| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹56.7 LAccepted-AOC HOSPITAL ROAD SOLAN TEHSIL SOLAN DISTRICT SOLAN HP | SOLAN | SOLAN | HIMACHAL PRADESH | 1 | Accepted-AOC L1 | |
| 2 | 2₹58.8 L+₹86,750 (1.50%)Rejected-Finance HOSPITAL ROAD OPP VIPUL GAS AGENCY SOLAN HP 173212 | SOLAN | SOLAN | HIMACHAL PRADESH | 173212 | 2 | Rejected-Finance L2 | |
| 3 | 3₹63.3 L+₹5.4 L (9.24%)Rejected-Finance | 3 | Rejected-Finance L3 |
Tender Value
₹32.6 L
EMD Value
₹56,400
Closing Date
22 Mar 2021, 11:00 amClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Executive Engineer
JSV Division Jubbal
Providing FHTC to left out house hold for NSJ under Jubbal Kotkhai constitunency in JSV Division Jubbal Distt Shimla HP SH S E of pumping machienry Job 7th Kotkhai
2021_HPIPH_45435_1
JBL-SML09-718
Open Tender
Pumps/Motors
Item Rate
180 days
Kotkhai
Please refer Tender documents.
8 documents required · 8 mandatory
₹400
₹56,400
Yes
11 Jun 2021
12 Mar 2021
22 Mar 2021
12 Mar 2021
22 Mar 2021
12 Mar 2021
120 days
Amount
Excavation in foundation,trenches (trenches for laying of pipes and man hole chambers) up to all depths in all classification of earth work such as pick work, jumper work, saturated soil including bailing or pumping out water, blasting soft/hard rock or chiseling soft/hard rock where blasting is prohibited in all lifts including trimming & dressing of sides, levelling of beds to correct grade i/c shoring/strutting, planking,timbering & dewatering wherever required, stacking the usable & unusable material/soil separaterly & after laying, jointing & testing of pipes, returning the useable soil in trenches in 15 Cm layers including consolidating of such deposited layer by ramming & watering & then disposing of all surplus excavated soil/unusable material as directed with in all leads & lifts including restoration of unmetalled surfaces to its original condition & including cost of diversion for traffic,night signals, fixing caution boards, crossing over trenches for access to houses, fencing etc. complete in all respects with in all leads & lifts as per directions of Engineer - in - charge.
Providing, laying, & commissioning at site in trenches to be leveled to grades with bevelled ended MS API pipes conforming to IS/ISO:3183-2007 (Latest with up to date amendments) having minimum wall thickness as specified below & capable of with standing required test pressure as prescribed in IS/ISO code, in random lengths of 5.5 to 6.5 mtr. The pipe ends shall be levelled suitable for butt welding, including the cost of jointing with butt welding confirming to IS 816-1969 or latest applicable and with uptodate ammendments (leak proof) in three layers at siteof work with welded rods of Advani/oeriliken make/ISI marked (welded rods 3mm to 4mm) and all allied accessories whatever required for welding at site, tail pieces,tee bends & other special manufactured from parent pipes as applicable to the particular reach and of approved specification as per site conditions. and cutting of pipes wherever required as per site requirement including carriage in all leads & lifts andas directed by the Engineer-In-Charge. The pipe shall have zinc coating inside & outside confirming to IS-4736-1986 or latest with upto date ammendments & shall be engraved with API grade. It shall include the cost of NRV, Scour valve and air valve of required rating which are to be fixed at required locations as per direction of Engineer in Charge. The laying shall cofirm to BIS 5822-970 or latest with upto date ammendments to the entire satisfaction of Engineer-In-Charge. (Earth work & cost of MS Flanges after 100meter length shall be measured & paid for seperately.) including all leads, lifts and carriage of materials at site andas per direction and to the entire satisfaction of the Engineer-In-Charge. Dia of pipe Class of pipe Thickness RD F.table
50mm API-L245 4.80 0-600 34
50mm API-L245 4.80 600-1800 28
50mm API-L245 4.80 1800-21 17
32mm API-L245 4.80 0-3 28
Laying, jointing, testing & commissioning at site in trenches following plain ended GMS pipe of various dia and classes as under confirming to BIS 1239 (Part-I) 1990 or latest with up to date amendments, capable of withstanding required test pressure in BIS code in rendom lengths of 5.5 to 6.5 mtr. The pipes ends shall be bevelled suitale for butt weld, including the cost of jointing with butt welding confirming to IS 819-1969 or latest as applicable (leak proof) in three layers at site of work with welding rods of standard make and all allied accessories whatever required for welding at site tail pieces tees bends manufactured from parents pipes etc. and cutting of pipes wherever required as per site requirement including carriage in all leads and lifts as directed by Engineer-in-charge (earth work shall be measured and paid saperately). Dia of pipe Class of pipe Thickness RD F.table
50mm G.I (H) -- 2100-2400 17
50mm G.I (M) 2400-2500 5
32mm G.I (H) -- 300-9 17
32mm G.I (M) -- 900-1500 5
Providing and welding MS flanges as per table below conforming to IS:6392-1971 ( latest upto date amendments) and welding of flanges with pipes as per IS: 816-1965 with a electrode as per IS: 814-1967 including required Nos. and size of MS nuts and bolts as per IS: 1369-1967 and compressed asbestos fiber jointless gaskets sheet not less than 3mm thick as per IS: 2712-1965. The welding of flanges to be done in three layers ( two out side+one inside)to make the joints leak proof and to the entire satisfaction of the Engineer-in-charge. Dia of pipe Class of pipe Thickness RD F.table
50mm API-L245 4.80 0-6 34
50mm API-L245 4.80 600-1800 28
50mm API-L245 4.80 1800-2100 17
50mm G.I (H) --- 2100-2400 17
50mm G.I (M) --- 2400-2500 5
32mm API-L245 4.80 0-300 28
32mm G.I (H) -- 300-900 17
32mm G.I (M) -- 900-1500 5
Supply and errection of pumping machinery (Bareon). Providing horizontal spindle,horizontal/redial split casing/and suction(Back-full out arrangements single/double/multi stage centrifugal pump or combination of pumps. In series/parallel of recommended make such as Mather and Platt/KSB/Beacon Weir/Kirlosker/BE/Jyoti as per BIS 1520-1980 with upto date ammend-ments read with IS:9137-1978 or latest edition suitable for lifting water for under mentioned characterestics with bronze,impellers/priming funnels,casing ring and shaft sleeves of bronze,shaft of steel grade 4508 FN8 with cast iron casing coupled directly through a flexible coupling on a common MS/Cast steel base plate (base plate to be from the manufacturer of the pumping unit only) to slip ring/ squirrel cage screen protected drip proof induction motor/motors of standard make such as Kirlosker/BHEL/Crompton/NGEF/GEC/Siemens/Jyoti and suitable for operation on 400(+/-)10% volts,50 cycles /second.3 phase AC electric supply. The power of electric motor/motors should be at +10% in excess of the maximum power required by the pump/pumps in the operation range of (+) 10% and (-)15% of the duty poiint head. The motor/motors as per ISI:325:1978 with upto date ammendments read with IS 900:1972. It should include cost of bearing nuts bolts and painting etc. and should meet the following requirements.
Discharge (Q) 1.35 LPS for each pump.
Total Dynamic head:- 688.29 Mtrs
a) LWL in sump well (h) 1980 metre
b) Shaft level 1980 metre
c) Level at discharge point 2616 metre
d) Suction lift (+) head 3.00 metre.
e) Discharge head 2616 metre
f) Static head 636 metre
Rising main
a) Length 2500 mtr
b) Dia 50 mm
Pumping hours 8 Hours
Altitude of installation above
MSL metre
Characterstics of water Raw water with turbidity up to 6000 PPM.
a) Temperature 0 degree centigrade.
b) Ambient temp 0 degree centigrade.
c) Turbidity JTU
d) Alkility
Size of the solid particals Nil.
f) Other
Providing ICTP Main switch with HRC fuses of Kilburn/L&T/siemens/Standard/Havells make and having capacity 30% extra of the operational rating as per IS: 4064:1978 with upto date ammendments immeidately after the power meter of the HPSEB. ICTP Switch Make Type Capacity
Providing MS sheet steel fabricated floor mounted closed(almirah type) switch board including angle iron post of suitable height and size ISA 40x4r0x6 duly painted with steel sheet of 16 gauge comprising and capacable of mounting the following accessories withina ll internal connections. All the accessories should be suitable for the proposed pumping machinery at item No.1 above and to the entire satisfaction of HPSEB authorities. The same shall have to be replaced with out extra cost if recommended by HPSEB authorities. Panel Switch Board Drawing Layout plan
i) MCB/MCCB of MEI/Havels/ standard make and of suitable capacity for offered motor on incoming feeder with or without initial oil filling as the case may be with neutral linked under voltage released as per relevent IS code with upto date ammendments. MCB/MCCB Make Type Range Capacity
II) Earth leakage circuit breaker of recommended make (Kilburn/L&T/MEI/GEC) as per IS:2516:1977 with upto date ammendments of suitable range which should have control box, operation, handle and trip/reset bush button on/off indicators, re-indicating off spring condition of the ciruit breaking for cover current protection. The circuit should be equipped with magnet thermal release with metallic tap etc, it should also be fitted with earth fault for tripping of breaker on occurnce of earth fault on off breaker load side end. E.L.C.B Make Type Range.
(III) The voltage monitor relay of AE/MEI/L&T / Havells make three phase with all protection and usual indicator and electric siren against single phasing,low voltage,high voltage, reverse phasing, over loading and phase voltage difference as per IS:3482(latest edition) Voltage Monitor Relay Make Type Range.
Digital Power factor meter of standard make AE/L&T/IMP/Havells as per relevant IS code with upto dateammendments. Power Fectoe Meter Type Make Range.
Digital Frequencey meter of standard makeAE/L&T/IMP/Havells as per relvant IS code with uptodate ammendments. Frequency Meter Type Make Range.
Bus bar chamber having three copper bars of suitable rating for full length equal to the width of the board for three live phases and suitable for inducted current, one copper bar of half the rating of full length for neutral phase as per IS 8084-1976 and IS:11353-1985 read with BIS 5578-1985 with upto date ammendments. Bus Bar Chamber Type Make Range.
ICTP switches with HRC fuses unit of Kilbur/L&T/siemens/stands/Havells make and of suitable capacity as per IS:4064:1978 with upto date ammendments. ICTP Switches Type Make Capacity.
Three phase indicator lamps complete with toggle switches for individual motors as per IS:3452:(P-I & II) with upto date ammendments. Three Phase Indicator Type Make Capacity.
Capacitor of crompton/L&T/NGEP make as per 15:2834:1986 with upto date ammendments, to raise the power factor at site to 0.95 for direct connections to induction motor individually of required KVA rting according to H.P.offered including cables as per relevant ISI code (of siemens/clocter.IEC make )from bus bar chamber to capacitor and also including ICTP switches of appropriate range as per Is:4064:1978 with upto date ammendments. Capacitor Type Make Range
Providing suitable oil immersed starter delta/direct on line/auto transformer/. starter rotor starter of MEI/.Kilburn/Jyoti /L&T/Siemens make as per IS:8544:1979 with upto date ammendments for squirrel cage/slip ring motor mounted on panel board with magnetic type over-load release and dashpot, time lag, under voltage release with or without initial oil filling as the case may be with single phase preventor as per IS:1248( P-V) 1983 with upto date ammendments. Starter Type Make
Providng Digital hour run meter of recommended make and suitable capacity as per IS:722(latest edition.). Hour Run Meter Type Make Capacity.
Providing antivibration pads under the pumps and motors of suitable size for the above pumping machinery as per IS:6337:1971. Antivibration Pads Size Make Material.
Providing double flanged CI sluice valve PN1 of Leader/BHEL/Kirlosker/GLEd/Kilburn Fourses / Kartar make and equal to dia of suction pipe and cpable of withstanding the normal seat pressure as per IS:780:1984 with upto date ammendments. Sluice Valve Make Class Seat Pressure.
Providng double flanged cast iron sluice valves PN-I of leader/BHEL Kirlosker/Kilburn GLED/fourses/ Kartar make and one step higher then delivery line of pump and capable of withstanding the normal seat pressure and as per BIS standards with upto date ammdnements. Sluice Valve Make Class Seat Pressure Material.
Providing double flanged swing type cast iron valve, PN-I of Leader/BHEL/Kirlosker/Kilburn/GLEd/Fourses/ Kartar make and having bye pass arrangements of one step higher then delivery line of pump and capable of withstanding normal seat pressure as per BIS standards with upto date amnmendments). Reflux Valve Make Class Seat Pressure Material
Providing double flanged cast iron reflux valves class PN-I of Leader/BHEL/KILROSKER/Kartar/KILBURN/GLED/FOURSES/ Kartar make and of 350 mm dia having bye pass arrangements for rising main and capable of withstanding normal seat pressure as per BIS standards with upto date ammendments. Reflux Valve Make Class Seat Pressure Material
Providing 100mm dia circular dial analog pressure gauge of suitable range of Fiebig /Bourden/ PREGA/precision make complete with all accessories such as stop cock, copper tubing etc.as per IS: 3624-1987 with upto date ammendments. Pressure Gauge Make Range.
Providing discharge meter of standard make to be fixed on the rising main in pump house as per the directions of the Engineer in charge as per Is:2373:1981 with upto date ammendments. Discharge Meter Make Type Range
Installation of all the items apparing at serial No.1 to 9 as per the systematic drawing.
Providing and fixing double flanged MS/GI piping work (Layout to be approved by the Engineer in charge) for suction and delivery pipes suitable to pump(s) offered and common header as per the R/Main respectively complete with all specials such as bends, tees, reducers. Increasers with companions flanges matching with the relevant specifications of the accessories including rubber/asbestos gasket of minimum 3mm thckness as per IS:2712:1979 and required number of nuts and bolts as per Is:1364:1983, The Pipes fittings and joints shall be as per relevant IS code & to withstand 1.5 times total head stipulated under item No.1. The size of the various components to be as under: i) Suction pipe : One dia higher then the suction of pump offered and suitable to keep the velocity of flow from 1 to 1.5M/second in the suction pipe. ii) Delivery pipe: One dia higher then the delivery of the pump offered and suitable to keep the velocity of flow from 1.5 to 2M/second in the delivery pipe. iii) Common header : One dia higher then delivery of pump x 350 mm dia and will extend upto 5 meters from the outer wall of the pump house in the direction to be jointed. Suction Pipe Material Grade Thickness Pressure rating. Delivery oioe and common header Material Grade Thickness Pressure rating.
Providing and laying copper PVC insulated arsoured power cable(One cable carrying all the three phases) of suitable size and capacity to motors and all other electircal equipments as per IS:1554(P-I) 1988 or latest ith upto date ammendments of siemens GLOSTER /IEC /ICC /EICD/NATIONAL/GRANDLAY make including all other accessories such as thinbles, flexible pipes,solders,nuts and bolts cable glands etc. laid in pipes or trenches under floor. Arsoured Power Cable A. Motor Side (from switch to starter and starter to motor) Size Make Type Capacity Core B. Supply Side (from meter to HPSEB to bus bar and switch) Size Make Type Capacity.
Supply and errection of pumping machinery (Panog). Providing horizontal spindle,horizontal/redial split casing/and suction(Back-full out arrangements single/double/multi stage centrifugal pump or combination of pumps. In series/parallel of recommended make such as Mather and Platt/KSB/Beacon Weir/Kirlosker/BE/Jyoti as per BIS 1520-1980 with upto date ammend-ments read with IS:9137-1978 or latest edition suitable for lifting water for under mentioned characterestics with bronze,impellers/priming funnels,casing ring and shaft sleeves of bronze,shaft of steel grade 4508 FN8 with cast iron casing coupled directly through a flexible coupling on a common MS/Cast steel base plate (base plate to be from the manufacturer of the pumping unit only) to slip ring/ squirrel cage screen protected drip proof induction motor/motors of standard make such as Kirlosker/BHEL/Crompton/NGEF/GEC/Siemens/Jyoti and suitable for operation on 400(+/-)10% volts,50 cycles /second.3 phase AC electric supply. The power of electric motor/motors should be at +10% in excess of the maximum power required by the pump/pumps in the operation range of (+) 10% and (-)15% of the duty poiint head. The motor/motors as per ISI:325:1978 with upto date ammendments read with IS 900:1972. It should include cost of bearing nuts bolts and painting etc. and should meet the following requirements.
Discharge (Q) 0.58 LPS for each pump.
Total Dynamic head:- 277.24 Mtrs
a) LWL in sump well (h) 1980 metre
b) Shaft level 1980 metre
c) Level at discharge point 2200.00 metre
d) Suction lift (+) head 3.00 metre.
e) Discharge head 2200 metre
f) Static head 220 metre
Rising main
a) Length 1500 mtr
b) Dia 32 mm
Pumping hours 8 Hours
Altitude of installation above
MSL metre
Characterstics of water Raw water with turbidity up to 6000 PPM.
a) Temperature 0 degree centigrade.
b) Ambient temp 0 degree centigrade.
c) Turbidity JTU
d) Alkility
Size of the solid particals Nil.
f) Other
Providing ICTP Main switch with HRC fuses of Kilburn/L&T/siemens/Standard/Havells make and having capacity 30% extra of the operational rating as per IS: 4064:1978 with upto date ammendments immeidately after the power meter of the HPSEB. ICTP Switch Make Type Capacity
Providing MS sheet steel fabricated floor mounted closed(almirah type) switch board including angle iron post of suitable height and size ISA 40x4r0x6 duly painted with steel sheet of 16 gauge comprising and capacable of mounting the following accessories withina ll internal connections. All the accessories should be suitable for the proposed pumping machinery at item No.1 above and to the entire satisfaction of HPSEB authorities. The same shall have to be replaced with out extra cost if recommended by HPSEB authorities. Panel Switch Board Drawing Layout plan
i) MCB/MCCB of MEI/Havels/ standard make and of suitable capacity for offered motor on incoming feeder with or without initial oil filling as the case may be with neutral linked under voltage released as per relevent IS code with upto date ammendments. MCB/MCCB Make Type Range Capacity
II) Earth leakage circuit breaker of recommended make (Kilburn/L&T/MEI/GEC) as per IS:2516:1977 with upto date ammendments of suitable range which should have control box, operation, handle and trip/reset bush button on/off indicators, re-indicating off spring condition of the ciruit breaking for cover current protection. The circuit should be equipped with magnet thermal release with metallic tap etc, it should also be fitted with earth fault for tripping of breaker on occurnce of earth fault on off breaker load side end. E.L.C.B Make Type Range.
(III) The voltage monitor relay of AE/MEI/L&T / Havells make three phase with all protection and usual indicator and electric siren against single phasing,low voltage,high voltage, reverse phasing, over loading and phase voltage difference as per IS:3482(latest edition) Voltage Monitor Relay Make Type Range.
Digital Power factor meter of standard make AE/L&T/IMP/Havells as per relevant IS code with upto dateammendments. Power Fectoe Meter Type Make Range.
Digital Frequencey meter of standard makeAE/L&T/IMP/Havells as per relvant IS code with uptodate ammendments. Frequency Meter Type Make Range.
Bus bar chamber having three copper bars of suitable rating for full length equal to the width of the board for three live phases and suitable for inducted current, one copper bar of half the rating of full length for neutral phase as per IS 8084-1976 and IS:11353-1985 read with BIS 5578-1985 with upto date ammendments. Bus Bar Chamber Type Make Range.
ICTP switches with HRC fuses unit of Kilbur/L&T/siemens/stands/Havells make and of suitable capacity as per IS:4064:1978 with upto date ammendments. ICTP Switches Type Make Capacity.
Three phase indicator lamps complete with toggle switches for individual motors as per IS:3452:(P-I & II) with upto date ammendments. Three Phase Indicator Type Make Capacity.
Capacitor of crompton/L&T/NGEP make as per 15:2834:1986 with upto date ammendments, to raise the power factor at site to 0.95 for direct connections to induction motor individually of required KVA rting according to H.P.offered including cables as per relevant ISI code (of siemens/clocter.IEC make )from bus bar chamber to capacitor and also including ICTP switches of appropriate range as per Is:4064:1978 with upto date ammendments. Capacitor Type Make Range
Providing suitable oil immersed starter delta/direct on line/auto transformer/. starter rotor starter of MEI/.Kilburn/Jyoti /L&T/Siemens make as per IS:8544:1979 with upto date ammendments for squirrel cage/slip ring motor mounted on panel board with magnetic type over-load release and dashpot, time lag, under voltage release with or without initial oil filling as the case may be with single phase preventor as per IS:1248( P-V) 1983 with upto date ammendments. Starter Type Make
Providng Digital hour run meter of recommended make and suitable capacity as per IS:722(latest edition.). Hour Run Meter Type Make Capacity.
Providing antivibration pads under the pumps and motors of suitable size for the above pumping machinery as per IS:6337:1971. Antivibration Pads Size Make Material.
Providing double flanged CI sluice valve PN1 of Leader/BHEL/Kirlosker/GLEd/Kilburn Fourses / Kartar make and equal to dia of suction pipe and cpable of withstanding the normal seat pressure as per IS:780:1984 with upto date ammendments. Sluice Valve Make Class Seat Pressure.
Providng double flanged cast iron sluice valves PN-I of leader/BHEL Kirlosker/Kilburn GLED/fourses/ Kartar make and one step higher then delivery line of pump and capable of withstanding the normal seat pressure and as per BIS standards with upto date ammdnements. Sluice Valve Make Class Seat Pressure Material.
Providing double flanged swing type cast iron valve, PN-I of Leader/BHEL/Kirlosker/Kilburn/GLEd/Fourses/ Kartar make and having bye pass arrangements of one step higher then delivery line of pump and capable of withstanding normal seat pressure as per BIS standards with upto date amnmendments). Reflux Valve Make Class Seat Pressure Material
Providing double flanged cast iron reflux valves class PN-I of Leader/BHEL/KILROSKER/Kartar/KILBURN/GLED/FOURSES/ Kartar make and of 350 mm dia having bye pass arrangements for rising main and capable of withstanding normal seat pressure as per BIS standards with upto date ammendments. Reflux Valve Make Class Seat Pressure Material
Providing 100mm dia circular dial analog pressure gauge of suitable range of Fiebig /Bourden/ PREGA/precision make complete with all accessories such as stop cock, copper tubing etc.as per IS: 3624-1987 with upto date ammendments. Pressure Gauge Make Range.
Providing discharge meter of standard make to be fixed on the rising main in pump house as per the directions of the Engineer in charge as per Is:2373:1981 with upto date ammendments. Discharge Meter Make Type Range
Installation of all the items apparing at serial No.1 to 9 as per the systematic drawing.
Providing and fixing double flanged MS/GI piping work (Layout to be approved by the Engineer in charge) for suction and delivery pipes suitable to pump(s) offered and common header as per the R/Main respectively complete with all specials such as bends, tees, reducers. Increasers with companions flanges matching with the relevant specifications of the accessories including rubber/asbestos gasket of minimum 3mm thckness as per IS:2712:1979 and required number of nuts and bolts as per Is:1364:1983, The Pipes fittings and joints shall be as per relevant IS code & to withstand 1.5 times total head stipulated under item No.1. The size of the various components to be as under: i) Suction pipe : One dia higher then the suction of pump offered and suitable to keep the velocity of flow from 1 to 1.5M/second in the suction pipe. ii) Delivery pipe: One dia higher then the delivery of the pump offered and suitable to keep the velocity of flow from 1.5 to 2M/second in the delivery pipe. iii) Common header : One dia higher then delivery of pump x 350 mm dia and will extend upto 5 meters from the outer wall of the pump house in the direction to be jointed. Suction Pipe Material Grade Thickness Pressure rating. Delivery oioe and common header Material Grade Thickness Pressure rating.
Providing and laying copper PVC insulated arsoured power cable(One cable carrying all the three phases) of suitable size and capacity to motors and all other electircal equipments as per IS:1554(P-I) 1988 or latest ith upto date ammendments of siemens GLOSTER /IEC /ICC /EICD/NATIONAL/GRANDLAY make including all other accessories such as thinbles, flexible pipes,solders,nuts and bolts cable glands etc. laid in pipes or trenches under floor. Arsoured Power Cable A. Motor Side (from switch to starter and starter to motor) Size Make Type Capacity Core B. Supply Side (from meter to HPSEB to bus bar and switch) Size Make Type Capacity.
HYDRAULIC ENGINEERING COMPANY
Raman Thakur Govt. Cont.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .