Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.7 CrAdmitted-Finance | ₹1.7 Cr | L1 | Admitted-Finance |
| 2 | L2₹2.7 CrAdmitted-Finance | ₹2.7 Cr | L2 | Admitted-Finance |
| 3 | L3₹2.9 CrAdmitted-Finance | ₹2.9 Cr | L3 | Admitted-Finance |
| 4 | Not Admitted-Fee/PreQual/Technical | - | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
| 5 | Not Admitted-Fee/PreQual/Technical G 102 PLOT NO 123 SECTOR 06 VAISHALI GHAZIABAD U P 2010 | 2010 | - | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
| Sl No | Description | Qty | Unit | M/S. R. K.LALA L2 | Essel Projects Pvt. Ltd. L3 | ENGINEERS COMBINE L1 |
|---|---|---|---|---|---|---|
| 1.00 | Panel Type-A : Supply, Installation, Testing and Commissioning of: Extension of existing LT Sw. Gear panel floor mounting, 415V,by two vertical sections, eight outgoing feeders and with adapter panel.
as per SLD -SS2/SLD-A/EL/0151 | 2 | Each | 16,90,000 ₹33.8 L | 13,78,293 ₹27.6 L | 9,00,000 ₹18 L |
| 2.00 | Panel type-B : Supply, Installation, Testing and Commissioning of: LT Sw. Gear panel, floor mounting, 415V, 3Phase, 630A with
Incoming – MCCB, 630A – 1 No.
Outgoing – MCCB, 400/315A/200/125A – 9 Nos.
as per SLD No-SS2/SLD-B/EL/0152 | 4 | Each | 8,60,000 ₹34.4 L | 9,78,395 ₹39.1 L | 8,50,000 ₹34 L |
| 3.00 | Panel Type-C : Supply, Installation, Testing and Commissioning of: Floor DB panel, Incomer 400A, MCCB – 1 No.
Outgoing 200A/125A - 6 Nos.
As per DRG.NO. SS2/SLD-C/EL/0153 | 5 | Each | 7,05,200 ₹35.3 L | 5,95,020 ₹29.8 L | 3,92,500 ₹19.6 L |
| 4.00 | Panel Type-D : Supply, Installation, Testing and Commissioning of: Auto Change over Panel- sheet steel enclosed, floor / wall mounting type with Two incoming motorised MCCBs 200Amp, outgoing cable termination, Auxiliary relays, timer, MCB. Indication lamps, control transformer etc.
As per DRG.NO. SS2/SLD-D/EL/0154 | 44 | Each | 2,50,000 ₹1.1 Cr | 2,51,483 ₹1.1 Cr | 1,00,000 ₹44 L |
| 5.00Retrofitting : Supply, Installation, Testing and Commissioning of:Replacement and retrofitting of existing draw out type MCCB (Siemens make) in PCC panel by D/O type MCCB with micro processor based tripping unit for O/L, S/C, & E/F protection. Communication port. | ||||||
| 5.01 | 630A, 4Pole | 2 | Each | 1,41,000 ₹2.8 L | 1,53,912 ₹3.1 L | 1,00,000 ₹2 L |
| 5.02 | 400A, 4Pole | 2 | Each | 1,30,000 ₹2.6 L | 1,40,169 ₹2.8 L | 1,00,000 ₹2 L |
| 6.00Retrofitting of circuit breaker : Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release, terminal spreaders and Panel mounted Extended Rotary handle in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. | ||||||
| 6.01 | 63 A/ 40A/ 32 A, 16KA, TPN MCCB | 30 | Each | 8,165 ₹2.4 L | 8,930 ₹2.7 L | 8,000 ₹2.4 L |
| 6.02 | 100 A,25KA,FPMCCB | 15 | Each | 13,230 ₹2.0 L | 14,769 ₹2.2 L | 12,000 ₹1.8 L |
Tender Value
₹2.3 Cr
Closing Date
26 Feb 2021, 11:00 amClosed
Executive Engineer (Civil)
Executive Engineer (Civil) Project Cell, AIIMS Raipur
Augmentation of Existing Electrical Distribution system for Phase- 1 (In Substation- 2, 3, 4 and Hospital Block) at AIIMS Raipur
2021_IMSRP_614771_1
66/EE/AIIMS/RPR/2020-21
Open Tender
Electrical Works
240 days
AIIMS Raipur
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
Exempted
4 May 2021
5 Feb 2021
27 Feb 2021
5 Feb 2021
26 Feb 2021
5 Feb 2021
Amount
Panel Type-A : Supply, Installation, Testing and Commissioning of: Extension of existing LT Sw. Gear panel floor mounting, 415V,by two vertical sections, eight outgoing feeders and with adapter panel. as per SLD -SS2/SLD-A/EL/0151
Panel type-B : Supply, Installation, Testing and Commissioning of: LT Sw. Gear panel, floor mounting, 415V, 3Phase, 630A with Incoming – MCCB, 630A – 1 No. Outgoing – MCCB, 400/315A/200/125A – 9 Nos. as per SLD No-SS2/SLD-B/EL/0152
Panel Type-C : Supply, Installation, Testing and Commissioning of: Floor DB panel, Incomer 400A, MCCB – 1 No. Outgoing 200A/125A - 6 Nos. As per DRG.NO. SS2/SLD-C/EL/0153
Panel Type-D : Supply, Installation, Testing and Commissioning of: Auto Change over Panel- sheet steel enclosed, floor / wall mounting type with Two incoming motorised MCCBs 200Amp, outgoing cable termination, Auxiliary relays, timer, MCB. Indication lamps, control transformer etc. As per DRG.NO. SS2/SLD-D/EL/0154
Retrofitting : Supply, Installation, Testing and Commissioning of:Replacement and retrofitting of existing draw out type MCCB (Siemens make) in PCC panel by D/O type MCCB with micro processor based tripping unit for O/L, S/C, & E/F protection. Communication port.
630A, 4Pole
400A, 4Pole
Retrofitting of circuit breaker : Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release, terminal spreaders and Panel mounted Extended Rotary handle in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.
63 A/ 40A/ 32 A, 16KA, TPN MCCB
100 A,25KA,FPMCCB
125 A,25KA,FPMCCB
200 A,36KA,FPMCCB
400 A, 36KA,FPMCCB
Supply, Installation, Testing and Commissioning of Tap Off box : Supplying, installation, testing & commisioning of following capacity Plug In/ tap off box on the existing Air Insulated Compact Type bus trunking/ rising mains for use on 3 phase 4 wire 415 volts, 50Hz A.C. supply made with 1.6mm thick sheet steel enclosure (IP54) duly powder coated with provision of MCCB/ACB (but without MCCB/ACB) complete etc. as required.
400 A SC for 1 sec
Supplying, laying and fixing following dia G.I. pipe (medium class) in ground / on wall surface, complete with G.I. fittings etc as required.
50 mm Dia
80 mm Dia
Supplying, Laying and fixing of 1.1 KV grade, XLPE insulated, PVC inner sheated, PVC- FRLS Outer sheathed, Unarmured Aluminium power cable of of following size on cable tray / on wall surface as required.
un- armoured 3.5C x 300 Sq.mm
un- armoured 3.5C x 240 Sq.mm
un- armoured 3.5C x 120 Sq.mm
un- armoured 3.5C x 70 Sq.mm
un- armoured 3.5C x 50 Sq.mm
Control Cable : Supply , Laying and fixing of 1.1 KV grade, PVC insulated and inner sheated, PVC- FRLS Outer sheathed, Unarmured Copper control cable of size 7x1.5 Sq.mm
End Termination of Power Cable : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
3½ X 300 Sq.mm
3½ X 240 Sq.mm
3½ X 185 sq. mm
3½ X 120 Sq.mm
3½ X 70 Sq.mm
3½ X 50 Sq.mm
Earth flat - Copper ; Providing and fixing earth bus of 50 mm X 5 mm copper strip on surface for connections etc. as required.
Earth flat - GI ; Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
Cable Tray : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required.
150 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 50 mm depth X 1.6 mm thickness
Structural steel : Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.
Foundation : Providing and laying in position reinforced cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc including form work etc as required (excluding reinforcement).
Steel reinforcement for R.C.C. work including straightening, cutting,bending, placing in position and binding all complete upto plinth level.
Thermo-Mechanically Treated bars of grade Fe-500D or more.
Supply of insulated rubber mats in front of LT panels . Width of mat 800mm
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.
Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)
Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)
Supplying and making straight through joint with heat shrinkable kit including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
3½ X 300 sq. mm
3½ X 185 sq. mm
3½ X 120 sq. mm
AMC (Annual Maintenance Contract )
1st year
2nd year
3rd year
4th year
5th year
M/S. R. K.LALA
Essel Projects Pvt. Ltd.
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.58 MB
BOQ_646260.xls
BOQ • 0.27 MB
Download all tender documents and submit your bid