| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.5 CrAccepted-AOC TRINNATH LAXMIPUR KHAYERPUR AGARTALA WEST TRIPURA PIN 799008 | WEST TRIPURA | TRIPURA | 799008 | ₹1.5 Cr | L1 | Accepted-AOC Quoted amount is reasonable |
| 2 | L2₹1.6 Cr+₹6.2 L (4.08%)Rejected-Finance VILL SANDIPUR PO DWARNARY DISTT PURBA MEDINIPUR KOLKATA 7134403 WB | KOLKATA | PURBA MEDINIPUR | WB | 7134403 | ₹1.6 Cr+₹6.2 L (4.08%) | L2 | Rejected-Finance Quoted amount is higher than L1 bidder |
| 3 | L3₹1.7 Cr+₹18.6 L (12.2%)Rejected-Finance | ₹1.7 Cr+₹18.6 L (12.2%) | L3 | Rejected-Finance Quoted amount is higher than L1 bidder |
Tender Value
Refer Docs
EMD Value
₹2.4 L
Closing Date
12 Apr 2021, 6:00 pmClosed
CWE (AF) PANAGARH
HQ CWE AF PANAGARH MILITARY ENGINEER SERVICES AIR FORCE STATION ARJAN SINGH PO BIRUDIAH DIST BURDWAN WEST BENGAL PIN 713148
UPGRADATION OF TRANSFORMERS, LT PANEL AND CONVERSION OF OVERHEAD ELECTRICAL LINES TO UNDERGROUND CABLE AT 31 WING AT AF STATION PANAGARH
2021_MES_429395_1
82341/PAN/E8
Open Tender
Miscellaneous Works
Item Rate
365 days
GE AF PANAGARH
Please refer tender documents
9 documents required · 9 mandatory
₹1,000
GE AF PANAGARH
₹2.4 L
Yes
4 May 2021
9 Mar 2021
14 Apr 2021
9 Mar 2021
12 Apr 2021
30 Mar 2021
9 Mar 2021 - 30 Mar 2021
Amount
ADDN/ALTN/REPAIR WORKS (Note: Common items under different parts/sections of Schedule 'A'(BoQ) has been clubbed together/considered under one part/section)
Demolition of cement concrete (reinforced, reinforcement cut as required to facilitate demolition) as in roofs, floors (other than ground floors), beams, staircases, landing, chajjas and similar suspended work and removing demolished materials upto a distance exc 50 m and n.exc. 250 m from the site of work complete all as specified and as directed .
M&L providing reinforced cement concrete 1:2:4 (Nominal Mix), type B-1(using 20 mm graded stone aggregate) in slabs supported on walls, beams and columns in floors, roofs, landings, balconies, canopies, deck slabs and in shelves and the like complete all as specified and as directed .
Material and Labour for deformed steel bars (TMT bars) in reinforcement 10mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including MS wire (annealed) not less than 0.9mm dia or securing with clips complete all as specified and by Engineer-in-Charge.
Use and waste of formwork to soffits of suspended slabs such as roof slabs, floor slabs, landings and similar work; not exceeding 200mm thick (Horizontal or sloping , to achieve rough finished surfaces of concrete flat complete all as specified and directed.
Dismantling floor, hearth or wall tiling including cement mortar bedding (but not backing) , removing serviceable tiles to store and rubbish off the premises complete all as specified and directed.
Roughening surfaces of old concrete floor by picking, sweeping clean and washing down with water to remove dust, etc complete all as specified and directed.
M&L for screed bed or bedding layer of 15 mm thick cement-sand mortar 1:6 for laying floor tiles etc. complete all as specified and directed
M&L for screed bed or bedding layer of 20 mm thick cement-sand mortar 1:6 for laying floor tiles etc. complete all as specified and directed
M&L rendering 10 mm thick on fair faces of brick work or concrete surfaces in cement mortar 1:4 and surfaces finished rough to receive wall tiles etc. complete all as specified and directed.
M&L Non - skid Ceramic tiles 7 to 8 mm thick (square/ rectangular), area of each tile exceeding 0.18 sqm but not exceeding 0.38 sqm, in floors etc., set and jointed in neat cement slurry and pointed in white cement mixed with pigment to match the shade of tiles complete all as specified and directed.
M&L for 20 mm thick Granite (of any type) work (table rubbed and polished) in wall lining (veneering to wall) laid over and including 10 mm thick cement mortar (1:3) including pointing in white cement and marble dust (1:2) with admixture of pigment to match with the shade of granite stone complete all as specified and directed.
M&L glazed ceramic tiles 350x 250x 7 mm/ 450X 350X 7mm thick in vertical surfaces such as skirtings, dados, risers of steps etc, set and jointed in neat cement slurry and pointed in white or colour cement to match the shade of tiles, complete all as specified and directed.
M&L machine cut kota stone slab flooring 20-25mm thick over cement screed base, laid and jointed with grey cement slurry mixed with pigment to match the shade of the slab including rubbing and polishing complete all as specified and directed.
All as per serial item No 1.13 here-in-before but in risers of steps, skirtings, dados and on vertical surfaces such as pillars etc complete all as specified and directed.
M&L Non - skid Ceramic tiles 7 to 8 mm thick (square/ rectangular), area of each tile exceeding 0.06 sqm but not exceeding 0.11 sqm, in floors etc., set and jointed in neat cement slurry and pointed in white cement mixed with pigment to match the shade of tiles complete all as specified and directed.
Demolition of cement concrete (un-reinforced) in ground floors and pavings n exc 15 cm thickness (below or above ground level ) complete all as specified and directed.
M&L providing 75 mm thick plain cement concrete 1:3:6, type C-2 (using 40 mm graded stone aggregate) as in plinth protection, laid to slope of 1 in 12 and finishing the top surface even and smooth without using extra cement, including use of necessary form work complete all as specified and directed.
M&L providing 100 mm thick plain cement concrete type B- 2, 1:2:4 (40mm graded aggregate) as in sub-floor, sub-bases of floor, floor topping, pavings etc and surface finished even and smooth without using extra cement complete all as specified and directed.
Excavation in trenches, not exc. 1.5 m wide and n.exc.1.5 m in depth, in soft/loose soil for foundations, or for taking out/laying of underground cables, foundation of electric poles, stays, etc., n.exc.10 sq. m on plan and n.exc.1.5 m in depth, and getting out complete all as specified and as directed.
Returning, filling in approved soft/loose soil, including spreading, leveling, watering and well ramming in layers n.exc.25cm thick complete all as specified and as directed.
Removing surplus excavated soil to a distance exc.500 m but n.exc. 1.5 am and depositing where directed at a level n.exc.1.5 m high above the starting point complete all as specified and as directed.
Demolition of brickwork or stone/ boulder masonry, built in cement mortar , including all quoins, arches, pillars, etc, but excluding ashlar facings, dressed stonework and precast concrete articles , complete all as specified and directed.
M&L Brickwork with flyash modular bricks, straight or curved on plan to any radius in half brick thick walls, built in CM 1:3 complete all as specified and directed.
M&L Brickwork with flyash modular bricks, straight or curved on plan exc 6 metre mean radius, built in CM 1:6 complete all as specified and directed.
M&L rendering 15 mm thick on fair faces of brick work or concrete surfaces in cement mortar 1:6 and surfaces finished even and smooth without using extra cement complete all as specified and directed.
M&L rendering 15 mm thick on fair faces of brick work or concrete surfaces in cement mortar 1:4 and surfaces finished even and smooth without using extra cement on external surfaces of wall complete all as specified and directed.
M&L rendering 10 mm thick in cement mortar 1:3 on fair faces of brick work or concrete surfaces of ceiling and surfaces finished even and smooth without using extra cement complete all as specified and directed.
Dismantling structural steel work including doors, gates but excluding framed truss etc. complete all as specified and directed.
Dismantling plain or corrugated steel sheeting, any gauge, thickness, including Nainital or similar pattern roof coverings complete all as specified and directed.
S&F Pre- painted galvalume aluminum zinc coating GI based corrugated steel sheet 0.50mm thick of any colour having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self tapping screws complete all as specified and as directed.
M&L steel work in tubular trusses including special shaped washer etc. complete using ERW or induction butt welded tubes conforming to I. S:1161-1979, grade St.-240 complete all as specified and as directed.
M&L painting steel and iron surfaces of any description, over 10cm in width or girth, not otherwise described and applying two coats of synthetic enamel paint of approved shade or tint over a coat of red-oxide primer after necessary preparation of surfaces complete all as specified and as directed.
M&L mild steel framed work such as grills, gratings, etc. with ends of bars shouldered and/or riveted, or forged into spikes; framed guard bars; barred iron doors; ladders; framed balusters; walk ways; railings; framework of water tanks and similar work con- forming to Fe.290.Gde-E-165 complete all as specified and as directed.
Demolition of existing roof padding including roof treatment complete carefully by cutting, chiselling etc cleaning the surfaces by scrapping, brooming brushing etc and removing the rubbish from site to a distance exc 50m and n.exc 100m all as directed by the Engineer-in-Charge and M&L for providing roof treatment as under :- (i) Providing 15mm thick (average) rendering in cement mortar 1:3 mixed with WPC as per manufacturer's instruction (to be measured separately as 'supply only') for levelling to a true surface and to receive new roof treatment complete. (ii) Providing a coat of cold bitumen primer @ 0.25 Ltr /Sqm complete in horizontal and vertical surfaces . (iii) Providing a coat of hot blown bitumen of grade 85/25 @ 1.2 Kg/Sqm over primer surfaces (iv) Providing a layer of APP based polymeric membrane of approved manufacturer, 3mm thick weighing 3.5kg/Sqm reinforced with polyester non woven fabric (weighing not less than 160 Gms/Sqm) laid by torch application method, side overlaps shall be minimum 75mm longitudinal and end laps shall be minimum 100mm transverse and sealing all overlaps and joints as per manufacturer's instructions and provided upto a height of 60cm in the parapets and inserted inside the parapets by cutting a groove and finished by membrane flashing complete all as directed
Dismantling wall and ceiling boards (fiber, pulp, insulation, etc.) or insulation boards/slabs/ blankets, any thickness, including cover fillet complete all as specified and as directed.
M&L for Anodised aluminium snap grid frame work of size 605mm x 605mm for false ceiling comprising of aluminium main 'T' section of size 36.5 mm x 25 mm x 1.4 mm weighing 0.24 kg/m, cross 'T' section of size 23.5 mm x 26.4 mm x 1.4 mm weighing 0.191 kg/m and aluminium wall angle of size 40 mm x 25 mm x 2 mm suspended by means of 3 mm dia. G.I. wire hangers complete all as specified and as directed.
M&L for 4 mm thick Non- asbestos fiber cement building boards complying with IS-14862, fixed or laid/ inserted to timber/ GI/Aluminium framework with screws complete all as specified and as directed.
Taking down chowkhats or frame with shutters (without taking off shutters from frame) of any description exceeding 1.5 Sqm but not exceeding 4.00 Sqm each, complete all as specified and as directed.
Taking down chowkhats or frame with shutters (without taking off shutters from frame) of any description not exceeding 1.5 Sqm each, complete all as specified and as directed.
Taking down shutters of any description exc 1 sq. m and n.exc. 2.0 sqm each and refixing in the same opening complete all as specified and as directed.
Supply and fixing pressed steel frame of size 165x60mm, made out from 1.60mm thick cold rolled mild steel sheets for doors with one or more rebates including necessary fixing lugs, hinges, lock strike plate etc. complete as specified and directed.
S&F solid PVC door frame of size 50 mm x 47 mm made out of 5mm thick plain colour PVC sheet re-inforced with MS square tube in opening as per specification and drawing given in clause 8.B.3 of SSR -2010 (Part-II) complete all as specified and directed.
Supply and fixing Factory made solid panel PVC door shutter 30mm thick (style) consisting of frame made out of MS tubes for top and bottom rails. MS frame shall be covered with heat moulded plain colour PVC 'C' Channel having a PVC sheet strip of 20mm width stuck inside with solvent cement for stiles and plain colour PVC sheets for top rail, lock rail and bottom rail on either side & as gap insert for top rail and bottom rail. Panelling of plain colour PVC sheet to be fitted in the MS frame welded/sealed to the stiles & rails with suitable PVC sheet beading and joined together with solvent cement, fixing in the frame at site as per specification and drawing given in clause 8.B.2 of SSR -2010 (Part-II) complete all as specified and directed.
S&F mild steel work as in bands, straps, supports or stays for rainwater, ventilating pipes, including bolts, if required: hooks (stay), heavy, for large gates; hook and pintle hinges: large hasps and staples; chains; hand made sliding bolts; clamps; hold fasts; wall ties; hooks for hanging fans; plain angle cleats for securing purlins to wood trusses or rafters; knee piece inserts; two way and three way straps, plate washers and similar small articles conforming to Fe-290 Gde-E-165
M&L sanding newly tarred or painted surfaces with clean sharp sand complete all as specified and directed.
M&L for PCC 1:3:6, type C-1(using 20 mm graded stone aggregate) as in hold fast embedding blocks using necessary formwork etc complete all as specified and directed.
Supply and fixing 2nd class hard wood, 35mm thick, glazed and skeleton shutter , kiln seasoned and chemically pressure treated, open rebated and prepared to receive glass, gauge etc divided into squares with plain, chamfered or rounded, mitred and rebated sash bars (any numbers), edges of framing plain, chamfered or rounded, fitted with cut and mitered beads for securing glass, gauge etc; sizes of members of shutters as specified in SSR Part-I Section 8, Clause 8.24 (a) supplied and fitted to chowkats.
Supply and fixing 40 mm thick Flush shutters (ISI marked), factory made, solid core construction, with block board core and plywood face panels, commercial type on both sides , complete all as specified and as directed.
Supply and fixing anodised aluminium window and ventilator shutters, side hung type without sash bars, aluminium sections weighing 0.55 kg/m including necessary joining cleats, glazing clips, rubber packing, anodised aluminium snap beading, screws, anodised aluminium fittings such as peg stays 150mm long (1 No.). hinges type B-21 100mm long (2 Nos.) suitable handle (1 No.) including taking out/taking down old shutters complete all as specified and directed.
S&F Butt hinges, 100 mm size, heavy weight, cold rolled mild steel complete all as specified and as directed .
S&F Mild steel barrel tower bolts, 150 mm long, stove enameled black, with bright bolt and fixed complete all as specified and as directed.
S&F 300 mm Aluminium alloy, anodised, sliding door bolt with hasp, staple (bolt type) and fixing clips of sheet, cast or extruded sections and fixing bolts and sliding bolts of extruded sections or cast-aluminium alloy and fixed complete all as specified and as directed.
Supply and fixing Aluminium alloy wire cloth. 0.45mm nominal dia of wire and average width of aperture 1.40mm and fixed with aluminium wire staples all as specified and directed.
S&F in repair Vitreous China squatting pan, ‘Orissa’ pattern, size 580 x 440 mm white, with integral foot rests (excluding flushing cistern and flush pipe), 'P' trap and including connection to trap and flush pipe, anti-syphonage pipe etc including making good to floor all as specified and directed.
S&F in repair Vitreous China wash basin, white, flat back, size 550x400mm excluding taps, waste, chain and plug and porcelain stopper but including brackets complete all as specified and directed.
S&F in repair Vitreous China wash down water closet pan (pedestal pattern), white with trap (excluding fixing bolts, flushing cistern and flush pipe) and connecting to drain(outgoing pipe) and flushing pipe, anti-syphonage pipe etc including making good to floor complete all as specified and directed.
S&F in repairs Stainless steel sink, 1.00mm thick for kitchen or laboratory, with plug, waste pipe, washers, including cantilever cast iron brackets, connecting union etc., overall size 495mm x 420mm with bowl size 410mm x 330mm x 160mm without draining board complete all as specified and directed.
S&F in repairs 15 mm bore Pillar taps, cast copper alloy, with capstan heads, fancy type, chromium plated, screwed down high pressure, with or without lettered 'Hot' or 'Cold' with long screwed shanks and fly-nuts, screwed for iron pipe and fixed complete all as specified and directed.
S&F in repairs 10 litres discharge capacity PVC valveless, syphonic action type, flushing cistern, low level, white, with inlet, ball valve, float and handle including brackets and 32 mm dia PVC flush pipe of standard length complete all as specified and directed.
S&F in repair PVC connections 15mm size with PTMT nuts of length 600mm complete all as specified and directed.
S&F in repair Toilet paper holder of vitreous china, box type, coloured, fixed to walls with chromium plated brass screws complete all as specified and directed.
S&F in repair Grating round 140 mm size of PTMT (Minimum weight 50gms) complete all as specified and directed.
S&F in repair Sheet glass shelf assembly consisting of 5.5mm thick sheet glass shelf 12cm wide with chromium plated bracket guard and railing 60cm long complete all as specified and directed.
Hacking out old broken glass (any thickness, size, quality or description) from metal frames glazed with putty and removing materials from site of work complete all as specified and directed.
Supply and fixing sheet glass 3mm thick, ordinary quality and glazing with oil putty in squares not exc. 0.50 sq.m in each pane complete all as specified and as directed.
Supply and fixing Figured glass, 3 mm thick , pinhead type and glazing with oil putty in squares not exc. 0.50 sq.m in each pane complete all as specified and as directed.
Taking down damaged cement plaster on brick or stone walls, etc. including raking out joints, hacking for key, scrubbing down with water, etc complete all as specified and as directed.
Material and labour for complete removal of existing treatment on wall and applying two coats of exterior Acrylic emulsion paint (Apex) of approved shade or tint over a coat of alkali-resistant priming paint after necessary preparation of surfaces complete all as specified and as directed.
Material and labour preparation of new plastered or unplastered surfaces of walls and applying two coats of oil bound /oil emulsion distemper of approved shade or tint over a coat of compatible primer complete all as specified and directed.
Material and labour preparation of new plastered or unplastered surfaces of ceiling and applying three coats of white wash complete all as specified and directed.
Material and labour washing/rubbing down old distempered surface of walls and applying one coat of Acrylic washable distemper of approved shade or tint complete all as specified and directed.
M&L providing 3mm thick cement based wall care putty on wall all as specified and directed.
M&L providing 3mm thick cement based wall care putty on ceiling all as specified and directed.
M&L preparing new or previously untreated surfaces of wood and wood based materials of any description , not otherwise described, over 10 cm width or girth, and applying two coats of synthetic enamel paint of approved shade or tint over a coat of pink primer complete all as specified and as directed.
M&L preparing old or previously treated surfaces of wood and wood based materials of any description , not otherwise described, over 10 cm width or girth, and applying one coat of synthetic enamel paint of approved shade or tint complete all as specified and as directed.
M&L preparing old or previously treated steel surfaces of any description , not otherwise described, over 10 cm width or girth, and applying one coat of synthetic enamel paint of approved shade or tint complete all as specified and as directed.
S&F Harrison rails, 19/20 mm dia, mild steel, chromium plated with fixing brackets, stops, rollers etc complete all as specified and as directed.
S&F 100 mm bore reinforced concrete pipes, class NP2, laid and jointed complete with collars complete all as specified and as directed.
S&F 150 mm bore reinforced concrete pipes, class NP2, laid and jointed complete with collars complete all as specified and as directed.
Excavating in post holes (or similar holes) each n exc 0.5 cu. m, getting out, returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25 cm and getting out in soft/loose soil complete all as specified and as directed.
M&L providing cement concrete 1:4:8, type D-2(using 40 mm graded stone aggregate) in foundations, filling and mass concrete as in path, culvert,etc. and surface finished even and fair complete all as specified and as directed.
M&L providing cement concrete 1:2:4, type B-1(using 20 mm graded stone aggregate) in lintels upto 1.5m clear span, cills, steps; copings, and the like including weathering, slightly rounded or chamfered angles and throating, as directed complete all as specified and as directed.
S&F rolled mild steel work in plates (plain or chequered) channels, square cut or notched (ordinary and counter sunk) forming holes, without any attachment ; steel confirming to Fe 410-W(Gde-E-250) quality A complete all as specified and as directed.
Surface excavation n.exc.30 cm deep and averaging 15cm deep and getting out in soft/loose soil complete all as specified and as directed.
M&L providing hardcore of broken stone aggregate of guage n.exc 63mm , deposited, spread and levelled in layers n exc. 15 cm thick, consolidated, watered and rolled/rammed to a true surface complete all as specified and directed.
Removing excavated material n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and directed.
M&L Sand filling under floors or in foundations including watering and consolidation complete all as specified and directed.
M&L Machine pressed precast concrete interlocking paver block any shape and size confirming to IS 15658-2006 of 60 mm thickness, M-35 Grade with grey cement and pigment complete all as specified and directed.
Taking up or down old steel tubing and connections, including cleaning for refixing or removal to store and supply and fixing steel tube, 20 mm bore, 'medium grade' galvanised, with all fitting and fixed complete to walls and ceilings or laid in floors complete all as specified and directed.
Taking up or down old steel tubing and connections, including cleaning for refixing or removal to store and supply and fixing steel tube, 15 mm bore, 'medium grade' galvanised, with all fitting and fixed complete to walls and ceilings or laid in floors complete all as specified and directed.
Cleaning steel vents/ windows to remove all deposited cement, extra thick paint by any means, cleaning any type of hinges for easing window movement/ operation without taking down shutter of any description exc 0.5 sqm but not exc 2.00 sqm complete incl welding of hinges, any other steel member complete all as specified and directed by Engineer in charge.
Easing , adjusting , greasing steel rolling shutter, without ball bearing, as specified including top cover, anchoring rod, hasp and staple and shop coat of primer; erected in position as indicated, complete: push pull or manual type wheel & top grid wheel of joist, channel, angle or 'T' sections, fixed independently, without connecting plates incl removal of old paint two coat of synthetic enamel paint over a coat of red oxide, zinc chrome including preparation of untreated surface of any description, over 10cm width or girth ,not otherwise described all as directed.
AREA DRAINAGE
Demolition of cement concrete (un-reinforced) in ground floors and pavings/drain bed/coping n exc 15 cm thickness (below or above ground level) including removal of debris to outside MD land complete all as specified and as directed .
M&L providing cement concrete 1:2:4, type B-2(using 40 mm graded stone aggregate) in surface channels and drains and surface finished even and fair complete all as specified and as directed.
Extra for forming fair finished drain or channel 30 cm inner girth in cement concrete, using ex- tra cement, including forms, moulds, mitred/stopped ends etc. complete all as specified and as directed.
M&L providing plain cement concrete 1:2:4, type B-1(using 20 mm graded stone aggregate) in lintels upto 1.5m clear span, copings and the like including weathering, slightly rounded or chamfered angles and throating, complete all as specified and directed.
Spike rolling to surfaces or making impressions of expanded metal, whilst the concrete is green complete all as specified and directed.
M&L cement concrete chequered tiles with mixture of white and grey cement in equal proportions and no pigments, 25cm x 25cm x 22mm thick, machine pressed; set jointed and pointed in neat cement slurry in floors, and cut and polished complete all as specified and directed
M&L providing plain cement concrete 1:2:4, type B-1 (using 20 mm graded stone aggregate) in mass concrete complete all as specified and directed.
M&L providing 75 mm thick plain cement concrete 1:3:6, type C-2 (using 40 mm graded stone aggregate) as in sub-base of floor complete all as specified and directed.
FENCING
Dismantling fencing wire mesh, any type complete all as specified and directed.
Dismantling wrought iron or mild steel work of any description not otherwise provided for complete all as specified and directed.
Dismantling RCC posts or struts in fencing carefully, any section, embedded in natural ground including taking out embedded portion and making good disturbed ground complete all as specified and directed.
Excavating in post holes (or similar holes) in soft/loose soil each n exc 0.5 cu. m, getting out, returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25 cm, water, and removing surplus soil to a distance n.exc 50m and making good disturbed ground complete all as specified and directed.
M&L providing plain cement concrete 1:2:4, type B-2 (using 40 mm graded stone aggregate) in foundations, filling and mass concrete complete all as specified and directed.
Use and waste of formwork to sides of pillars, posts, struts, piers, columns and stanchions, square or rectangular, to achieve rough finished surfaces of concrete flat complete all as specified and directed.
S&F mild steel work in posts and struts in fencing including cutting tops to shape as directed, drilling holes, notching for wire, etc.; flat iron fillets (for securing wire mesh etc.) including all necessary drilling, bolting or riveting, etc., and similar work conforming to Fe-290 Gde E-165 complete all as specified and directed.
S&F chain link galvanised fencing 50 x 50 mesh size x 3 mm dia GI wire PVC coated (thickness of PVC coating 1.0mm ), including line wires, fixed to any type of standards, rails, straining bolts, etc. including provision of binding wire complete all as specified and directed.
M&L painting new or previously untreated steel and iron surfaces of any description, over 10cm in width or girth, not otherwise described and applying two coats of synthetic enamel paint of approved shade or tint over a coat of red-oxide primer after necessary preparation of surfaces complete all as specified and as directed.
M&L preparing surfaces of steel and iron work in fencing posts etc, new or old, of any description and girth, not otherwise described, and treated with tar or coal tar black paint exc 0.10 sqm and n.exc. 0.50 sqm complete all as specified and as directed.
S&F mild steel screw bolts (machine made) with hexagonal or square heads at one end and screwed the other, or screwed both ends, each screwed end to be fitted with washers and one hexagonal or square nut, exc 10cm and n.exc.15 cm long and dia of shank 10 mm complete all as specified and as directed.
M&L mild steel plain round bars 10mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips complete all as specified and as directed.
M&L providing cement concrete 1:3:6, type C-2(using 40 mm graded stone aggregate) in foundations, filling and mass concrete complete all as specified and as directed.
M&L providing reinforced cement concrete 1:1.5:3, type A-1 (using 20 mm graded stone aggregate) in foundations, footings etc complete all as specified and as directed.
M&L providing reinforced cement concrete 1:1.5:3, type A-1 (using 20 mm graded stone aggregate) in columns, pillars, posts etc complete all as specified and as directed.
Use and waste of formwork to sides of concrete foundations, footings, bases of columns, raft and raft beams, sides and soffits (if any) of foundation and plinth beams; and similar work; vertical or to batter, to achieve rough finished surfaces of concrete flat complete all as specified and directed.
Use and waste of formwork to sides of concrete pillars, posts,etc square or rectangular, to achieve rough finished surfaces of concrete flat complete all as specified and directed.
Use and waste of formwork to sides and soffits square or rectangular of floor or roof beams, arched beams, beam hunching, girders, bressummers, lintels, cantilevers, shelves including sup-ports, overhangs, etc. also splays between floors and beams, etc complete all as specified and directed.
Material and Labour for deformed steel bars (TMT bars) in reinforcement 6 to 8 mm dia, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including MS wire (annealed) not less than 0.9mm dia or securing with clips complete all as specified and by Engineer-in-Charge.
All as per serial item No 5.07 here-in-before but 5 mm dia and over upto and including 10 mm dia in stirrups, spacers, binders etc complete all as specified and directed.
M&L 20 mm thick Granite (of any type) tiles, machine cut, in work on vertical surfaces such as skirting's, dados etc , laid over and including 10 mm thick rendering in cement mortar (1:4), pointed in white cement with admixture of pigment to match the shade of granite stone including cutting and polishing complete all as specified and directed.
E/M WORKS NOTE: (i) The contractor shall obtain valid electrical license of required class in the firm's name or engage any agency having valid Electrical License of required class through proper agreement/MoU for execution of the electrical works as per Rule 29 under Part III of Central Electricity Authority Regulation 2010(Measures Relating to Safety and Electric Supply) is applicable forming either in full or in part of the scope of the contract. The work shall be executed by the contractor through such agency only (either by the contractor or other agency) having valid Electrical License of required class. Such license shall be obtained from the concerned authorities of State Govt /Union Territory where the works are to be executed. (ii) Prior to commencement of electrical work/electrical component of works under the contract, copy of valid electrical license shall be submitted by the contractor to the GE through the Engineer-in-Charge.
Supply and installation of copper wound transformer step down, outdoor type complete with standard fittings, HT 11 KV 3 Phase, LT 433 volts, 3 Phase 4 wire with off load tappings on HT side to vary secondary voltage within limit, all as per IS:1180 (Part-I) - 2014 of capacity 250 KVA including all jointing materials, connecting with electrical system, earthing, testing and commissioning all as specified and directed. (For ATC power House)
Supply, laying & testing HT cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminium conductor, 11000 volts grade, of size 3 core 95 sq mm all as specified and directed.
Supply and fix HT cable jointing kit for 11 KV grade cable for outdoor termination, cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 50 Sqmm to 95 Sqmm all as specified and directed.
Supply and fix HT cable jointing kit for 11 KV grade cable for indoor termination, cold shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 50 Sqmm to 95 Sqmm all as specified and directed.
Material and labour mild steel cross-arms,bracing,brackets, supports, clamps and back plates fabricated from structural steel section including nuts, bolts, washers, welding, bending cold or hot , drilling holes for bolts in any shape/size as directed including painting with two coats of aluminium paint over a coat red oxide primer complete all as specified and directed.
M&L earthing complete with galvanised earth plate electrode 600 x 600 x 6.3 mm buried directly in ground vertically to a depth of not less than 2.25 mtr below ground level connected to galvanised iron strip 32x6 mm earth lead by means of bolts, nuts, check nuts and washers made of galvanised iron or steel protected by 50 mm bore GI pipe (light grade) and connected to control board or transformer neutral earth or as directed by Engineer -in-Charge, PCC (1:3:6) type C1 earthing pit with pre-cast cover slab of size 300 mm x 300 mm x 100 mm with one number lifting handle made out of 8 mm dia round bar, 20 mm bore GI pipe (medium grade) for watering, GI sheet funnel with wire mesh, and provided with charcoal or coke in alternative layers of 15 cm alround the electrode including all necessary excavation and earth work , complete all as shown in Electrical Plate No 3 and testing on completion. (NOTE : The earth pit shall be provided with proper earth pit and pit cover. Pit cover should be painted with synthetic enamel paint of approved colour and pit number to be marked on a GI plate above 45 cm from GL as per colour code followed in AF Station.)
M&L earthing complete with copper earth plate electrode 600 x 600 x 3.15 mm buried directly in ground vertically to a depth of not less than 2.25 mtr below ground level connected to copper strip 20 x 3 mm earth lead by means of bolts, nuts, check nuts and washers made of galvanised iron or steel protected by 40 mm bore GI pipe (light grade) and connected to control board or transformer neutral earth or as directed by Engineer -in-Charge, PCC (1:3:6) type C1 earthing pit with pre-cast cover slab of size 300 mm x 300 mm x 100 mm with one number lifting handle made out of 8 mm dia round bar, 20 mm bore GI pipe (medium grade) for watering, GI sheet funnel with wire mesh, provided with charcoal or coke in alternative layers of 15 cm alround the electrode including all necessary excavation and earth work , complete all as shown in Electrical Plate No 3 and testing on completion. (NOTE : The earth pit shall be provided with proper earth pit and pit cover. Pit cover should be painted with synthetic enamel paint of approved colour and pit number to be marked on a GI plate above 45 cm from GL as per colour code followed in AF Station.)
M&L Earthing complete with galvanized steel earth plate electrode 600 x 600 x 6.3 mm thick buried directly in ground( earth pit not less than 2.25 mtrs deep below normal ground level )with the top edge of earth plate not less than 1.5 mtrs below normal ground level, connected to GI wire 4mm dia by means of GI bolts, nuts, check nuts and washers of galvanised iron or steel, earth lead protected by15mm bore GI pipe (light grade) and connected to main distribution board/earthing test point , provided with charcoal or coke in alternative layers of 15 cm alround the electrode including all necessary excavation and earth work all as shown in Electrical Plate No 3 of SSR Part-I all as specified including testing on completion. (Note:-The unit rate shall deemed to include for all necessary excavation, earth work in any type of strata, plain cement concrete 1:3:6 type C1 pit with 40mm thick precast RCC 1:2:4, type B1 cover reinforced with 8mm dia TMT bars @150mm c/c both ways ,GI sheet funnel with wire mesh, GI watering pipe 20mm bore (medium grade), earth lead protection pipe 15mm bore (light grade) for earth lead upto 7.50m long complete.)
M&L Earth continuity conductor or main earthing lead of 20 mm x 3 mm copper strip using porcelain clit/post insulators including brazing (if required), fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing complete all as specified and directed.
M&L Earth continuity conductor or main earthing lead of 32 mm x 6 mm galvanised iron strip using porcelain clit/post insulators including brazing (if required), fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing . complete all as specified and directed.
S&F 4 mm dia GI wire as earth continuity conductor with necessary clamp, connection etc, fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing complete all as specified and directed.
Supply and fix LED Flood light 200 Watt ,epoxy powder coated pressure die-cast aluminium housing in grey finish with elegantly designed heat sink for efficient thermal management , sturdiness and excellant corrosion resistant, with electronic LED driver with lower THD, with high quality toughened glass cover fixed to housing, IP 66 protection, complete with fixing arrangement such as M.S. clamps/bolts/nuts of suitable size for mounting the fitting on Steel tublar poles all as specified and as directed. (Note: Cost of necessary clamps/bolts/nuts duly treated with two coats of synthetic enamel paint over a coat of red-oxide primer after necessary preparation of surfaces shall be deemed to be included in the quoted unit rate for the item.) ( Make: Havells Model No JETA PROPLUS FL200WLED757LTG or Crompton Greaves Cat Ref LSFD-200-CDL/60 or Phillips LED 200W or Wipro Cat No LF20-272-060-57-XX (Loc : TMQ Power House).
Supply and fix Bollard lamp pressure die cast powder coated housing with PC diffuser with IP-66 protection for 10 Watt LED lamp complete providing electrical connection to the bollard light fitting from the electrical system using suitable size and type of copper conductor cable and suitable size GI mast complete all as specified and directed (Note: Necessary Excavation earth work, PCC foundation including necessary bolts and nuts shall be deemed to be included in the quoted unit rate.) (Make: Crompton Greaves Cat Ref MAYA I( LBLA1-10-CDL) or its equivalent model in Phillips/Havells (Loc : TMQ Power House).
M & L steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts and screws as specified , type 410 SP-31 (9.0 metres long) completewith one coat of primer and two coats of synthetic enamel paint of approved shade/colour all as specified and directed. (Note: Necessary excavation and earth work, PCC foundation, PCC coping/plinth block will be measured and paid separately.)
M & L disconnecting all HT/LT electrical connections, earthing strips of transformer of 100 KVA capacity at its existing location, removing foundation bolts & nuts etc, lifting it carefully and loading into suitable motor vehicle for shifting/transportation to new site , unloading at new site/location , re-installation after providing PCC foundation in PCC 1:2:4, type B-2(using 40 mm graded stone aggregate) of suitable size , making all HT/LT electrical connections with the electrical system at new place and carrying out all necessary testing on completion all as specified and directed by Engineer-in-Charge. (Loc : 1. ATC 100 KVA Txr & 2 From Birudhia Gate to Near Pump House 2.)
M & L cable junction box with IP 66 protection (Halogen free and weather proof ) for outdoor installations of size 260 x 210 x 116 mm , including SP MCB of 6 Amp, gland for cable, FI clamp of size 20x3 mm with bolts, , nuts, washers of suitable size including provision of connectors for connection of cables etc complete all as specified and directed.(Make : Hensel or its equivalent).
Supply , install, testing and commissioning of floor mounted LT indoor panel board of suitable dimension with canopy , CPRI approved, suitable for operation on AC 415 V , 50 Hz, 3 Phase 4 wire electrical system and accommodating the following switchgear and accessories, totally enclosed, self supporting structure / cubicle , fully compartmentalized design, outdoor type , with bottom cable entry with suitable cable glands, structure made out of 3.15 mm thick CRCA steel sheet , with angle iron frame work and legs of ISA 50X50X5 mm , with four legs grouted in PCC (1:2:4) type B1(using 20 mm graded stone aggregate) foundation block with suitable mounting arrangement for bus bars, voltmeter, ammeter , MCCBs , hinged doors at front with suitable locking arrangement , provision of louvers at sides , structure treated under 8 - tank metal treatment process and duly powder coated with approved colour , complete all as specified and directed (For NAA Qtrs and MGR) :-
BUSBAR :- (i) Copper bus bar 200 Amps , supported on non hygroscopic fibers and brass screws for mounting -04 Nos
INCOMER (a) S&F MCCB 4 Pole, AC 415 Volts,50 Hz of breaking capacity of 36 KA of 200 Amps with Fixed thermal and Fixed magnetic setting- 01 No.
INDICATING DEVICES (a) S&F LED Indicating lamps for Main Supply indicating R, Y, B - 03 Nos (b) S&F Digital Multifunctional Meter 31/2 digit display for measuring V, A, F, PF, kW, kVA, kVAR, kWh, kVAh, kVARh, Runhours, On hours, Phase angle, Interrupts, THD, Events (High-Low), Neutral Current , incl CT having CTR 1A/5A - 01 No, Accuracy Class 1.0 - 01 No.
OUTGOING FEEDERS (a) S&F MCCB of 3 pole , AC 415 Volts,50 Hz of capacity 63 amps with breaking capacity of 25 KA with Fixed thermal and fixed magnetic setting - 01 No (For SBI Bank & AO Office ) (b) S&F MCCB of 3 pole ,AC 415 Volts,50 Hz of capacity 125 amps with breaking capacity of 25 KA with Fixed thermal and fixed magnetic setting - 02 Nos. (For MGR & Pump House 2 ) (c) S&F MCCB of 3 pole , AC 415 Volts,50 Hz of capacity 100 amps with breaking capacity of 25 KA with Fixed thermal and fixed magnetic setting - 03 Nos(02 Nos. spares) (For NAA Qtrs. ) (d) S&F time switches, AC 415 V, three Phase & Astronomical timer rating with 63 Amp MCCB, contactor fitted inside steel enclosure - 02 Nos.
S&F APFC Panel comprising MD-XL Double metalized paper (Extra Low Loss) Capacitor for 3 phase, AC, 440 V, 50 Hz electrical system for permissible non- linear load 20% of capacity 30 KVAR complete all as specified.
Laying , jointing and testing LT cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of following size 240.00 sq mm 3½ core complete all as specified. (Note: 1. Cable will be issued under Schedule 'B' as 'Free for Laying' only. 2. Cable joints will be measured and paid for separately under relevant item(s) of this Schedule.)
(a) 3.5 core 240 Sqmm
(b) 3.5 core 95 Sqmm
(c) 3.5 core 35 Sqmm
(d) 4.0 core 25 Sqmm
(e) 4.0 core 16 Sqmm
Supply , install, testing and commissioning of floor mounted LT indoor panel board of suitable dimensionwith canopy , CPRI Approved, suitable for operation on AC 415 V , 50 Hz, 3 Phase 4 wire electrical system for accommodating the following switchgear and accessories, totally enclosed, self supporting structure / cubicle , fully compartmentalized design, outdoor type , with bottom cable entry with suitable cable glands, structure made out of 3.15 mm thick CRCA steel sheet, with angle iron frame work and legs of ISA 50X50X5 mm , with four legs grouted in PCC (1:2:4) type B1(using 20 mm graded stone aggregate) foundation block with suitable mounting arrangement for bus bars, voltmeter, ammeter & MCCBs , hinged doors at front with suitable locking arrangement , provision of louvers at sides , structure treated under 8 - tank metal treatment process and duly powder coated with approved colour , complete all as specified and directed :- (For TMQ Qtr Area)
BUSBAR :- (i) Copper bus bars 250 Amps , supported on non-hygroscopic fibers and brass screws for mounting -04 Nos
INCOMER (a) S&F MCCB 4 Pole, AC 415 Volts,50 Hz of breaking capacity of 36 KA of 250 Amps with Fixed thermal and Fixed magnetic setting- 01 Nos
INDICATING DEVICES (a) S&F LED Indicating lamps for Main Supply indicating R, Y, B - 03 Nos (b) S&F Digital Multifunctional Meter 31/2 digit display for measuring V, A, F, PF, kW, kVA, kVAR, kWh, kVAh, kVARh, Runhours, On hours, Phase angle, Interrupts, THD, Events (High-Low), Neutral Current , incl CT having CTR 1A/5A - 01 No, Accuracy Class 1.0 - 01 No.
OUTGOING FEEDERS (a) S&F MCCB of 3 Pole , AC 415 Volts,50 Hz of capacity 63 amps with breaking capacity of 25 KA Fixed thermal and fixed magnetic setting - 06 Nos.(04 Nos + 02 Nos(spares) (For TMQ Qtrs. ) (b) S&F time switch,AC, 415 V, 50 Hz, three Phase & Astronomical timer with 63 Amp MCCB, contactor fitted inside steel enclosure - 01 No
Supply , install, testing and commissioning of floor mounted LT indoor panel board of suitable dimensionwith canopy , CPRI Approved, suitable for operation on AC 415 V , 50 Hz, 3 Phase 4 wire electrical system for accommodating the following switchgear and accessories, totally enclosed, self supporting structure / cubicle , fully compartmentalized design, outdoor type , with bottom cable entry with suitable cable glands, structure made out of 3.15 mm thick CRCA steel sheet of size ( 1.2 m x 1.5 m x 0.6 m) with angle iron frame work and legs of ISA 50X50X5 mm , with four legs grouted in PCC (1:2:4) type B1(using 20 mm graded stone aggregate) foundation block with suitable mounting arrangement for bus bars, voltmeter, ammeter and MCCBs , hinged doors at front with suitable locking arrangement , provision of louvers at sides , structure treated under 8 - tank metal treatment process and duly powder coated with approved colour , complete all as specified and directed :- (For GE Office)
BUSBAR :- (i) Copper bus bar 200 Amps , supported on non hygroscopic fibers and brass screws for mounting -04 Nos
INCOMER (a) S&F MCCB 4 Pole, AC 415 Volts,50 Hz of breaking capacity of 36 KA of 200 Amps with Fixed thermal and Fixed magnetic setting- 01 Nos
INDICATING DEVICES (a) S&F LED Indicating lamps for Main Supply indicating R, Y, B - 03 Nos (b) S&F Digital Multifunctional Meter 31/2 digit display for measuring V, A, F, PF, kW, kVA, kVAR, kWh, kVAh, kVARh, Runhours, On hours, Phase angle, Interrupts, THD, Events (High-Low), Neutral Current , incl CT having CTR 1A/5A - 01 Nos Accuracy Class 1.0 - 01 Nos
OUTGOING FEEDERS (a) S&F MCCB 3 Pole, AC 415 Volts,50 Hz of capacity 125 amps with breaking capacity of 25 KA Fixed thermal and fixed magnetic setting - 01 No (For GE Office). (b) S&F MCCB 3 Pole, AC 415 Volts,50 Hz of capacity 63 amps with breaking capacity of 25 KA Fixed thermal and fixed magnetic setting - 02 No (For Living-in & Old Pump House) (c) S&F MCCB 3 Pole, AC 415 Volts,50 Hz of capacity 100 amps with breaking capacity of 25 KA Fixed thermal and fixed magnetic setting - 01 No. (For AF School ) (d) S&F time switch, AC, 415 V, 50 Hz, three Phase & Astronomical timer with 63 Amp MCCB, contactor fitted inside steel enclosure - 02 Nos.
Supply & fixing High density polyethylene pipes (HDPE) of pressure rating 6 kgf/cm2 laid in trenches for protection of underground cables with all fittings of 100 mm dia.complete all as specified and ass directed.
S&F in replacement of insulated synthetic mat of size 2 meter x 1 meter x1 2 mm thickness suitable for working pressure 1.1 KV including taking down worn-out mat from various locations of E/M installation complete all as specified and ass directed.
Supply, spread & leveling aggregate of 40 to 80 mm gauge/ size around transformer, HT two pole structure, HT four pole structure etc in the proposed MRS complete all as specified and ass directed.
Dismantling existing HT Steel/Iron Poles from any place/area and any height complete all as specified and ass directed. (NOTE :- Quoted rate shall be deemed to be inclusive of all necessary excavation and earthwork required for dismantling of the poles and making good disturbed surfaces.)
Dismantling existing HT RCC/Steel tubular Poles from any place/area and any height including connected items like gang operating device, DO fuse, channels and all other accessories complete all as specified and ass directed. (NOTE :- Quoted rate shall deemed to be inclusive of all earthwork required for dismantling of the poles. and making good surface.)
M & L for dismantling cross-arms of M.S. channel or angle sections etc. including nuts and bolts complete and setting aside complete all as specified and as directed.
M & L for dismantling insulators any type, any size from HT/LT poles complete and setting aside all as specified and as directed.
M& L for dismantling of ACSR conductors of any type and any size from the existing HT/LT poles and setting aside complete all as specified and as directed.
M&L for 10 cm dia 8 mm thick cast iron cable route indicator HT/LT in round shape, fixed on angle iron post of size 25x25x4mm, 45 cm long complete, embedded in PCC 1:3:6, type C-1 block of size 250x250x250mm , duly marked /engraved HT cable 11 KV / LT cable 1.1 KV (HT cable brown colour and LT cable blue colour ), including all necessary excavation , returning, filling in and removal of surplus soil to a distance n.exc. 50m complete all as specified and directed.
M&L providing sand cushioning with a layer of fine sand 80mm thick before laying of cable and 150 mm thick after laying of cable in trenches, ducts etc complete all as specified and directed.
M&L brick protection with common burnt clay sub- class ‘B’ bricks (old size), laid dry, flat in trenches over cable with longest dimension perpendicular to the axis of the cable complete all as specified and directed.
S&F in replacement GI tubing ( light grade) including all necessary fittings as required, 40mm bore (ISI marked) complete for protection of electric cable laid in trenches or fixed on pole including taking down the old worn-out pipe complete all as specified and directed
S&F in replacement GI tubing ( light grade) including all necessary fittings as required, 50mm bore (ISI marked) complete for protection of electric cable laid in trenches or fixed on pole including taking down the old worn-out pipe complete all as specified and directed
M&L boring holes under road, pavement, hard-standing by trenchless technology using ultra sounding technique and necessary boring machine as per site requirement complete all as specified and directed.
Excavation in trenches, not exc. 1.5 m wide and exc.1.5 m & n.exc.3.0m in depth in soft/loose soil for taking out/laying of underground cable, foundation of poles, stays etc., n.exc.10 sq. m on plan and n.exc.1.5 m in depth, and getting out complete all as specified and as directed.
Supplying and laying reinforced precast concrete cable cover, class EHV, type 1 with peak, size 450mm x 230mm x 50mm complete all as specified and as directed.
M&L providing cement concrete 1:2:4, type B-2(using 40 mm graded stone aggregate) in foundations of electric poles, filling and mass concrete complete all as specified and as directed.
M&L construction in repairs PCC platform of size 2500 x 2500 x 1200 mm height above ground level and 600 mm below GL for mounting transformer in accordance with the following brief specifications complete all as specified and directed.:- (i) Excavation & earthwork : In any type of soil (soft/loose/hard/ dense). Surplus earth be disposed off to a distance not exceeding 50 metres. (ii) Foundation lean Concrete : 150 mm thick PCC 1:3:6 type C-2 (using 40mm graded stone aggregate). (iii) Brick Wall : 230 mm thick solid brick work with sub-class ‘B’ bricks built in CM 1:4. (iv) Flooring : 100 mm thick PCC 1:2:4 type B-1 (using 20mm graded stone aggregate) laid over 150 mm thick PCC 1:4:8, type D-2 (using 40 mm graded stone aggregate). (v) Earth Filling under floor : With approved soil (soft/loose/hard/ dense) as specified. (vi) Brick Steps (on one side of platform): Sub-class ‘B’ bricks built in CM 1:4 (vii) Angle Iron Posts with Chain link Fencing alround the Platform : ISA 50x50x6mm posts at equal spacing with 50mm x 50mm mesh size x 3mm dia of wire PVC coated chain link fencing. (viii) Hinged Door (on one side) : 1.5m wide x 1.0 m high made out of MS angle 50x50x6 mm section with angle iron cross bracings. (ix) Finishing : Steel and iron surfaces to be treated with two coats of synthetic enamel paint over a coat of red-oxide primer after necessary preparation of surfaces.
Supply & replace PVC insulated and sheathed copper conductor(flexible) industrial round cable 2.5 sq.mm 3 core, drawn through and including 15 mm bore GI tubing(light grade) for making connection to street light on pole/wall from junction box/DB including termination clip etc. complete all as specified and directed.
UNIVERSAL TRADING
FRIENDS CONSTRUCTION
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .