Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹28.4 LAccepted-AOC FLAT NO 06 BLDG NO B 2 PLEASANT PARK WANWADI PUNE 411040 | PUNE | MAHARASHTRA | 411040 | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹29.9 L+₹67,438 (2.31%)Rejected-Finance | L2 | Rejected-Finance High Rate | |
| 3 | L3₹36.2 L+₹7.1 L (24.2%)Rejected-Finance | L3 | Rejected-Finance High Rate | |
| 4 | L4₹37.0 L+₹7.8 L (26.7%)Rejected-Finance | L4 | Rejected-Finance High Rate | |
| 5 | L5₹37.4 L+₹8.2 L (28.2%)Rejected-Finance N A | NA | NA | 121004 | L5 | Rejected-Finance High Rate |
Tender Value
₹48.8 L
EMD Value
₹97,600
Closing Date
28 Dec 2023, 6:00 pmClosed
GE (Central) Pune
Garrison Engineer (Central) Pune, Arjun Marg, Pune-411001
8408 SPECIAL REPAIR / REPLACEMENT TO INTERNAL ELECTRIC WIRING / FITTINGS AND FIXTURES IN BLDG NO P-177, P-191 AND P-81 OF DEPARTMENT OF DENTAL SURGERY AND ORAL ORAL HEALTH SCIENCES AND REPLACEMENT OF OLD CONVENTIONAL CEILING LIGHT FITTINGS INTO LED L
2023_MES_631050_1
8408 SPECIAL REPAIR/ REPLACEMENT TO INTERNAL WIRIN
Open Tender
Civil Works
Item Rate
180 days
GE (Central) Pune
As per Tender NIT
9 documents required · 9 mandatory
₹500
GE (Central) Pune
₹97,600
Yes
27 Feb 2024
4 Dec 2023
30 Dec 2023
4 Dec 2023
28 Dec 2023
16 Dec 2023
Amount
Taking down copper / aluminium point wiring (light, fan, socket or power) complete including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets, light fitting etc and making good disturbed surfaces of walls, floors etc all as specified and directed.
Taking down Main switches / DBs of any make and type including teak wood board, MCBs / MCCBs etc complete and making good the disturbed surfaces including colour washing complete all as specified.
Taking down Ceiling fan / exhaust fan of any sweep, keeping with safe custody , replacement of unserviceable 3 core PVC insulated, PVC sheated 3 core multistranded copper conductor cable of size 23/0.193 from ceiling rose to fan terminal , overhauling the fans complete , replace the capacitor , rubber coupling , bearing etc of suitable size, painting of fans complete with synthetic enamel paint by spray painting including filling cavities with filler one coat after cleaning all dust etc and and refixing the same to its original position in servicable conditions complete all as specified.
M & L for point wiring of any length using approved colour coding as per IS, with stranded copper conductor 1.5 Sqmm (Nominal area) single core, PVC insulated and unsheathed stranded FRLS H cable 1100 Volts grade, ISI-694 marked in PVC rigid conduits heavy duty ISI marked of suitable size totally concealed in wall / floor / roof including all accessories etc with Modular sunken boxes including modular frame / cover plate suitable for mounting switches / sockets etc and PVC insulated standed copper conductor 1.5 Sqmm single core cable as earth and connecting to common earth dolly complete all as specified and directed for the following :- Note :- (i) Cutting in chases and pointing in will be done by contractor withou any extra cost. (ii) Making good of distrubed surfaces matching with existing finishes will be done by contractor without any extra cost. (iii) Rates quoted by the contractor shall deemed to be included of above provision.
(a) One light controlled by one, One way switch complete all as specified.
(b) One fan point controlled by one, One way switch complete all as specified.
(c) One 5 pin 5 Amps socket outlet point controlled by one, one way switch on same board including earth wire complete all as specified.
(b) One 5 pin 5 Amps socket outlet point controlled by one, one way switch on independent board complete all as specified.
(e) One bell / buzzer point controlled by one, bell push complete all as specified .
(f) One light point controlled by two , two way switches complete all as specified.
All as per item No 04 above but with 2.50 Sqmm (Nominal area) single core, PVC insulated and unsheathed stranded FRLS H cable 1100 Volts grade, ISI - 694 marked, including PVC insulated stranded copper conductor 2.50 Sqmm single core cable as earth and connecting to common earth dolly complete all as specified for one 15 Amps socket outlet point on independent board. Note :- Making good of disturbed surfaces will be done by contractor without any extra coat to Govt.
S & F Modular switch 6 Amps SP one way 230 Volts , white / ivory finish complete all as specified.
S & F Modular switch 6/16 Amps SP one way 230 Volts white / ivory finish complete all as specified.
S & F Modular socket outlet 2/3 pin 6 Amps, multipurpose , 2 Module 230 Volts, single pole one way suitable for plug tops complete all as specified.
S & F Modular socket outlet 2/3 pin 16 Amps, multipurpose 2 Module 230 Volts, single pole one way suitable for plug tops, complete all as specified.
S & F Bell push , flush type, 5 Amps complete all as specified.
S & F bell electrical ding dong including hard PVC board ISI marked complete all as specified.
S & F ceiling rose surface bakelite type three terminals complete all as specified and directed.
S & F Modular type stepped electronic fan regulator (1 to 5 steps) all as specified.
S & F modular switch 6 Amps SP Two way 230 Volts white / ivory finish complete all as specified
S & F 240 Volts, Single pole and neutral enclosure with a two pin and earth plug and socket with incliuding one 20 Amps single pole MCB complete all as specified.
M & L for sub main wiring complete with two single core 2.5 Sqmm 1100 Volts grade PVC insulated stranded copper conductor FRLS cable with continuous copper earth conductor of 2.5 Sqmm in and including non-metallic PVC conduit of suitable size, totally concealed in wall/ floor/ roof etc including all accessories including taking down old unserviceable / worn out sub main wiring of any type and size complete all as specified. Note :- (i) Making good of disturbed surfaces wiil be done by contractor without any extra cost. (ii) 2 Runs of 2.5 Sqmm conductor , one run of 2.5 Sqmm earth conductor and one run of PVC conduit shall be measured as one unit length.
M & L for sub main wiring complete with two single core 4 Sqmm 1100 Volts grade PVC insulated stranded copper conductor FRLS cable with continuous copper earth conductor of 4 Sqmm in and including non-metallic PVC conduit of suitable size, totally concealed in wall/ floor/ roof etc including all accessories all accessories including taking down old unserviceable / worn out sub main wiring of any type and size complete all as specified. Note :- (i) Making good of disturbed surfaces wiil be done by contractor without any extra cost. (ii) 2 Runs of 4 Sqmm conductor , one run of 4Sqmm earth conductor and one run of PVC conduit shall be measured as one unit length.
M & L for sub main wiring complete with two single core 6 Sqmm 1100 Volts grade PVC insulated stranded copper conductor FRLS cable with continuous copper earth conductor of 6 Sqmm in and including non-metallic PVC conduit of suitable size, totally concealed in wall/ floor/ roof etc including all accessories all accessories including taking down old unserviceable / worn out sub main wiring of any type and size complete all as specified. Note :- (i) Making good of disturbed surfaces wiil be done by contractor without any extra cost. (ii) 2 Runs of 6 Sqmm conductor , one run of 6 Sqmm earth conductor and one run of PVC conduit shall be measured as one unit length.
M & L for sub main wiring complete with two single core 10 Sqmm 1100 Volts grade PVC insulated stranded copper conductor FRLS cable with continuous copper earth conductor of 10 Sqmm in and including non-metallic PVC conduit of suitable size, totally concealed in wall/ floor/ roof etc including all accessories all accessories including taking down old unserviceable / worn out sub main wiring of any type and size complete all as specified. Note :- (i) Making good of disturbed surfaces wiil be done by contractor without any extra cost. (ii) 2 Runs of 10 Sqmm conductor , one run of 10 Sqmm earth conductor and one run of PVC conduit shall be measured as one unit length.
M & L for sub main wiring complete with four single core 10 Sqmm 1100 Volts grade PVC insulated stranded copper conductor FRLS cable with continuous copper earth conductor of 10 Sqmm in and including non-metallic PVC conduit of suitable size including all accessories including taking down old unserviceable / worn out sub main wiring of any type and size complete all as specified. Note :- (i) Making good of disturbed surfaces wiil be done by contractor without any extra cost. (ii) 4 Runs of 10 Sqmm conductor , one run of 10 Sqmm earth conductor and one run of PVC conduit shall be measured as one unit length.
M & L for sub main wiring complete with four single core 16 Sqmm 1100 Volts grade PVC insulated stranded copper conductor FRLS cable with continuous copper earth conductor of 16 Sqmm in and including non-metallic PVC conduit of suitable size including all accessories including taking down old unserviceable / worn out sub main wiring of any type and size complete all as specified. Note :- (i) Making good of disturbed surfaces wiil be done by contractor without any extra cost. (ii) 4 Runs of 16 Sqmm conductor , one run of 16 Sqmm earth conductor and one run of PVC conduit shall be measured as one unit length.
S&F pop up type flush mounting box four module matt aluminium finish or glossy white for floor equipped with push and slide locking system to avoid accidental opening by feet and including with two Nos socket outlets 6/16 Amps fixed in box complete all as specified and directed. Note : (i) Cutting in chases and pointing in will be done by contractor without any cost. (ii) Making good of disturbed surfaces matching with existing finishes shall be done by contractor without any extra cost to the Govt. Make : Legrand/ Anchor/ Panasonic
S & F copper Bus bar chamber including space for 4 pole MCCB upto 630 Amps 415 Volts complete all as specified.
S & F MCB TPN DB 4 way double door with 200 Amps rated busbar 415 Volt including MCCB complete all as specified.
S & F MCB SPN DB 8 way , double door with 200 Amps rated busbar 240 Volts all as specified.
S & F MCB SPN DB 6 way , double door with 200 Amps rated busbar 240 Volts all as specified.
S & F MCB SPN DB 4 way , double door with 200 Amps rated busbar 240 Volts all as specified.
S & F MCCB adjustable type 4 Pole 400 Amps with breaking capacity 36 KA 'B' curve 415 Volts complete all as specified.
S & F MCB single pole rated capacity 6 to 40 Amps, 240 Volt , breaking capacity 10 KA, C-curve complete all as specified and as directed.
S & F MCB double pole of rated capacity 6 to 40 Amps, 240 Volts breaking capacity 10 KA, C-curve complete all as specified and as directed.
S & F MCB four pole rated capacity 40 to 100 Amps, 415 Volts, breaking capacity 10 KA, C-curve complete all as specified.
Taking down existing serviceable MCB TPN DB 4 way, double door with 200 Amps rated busbar 415 Volts & Refixing same to its original or other position complete all as directed.
Taking down existing serviceable LED Tube light fittings wall mounted of capacity 20 Watt LED 6500 K with Ultra bright LED polycarbonate tube light with very high efficiency provided with high efficient integral constant current LED Driver 230 Volts etc complete with mounting batten including all accessories internally prewired and & Refixing same to its original or other position including connecting up with provision of new twin core twisted flexible copper conductor cable with suitable size from ceiling rose to connector complete all as directed.
Taking down existing serviceable LED light fittings 2 'x 2' of capacity 28 Watts environmental friendly, new genereation, aesthetically designed, ultra modern recess mounting luminaire with high brightness SMD LEDs as light source 230 Volts with all accessories internally pre wired and necessary mounting arrangements & Refixing same to its original or other position complete all as directed.
S & F in replacement LED light fittings 2 'x 2' of capacity 36 Watts environmental friendly, new genereation, aesthetically designed, ultra modern recess mounting luminaire with high brightness SMD LEDs as light source 230 Volts with all accessories internally pre wired and necessary mounting arrangements complete ll as specified and directed.
S & F in replacement LED Tube light fittings surface and wall mounted LED batten, Ivory LED batten Lumen efficiency of 100 Lm/Watt, 3.5 KV Voltage surge protection, power factor > 0.9 designed to deliver glare free light with housing made of engineering plastic in CDL 6500 K 20 Watt LED complete including all accessories internally prewired in and including connecting up with 3 core twisted flexible copper conductor cable of suitable size from ceiling rose to connector complete all as specified and directed..
S & F in replacement of round recessed mounted Edge-lit technology for glare free light 25 KV Voltage surge protection housing made from engineering plastic with in-built driver, power factor > 0.9 operating voltage range 100-300 Volts AC unique designed unabled by a separate modular surface rim convert from recessed to surface mounting in round shape 12 Watt LED downlighter of white/neutral white/ warm white color temperature as per site requirement etc 3 core prewired and all accessories complete all as specified and directed.
S & F in replacement of LED light fitting 10W capacity surface and wall mounted LED batten with aluminium housing & integrated electronic driver complete all as specified and directed.
S & F in replacement LED street light with pressure die-cast housing along with prismatic polycarbonate diffuser and LEDs with secondary optics and IP-65 protection 30 Watt complete with all accessories and wall mounting bracket of suitable size including clamps, nut bolts etc prewired 3 core flexible wire complete all as specified and directed.
M & L in replacement for earthing with GI Electrode 3 Mtr long consist of GI pipe outer dia 76mm and GI pipe inner dia 32mm , inner space should be compacted with dry chemical compound for enhancing conductivity all including boring installation, transportaion, concrete pit including excavation and earth work in any type of soil and sufficient quantity of ground enhancing backfil compound testing of soil condition, PVC pit cover and GI strip 32 x 6mm up to 7.5 Mtrs long etc and testing on completion etc complete all as specified and directed. NOTE :- GI strip 32 x 6mm beyond 7.5 Mtr will be measured and paid separately.
S & F in replacement 4mm dia galvanised iron or steel wire as earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit / pipe or fixed to poles or any other indicated situation for loop earthing etc as required complete all as specified.
Labour only for removing / reinstallation of split type AC 1.5 / 2 TR capacity indoor & outdoor unit including all allied work such as bending, shaping, brazing to copper tubing & insulation to tubing, connection of water drain piping & fixing it properly including testing & commissioning complete all as directed.
Akash Constructions
Akanksha Enterprises
ANUSHKA BUILDERS
N B ENTERPRISES
M/s Asrani and sons
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .