Design, Engg, Supply, Erection, Installation, Testing, Commissioning and other associated works for augmentation of Jhanjra Substation with additional 2x10MVA capacity and facilities required to make it complete on turnkey basis with 5yr maintenance
2022_ECL_253746_1
ECL/HQ/GM(EnM)/HOD/2022/219 date 18.08.2022
Turnkey
Miscellaneous Works
2095 days
Jhanjra Main Substation Jhanjra Area
Please refer Tender documents
9 documents required · 9 mandatory
₹21.6 L
21 Mar 2023
18 Aug 2022
14 Sept 2022
18 Aug 2022
12 Sept 2022
19 Aug 2022
18 Aug 2022 - 1 Sept 2022
Amount
Civil works
Development Work and Infrastructure a) Site Development including Horticulture/ Plantation b) Back filling with all kind of soil in layers c) Leveling & dressing d) Substation Building e) Yard fencing with Gates f) Dyke wall g) Pebbling h) 3 mtrs & 5 mtrs Concrete roads i) Pavement for parking and pathway j) Drain, Hume pipe culvert k) Water supply & Sewage l) Underground sump m) Rain water harvesting n) Lighitng mast o) DG shed
Civil(RCC) and Structural Steel Works a) RCC Cable Trenches b) R.C.C. Foundation for structural steel works c) soak pits d) Structural Steel Work for installation of different outdoor equipment like isolators, transformers, breakers, CTs, PTs, lightening arrestors, Gantry etc. e) Painting of Steel Works
SUPPLY OF ELECTRICAL (LIST OF EQUIPMENT)
Outdoor Switchyard Equipment Comprising the following a) L.A., Station Class, 30kV,10kA, for 33kV system (Set of 3) with surge counter -6 sets. b) Isolator Off Load type, 33kV, Outdoor Type, with earth switch. -2 sets. c) Isolator Off Load type, 33kV, Outdoor Type, without earth switch. -14 sets. d) 33 kV drop out fuse, out door type.-6 sets. e) 33 kV/110 V PT, out door type.-2 sets. f) 33 kV CT out door type.-5 sets. g) 33 kV, 750 MVA, 1250 Amps VCB - 5 nos. h) 10 MVA, 33/6.6 kV power transformer - 2 nos. i) Nitrogen injection firefighting system for 10 MVA transformers - 2 nos. j)160kVA , 33/0.433 kV Station Transformer (Cu)-2 nos. k) 100 kVA, 33/0.230 (L-L) kV Lighting Transformer (Cu). - 2 nos. l) 6.6 kV off load isolators without earth switch-2 sets. m) 6.6 kV off load isolators with earth switch-12 sets. n) 6 kV grade, 5 kA lighting arrestor with surge counter - 14 sets o) Neutral grounding resistor with CT - 2 sets p) Differential protection for 10 MVA transformers q) DP Structure (H-Pole) for outgoing feeders through overhead lines - 12 nos.
Indoor Equipment Comprising the following a) 6.6 kV Capacitor Bank (As Required to maintain power factor 0.99) with APFC control -4 Sets. b) 6.6 kV, 41 panel VCB switchboard panel - 1 set c) SCADA system complete - lot d) 220 V, 200 AH battery bank with charger unit - 1 set e) Inverter (min. 5 kVA) for emergency illumination along with batteries, separate wiring and LED luminaries - complete - Lot f) 415 V MPDB - 1 no. g) 230 V MLDB - 1 no. h) 25 kVA, 415 V DG set with changeover switch and 415 V Swithcboard. i) DC power distribution board - 1no.
Conductors , Cables and Busbars a) Insulators,Tubular busbar for 33 kV , Steel hardware, Post Insulator clamps, terminal connectors etc for 33 kV etc .-As Required-1 Lot. b) Control cable of size 2.5 sq. mm. of various cores, complete as per requirement.-1 Lot. c) 6.6 kV(UE), XLPE, DWA, FRLS HT Copper Power Cables - Lot d) 1100/660 V grade, PVC/XLPE insulated double wire armored Power cable with Copper conductors of required sizes e) Cable trays, cable racks, binding material, cable glands, cable terminal lugs, nuts, bolts, washer, cable jointing and termination kit etc
Illumination a) Substation lighting, indoor & outdoor including cables, switch boards, luminaries/light fittings (LED) etc.
Miscellaneous a) Earthing System including earth pits, GI Strips for earthing of Substation equipment and structurals -As required b) Lightning protection system - As required c) Fire Detection & Alarm System-As Required d) Portable Fire fighting system i) 22 kG CO2 type-As Required ii) 9 kg CO2 type- As Required iii) 4.5 kg powder type- As Required . iv) Sand Bucket with stand- As Required e) Galvanizedmultistrand steel wire of size 7/12 SWG (Shield wire) for lightning protection system.-As required f) insulators, hardwares, clamps and connectors.-As required g) safety equipment including rubber insulating mat, hand gloves, discharging rod, danger plate, etc.-1 Lot h) 5 star Split AC, pressurization and ventilation system for Substation Building-As required i) Tools and Tackles- 1Lot j) Pressurization system for switchgear room - Lot k) Miscellaneous items like rubber mat, hand gloves, danger plate, notice board, portable temperature recorder with thermostat etc. j) other items not specifically included above but essential for completion of entire work.-1 Lot
ERECTION, INSTALLATION & COMMISSIONING OF ELECTRICAL (LIST OF EQUIPMENT)
Outdoor Switchyard Equipment Comprising the following a) L.A., Station Class, 30kV,10kA, for 33kV system (Set of 3) with surge counter -6 sets. b) Isolator Off Load type, 33kV, Outdoor Type, with earth switch. -2 sets. c) Isolator Off Load type, 33kV, Outdoor Type, without earth switch. -14 sets. d) 33 kV drop out fuse, out door type.-6 sets. e) 33 kV/110 V PT, out door type.-2 sets. f) 33 kV CT out door type.-5 sets. g) 33 kV, 750 MVA, 1250 Amps VCB - 5 nos. h) 10 MVA, 33/6.6 kV power transformer - 2 nos. i) Nitrogen injection firefighting system for 10 MVA transformers - 2 nos. j)160kVA , 33/0.433 kV Station Transformer (Cu)-2 nos. k) 100 kVA, 33/0.230 (L-L) kV Lighting Transformer (Cu). - 2 nos. l) 6.6 kV off load isolators without earth switch-2 sets. m) 6.6 kV off load isolators with earth switch-12 sets. n) 6 kV grade, 5 kA lighting arrestor with surge counter - 14 sets o) Neutral grounding resistor with CT - 2 sets p) Differential protection for 10 MVA transformers q) DP Structure (H-Pole) for outgoing feeders through overhead lines - 12 nos.
Indoor Equipment Comprising the following a) 6.6 kV Capacitor Bank (As Required to maintain power factor 0.99) with APFC control -4 Sets. b) 6.6 kV, 41 panel VCB switchboard panel - 1 set c) SCADA system complete d) 220 V, 200 AH battery bank with charger unit - 1 set e) Inverter (min. 5 kVA) for emergency illumination along with batteries, separate wiring and LED luminaries - complete - Lot f) 415 V MPDB - 1 no. g) 230 V MLDB - 1 no. h) 25 kVA, 415 V DG set with changeover switch and 415 V Swithcboard. i) DC power distribution board - 1no.
Conductors , Cables and Busbars a) Insulators,Tubular busbar for 33 kV , Steel hardware, Post Insulator clamps, terminal connectors etc for 33 kV etc .-As Required-1 Lot. b) Control cable of size 2.5 sq. mm. of various cores, complete as per requirement.-1 Lot. c) 6.6 kV(UE), XLPE, DWA, FRLS HT Copper Power Cables - Lot d) 1100/660 V grade, PVC/XLPE insulated double wire armored Power cable with Copper conductors of required sizes e) Cable trays, cable racks, binding material, cable glands, cable terminal lugs, nuts, bolts, washer, cable jointing and termination kit etc
Illumination a) Substation lighting, indoor & outdoor including cables, switch boards, luminaries/light fittings (LED) etc.
Miscellaneous a) Earthing System including earth pits, GI Strips for earthing of Substation equipment and structurals -As required b) Lightning protection system - As required c) Fire Detection System-As Required d) Portable Fire fighting system i) 22 kG CO2 type-As Required ii) 9 kg CO2 type- As Required iii) 4.5 kg powder type- As Required . iv) Sand Bucket with stand- As Required e) Galvanizedmultistrand steel wire of size 7/12 SWG (Shield wire) for lightning protection system.-As required f) insulators, hardwares, clamps and connectors.-As required g) safety equipment including rubber insulating mat, hand gloves, discharging rod, danger plate, etc.-1 Lot h) 5 star Split AC, pressurization and ventilation system for Substation Building-As required i) Tools and Tackles- 1Lot j) Pressurization system for switchgear room - Lot k) Miscellaneous items like rubber mat, hand gloves, danger plate, notice board,portable temperature recorder with thermostat etc. j) other items not specifically included above but essential for completion of entire work.-1 Lot
Other Items
Any other item left out for completion of the project i.e. Overhead Construction Cost, Insurance, Contingency charges etc.
Defect Liability Period (Maintenance of the Plant) & COMMISSIONING
Maintenance of the plant for five year after commissiong
Training of the employer personnel as per requirement
Total impact of GST for the purpose of CTC
T AND T PROJECTS LIMITED
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Download all tender documents and submit your bid