Electrical Installation to arrange Split Air Conditioning machines and make Electric power point multiplug for installation of Medical Equipment for New Covid 19 SNCU ward at Bolpur SD Hospital.
2021_WBPWD_341656_1
BIRED/20/e-NIQ (1st call) of 2021-2022
Open Tender
ELECTRICAL WORKS ORG
Item Rate
30 days
NEW COVID HOSPITAL, Bolpur
Please refer Tender documents.
8 documents required · 8 mandatory
₹24,700
Office of The Exe Eng,PWD,Birbhum Elec Divn
1 Nov 2021
26 Aug 2021
13 Sept 2021
26 Aug 2021
10 Sept 2021
1 Sept 2021
1 Sept 2021
Amount
Supply and Fixing of 8 nos 6/16 Amp piano type switch, 6/16 Amp 3 pin piano type socket (Brand approved by EIC),1 no 32 Amp DP MCB switch type (Legrand) and one no indicator without plug top on 500 mm X 300mm X 65 mm 16 SWG MS Box on wall with suitable bakelite/ perspex top cover plate of 3 mm thick by brass screws after making housing for switch by cutting bakelite/ perpex cover connection made through bar on insulator chair and making necessary connections as required. [N.S]
Supply & Fixing 240 V, 25 A, 3 pin Modular type plug socket (Brand approved by EIC), without plug top and switch with 2 Module GI Modular type switch board with top cover plate flushed in wall and making necy. connections with PVC Cu wire and earth continuity wire etc. [5(a)/ E-17 ] [For AC]
Supply & Fixing 240 V, 25 A, Modular type starter (Brand approved by EIC) with 25A Modular switch type DP MCB (CCurve) and 4 Module GI Modular type switch board with 4 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc.[17/E-19] [For AC]
Supplying and fixing double door Vertical TPN MCB Distribution board for MCCB incomer with IP-42/43 protection, on angle iron frame on wall as per GS ( Make - Legrand/L&T/Siemens) 12 Way ( Up to 250 A ) [15 / D- 11 ]
Supplying and fixing 415 V Four Pole MCCB of Breaking capacity 25kA/35kA in existing Vertical DBs including necessary connection as per GS [ Make - Legrand/L&T/Siemens) ]. 250 A FP [ 10/ D- 8 ]
Supplying and fixing Changeover switch with Sheet Steel enclosure on angle iron frame on wall with nuts bolts etc (a) 415 Volt 63 Amp on angle iron frame. (Make-L&T/Siemens/ABB)(D-1 /2-b)
Supplying and fixing double-door SPN MCB Distribution Board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. 2+16 Way[ Legrand/ABB/L&T ] [ 13 / D- 9 ]
Supplying and fixing double door Horizontal TPN MCB Distribution board with IP-42/43 protection, fixing on wall with L type clamp & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment ( Make - Legrand/ABB/L&T ) 8 Way [ 14 / D- 10 ]
Supplying and fixing 240/415 V MCB Isolator on din rail of existing DBs and necessary connection as perGS [Make-Legrand/ABB/L&T ]
Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connectionas per GS [ Make -Legrand/L&T/ABB) ]
Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required
2x(2.5 sqmm)+1x(1.5 sqmm) (For Power plug & Computer Plug) [ 1(a) / E-14 ]
2x(4 sqmm)+1x (2.5 sqmm) (For Split type A.C Machine and Industrial power point )[ 1(a) / E-14 ]
2x (6 sqmm) + 1x (4 sqmm) (For TPNDB to SPNDB) and Powe Pt [ 1(a) / E-14 ]
3 X 1.5 Sqmm [ 1(a) / E-14 ]
Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 32 mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required. 4x (16 sqmm) + 2x (10 sqmm). (From I/C Main switch to UPS and UPS to O/G Main switch)
Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes.
2.5sqmm [9 (i)/F-5]
4 sqmm [9 (ii)/F-5]
6 sqmm [9 (iii)/F-5]
10 Sqmm [9 (iv)/F-5]
16 Sqmm [9 (v)/F-5]
Supply of 4 Core XLPE Insulated & Sheathed Armoured Aluminium Conductor cables for Working Voltage up to 1100 Volts of following sizes [ Make Polycab / havells / currency/Gloster/KEI] 4 Core 50 Sq. mm [ NS ]
Laying of cable from 4/3½ core 35 sqmm to 50 sqmm on wall/surface incl. S & F MS saddles with earthing attachment in 2 x 10 SWG GI (Hot Dip) Wire, making holes etc. as necy., mending good damages and painting 4 Core 50 Sq. mm [F-1/2-C]
Supplying and fixing compression type gland and finishing those for following XLPE / PVC armoured cable (2/4 / 3.5)Core as per GS. 4 Core 50 sq. mm ( F-4/7-c) + (F-5/8-b-xvi)
Supplying & Fixing 240 V AC/DC superior type Multitune Call Bell (10 nos tune) (Anchor) as per GS [ 20( a )/D-13 ]
Supplying and fixing of 25 mm X 6mm copper bar of 0.5 Mtr length with 8 nos of equal distance hole with two nos spacing PVC/ Ebonite insulator fixed on wall by nuts and bolts (As per direction of EIC).
SITC of 2.2 Ton Split type A.C. machine having the following specification & feutures:- a) Cooling capacity (Maximum) (BTU /HR): 26272; cooling capacity(Rated) Guaranted(BTU/HR):26017 b) Star Rating -3 star (Minimum) c) Rated Voltage-230 V + / -5%, Frequency -50 Hz d) Compressor type- Rotary e) Mini. Room Discharge Air Flow Rate-1300CMH f) Refrigrant: R-410A g) Cordless Remote Arrangement with all modernized provision of temperature setting , Fan speed option ( Low. Medium /High ) Auto Swing h) Out door operating Temperature:-50c (Minimum) i) PCB control unit of indoor unit should be covered by metalic enclosure. With 15A plug top, 2mt long input cord ,& all other installation kit including3mtr 15.88mm &6.35mm copper pipe (Make-Godrej/Totaline/Raiku) with nitrallile rubber (Make-Suprime) insulation for indoor to out door unit connection, out door unit will be fixed on wall with heavy type wall base. Incl supply of wall base./on floor with necessary iron chair (300mm hight). fixed on roof floor as per instruction of EIC.( Mak-Mitsubishi Heavy Electric/O- General/Hitachi/Daikin).(Model No-SRK25CSS-S6/A or ar per similar model)
S&F 15.88mm& 6.35mm copper pipe (Make-Godrej/Totaline/Raiku) with nitrallile rubber (Make-Suprime) insulation and wrapper tape & 3core 2.5Sqmm& 4 core 1.55qmm copper un aurmored cable (Make-Finolex or KEI). [ for connection of plug socket to out door unit & out door to indoor unit]
S & F 15mm PVC flexible drain pipe.
Supply & Installation of suitable size iron grill protection(cage) for outdoor unit of 1.5/2.2 Ton Split type A.C. Machine incl. 5 liver Godrej Novtal Lock incl. painting.
S & F of suitable size single phase timer box on wall with locking arrangement & DIN Rail consisting of following items incl. necy. inter connection by suitable size of stranded PVC insulated 1.1 kV Gr.Cu wire after crimping as per direction of EIC (A) Double door (2+8) way SPNDB with IP 42/43 protection (Make:Crabtree/Siemens/ABB/Hager) - 1 No. (B) Digital timer having provision of adjustment 24 hour (Make : L&T/GIC/GE/Legrand/ABB/Hagger) - 1 No. (C) 250 V magnetic coil with DP 32A power contactor having 2 NO & 2 NC Contact (Make : L&T/Siemens/Havells/Legrand/ABB/Hager) - 1 No (D)250V 25/32A 10kA, DIN mounted DP MCB 'C' curve (Make : Legrand/Siemens/ L&T/ Schneider/ABB /Hager) -1 No (E) One no.red and one no.green 240V LED indicator for indicating Auto & bypass indication(Make : L&T/Kaycee/ABB) - 1 Set (F) Toggle Switch - 1 Set (G) Locking arrangement and two way malamine terminal - 1 No.
S & F (Hot Dip) strips 25 mm x 6 mm thick for vertical run on wall for lighting conductor with GI Shaddle spaced not exceeding 250 mm apart incl. mending good the damages to building work.
S & F (Hot Dip) strips 25 mm x 6 mm thick for parapet / roof/ horizontal run/ plinth surface on wall for lighting conductor with GI shaddle spaced not exceeding 250 mm apart incl. mending good the damages to building work.wire at top with 85 mm dia 6 mm thick GI base plate at bottom ibcl. Necessary holes etc.
Earthing with 65 mm dia GI pipe (TATA-Medium)x 3.0 Mts. long and 1 x 19/10 stranded GI (Hot Dip) wire (4 Mts. long), 20 mm dia x 125 mm long galvanized bolt, double nuts, double washers including socketing at both ends of stranded GI (Hot Dip) wire by crimping sockets/ thimbles and S & F 40 mm dia GI pipe (ISI-Medium) protection (3 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level to an average depth of 3.65 Mts.[G-1/2-C]
Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe.[G-2/3-a]
Extra for treatment of soil by using salt & charcoal or coke for plate electrode.[G-2/3-b]
Excavantion of morrum soil for install. Of earth, electrode and filled incl. ramming the same properly.[G-1/1-b]
S & laying 32 mm dia GI pipe protection in UG Trench, different drain for 25 mm x 6 mm GI Flat.
Hiring charges for scaffolding arrangement incl dismantling at the end of work and carriage for LC installation of vertical run.
Making solderd joint between GI stripes and air terminal and other metallic objects incl. supplying of jointing materials with two nos 8 mm dia and 3/4 th length nut bolt of same matrerials with contact grease and painting with 2 coats of bituminous paint.
Supply, installation, testing & commissioning 10KVA UPS with on-line double conversion with PWM Hi-Frequency technology & 60 Mins Back-up, passing trough neutral and Modular Architecture with the possibility to have N+X internal redundancy. The UPS should have modular architecture composed by identical redundant intelligence modules which work in parallel. These modules should be installed inside the UPS and have identical functions. Power Modules consist of the following circuits:-(i)Rectifier/PFC, (ii) Inverter, (iii) Battery-Charger, (iv) Command Logic Circuit, (v) Automatic By-Pass. The Redundancy is achieved using more modules than needed being run in "load sharing". The UPS 10KVA should have Single Phase / three–phase input and output, the architecture is distributed parallel architecture in each phase .In each Power Module, there should be built-in static by-pass system which transfer the load to utility power without interruption in case of heavy overloaded or faulty conditions. A dedicated software of Remote Monitoring & Management, installed on a PC connected to the UPS, allows to check & set all working parameters and the same functions is available on the UPS control panel & fyrthermore to schedule & programme for Computer Remote shutdown. [Make:-Numeric/Emerson /APC/Vertive/ Switching Avo/Quatron/Power One/As per choice of EIC] with open batter rack (by 50mm X 50 mm X 6 mm size angle iron of over all dimension of rack 2.5 ft X 6 ft X 5 ft and should be painted by one coat red lead and two coat alluminium paint ISI approved)
Nominal Power: 10 KVA
Active Power : 10 KW
UPS Topology: DSP-Controlled On line double conversion VFI-SS-111 system
In/Out phase Configuration: Three/ Three, Single/Single, Single/Three, Three/Single (Configurable at site)
Neutral: Neutral Passing through
Output wave form on mains run: Pure Sinusoidal
Output wave form on battery run: Pure Sinusoidal
Bypass type: Static and electro - mechanical
Transfer time: Zero
ECO Mode: Availabale
Cold Start Features: Availabale. UPS can be power tested without load
INPUT
Rated Input Voltage: 380/400/415 VAC 3 PH +N( for 3 Phase) and 220/230/240 VAC ( for 1 Phase)
Input Voltage range: 305V-477V
Rated Operating Frequency: 50 Hz/ 60 Hz (Autosensing)
Input Frequency Range: 40-70 Hz
THDi: < 4% at 100% of nominal load
Isolation Transformer : At the Input side
Input Power Factor: >=0.99
OUTPUT WITH MAINS (AC-AC)
Nominal Voltage: 380/400/415V 3PH + N( for 3 Phase), 220/230/240V ( for 1 Phase)
Nominal Power: 10 kVA
Active Power: 10 kW
Voltage variation (static): ± 1%
Voltage variation ( dynamic 0-100%;100-0%): ± 1%
THDv on nominal power (linear load): < 0.5 %
THDv on nominal power (non- linear load): < 1%
Nominal Output Frequency: 50 Hz/ 60 Hz (Autosensing)
Frequency Range: 50 Hz +/- 1% or 60 Hz +/- 1%
Frequency tolerance: Synchronized with input frequency or ± 1% in free running
Current Crest Factor: 3:1 according with IEC C62040 -3
Overload Capability: @ unity PF
10 min: 110% load rate with no bypass intervention
60 sec: 130% load tare with no bypass intervention
30 sec: >130% load tare with no bypass intervention
BATTERY
Type & Voltage: SMF & 12V
Minimum VAH required: 16320 VAH
Make: Exide/Amaron
Charging Cycle: Automatic float cum boost charging capability with settable float & boost charging voltages & current levels and boots charger timer.
GENERAL FEATURES
Efficiency in online mode: Upto 96%
Efficiency in Eco Mode: 99%
Noise level @1m: 46 dBA
Working temperature range: from 0°C to 40°C
Storage temperature range: from - 20°C to + 50°C ( Excluded batteries)
Relative Humidity range: 20-95% without condensation
Protection Degree: IP 21
Configuration and Management
Technology Rectifier/Booster/Inverter: IGBT
Communication Interface:
(i) Smart Port RS 232, RS 485, SNMP Enabled
(ii) Slots for communication interface for SNMP & BMS integration
Input /Output connection: 3P + N + PE Connectors on omega bar
Remote Monitoring Features : Available
Standards, Regulatory compliance and Certification
General and Safety requirements for UPS: EN/IEC-62040-1-1
EMC requirements for UPS: EN/IEC-62040-2
Design and Test Method: EN/IEC-62040-3
Certificates: CE
Display/Indication, Metering, Alarm
Audio alarm: Mains fail, Battery low pre-alarm, Inverter trip etc.
Metering:
(i) Input & Output:
Current:- RMS Value, peak value Crest factor
Voltage:- Ph-N RMS Value, Ph-Ph RMS value, By-Pass Line voltage( for Input)
Power:- Nominal Power(VA), Active Power(W), Power factor, frequency
(ii)Battery: Voltage, Current, Capacity, History data, Residual capacity, Charging status
(iii) Bypass: Enabling, Forced, DIP Speed, ECO Mode
(iv) Miscellaneous: Internal Temperature, Fan speed, DC Bus Voltage
Indication/Display: Mains:- On/Fail/High/Low/Single Phasing, DC:- On/High, Battery:- Low Pre-alarm/Low Trip, Inverter:- On/Trip, By-Pass Intervention, Overheats, Overloads, Battery Intervention, Total Discharge etc.
Rate should be qouted including all Tax ( IT GST Cess etc).
MODERN ENGINEERING ENTERPRISE
RIK ENTERPRISE
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .