Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.0 LAccepted-AOC GLYPTIC RAIPUR P O BHITA BURDWAN 713102 | BURDWAN | PURBA BARDHAMAN | WEST BENGAL | 713102 | ₹7.0 L | L1 | Accepted-AOC STOOD L1 |
| 2 | L2₹7.3 L+₹31,610 (4.54%)Rejected-Finance | ₹7.3 L+₹31,610 (4.54%) | L2 | Rejected-Finance L2 |
| 3 | L3₹7.7 L+₹74,045 (10.6%)Rejected-Finance 12 1 FERRIGHAT ROAD P O BHATPARA DIST NORTH 24 PGS WEST BENGAL PIN 743123 | BHATPARA | NORTH 24 PARGANAS | WEST BENGAL | 743123 | ₹7.7 L+₹74,045 (10.6%) | L3 | Rejected-Finance L3 |
| Sl No | Description | Qty | Unit | GLYPTIC L1 | MAM ENTERPRISE L2 | Creative Projects L3 |
|---|---|---|---|---|---|---|
| 1.00 | Supply, Installation,Testing & Commisioning of Microprocessor based 3 Loops expandable upto 4 fire alarm control panel (EN -54 standard VDS / UL&FM Approved )fully networkable with each loop capable of taking 125 devices, 1/4 VGA display .The panel shall be soft addressable type. The panel shall be able to give pin point location of all fire/fault conditions. Further, the panel must be able to automatically switch off respective control switches when ever any alarm is triggered The panel shall have in built rectifier, provision for external & internal printer (if required),Loop cards, LCD unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, having event memory, integral SMF lead acid batteries with sealed cells of 24 V capable of running for a minimum of 2 hours with integral battery charger complete as required. (Approved Make: Esser / Secutron/ Siemens / Edwards) | 1 | Nos | 3,10,000 ₹3,10,000 | 1,68,000 ₹1,68,000 Lowest | 1,74,000 ₹1,74,000 |
| 2.00 | Supply installation Testing & Commisioning of (EN -54 standard VDS / UL&FM Approved ) Addressable Multi sensor Detector (Dual optical smoke as well as heat ) with inbulit / additional isolator as per IS-2189.(Note : Detectors without built-in
fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for after every 20 nos of addressable
devices) and integral LED status indicator with 360 degree viewing angle Detector shall commumcate 3 danger levels for differentiated alarm activation and high tolerance to dust dirt temperature fluctuation and air currents Detector should have unquie address for communication and assigned through panel with Mounting Base as rqequired with the protection category of IP40 (Approved Make: Esser / Secutron/ Siemens / Edwards) | 170 | nos | 1,300 ₹2,21,000 Lowest | 1,940 ₹3,29,800 | 2,100 ₹3,57,000 |
| 3.00 | Supply, Installation, Testing & Commissioning of Intelligent Addressable (EN -54 standard VDS / UL&FM Approved ) Heat (Fixed Temp + ROR Temp) Detector with with inbulit / additional isolator as per IS-2189 .(Note : Detectors without built-in
fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for after every 20 nos of addressable devices) & Necessary accessories for fitting, etc. (Approved Make: Esser / Secutron/ Siemens / Edwards) | 5 | Nos | 1,300 ₹6,500 Lowest | 1,550 ₹7,750 | 1,625 ₹8,125 |
| 4.00 | Supply, installation, testing & commissioning of (EN -54 standard VDS / UL&FM Approved ) Inteliigent addressable manual call point with with inbulit / additional isolator as per IS-2189 (Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for after every 20 nos of addressable devices) for each manual call point suitable for flush or surface mounting, call point shall include test key feature without removing the glass with extra acceesories as required. (Approved Make: Esser / Secutron/ Siemens / Edwards) | 12 | Nos | 1,500 ₹18,000 Lowest | 1,900 ₹22,800 | 2,100 ₹25,200 |
| 5.00 | Supply, Installation, Testing & Commissioning of (EN -54 standard VDS / UL&FM Approved ) Addressable Sounder cum Strobe with inbulit / additional isolator as per IS-2189 (Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for after every 20 nos of addressable devices) & necessary accessories for fitting, J.B etc. (Approved Make: Esser / Secutron/ Siemens / Edwards) | 12 | Nos | 1,500 ₹18,000 Lowest | 3,800 ₹45,600 | 4,050 ₹48,600 |
| 6.00 | Supply, erection, testing & commissioning of RESPONSE INDICATOR Complete with base, mounting box, gland, lugs, etc. as required completing in all respect. (Approved Make: Esser / Secutron/ Siemens / Edwards) | 20 | Nos | 1 ₹20 Lowest | 50 ₹1,000 | 65 ₹1,300 |
| 7.00 | Supply & Laying of 2 Core 1.5 sq.mm flexible FRLS Cable (Make. KEI/ Polycab/ RR kable) and 20 mm NB FR PVC rigid conduit pipe on the surface of the wall. (Make. Precisson /Polycab). | 1,500 | Mtr | 82 ₹1,23,000 Lowest | 97 ₹1,45,500 | 99 ₹1,48,500 |
| 8.00 | Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) (Make. RR kable/Popycab/ KEI ).(on pre laid pipe) | 80 | Mtr | 1 ₹80 Lowest | 97 ₹7,760 | 99 ₹7,920 |
| 9.00Note:- The successful Bidder is required to submit the General Arrangement drawings[both soft copy(Auto-cad/PDF) & HARD COPY] of the equipments/components like Detectors, R.I, MCP, FACP, PA/sound systems etc. in the building plan drawing with complete dimensions. Respective/relative distances etc. within 7 days from the Award of contract for approval of E.I.C before commencement of work. | ||||||
Tender Value
Refer Docs
EMD Value
₹18,088
Closing Date
15 Mar 2022, 2:00 pmClosed
Executive Engineer, PWD, Asansol Electrical Divisi
O/O of the EE/AED/PWD , Near Polo Ground Asansol
Construction of Second and Third floor of Khadya Bhawan at Asansol for accommodating office of the DCF S in the district of Paschim Bardhaman,under Asansol division,PWD-SITC of fire alarm system.
2022_WBPWD_367346_1
WBPWD/EE/AED /eNIQ-29(4th call)/2021-22
Open Tender
ELECTRICAL WORKS ORG
Item Rate
14 days
Asansol
Please refer Tender documents.
4 documents required · 4 mandatory
₹18,088
O/O of the EE/AED/PWD , Near Polo Ground Asansol
16 Sept 2026
23 Feb 2022
17 Mar 2022
23 Feb 2022
15 Mar 2022
25 Feb 2022
9 Mar 2022
Amount
Supply, Installation,Testing & Commisioning of Microprocessor based 3 Loops expandable upto 4 fire alarm control panel (EN -54 standard VDS / UL&FM Approved )fully networkable with each loop capable of taking 125 devices, 1/4 VGA display .The panel shall be soft addressable type. The panel shall be able to give pin point location of all fire/fault conditions. Further, the panel must be able to automatically switch off respective control switches when ever any alarm is triggered The panel shall have in built rectifier, provision for external & internal printer (if required),Loop cards, LCD unit to indicate Fire/Fault Signal with address and analog output, complete in all respects, having event memory, integral SMF lead acid batteries with sealed cells of 24 V capable of running for a minimum of 2 hours with integral battery charger complete as required. (Approved Make: Esser / Secutron/ Siemens / Edwards)
Supply installation Testing & Commisioning of (EN -54 standard VDS / UL&FM Approved ) Addressable Multi sensor Detector (Dual optical smoke as well as heat ) with inbulit / additional isolator as per IS-2189.(Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for after every 20 nos of addressable devices) and integral LED status indicator with 360 degree viewing angle Detector shall commumcate 3 danger levels for differentiated alarm activation and high tolerance to dust dirt temperature fluctuation and air currents Detector should have unquie address for communication and assigned through panel with Mounting Base as rqequired with the protection category of IP40 (Approved Make: Esser / Secutron/ Siemens / Edwards)
Supply, Installation, Testing & Commissioning of Intelligent Addressable (EN -54 standard VDS / UL&FM Approved ) Heat (Fixed Temp + ROR Temp) Detector with with inbulit / additional isolator as per IS-2189 .(Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for after every 20 nos of addressable devices) & Necessary accessories for fitting, etc. (Approved Make: Esser / Secutron/ Siemens / Edwards)
Supply, installation, testing & commissioning of (EN -54 standard VDS / UL&FM Approved ) Inteliigent addressable manual call point with with inbulit / additional isolator as per IS-2189 (Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for after every 20 nos of addressable devices) for each manual call point suitable for flush or surface mounting, call point shall include test key feature without removing the glass with extra acceesories as required. (Approved Make: Esser / Secutron/ Siemens / Edwards)
Supply, Installation, Testing & Commissioning of (EN -54 standard VDS / UL&FM Approved ) Addressable Sounder cum Strobe with inbulit / additional isolator as per IS-2189 (Note : Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for after every 20 nos of addressable devices) & necessary accessories for fitting, J.B etc. (Approved Make: Esser / Secutron/ Siemens / Edwards)
Supply, erection, testing & commissioning of RESPONSE INDICATOR Complete with base, mounting box, gland, lugs, etc. as required completing in all respect. (Approved Make: Esser / Secutron/ Siemens / Edwards)
Supply & Laying of 2 Core 1.5 sq.mm flexible FRLS Cable (Make. KEI/ Polycab/ RR kable) and 20 mm NB FR PVC rigid conduit pipe on the surface of the wall. (Make. Precisson /Polycab).
Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) (Make. RR kable/Popycab/ KEI ).(on pre laid pipe)
Note:- The successful Bidder is required to submit the General Arrangement drawings[both soft copy(Auto-cad/PDF) & HARD COPY] of the equipments/components like Detectors, R.I, MCP, FACP, PA/sound systems etc. in the building plan drawing with complete dimensions. Respective/relative distances etc. within 7 days from the Award of contract for approval of E.I.C before commencement of work.
MAM ENTERPRISE
Creative Projects
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .