10HP 2x10HP=20BHP
Supply of suitable oil immersed star delta starter/ATS/stator rotor starter of standarad make such as MEI/Kilburn/Jyoti/ Siemens cnonforming to BIS-8544-1979 latest with up to date ammendments for squirrelcage/slipriing motor (make to be specified by the tenderers) mounted on panel board with magnetic type over load release & dashpot,time lag,under voltage release with initial oil filling . Note:- Star - delta - starter upto 37.5 KW , ATS between 37.5 KW to 50 KW and stater rotor starter with slipring motor beyond 50 KW.
Providing M S sheet 16 SWG steel fabricated floor mounted closed almirah type switch board including angale iron post of suitable height and size ISA 40x40x6mm duly painted comprising and capable of mounting the following accessaries with all internal electric connections. The drawing of panel board shall be subject to approval of Engineer in charge.
ICTP switches with HRC fuses Kilburn/Larsen & turbo/Standard/Siemen make and having capacity 30% extra of the operational rating of motor as per BIS 4064-1978 with upto date ammendments immediatly after the power meter of HPSEB.
Busbar chamber having 3 copper bars of suitable rating for full length equal to wirdth of board of 3 live phases and one copper bar of half reating of full length for neutral conforming to BIS 8084-1976 and 11353-1985 read with 5578-1985 all latest with upto date ammendments.
MCB/Oil circuit breaker of suitable capacity of Kilburn/LT/LK/MEI/Standard make on in comming feeder for motors offered by the tenderer conforming to BIS 2516-1985 latest with upto date ammendments with neutral linked under voltage release.
3 phase indicating lamps complete with toggle switches for individual motors conforming to BIS 3452 part I & II latest with up to date ammendments.
Earth leakage circuit breaker of requcemended (Kilburn/L&T/MET/GEC as per BIS-2516-1977 with upto date ammendments and of suitaible range with which should have control box, oprating handel and trip/reset bush button on/ off indicators, re-indicating off spring condition of the circut breaker for over current protection. The circuit should be equipped with magnet thermal release with metallic tap CTS. It should also be fitted earth fault for tripping of breaker on occurance of earth fault on/ of breaker load side.
Hour run meter of reputed make of four digit capacity conforming to BIS-722(latest edition)/recommendations.
Suitable three phase voltage monitor relay with all protections & usual indicators with electrical sirens against single phasing,no voltage,high voltage & overloading & phase voltage difference
Change over Switch of reputed make & suitable capacity
Single phase preventor of reputed make & suitable capacity
Supply of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader/ of reputed make of suitable size cast iron/cast steel double flanged sluice valve having size equal to delivery of pump and capable of with standing nominal seat pressure of 52 kg/cm^2 NOTE:- The sluice valve shall conform to BIS 780-1984 latest with up to date ammend--ments.However if the seat pressure exceeds the limits prescribed in BIS 780 then thesluice valves shall be of cast steel conforming to class 150 ASA (Seat pressure 21 Kg/cm^2) or class 300 ASA (seat pressure 52 Kg/cm^2) or class 600 ASA (seat pressure 104 Kg/Cm2)as per BS 1414(API 600) .
Supply of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader of suitable size cast iron/ cast steel double flanged swing check type reflux valve having bye pass arrangement & size equal to delivery of pump for withstanding nominal seat pressure of 52 kg/cm^2 NOTE:- The sluice valve shall conform to BIS 780-1984 latest with up to date ammend--ments.However if the seat pressure exceeds the limits prescribed in BIS 780 then thesluice valves shall be of cast steel conforming to class 150 ASA (Seat pressure 21 Kg/cm^2) or class 300 ASA (seat pressure 52 Kg/cm^2) or class 600 ASA (seat pressure 104 Kg/Cm2)as per BS 1414(API 600) .
Supply of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader of suitable size cast iron/Cast Steel double flanged swing check type reflux valve having bye pass arrangement & size equal to dia of R/main for withstanding nominal seat pressure of 52 kg/cm^2 NOTE:- The sluice valve shall conform to BIS 780-1984 latest with up to date ammend--ments.However if the seat pressure exceeds the limits prescribed in BIS 780 then the sluice valves shall be of cast steel conforming to class 150 ASA (Seat pressure 21 Kg/cm^2) or class 300 ASA (seat pressure 52 Kg/cm^2) or class 600 ASA (seat pressure 104 Kg/Cm2)as per BS 1414(API 600) .
Supply of Kirloskar/Jyoti/Standard/Kilburn make cast irom flanged screwed type foot valve with strainer of dia equal to dia of suction pipe conforming to BIS 4038-1986 or latest with up to date ammendments.
P/L suitable size copper PVC insulated armoured power 3 1/2 core cable conforming to BIS 1554 (Part I) -1988 or latest with up to date ammendments Siemen/Gloster/ICC make from meter of HPSEB to OCB & from OCB to Busbar switch & starter (one cable carrying all three phases) including all other electrical equipment/accessories such as thimbles,flexible pipe,solder,nuts & bolts,cable glands etc. laid in pipes or trenches under floor .The type,size & make will be subject to approval of HPSEB authorities.In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost..
P/L suitable size copper PVC insulated armoured power three core cable conforming to BIS 1554(part I)-1988 or latest with up to date ammendments Siemen/Gloster/ICC make from switch to starter & starter to motor (one cable for carrying all three phases) including all other electrical equipment /accesories such as thimbles,flexible pipes, solder,nuts & bolts,cable glands etc. laid in pipes or trenches under floor. The type,size & make will be subject to approval of HPSEB authorities.In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost.
P/L double loop earthing with copper plate 600x600x3mm thick electrode complete with material such as charcoal, common salt ,GI pipes,thimbles,nuts & bolts,digging of pits,GI wiring & 25x5mm copper strips of required capacity conforming to BIS 3043-1987 latest with up to date ammendments for above motors & other electrical equipment.
Supply & errection of floor/wall mounted power factor shunt capacitor conforming to BIS 2834-1986 latest with upto date ammendments BHEL/GEC/Machneil/ Mager/Bajaj make to raise the prevailing power factor at site to 0.95 for direct connection to induction motor individually,of required KVAR according to HP of motor offered including cable Siemens/Gloster/ICC make from busbar chamber to capacitor & also including LT/LK/Kilburn make ICTP switches conforming to BIS 4064-1978 or latest with HRC fuses (Range to be specified by the tenderer.
Supply of standarad make 100mm dia circular dial pressure gauge of suitable range Fiebeg/Bourden/ Precision make with all accessories such as stop cock,copper tubing etc. conforming to BIS 3624-1987 latest with up to date ammendments.
P/L suction,delivery pipe considering site requirements,NPSH required & available & common header having area equal to two times the area of delivery branch of pump including tapers,flanges,rubber gaskets,3mm thick as per BIS-2712-1978 nuts & bolts as per1364-1983 & special up to 5 mtrs. away from the outer wall of pump house as per layout drawings approved by Engineer-in-Charge The pipes shall be capable of withstanding 1.5 times the total presure indicated in item no. 1e(ii). NOTE:- Actual laying to be done as per final drawings to be approved by the Engineer in charge
Supply of antivibration pads conforming to BIS 6337-1971 or latest with upto date ammendmentsof suitable size for above machinery.
Errection of all equipments from S.No. 1 to 4, 6 & 8 i/c cost of tees,bends tapers & any other fittings required as per site conditions & as per directions of Engineer-in-Charge.
Stage-1st. Supply of horizontal spindle,horizontal split casing Single/Multistage centrifugal pumps of standarad make such as KSB/Mather & Platt/Jyoti/Kirloskar conforming to BIS 1520-1980 (latest with upto date ammendments) read with BIS 9137-1978 or latest to handle clear water having turbidity 50 ppm. with impelleres,casing ring & shaft sleeves of bronze, shaft of steel with cast iron casing of suitable capacity coupled directly through a flexible coupling on a common base plate to Kirlokar/NGEF/Crompton/ Siemen/Jyoti slip ring/squirrel cage screen protected drip proof induction electric motor suitable for operation on the data given below. 2 sets of 100HP 100x2=200 BHP
Supply of suitable oil immersed star delta starter/ATS/stator rotor starter of standarad make such as MEI/Kilburn/Jyoti/ Siemens cnonforming to BIS-8544-1979 latest with up to date ammendments for squirrel cage/slipriing motor (make to be specified by the tenderers) mounted on panel board with magnetic type over load release & dashpot,time lag,under voltage release with initial oil filling . Note:- Star - delta - starter upto 37.5 KW , ATS between 37.5 KW to 50 KW and stater rotor starter with slipring motor beyond 50 KW.
Providing M S sheet 16 SWG steel fabricated floor mounted closed almirah type switch board including angale iron post of suitable height and size ISA 40x40x6mm duly painted comprising and capable of mounting the following accessaries with all internal electric connections. The drawing of panel board shall be subject to approval of Engineer in charge.
ICTP switches with HRC fuses Kilburn/Larsen & turbo/Standard/Siemen make and having capacity 30% extra of the operational rating of motor as per BIS 4064-1978 with upto date ammendments immediatly after the power meter of HPSEB.
Busbar chamber having 3 copper bars of suitable rating for full length equal to wirdth of board of 3 live phases and one copper bar of half reating of full length for neutral conforming to BIS 8084-1976 and 11353-1985 read with 5578-1985 all latest with upto date ammendments.
MCB/Oil circuit breaker of suitable capacity of Kilburn/LT/LK/MEI/Standard make on in comming feeder for motors offered by the tenderer conforming to BIS 2516-1985 latest with upto date ammendments with neutral linked under voltage release.
3 phase indicating lamps complete with toggle switches for individual motors conforming to BIS 3452 part I & II latest with up to date ammendments.
Earth leakage circuit breaker of requcemended (Kilburn/L&T/MET/GEC as per BIS-2516-1977 with upto date ammendments and of suitaible range with which should have control box, oprating handel and trip/reset bush button on/ off indicators, re-indicating off spring condition of the circut breaker for over current protection. The circuit should be equipped with magnet thermal release with metallic tap CTS. It should also be fitted earth fault for tripping of breaker on occurance of earth fault on/ of breaker load side.
Hour run meter of reputed make of four digit capacity conforming to BIS-722(latest edition)/recommendations.
Suitable three phase voltage monitor relay with all protections & usual indicators with electrical sirens against single phasing,no voltage,high voltage & overloading & phase voltage difference
Change over Switch of reputed make & suitable capacity
Single phase preventor of reputed make & suitable capacity
Supply of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader/ of reputed make of suitable size cast iron/cast steel double flanged sluice valve having size equal to delivery of pump and capable of with standing nominal seat pressure of 52 kg/cm^2 NOTE:- The sluice valve shall conform to BIS 780-1984 latest with up to date ammend--ments.However if the seat pressure exceeds the limits prescribed in BIS 780 then thesluice valves shall be of cast steel conforming to class 150 ASA (Seat pressure \21 Kg/cm^2) or class 300 ASA (seat pressure 52 Kg/cm^2) or class 600 ASA (seat pressure 104 Kg/Cm2)as per BS 1414(API 600) .
Supply of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader of suitable size cast iron/ cast steel double flanged swing check type reflux valve having bye pass arrangement & size equal to delivery of pump for withstanding nominal seat pressure of 52 kg/cm^2 NOTE:- The sluice valve shall conform to BIS 780-1984 latest with up to date ammend--ments.However if the seat pressure exceeds the limits prescribed in BIS 780 then thesluice valves shall be of cast steel conforming to class 150 ASA (Seat pressure 21 Kg/cm^2) or class 300 ASA (seat pressure 52 Kg/cm^2) or class 600 ASA (seat pressure 104 Kg/Cm2) as per BS 1414(API 600) .
Supply of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader of suitable size cast iron/Cast Steel double flanged swing check type reflux valve having bye pass arrangement & size equal to dia of R/main for withstanding nominal seat pressure of 52 kg/cm^2 NOTE:- The sluice valve shall conform to BIS 780-1984 latest with up to date ammend--ments.However if the seat pressure exceeds the limits prescribed in BIS 780 then the sluice valves shall be of cast steel conforming to class 150 ASA (Seat pressure 21 Kg/cm^2) or class 300 ASA (seat pressure 52 Kg/cm^2) or class 600 ASA (seat pressure 104 Kg/Cm2)as per BS 1414(API 600) .
Supply of Kirloskar/Jyoti/Standard/Kilburn make cast irom flanged screwed type foot valve with strainer of dia equal to dia of suction pipe conforming to BIS 4038-1986 or latest with up to date ammendments.
P/L suitable size copper PVC insulated armoured power 3 1/2 core cable conforming to BIS 1554 (Part I) -1988 or latest with up to date ammendments Siemen/Gloster/ICC make from meter of HPSEB to OCB & from OCB to Busbar switch & starter (one cable carrying all three phases) including all other electrical equipment/accessories such as thimbles,flexible pipe,solder,nuts & bolts,cable glands etc. laid in pipes or trenches under floor .The type,size & make will be subject to approval of HPSEB authorities.In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost..
P/L suitable size copper PVC insulated armoured power three core cable conforming to BIS 1554(part I)-1988 or latest with up to date ammendments Siemen/Gloster/ICC make from switch to starter & starter to motor (one cable for carrying all three phases) including all other electrical equipment /accesories such as thimbles,flexible pipes, solder,nuts & bolts,cable glands etc. laid in pipes or trenches under floor. The type,size & make will be subject to approval of HPSEB authorities.In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost.
P/L double loop earthing with copper plate 600x600x3mm thick electrode complete with material such as charcoal, common salt ,GI pipes,thimbles,nuts & bolts,digging of pits,GI wiring & 25x5mm copper strips of required capacity conforming to BIS 3043-1987 latest with up to date ammendments for above motors & other electrical equipment.
Supply & errection of floor/wall mounted power factor shunt capacitor conforming to BIS 2834-1986 latest with upto date ammendments BHEL/GEC/Machneil/ Mager/Bajaj make to raise the prevailing power factor at site to 0.95 for direct connection to induction motor individually,of required KVAR according to HP of motor offered including cable Siemens/Gloster/ICC make from busbar chamber to capacitor & also including LT/LK/Kilburn make ICTP switches conforming to BIS 4064-1978 or latest with HRC fuses (Range to be specified by the tenderer.
Supply of standarad make 100mm dia circular dial pressure gauge of suitable range Fiebeg/Bourden/ Precision make with all accessories such as stop cock,copper tubing etc. conforming to BIS 3624-1987 latest with up to date ammendments.
P/L suction,delivery pipe considering site requirements,NPSH required & available & common header having area equal to two times the area of delivery branch of pump including tapers,flanges,rubber gaskets,3mm thick as per BIS-2712-1978 nuts & bolts as per1364-1983 & special up to 5 mtrs. away from the outer wall of pump house as per layout drawings approved by Engineer-in-Charge The pipes shall be capable of withstanding 1.5 times thetotal presure indicated in item no. 1e(ii). NOTE:- Actual laying to be done as per final drawings to be approved by the Engineer in charge
Supply of antivibration pads conforming to BIS 6337-1971 or latest with upto date ammendmentsof suitable size for above machinery.
Errection of all equipments from S.No. 1 to 4, 6 & 8 i/c cost of tees,bends tapers & any other fittings required as per site conditions & as per directions of Engineer-in-Charge.
Phase 2nd Village Mandli Providing and installation of submersible pump confirming to ISS8034-1976 along with a directy coupled submersible type squrrile cage electric induction motor suitable for operation on 400/-+10% volts 3 phase 50 cycles AC supply water iubericated bearing i/c Supply and fixing of control panel complete with sheet and angle iron fabricvated dully painted and complete with intermal wiring and comprising of air break starter main switch of suitable amperage T.P. Volt meter an meter phase indicate , Supply and fixing of submersible cable sets 6mmsqmt( 50m length ) Providing and fixing of reputed make of 50mm cast Steel double flanged cast steel reflux valve 1 no of various dia. with req. accessaries in 50 mm dia,rope wire 4mm dia suitable to bear the wight of submersible motor pump set and GI pipe etc including entire carriage of material and supporting clamps submersible set including entire carriage of material upto all leads and lifts. 1 sets of 20HP 1x20HP=20BHP
Supply of suitable oil immersed star delta starter/ATS/stator rotor starter of standarad make such as MEI/Kilburn/Jyoti/ Siemens cnonforming to BIS-8544-1979 latest with up to date ammendments for squirrel cage/slipriing motor (make to be specified by the tenderers) mounted on panel board withmagnetic type over load release & dashpot,time lag,under voltage release with initial oil filling . Note:- Star - delta - starter upto 37.5 KW , ATS between 37.5 KW to 50 KW and stater rotor starter with slipring motor beyond 50 KW.
Providing M S sheet 16 SWG steel fabricated floor mounted closed almirah type switch board including angale iron post of suitable height and size ISA 40x40x6mm duly painted comprising and capable of mounting the following accessaries with all internal electric connections. The drawing of panel board shall be subject to approval of Engineer in charge.
ICTP switches with HRC fuses Kilburn/Larsen & turbo/Standard/Siemen make and having capacity 30% extra of the operational rating of motor as per BIS 4064-1978 with upto date ammendments immediatly after the power meter of HPSEB.
Busbar chamber having 3 copper bars of suitable rating for full length equal to wirdth of board of 3 live phases and one copper bar of half reating of full length for neutral conforming to BIS 8084-1976 and 11353-1985 read with 5578-1985 all latest with upto date ammendments.
MCB/Oil circuit breaker of suitable capacity of Kilburn/LT/LK/MEI/Standard make on in comming feeder for motors offered by the tenderer conforming to BIS 2516-1985 latest with upto date ammendments with neutral linked under voltage release.
3 phase indicating lamps complete with toggle switches for individual motors conforming to BIS 3452 part I & II latest with up to date ammendments.
Earth leakage circuit breaker of requcemended (Kilburn/L&T/MET/GEC as per BIS-2516-1977with upto date ammendments and of suitaible range with which should have control box, oprating handel and trip/reset bush button on/ off indicators, re-indicating off spring conditionof the circut breaker for over current protection. The circuit should be equipped with magnet thermal release with metallic tap CTS. It should also be fitted earth fault for tripping of breaker on occurance of earth fault on/ of breaker load side.
Hour run meter of reputed make of four digit capacity conforming to BIS-722(latest edition)/recommendations.
Suitable three phase voltage monitor relay with all protections & usual indicators with electrical sirens against single phasing,no voltage,high voltage & overloading & phase voltage difference
Change over Switch of reputed make & suitable capacity
Single phase preventor of reputed make & suitable capacity
Supply of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader/ of reputed make of suitable size cast iron/cast steel double flanged sluice valve having size equal to delivery of pump and capable of with standing nominal seat pressure of 52 kg/cm^2 NOTE:- The sluice valve shall conform to BIS 780-1984 latest with up to date ammend--ments.However if the seat pressure exceeds the limits prescribed in BIS 780 then the sluice valves shall be of cast steel conforming to class 150 ASA (Seat pressure 21 Kg/cm^2) or class 300 ASA (seat pressure 52 Kg/cm^2) or class 600 ASA (seat pressure 104 Kg/Cm2)as per BS 1414(API 600) .
Supply of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader of suitable size cast iron/ cast steel double flanged swing check type reflux valve having bye pass arrangement & size equal to delivery of pump for withstanding nominal seat pressure of 52 kg/cm^2 NOTE:- The sluice valve shall conform to BIS 780-1984 latest with up to date ammend--ments.However if the seat pressure exceeds the limits prescribed in BIS 780 then the sluice valves shall be of cast steel conforming to class 150 ASA (Seat pressure 21 Kg/cm^2) or class 300 ASA (seat pressure 52 Kg/cm^2) or class 600 ASA (seat pressure 104 Kg/Cm2)as per BS 1414(API 600) .
Supply of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader of suitable size cast iron/Cast Steeldouble flanged swing check type reflux valve having bye pass arrangement & size equal to dia of R/main for withstanding nominal seat pressure of 52 kg/cm^2 NOTE:- The sluice valve shall conform to BIS 780-1984 latest with up to date ammend--ments.However if the seat pressure exceeds the limits prescribed in BIS 780 then the sluice valves shall be of cast steel conforming to class 150 ASA (Seat pressure 21 Kg/cm^2) or class 300 ASA (seat pressure 52 Kg/cm^2) or class 600 ASA (seat pressure 104 Kg/Cm2) as per BS 1414(API 600) .
Supply of Kirloskar/Jyoti/Standard/Kilburn make cast irom flanged screwed type foot valve with strainer of dia equal to dia of suction pipe conforming to BIS 4038-1986 or latest with up to date ammendments.
P/L suitable size copper PVC insulated armoured power 3 1/2 core cable conforming to BIS 1554 (Part I) -1988 or latest with up to date ammendments Siemen/Gloster/ICC make from meter of HPSEB to OCB & from OCB to Busbar switch & starter (one cable carrying all three phases) including all other electrical equipment/accessories such as thimbles,flexible pipe,solder,nuts & bolts,cable glands etc. laid in pipes or trenches under floor .The type,size & make will be subject to approval of HPSEB authorities.In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost..
P/L suitable size copper PVC insulated armoured power three core cable conforming to BIS 1554(part I)-1988 or latest with up to date ammendments Siemen/Gloster/ICC make from switch to starter & starter to motor (one cable for carrying all three phases) including all other electrical equipment /accesories such as thimbles,flexible pipes, solder,nuts & bolts,cable glands etc. laid in pipes or trenches under floor. The type,size & make will be subject to approval of HPSEB authorities.In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost.
P/L double loop earthing with copper plate 600x600x3mm thick electrode complete with material such as charcoal, common salt ,GI pipes,thimbles,nuts & bolts,digging of pits,GI wiring & 25x5mm copper strips of required capacity conforming to BIS 3043-1987 latest with up to date ammendments for above motors & other electrical equipment.
Supply & errection of floor/wall mounted power factor shunt capacitor conforming to BIS 2834-1986 latest with upto date ammendments BHEL/GEC/Machneil/ Mager/Bajaj make to raise the prevailing power factor at site to 0.95 for direct connection to induction motor individually,of required KVAR according to HP of motor offered including cable Siemens/Gloster/ICC make from busbar chamber to capacitor & also including LT/LK/Kilburn make ICTP switches conforming to BIS 4064-1978 or latest with HRC fuses (Range to be specified by the tenderer.
Supply of standarad make 100mm dia circular dial pressure gauge of suitable range Fiebeg/Bourden/ Precision make with all accessories such as stop cock,copper tubing etc. conforming to BIS 3624-1987 latest with up to date ammendments.
P/L suction,delivery pipe considering site requirements,NPSH required & available & common header having area equal to two times the area of delivery branch of pump including tapers,flanges,rubber gaskets,3mm thick as per BIS-2712-1978 nuts & bolts as per1364-1983 & special up to 5 mtrs. away from the outer wall of pump house as per layout drawings approved by Engineer-in-Charge The pipes shall be capable of withstanding 1.5 times the total presure indicated in item no. 1e(ii). NOTE:- Actual laying to be done as per final drawings to be approved by the Engineer in charge
Supply of antivibration pads conforming to BIS 6337-1971 or latest with upto date ammendmentsof suitable size for above machinery.
Errection of all equipments from S.No. 1 to 4, 6 & 8 i/c cost of tees,bends tapers & any other fittings required as per site conditions & as per directions of Engineer-in-Charge.
Rising Main Providing, laying, & commissioning at site in trenches to be beveled ended pipe conforming to IS/ISO:3183-2007 (Latest with up to date amendments) having minimum wall thickness as specified below & capable of withstanding required test pressure as prescribed in IS/ISO code, in random lengths of 5.5 to 6.5 mtr. The pipe ends shall be levelled suitable for butt welding, including thecost of jointing with butt welding confirming to IS 816-1969 or latest applicable and with uptodate ammendments (leak proof) in three layers at siteof work with welded rods of Advani/oeriliken make/ISI marked (welded rods 3mm to 4mm) and all allied accessories whatever required for welding at site, tail pieces,tee bends & other special manufactured from parent pipes as applicable to the particular reach and of approved specification as per site conditions. and cutting of pipes wherever required as per site requirement including carriage in all leads & lifts andas directed by the Engineer-In-Charge. The pipe shall have zinc coating inside & outside confirming to IS-4736-1986 or latest with upto date ammendments & shall be engraved with API X42. The laying shall cofirm to BIS 5822-970 or latest with upto date ammendments to the entire satisfaction of Engineer-In-Charge. (Earth work & cost of MS Flanges after 100meter length shall be measured & paid for seperately.) including all leads, lifts and carriage of materials at site andas per direction and to the entire satisfaction of the Engineer-In-Charge.
Booster Stage 125mm dia APIX-42 T-28
Stage 1st 125mm dia APIX-42 T-34 RD 0 to 800 4.80mm
Providing, Laying ,jointing, with circumferential butt joints by electrical arc welding (Welding thickness shall be equal to pipe wall thickness) and testing of G.I Pipe of approved rate contract of DGS and D / HP Govt make of following diameter confirming to IS:1239:2002 (Part-ii) (latest with up to date amendments having wall thickness as specified below capable of withstanding required test pressure , including manufacturing and fabrication of reducers taper all shorts pieces, bends etc as per site requirement made from parent tubes. The laying of pipe shall also include flanged joints duly welded in three layer (one inner and two outer) Where ever required as per direction of Engineer in charge (Earth work in trenches and the cost of flanges I/C nut and bolts gasket will be measured and paid for separately) and all operation such as cutting welding and jointing fabrication of bends tees i.e lowering and laying in excavated trench to ensure required level including flushing cleaning and hydraulic testing complete in all respect to the entire satisfaction of the Engineer in charge. The fabricated bends shall have three or four cuts having its radius not less than five times the dia of pipe. The welding electrodes shall be as per IS 814 of Advani Overlikon/Over cord s/s make.The damaged portion of the pipe and all specials (if damaged during laying and jointing operation of pipe ) made from the parents tube shall be provided anticorrosive treatment by applying two coats of anticorrosive bituminous paints over a priming coat as per AWWA specification C-203-1978. The rates also includes entire carriage of material ,flushing, Cleaning and Hydraulic testing,DP test of butt welded joints complete in all respect and to the entire satisfaction of Engineer in charge with in all leads and lifts
Stage 1st 125mm dia GI (H) T-28 RD 800 to 1200 4.80mm thick
125mm dia GI (H) T-17 RD 1200 to 1400 4.80mm thick
Phase 2nd village Mandli 65mm dia GI (H) T-17 RD 0 to 480 4.80mm thick
Providing MS Flange (in Pairs) for joints of G.I. pipe mentioned as below and same shall conform to BIS 6392-1971 ( Latest with uptodate ammendments ) including the cost of Nut and Bolts of Required size 3mm thick compressed asbestos fibre/ synthetic rubber gasket conforming to relevant BIS Standards the rates also include entire carriage of Flange and welding of one flange in three layers other Flange consider in butt welding testing , complete to the best satisfaction and direction of engineer -in Charge.
Booster Stage 125mm dia T-34
Stage 1st 125mm dia T-34
125mm dia T-28
125mm dia T-17
125mm dia T-5
Phase 2nd village Mandli 65mm dia T-17
65mm dia T-5
Vikram Rithwan Contractor
CHATTER SINGH RATHORE
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .