| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.6 CrAdmitted-Finance | ₹1.6 Cr | L1 | Admitted-Finance |
| 2 | L2₹1.6 CrAdmitted-Finance | ₹1.6 Cr | L2 | Admitted-Finance |
| 3 | L3₹1.8 CrAdmitted-Finance | ₹1.8 Cr | L3 | Admitted-Finance |
| Sl No | Description | Qty | Unit | ICEBERGS L2 | SPECDEL ENGINEERING PRIVATE LIMITED L1 | DD CLIMATE CONTROLS L3 |
|---|---|---|---|---|---|---|
| 0.00HVAC WORKS | ||||||
| 1.00Plate Heat Exchanger Servicing | ||||||
| 1.01Comprehensive servicing of the Plate Heat Exchanger (PHE) assembly includes complete isolation, draining, and dismantling of the plate pack using hydraulic tools; thorough mechanical and chemical cleaning of all plates; visual inspection and condition reporting; complete re-gasketing with OEM-specified glue/clip-type gaskets; re-assembly, alignment, and final torque tightening as per OEM manual; hydrostatic pressure testing at 1.5 times design pressure; functional servicing and calibration of all associated valves, inspection of the SS-302 support frame, piping connections, and expansion tank; followed by commissioning, performance validation against design approach temperature, and submission of a complete service dossier including test certificates. The costing shall include all labour, tools, chemicals, a complete set of gaskets, and consumables. | ||||||
| 1.02PHE Servicing @ VVF Block | ||||||
| 1.03 | PHE (Primary/Process Side: 310 M³/hr @ 7°C Inlet / 12°C Outlet,
Secondary/Utility Side: 240 M³/hr @ 4°C Inlet / 11.5°C Outlet) | 1 | Lot | 20,440 ₹20,440 | 31,240 ₹31,240 | 35,000 ₹35,000 |
| 1.04PHE Servicing @ QC Block | ||||||
| 1.05 | PHE (Primary/Process Side: 280 M³/hr @ 7°C Inlet / 12°C Outlet,
Secondary/Utility Side: 190 M³/hr @ 4°C Inlet / 11.5°C Outlet) | 1 | Lot | 20,440 ₹20,440 | 24,530 ₹24,530 | 35,000 ₹35,000 |
| 1.06PHE Servicing @ AR Block | ||||||
| 1.07 | PHE (Primary/Process Side: 155 M³/hr @ 7°C Inlet / 12°C Outlet,
Secondary/Utility Side: 105 M³/hr @ 4°C Inlet / 11.5°C Outlet) | 1 | Lot | 20,440 ₹20,440 | 28,620 ₹28,620 | 35,000 ₹35,000 |
| 1.08Chilled Water Manifold Valve Package Servicing | ||||||
Updated dates
Tender Value
₹1.8 Cr
EMD Value
₹4.6 L
Closing Date
12 Mar 2026, 3:00 pmClosed
Deputy General Manager Proc.
HLL BIOTECH LIMITED, Integrated vaccine complex, Survey no 192 195, Meleripakkam village, Chengalpattu PIN 603003
Comprehensive Maintenance, Testing, Validation and Supply Services for HVAC systems, cold rooms, door interlocks, filters and allied works at IVC facility at HLL biotech limited, Chengalpattu
2026_HBL_268296_1
HBL/HVAC1/IVC/CPT/25-26
Open Tender
Electrical Works
60 days
Chengalapattu
17 documents required · 17 mandatory
₹2,950
Yes
HLL Biotech Limited
₹4.6 L
Yes
ONLINE
30 Mar 2026
21 Feb 2026
13 Mar 2026
21 Feb 2026
12 Mar 2026
23 Feb 2026
25 Feb 2026
HVAC WORKS
Plate Heat Exchanger Servicing
Comprehensive servicing of the Plate Heat Exchanger (PHE) assembly includes complete isolation, draining, and dismantling of the plate pack using hydraulic tools; thorough mechanical and chemical cleaning of all plates; visual inspection and condition reporting; complete re-gasketing with OEM-specified glue/clip-type gaskets; re-assembly, alignment, and final torque tightening as per OEM manual; hydrostatic pressure testing at 1.5 times design pressure; functional servicing and calibration of all associated valves, inspection of the SS-302 support frame, piping connections, and expansion tank; followed by commissioning, performance validation against design approach temperature, and submission of a complete service dossier including test certificates. The costing shall include all labour, tools, chemicals, a complete set of gaskets, and consumables.
PHE Servicing @ VVF Block
PHE (Primary/Process Side: 310 M³/hr @ 7°C Inlet / 12°C Outlet, Secondary/Utility Side: 240 M³/hr @ 4°C Inlet / 11.5°C Outlet)
PHE Servicing @ QC Block
PHE (Primary/Process Side: 280 M³/hr @ 7°C Inlet / 12°C Outlet, Secondary/Utility Side: 190 M³/hr @ 4°C Inlet / 11.5°C Outlet)
PHE Servicing @ AR Block
PHE (Primary/Process Side: 155 M³/hr @ 7°C Inlet / 12°C Outlet, Secondary/Utility Side: 105 M³/hr @ 4°C Inlet / 11.5°C Outlet)
Chilled Water Manifold Valve Package Servicing
Comprehensive servicing of AHU chilled water manifold valve package with each set comprising of isolation valves (5 nos. in each set ) (Butterfly valves for sizes > 50 mm and ball valve for sizes < 40 mm), Y-Strainer, Manual balancing valve, 2-way control valve(globe valve type) with actuators & thermostat, pressure gauge with ball valve, Temperature Gauge, Ball valve for Airvent and Ball valve for Drain Line. Scope of service should include system isolation and draining as required, dismantling of strainer and accessible valve internals, thorough cleaning of Y-strainer screen and flushing of line to remove debris, scale and sludge, checking and smooth operation of all valves for leakage and proper functioning, tightening of gland packing, flange bolts and threaded joints, checking actuator stroke of 2-way valve, rectification of minor leakages, refilling and venting of system after servicing, hydraulic pressure testing of manifold assembly at 1.5 times working pressure to ensure joint integrity and leak-free performance, restoration of insulation disturbed during work, and commissioning checks for normal flow and pressure conditions, complete in all respects as per manufacturer recommendations and site engineer’s instructions.
CHW Manifold Valve Package Servicing @ VVF Block
AHU-01 / 98.4 GPM / Pipe Size 80mm
AHU-02 / 41.2 GPM / Pipe Size 50mm
AHU-03 / 18.6 GPM / Pipe Size 40mm
AHU-04 / 71.8 GPM / Pipe Size 65mm
AHU-05 / 28 GPM / Pipe Size 40mm
AHU-06 / 25.5 GPM / Pipe Size 50mm
AHU-07 / 87.8 GPM / Pipe Size 80mm
AHU-08 / 23.9 GPM / Pipe Size 40mm
AHU-09 / 20 GPM / Pipe Size 40mm
AHU-10 / 63.8 GPM / Pipe Size 65mm
VUS - 01 / 60 GPM / Pipe Size 65mm
VUS - 02 / 75 GPM / Pipe Size 65mm
TFA - 01 / 166.3 GPM / Pipe Size 80mm
TFA - 02 / 164.9 GPM / Pipe Size 80mm
CHW Manifold Valve Package Servicing @ QC Block
AHU-01 / 33.3 GPM / Pipe Size 50mm
AHU-02 / 55.9 GPM / Pipe Size 65mm
AHU-03 / 14.6 GPM / Pipe Size 32mm
AHU-04 / 42.6 GPM / Pipe Size 50mm
AHU-05 / 21.3 GPM / Pipe Size 40mm
AHU-06 / 73.2 GPM / Pipe Size 65mm
AHU-07 / 31.9 GPM / Pipe Size 50mm
AHU-08 / 37.2 GPM / Pipe Size 50mm
AHU-09 / 55.9 GPM / Pipe Size 65mm
VUS-01 / 17.3 GPM / Pipe Size 40mm
TFA-01 / 202.2 GPM / Pipe Size 100mm
TFA-02 / 151.6 GPM / Pipe Size 100mm
TFA-03 / 50.5 GPM / Pipe Size 65mm
TFA-04 / 83.8 GPM / Pipe Size 80mm
CHW Manifold Valve Package Servicing @ AR Block
AHU-01 / 27.9 GPM / Pipe Size 50mm
AHU-02 / 21.3 GPM / Pipe Size 40mm
AHU-03 / 37.2 GPM / Pipe Size 50mm
AHU-04 / 67.8 GPM / Pipe Size 65mm
AHU-05 / 63.8 GPM / Pipe Size 65mm
AHU-06 / 41.2 GPM / Pipe Size 50mm
AHU-07 / 19 GPM / Pipe Size 40mm
AHU-08 / 20 GPM / Pipe Size 50mm
TFA-01 / 90 GPM / Pipe Size 65mm
VUS-01 / 236.7 GPM / Pipe Size 100mm
Brine Manifold Valve Package Servicing
Comprehensive servicing of AHU brine manifold valve package with each set comprising of isolation valves (6 nos. in each set ) (Butterfly valves for sizes > 50 mm and ball valve for sizes < 40 mm), Y-Strainer, Manual balancing valve, 3-way control valve(globe valve type) with actuators & thermostat, pressure gauge with ball valve, Temperature Gauge, Ball valve for Airvent and Ball valve for Drain Line. Scope of service should include system isolation and draining as required, dismantling of strainer and accessible valve internals, thorough cleaning of Y-strainer screen and flushing of line to remove debris, scale and sludge, checking and smooth operation of all valves for leakage and proper functioning, tightening of gland packing, flange bolts and threaded joints, checking actuator stroke of 3-way valve, rectification of minor leakages, refilling and venting of system after servicing, hydraulic pressure testing of manifold assembly at 1.5 times working pressure to ensure joint integrity and leak-free performance, restoration of insulation disturbed during work, and commissioning checks for normal flow and pressure conditions, complete in all respects as per manufacturer recommendations and site engineer’s instructions.
Brine Manifold Valve Package Servicing @ VVF Block
CAHU-01 / 21 GPM / Pipe Size 40mm
CAHU-01 / 21 GPM / Pipe Size 40mm
CAHU-02 / 29 GPM / Pipe Size 40mm
CAHU-02 / 29 GPM / Pipe Size 40mm
CAHU-04 / 40 GPM / Pipe Size 50mm
CAHU-04 / 40 GPM / Pipe Size 50mm
Brine Manifold Valve Package Servicing @ AR Block
CAHU-01 / 28 GPM / Pipe Size 40mm
CAHU-01 / 28 GPM / Pipe Size 40mm
AHU General Servicing
Providing comprehensive general servicing of AHU including isolation of power supply, opening and cleaning of blower section, inspection and servicing of plug fan assembly, checking fan wheel condition, bearing condition and lubrication/greasing, verification of fan and motor mounting integrity, motor general check-up including insulation condition, abnormal noise, vibration and temperature, tightening of foundation bolts, thorough chemical cleaning of cooling coil using approved non-corrosive coil cleaner with pressurised water/air to remove dust, grease and microbial deposits to restore heat transfer efficiency, cleaning of drain tray and condensate line, checking casing panels for air leakage and proper sealing, inspection and integrity checking of AHU AHU control panel including incoming/outgoing terminals, contactors, overload relays and functional performance, earthing continuity, cable tightness and overheating indications, followed by operational testing of AHU for smooth operation, airflow performance and noise level, complete in all respects as per OEM recommendations and site engineer’s instructions.
AHU General Servicing @ VVF Block
AHU-01 / 98.4 GPM
AHU-02 / 41.2 GPM
AHU-03 / 18.6 GPM
AHU-04 / 71.8 GPM
AHU-05 / 28 GPM
AHU-06 / 25.5 GPM
AHU-07 / 87.8 GPM
AHU-08 / 23.9 GPM
AHU-09 / 20 GPM
AHU-10 / 63.8 GPM
VUS - 01 / 60 GPM
VUS - 02 / 75 GPM
TFA - 01 / 166.3 GPM
TFA - 02 / 164.9 GPM
CAHU-01 / 21 GPM
CAHU-01 / 21 GPM
CAHU-02 / 29 GPM
CAHU-02 / 29 GPM
CAHU-04 / 40 GPM
CAHU-04 / 40 GPM
AHU General Servicing @ QC Block
AHU-01 / 33.3 GPM
AHU-02 / 55.9 GPM
AHU-03 / 14.6 GPM
AHU-04 / 42.6 GPM
AHU-05 / 21.3 GPM
AHU-06 / 73.2 GPM
AHU-07 / 31.9 GPM
AHU-08 / 37.2 GPM
AHU-09 / 55.9 GPM
AHU-10 [Hot Air]
AHU-11 [Hot Air]
VUS-01 / 17.3 GPM
TFA-01 / 202.2 GPM
TFA-02 / 151.6 GPM
TFA-03 / 50.5 GPM
TFA-04 / 83.8 GPM
AHU General Servicing @ AR Block
AHU-01 / 27.9 GPM
AHU-02 / 21.3 GPM
AHU-03 / 37.2 GPM
AHU-04 / 67.8 GPM
AHU-05 / 63.8 GPM
AHU-06 / 41.2 GPM
AHU-07 / 19 GPM
AHU-08 / 20 GPM
TFA-01 / 90 GPM
VUS-01 / 236.7 GPM
CAHU-01 / 28 GPM
SITC of G4 Filters [AHU Side & Return Riser]
Supply, Installation, Testing & Commissioning of Filters (G4) as per the specification mentioned below: The G4 filters shall conform to EN 779 (Revised) classification G4, with minimum efficiency of 90% arrestance for coarse dust particles. Filter media shall be synthetic HDPE layered, pleated, housed in rigid extruded aluminium frame. Initial pressure drop at rated airflow shall be 4–5 mm of WC and final pressure drop shall be 12–13 mm of WC. Maximum sustainable temperature shall be below 60°C. Bidder shall provide manufacturer's test certificates and compliance declaration.
SITC of G4 Filters @ VVF Block
AHU Side - Flange Type
Return Riser Side - Box Type
SITC of G4 Filters @ QC Block
AHU Side - Flange Type
Return Riser Side - Box Type
SITC of G4 Filters @ AR Block
AHU Side - Flange Type
Return Riser Side - Box Type
SITC of F6 Filters [AHU Side]
Supply, Installation, Testing & Commissioning of Filters (F6) as per the specification mentioned below: The F6 filters shall conform to EN 779 (Revised) classification F6, with minimum efficiency of 99% for fine dust particles as per manufacturer’s test data. Filter media shall be non woven synthetic HDPE layered with aluminium mesh support, pleated, housed in rigid extruded aluminium and sheet metal casing. Initial pressure drop at rated airflow shall be 6.5–7.5 mm of WC and final pressure drop shall be 18–19 mm of WC. Maximum sustainable temperature shall be below 60°C. Bidder shall provide manufacturer's test certificates and compliance declaration.
SITC of F6 Filters - Flange Type @ VVF Block
SITC of F6 Filters - Flange Type @ QC Block
SITC of F6 Filters - Flange Type @ AR Block
SITC of F9 Filters [AHU Side]
Supply, Installation, Testing & Commissioning of Filters (F9) as per the specification mentioned below: The F9 filters shall conform to EN 779 (Revised) classification F9, with minimum efficiency of 50% at sub-micron particle size range as per manufacturer’s test certificate. Filter media shall be sub-micronic glass fibre, pleated, housed in aluminium extrusion and sheet metal casing. Initial pressure drop at rated airflow shall be 12–15 mm of WC and final pressure drop shall be 45 mm of WC. Maximum sustainable temperature shall be below 60°C. Bidder shall provide manufacturer's test certificates and compliance declaration.
SITC of F9 Filters - Flange Type @ VVF Block
SITC of F9 Filters - Flange Type @ QC Block
SITC of F9 Filters - Flange Type @ AR Block
SITC of HEPA Filters (H14)
Supply, Installation, Testing & Commissioning of HEPA Filters (H14) as per the specification mentioned below: The H14 HEPA filters shall conform to EN 1822 classification H14, having minimum efficiency of 99.995% at MPPS with PAO/DOP penetration as per standard. Filter media shall be sub-micronic glass fibre, housed in rigid aluminium extrusion frame suitable for terminal or modular housings. Initial pressure drop at rated airflow shall be 25 mm of WC and final pressure drop shall be 60 mm of WC. Bidder shall provide manufacturer's test certificates and compliance declaration.
SITC of Terminal HEPA Filters - Flange Type @ VVF Block
SITC of Terminal HEPA Filters - Flange Type @ QC Block
SITC of HEPA Filters - @ AR Block
610 x 610 x 305[mm] - AHU - Flange Type
610 x 305 x 305[mm] - AHU - Flange Type
610 x 610 x 120 [mm] - Terminal - Flange Type
305 x 305 x 120 [mm] - Terminal - Flange Type
450 x 450 x 120 [mm] - Terminal - Flange Type
375 x 375 x 120 [mm] - Terminal - Flange Type
612 x 582 x 70 [mm] - Riser - Box Type
612 x 282 x 70 [mm] - Riser - Box Type
SITC of Terminal HEPA Filters for Cold Room (H14)
Supply, Installation, Testing & Commissioning of Cold Room HEPA Filters (H14) as per the specification mentioned below: The Cold Room HEPA filters shall conform to EN 1822 classification H14 with minimum efficiency of 99.995% at MPPS. Filters shall be box type construction with PTFE membrane media housed in galvanized iron frame, specifically suitable for low-temperature cold room applications. Initial pressure drop at rated airflow shall be 19 mm of WC. Bidder shall provide manufacturer's test certificates and compliance declaration.
SITC of Cold Room HEPA Filters - Flange Type @ VVF Block
SITC of Cold Room HEPA Filters - Flange Type @ AR Block
Door Interlock Repair & Service
Providing repair, servicing, testing, and commissioning of cleanroom door interlock systems [Make-Eltech] (2-door, 4-door, 5-door, 6-door, and 8-door configuration) including inspection, diagnosis, repair or replacement of faulty controllers, sensors, electromagnetic locks, relays, wiring, and control logic to ensure correct interlocking, fail-safe operation, and prevention of simultaneous door opening. The scope includes cleaning and adjustment of components using non-particulating methods, electrical testing with calibrated instruments and final commissioning through functional testing under simulated and actual operating conditions. All work shall comply with cGMP, Schedule M, IS/ISO 14644, IEC 60204-1, and relevant Indian Standards, ensuring cleanroom integrity and zero cross-contamination. The job includes supply of required OEM-compatible spares, test/calibration records, and commissioning and compliance reports, complete as directed by the engineer-in-charge.
Door Interlock Repair & Service @ VVF Block
Repair, servicing, and commissioning of 2-Door Interlocking system
Repair, servicing, and commissioning of 3-Door Interlocking system
Repair, servicing, and commissioning of 2- Door interlocking with privacy logic
Repair, servicing, and commissioning of 3- Door interlocking with privacy logic
Supply, Installation, Testing & Commisioning of Single Leaf Electromagnetic Lock Projected type, 12V DC (600 lbs)
Supply, Installation, Testing & Commisioning of enclosure for EML Lock
Supply, Installation, Testing & Commisioning of Contactless Switch with Door position indications
Supply, Installation, Testing & Commisioning of Stainless Steel Emergency Keypads
Supply, Installation, Testing & Commisioning of Stainless Steel Privacy Keypads
Supply, Installation, Testing & Commisioning of SMPS Power Supply 12V DC, 2 Amps - 2 Door
Supply, Installation, Testing & Commisioning of SMPS Power Supply 12V DC, 3.5 Amps - 3 Door
Door Interlock Repair & Service @ QC Block
Repair, servicing, and commissioning of 2-Door Interlocking system
Repair, servicing, and commissioning of 3-Door Interlocking system
Repair, servicing, and commissioning of 2- Door interlocking with privacy logic
Repair, servicing, and commissioning of 3- Door interlocking with privacy logic
Supply, Installation, Testing & Commisioning of Single Leaf Electromagnetic Lock Projected type, 12V DC (600 lbs)
Supply, Installation, Testing & Commisioning of enclosure for EML Lock
Supply, Installation, Testing & Commisioning of Contactless Switch with Door position indications
Supply, Installation, Testing & Commisioning of Stainless Steel Emergency Keypads
Supply, Installation, Testing & Commisioning of Stainless Steel Privacy Keypads
Supply, Installation, Testing & Commisioning of SMPS Power Supply 12V DC, 2 Amps - 2 Door
Supply, Installation, Testing & Commisioning of SMPS Power Supply 12V DC, 3.5 Amps - 3 Door
Repair, servicing, and commissioning of 4-Door Interlocking system
Repair, servicing, and commissioning of 5-Door Interlocking system
Repair, servicing, and commissioning of 6-Door Interlocking system
Repair, servicing, and commissioning of 8-Door Interlocking system
Repair, servicing, and commissioning of 4- Door interlocking with privacy logic
Repair, servicing, and commissioning of 6- Door interlocking with privacy logic
Repair, servicing, and commissioning of 6- Door interlocking with privacy logic
Repair, servicing, and commissioning of 8- Door interlocking with privacy logic
Supply, Installation, Testing & Commisioning of Single Leaf Electromagnetic Lock Projected type, 12V DC (600 lbs)
Supply, Installation, Testing & Commisioning of enclosure for EML Lock
Supply, Installation, Testing & Commisioning of Contactless Switch with Door position indications
Supply, Installation, Testing & Commisioning of Stainless Steel Emergency Keypads
Supply, Installation, Testing & Commisioning of Stainless Steel Privacy Keypads
Supply, Installation, Testing & Commisioning of SMPS Power Supply 12V DC, 4.2 Amps - 4 Door
Supply, Installation, Testing & Commisioning of SMPS Power Supply 12V DC, 6 Amps - 5 Door
Supply, Installation, Testing & Commisioning of SMPS Power Supply 12V DC, 8.5 Amps - 6 Door / 8Door
Door Interlock Repair & Service @ AR Block
Repair, servicing, and commissioning of 2-Door Interlocking system
Repair, servicing, and commissioning of 3-Door Interlocking system
Repair, servicing, and commissioning of 2- Door interlocking with privacy logic
Repair, servicing, and commissioning of 3- Door interlocking with privacy logic
Supply, Installation, Testing & Commisioning of Single Leaf Electromagnetic Lock Projected type, 12V DC (600 lbs)
Supply, Installation, Testing & Commisioning of enclosure for EML Lock
Supply, Installation, Testing & Commisioning of Contactless Switch with Door position indications
Supply, Installation, Testing & Commisioning of Stainless Steel Emergency Keypads
Supply, Installation, Testing & Commisioning of Stainless Steel Privacy Keypads
Supply, Installation, Testing & Commisioning of SMPS Power Supply 12V DC, 2 Amps - 2 Door
Supply, Installation, Testing & Commisioning of SMPS Power Supply 12V DC, 3.5 Amps - 3 Door
Cold Room - Dx System Service
Providing comprehensive maintenance servicing and refrigerant gas charging for DX type coldroom units , including detailed visual inspection of all components such as evaporator coils, condenser units, compressors, expansion valves, and piping systems for any signs of wear, corrosion, or leaks; thorough cleaning of evaporator and condenser coils using approved non-corrosive cleaners to remove dust, debris, and contaminants; checking and tightening of all electrical connections, relays, contactors, and control panels; testing of safety devices including high/low pressure switches, thermostats, and defrost timers; leak detection using electronic detectors or soap solution methods followed by necessary repairs with compatible materials; system evacuation using vacuum pumps to achieve a minimum of 500 microns hold; charging with the specified refrigerant gas to the recommended pressure and quantity based on manufacturer's guidelines; performance testing post-charging to verify temperature pull-down, superheat, subcooling, and overall efficiency within ±2°C tolerance for storage requirements; submission of detailed service reports including pre- and post-service parameters and compliance certifications
Cold Room DX System Service @ QC Block + SP Block
Block- QC / Coldroom - 1/ Capacity- 19.34KW [01-IDU / 02-ODUs] [Make- Emerson]
Block- QC / Coldroom - 2/ Capacity- 27.84KW [01-IDU / 02-ODUs] [Make- Emerson]
Block- SP / Capacity- 14.4KW [01-IDU / 02-ODUs] [Make- Carrier]
Dx System - Split AC Service
Comprehensive servicing of DX Split Air Conditioning units including isolation of power supply, opening and cleaning of indoor and outdoor units, inspection and cleaning of filters, evaporator and condenser coils with suitable coil cleaner/soft brush, blowing out dust and foreign matter with compressed air, checking refrigerant level and topping up, inspection of fan blades, motor mounts and blower assembly, lubrication of moving parts where applicable, checking drain line for blockage and clearing, checks for abnormal noise/vibration and submission of service report, complete in all respects as per manufacturer recommendations and site engineer’s instructions
DX System Service @ AR Block
1 TR (Meeting Room, Document Room, Office - 1 )
2 TR (BMS, UPS & IT Room)
Robotic Duct Cleaning
The robotic duct cleaning for the AHU Ducting shall be executed in compliance with the latest Indian Standards (IS), Codes of Practice, Indian following CPWD General Specifications for Heating, Ventilation & Air-Conditioning (HVAC) 2024 and NADCA guidelines; the work entails cleaning the inside surfaces of supply and return air ducts by using robotics technology for mechanical cleaning to remove dust, impurities, and indoor air pollutants, with dust/rubbish collected in a box after passing through filters and disposed manually, followed by fumigation with appropriate and safe chemicals from the grill side to the AHU room side; the scope includes pre- and post-cleaning inspections via color photographs and video recordings provided on a pen drive, issuance of a cleaning certificate and service report, and all ancillary tasks such as duct opening, filter dismantling, and re-installation at the agency's cost
Robotic Duct Cleaning @ VVF Block
Robotic Duct Cleaning @ QC Block
Robotic Duct Cleaning @ AR Block
Validation, Performance Testing, Balancing of the HVAC System
Vendor to conduct the following tests and validate the HVAC system 1.HVAC Testing, Adjusting and Balancing as per ASHRAE standard (Air side & Water side). 2.Checking and Recording all the parameters in TAB format for the equipments like: Air Handling Units. This to includes Electrical measures (Frequency, Power factor & Kw.), Hydronic flow measures, Pressures across heat exchangers (Water & Air), Airflow measures, Motor RPM measures & Thermal measure. 3. Water balancing of chilled/hot water system including: 4.Programming, Documentation, Simulation & Commissioning of BAS 5.Cleanroom Performance Testing, Adjusting, Balancing and Recording, As per DQ confirming 1S0-14644 Part - 3. Clean room validation to be done both at at rest & in operation conditions. a.Air balancing with Flow Hood b.Room Temperature & Humidity Test c.Room Pressure Balancing d.HEPA Filter Integrity Test e.Particle count test f.Room Recovery Test g.Airflow Visualization Test Providing all documentation of IOQ (at rest & in operation) in HBL approved formats *For Cold Room AHU (CAHU) - Temperature Mapping to be performed
Validation @ QC Block
AHU-01 / 33.3 GPM / 10095 CFM
AHU-02 / 55.9 GPM / 11175 CFM
AHU-03 / 14.6 GPM / 2730 CFM
AHU-04 / 42.6 GPM / 6435 CFM
AHU-05 / 21.3 GPM / 3340 CFM
AHU-06 / 73.2 GPM / 8695 CFM
AHU-10 / 1000 CFM [Hot Air]
AHU-11 / 1000 CFM [Hot Air]
Validation of Unclassified Room AHUs / Rooms. Validation scope reamains same as the above, but tests limited to Airvelocity , Temperature & RH Test
TFA-01 / 202.2 GPM / 8210 CFM
VUS-01 / 17.3 GPM / 2275 CFM
QC Block - Cold Room - 1 / Dimension (m) - 2.6(L) x 4.75(W) x 2.4(H)
QC Block - Cold Room - 2 / Dimension (m) - 6.6(L) x 4.04(W) x 2.4(H)
SP Block - Cold Room - 1 / Dimension (m) - 5.05 (L) x 3.75(W) x 3.0(H)
SP Block - Cold Room - 2 / Dimension (m) - 5.05 (L) x 3.75(W) x 3.0(H)
SP Block - Cold Room - 3 / Dimension (m) - 4.90(L) x 3.75(W) x 3.0(H)
SP Block - Cold Room - 4 / Dimension (m) - 4.90(L) x 3.75(W) x 3.0(H)
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.66 MB
TEDOHVAC.pdf
Tender Documents • 0.65 MB
BOQ_312233.xls
BOQ • 0.40 MB
Download all tender documents and submit your bid