Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹397.0 CrAdmitted-Finance DADRA AND NAGAR HAVELI DN | DADRA AND NAGAR HAVELI | THE DADRA AND NAGAR HAVELI AND DAMAN AND DIU | 396193 | ₹397.0 Cr | L1 | Admitted-Finance |
| 2 | L2₹406.1 CrAdmitted-Finance | ₹406.1 Cr | L2 | Admitted-Finance |
| 3 | L3₹411.0 CrAdmitted-Finance AT MALANI COMPLEX 58 KOTECHA NAGAR KALAVAD ROAD RAJKOT 360001 GUJARAT INDIA | RAJKOT | GUJARAT | 360001 | ₹411.0 Cr | L3 | Admitted-Finance |
| Sl No | Description | Qty | Unit | Malani Construction Co. L3 | SHANTI PROCON LLP L1 | PSP PROJECTS LIMITED L2 |
|---|---|---|---|---|---|---|
| 1.00 | Note:
1) Rate shall be inclusive of dewatering work (pumping out and removing slush) while execution in under water condition.
EARTH WORK
Clearing and grubbing of top soil, up-rooting rank vegetation, grass bushes, shrubs, saplings, trees of any girth, any size and any species, removal of stumps of trees cut earlier, debris of dismantling work, etc. by any means and disposing of all materials for all lead and all lift at non objectionable place etc. complete as directed by Engineer-in-charge. | 13,388 | Sqm | 4 ₹53,552 | 3 ₹40,164 | 5 ₹66,940 |
| 2.00 | Earthwork in excavation for all kind of soil by any means including getting out the excavated soil, sorting and stacking of useful material, dressing of the sides, ramming of bottom and disposal of surplus excavated earth for all lead within site area/ plot boundary and lift upto 1.5 mt depth, dewatering in or under water and/or liquid mud, including pumping out water/ slush as required etc complete as directed by engineer-in-charge. | 21,472 | Cum | 200 ₹42.9 L | 150 ₹32.2 L | 200 ₹42.9 L |
| 3.00 | Earthwork in excavation for all kind of soil by any means including getting out the excavated soil, sorting and stacking of useful material, dressing of the sides, ramming of bottom and disposal of surplus excavated earth for all lead within site area/ plot boundary and lift from 1.5 mt to 3.0 mt depth, dewatering in or under water and/or liquid mud, including pumping out water/ slush as required etc complete as directed by engineer-in-charge. | 38,604 | Cum | 200 ₹77.2 L | 150 ₹57.9 L | 210 ₹81.1 L |
| 4.00 | Earthwork in excavation for all kind of soil by any means including getting out the excavated soil, sorting and stacking of useful material, dressing of the sides, ramming of bottom and disposal of surplus excavated earth for all lead within site area/ plot boundary and lift from 3.0 mt to 5.0 mt depth, dewatering in or under water and/or liquid mud, including pumping out water/ slush as required etc complete as directed by engineer-in-charge. | 38,604 | Cum | 200 ₹77.2 L | 170 ₹65.6 L | 220 ₹84.9 L |
| 5.00 | Earthwork in excavation for all kind of soil by any means including getting out the excavated soil, sorting and stacking of useful material, dressing of the sides, ramming of bottom and disposal of surplus excavated earth for all lead within site area/ plot boundary and lift from 5.0 mt to 7.0 mt depth, dewatering in or under water and/or liquid mud, including pumping out water/ slush as required etc complete as directed by engineer-in-charge. | 25,736 | Cum | 300 ₹77.2 L | 200 ₹51.5 L | 230 ₹59.2 L |
| 6.00 | Earthwork in excavation for all kind of soil by any means including getting out the excavated soil, sorting and stacking of useful material, dressing of the sides, ramming of bottom and disposal of surplus excavated earth for all lead within site area/ plot boundary and lift from 7.0 mt to 9.0 mt depth, dewatering in or under water and/or liquid mud, including pumping out water/ slush as required etc complete as directed by engineer-in-charge. | 25,736 | Cum | 400 ₹1.0 Cr | 230 ₹59.2 L | 240 ₹61.8 L |
| 7.00 | Earthwork in excavation for all kind of soil by any means including getting out the excavated soil, sorting and stacking of useful material, dressing of the sides, ramming of bottom and disposal of surplus excavated earth for all lead within site area/ plot boundary and lift from 9.0 mt to 11.0 mt depth, dewatering in or under water and/or liquid mud, including pumping out water/ slush as required etc complete as directed by engineer-in-charge. | 25,736 | Cum | 400 ₹1.0 Cr | 280 ₹72.1 L | 250 ₹64.3 L |
| 8.00 | Earthwork in excavation for all kind of soil by any means including getting out the excavated soil, sorting and stacking of useful material, dressing of the sides, ramming of bottom and disposal of surplus excavated earth for all lead within site area/ plot boundary and lift from 11.0 mt to 13.0 mt depth, dewatering in or under water and/or liquid mud, including pumping out water/ slush as required etc complete as directed by engineer-in-charge. | 10,938 | Cum | 500 ₹54.7 L | 300 ₹32.8 L | 260 ₹28.4 L |
| 9.00 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations, plot filling etc. in layers not exceeding 20cm in depth, with optimum moisture content to give at least 95% of the maximum dry density (proctor density) including watering, ramming and compacting using mechanical vibrator of required type and capacity, including transportation, loading, unloading, screening, passes etc. all complete for all lead (from anywhere from site/ plot area) and lift and as directed by the Engineer-in-charge | 6,118.5 | Cum | 200 ₹12.2 L | 100 ₹6.1 L | 100 ₹6.1 L |
| 10.00 | Excavating, supplying and filling of good earth/ murrum brought form out side (including royalty) by any means; in trenches, plinth, sides of foundations, plot filling etc. in layers not exceeding 20cm in depth, with optimum moisture content to give at least 95% of the maximum dry density (proctor density) including watering, ramming and compacting using mechanical vibrator of required type and capacity, including transportation, loading, unloading, screening, passes etc. all complete for all lead and all lift and as directed by the Engineer-in-charge. | 9,782.5 | Cum | 400 ₹39.1 L | 500 ₹48.9 L | 500 ₹48.9 L |
Tender Value
₹311.1 Cr
EMD Value
₹3.2 Cr
Closing Date
26 Feb 2024, 12:00 pmClosed
Executive Engineer, PWD,Project Cell ,DNH,Silvassa
PWD Campus Block No.I(bldg),DNH,Silvassa
Construction of 480 Bedded Shri Vinoba Bhave Civil Hospital and Allied Building (Phase-II) at Dadra and Nagar Haveli, Silvassa
2024_UTDNH_6935_1
E-TENDER NOTICE NO. 50 OF 2023-24 (BLDG)
Open Tender
Civil Works - Buildings
730 days
UT OF DNH
As per NIT refer
3 documents required · 3 mandatory
₹10,000
Executive Engineer, PWD,Project Cell ,DNH,Silvassa
₹3.2 Cr
Executive Engineer, PWD,Project Cell ,DNH,Silvassa
2 Mar 2024
30 Jan 2024
26 Feb 2024
30 Jan 2024
26 Feb 2024
30 Jan 2024
9 Feb 2024
Amount
Note: 1) Rate shall be inclusive of dewatering work (pumping out and removing slush) while execution in under water condition. EARTH WORK Clearing and grubbing of top soil, up-rooting rank vegetation, grass bushes, shrubs, saplings, trees of any girth, any size and any species, removal of stumps of trees cut earlier, debris of dismantling work, etc. by any means and disposing of all materials for all lead and all lift at non objectionable place etc. complete as directed by Engineer-in-charge.
Earthwork in excavation for all kind of soil by any means including getting out the excavated soil, sorting and stacking of useful material, dressing of the sides, ramming of bottom and disposal of surplus excavated earth for all lead within site area/ plot boundary and lift upto 1.5 mt depth, dewatering in or under water and/or liquid mud, including pumping out water/ slush as required etc complete as directed by engineer-in-charge.
Earthwork in excavation for all kind of soil by any means including getting out the excavated soil, sorting and stacking of useful material, dressing of the sides, ramming of bottom and disposal of surplus excavated earth for all lead within site area/ plot boundary and lift from 1.5 mt to 3.0 mt depth, dewatering in or under water and/or liquid mud, including pumping out water/ slush as required etc complete as directed by engineer-in-charge.
Earthwork in excavation for all kind of soil by any means including getting out the excavated soil, sorting and stacking of useful material, dressing of the sides, ramming of bottom and disposal of surplus excavated earth for all lead within site area/ plot boundary and lift from 3.0 mt to 5.0 mt depth, dewatering in or under water and/or liquid mud, including pumping out water/ slush as required etc complete as directed by engineer-in-charge.
Earthwork in excavation for all kind of soil by any means including getting out the excavated soil, sorting and stacking of useful material, dressing of the sides, ramming of bottom and disposal of surplus excavated earth for all lead within site area/ plot boundary and lift from 5.0 mt to 7.0 mt depth, dewatering in or under water and/or liquid mud, including pumping out water/ slush as required etc complete as directed by engineer-in-charge.
Earthwork in excavation for all kind of soil by any means including getting out the excavated soil, sorting and stacking of useful material, dressing of the sides, ramming of bottom and disposal of surplus excavated earth for all lead within site area/ plot boundary and lift from 7.0 mt to 9.0 mt depth, dewatering in or under water and/or liquid mud, including pumping out water/ slush as required etc complete as directed by engineer-in-charge.
Earthwork in excavation for all kind of soil by any means including getting out the excavated soil, sorting and stacking of useful material, dressing of the sides, ramming of bottom and disposal of surplus excavated earth for all lead within site area/ plot boundary and lift from 9.0 mt to 11.0 mt depth, dewatering in or under water and/or liquid mud, including pumping out water/ slush as required etc complete as directed by engineer-in-charge.
Earthwork in excavation for all kind of soil by any means including getting out the excavated soil, sorting and stacking of useful material, dressing of the sides, ramming of bottom and disposal of surplus excavated earth for all lead within site area/ plot boundary and lift from 11.0 mt to 13.0 mt depth, dewatering in or under water and/or liquid mud, including pumping out water/ slush as required etc complete as directed by engineer-in-charge.
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations, plot filling etc. in layers not exceeding 20cm in depth, with optimum moisture content to give at least 95% of the maximum dry density (proctor density) including watering, ramming and compacting using mechanical vibrator of required type and capacity, including transportation, loading, unloading, screening, passes etc. all complete for all lead (from anywhere from site/ plot area) and lift and as directed by the Engineer-in-charge
Excavating, supplying and filling of good earth/ murrum brought form out side (including royalty) by any means; in trenches, plinth, sides of foundations, plot filling etc. in layers not exceeding 20cm in depth, with optimum moisture content to give at least 95% of the maximum dry density (proctor density) including watering, ramming and compacting using mechanical vibrator of required type and capacity, including transportation, loading, unloading, screening, passes etc. all complete for all lead and all lift and as directed by the Engineer-in-charge.
Supplying and filling in plinth, under floor, sunk or other location as per drawing with river sand/ manufactured sand etc including, watering, ramming consolidating and dressing complete for all lead and all lift and as directed by the Engineer-in-charge.
Providing and laying metal/ rubble soiling in foundation and for plinth protection, using upto 300mm thick size of hard stones (as per thickness of soiling), filling, covering and levelling the surface with a layer of sand after filling the voids (up to 25%) with smaller sized black trap stones 20-40 mm, 40-63 mm, 63-90 mm, 90-150 mm size of stone/ metals or stone chips, including watering, ramming well and consolidating each layer by static roller/ vibratory roller of required capacity for all lead and lifts as directed by Engineer-in-charge.
Carriage of excavated earth/ gravel by mechanical transport including loading, transporting, unloading, stacking & levelling at non objectional location for lead of 5.0 Km beyond initial lead and all lifts etc complete and as per direction of Engineer-in-Charge. Item shall be executed after prior approval of Engineer in charge.
Carriage of excavated earth/ gravel by mechanical transport including loading, transporting, unloading, stacking & levelling at non objectional place for lead beyond 5.0 Km per Km and all lifts etc complete and as per direction of Engineer-in-Charge. Item shall be executed after prior approval of Engineer in charge.
Providing and injecting Chemical emulsion for PRE - CONSTRUCTIONAL anti-termite treatment and creating a chemical barrier on the top surface of plinth filling, inside junction of wall and floor, on top of damp proof course or on masonry at level of plinth filling as per IS 6313 (Part-2)-2013 using chemical like Imidacloprid 30.5% SC (CIB approved, BIS & CBRI certified) and proportion of dilution with water shall be as per manufacturer's specification. The emulsion shall be applied as mentioned below, all as per specification and directions of Engineer-in-charge. A guarantee bond of 10 years shall be furnished in prescribed proforma. Rate shall be inclusive of material required for Anti Termite Treatment and labour and equipment's required for applying in any condition all etc. complete as directed by engineer in charge. (Stage of treatment may vary as per site condition and approved by Engineer in charge before execution.) a) Treatment to soil below raft or any type foundation - Before laying the PCC, the compact and levelled soil shall be treated at 5 liters per sqm. OR In case of soils/ sand filled above the raft, the treatment at 5 liters per sqm shall be carried out on the top surface of filled soil/ sand. b) Treatment to soil along the retaining wall - The soil retained by the walls (soil coming in contact with retaining wall) shall be treated at the rate of 7.5 liter per sqm of the vertical surface in full depth. c) Treatment of soil along external perimeter of building - After the building is complete, the earth along the external perimeter of the building shall be rodded at intervals of 150 mm and to a depth of 300 mm. The rods should be moved backward and forward, parallel to the wall to break up the earth and emulsion poured along the wall at the rate of 7.5 liter per square meter of vertical surfaces. d) Top surface of the plinth filling including damp proof courses at the rate of 5 liter/sqm of internal plinth area (if required)( As per IS:6313 Part II-2013). For any area without basement, treatment shall be done as per IS:6313 Part-II-2013. e) Treatment of soil surrounding pipes, wastes and conduits - When pipes, wastes and conduits enter the soil inside the area of the foundation, soil surrounding the point of entry shall be loosened around each of such pipe, waste or conduits for a distance of 150mm and up to a depth of 75 mm before the treatment is commenced. When they enter the soil external to the foundation, they shall be similarly treatment for a distance of 300 mm, unless they stand clear of the walls of the building are about 75 mm. f) 1 liter / linear meter along the junction of wall and floor at all stages g) 2 litre per linear meter for expansion joints in touch with soil/sand. Foot print area of Ground Floor of the building shall be considered for payment in sqm.
Providing, driving with hydraulic piling rigs with power units and installing driven cast-insitu reinforced cement concrete piles of grade M-25 of specified diameter and length below the pile cap, to carry safe working load not less than specified, excluding the cost of steel reinforcement but including the cost of shoe and the length of pile to be embedded in the pile cap etc. all complete. (Length of pile for payment shall be measured from top of shoe to the bottom of pile cap) : 550 mm dia piles
750 mm dia piles
Note - 1) All type of shuttering shall be designed by contractor and submitted to Engineer in charge along with design calculations (if required) for approval and got approved by Engineer in charge. Shuttering shall be executed as per approved shop drawing. 2) Some RCC elements (as suggested by EIC) shall be lapped by using mechanical coupler, without any extra cost. 3) Contractor shall not claim for dewatering if required. 5) Rate shall be inclusive of providing grooves, drip moulds, pockets, cut-outs etc. and co-ordination of insert sleeves, insert plate (cost of insert sleeves shall be paid separately), encasing if any wherever required while casting for all level all height. 6) Shuttering shall be compatible for heavy / bulky RCC elements, wherever required. 7) Rate shall be inclusive of dewatering work (pumping out and removing slush) while execution in under water condition. PLAIN CEMENT CONCRETE WORK Providing and laying in position machine batched, machine mixed plain cement concrete (PCC) of grade - M15 including compaction, vibration, curing, transporting and pumping wherever necessary, dewatering (if required) etc. complete for all level, all height/ depth and for all lead and lift and as directed by the Engineer. Formwork shall be paid in relavant item.
REINFORCEMENT CEMENT CONCRETE WORK Providing and laying in position Ready mix concrete/ batch mix concrete of specified grade for reinforced cement conctere work, using cement content as per approved design mix (Min cementitious level as per latest IS 456 shall be maintained) manufactured in fully automatic batching plant and transported to site of work in transit mixer for all lead having continuous agitated mixer, for reinforced cement concrete work including pumping from transit mixer to site of laying; cost of admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability; finishing, compacting, vibrating, curing etc excluding cost of Form work and reinforcement etc complete for all elements, all floors, all level, any heights/ depths, any lead and lift as directed by Engineer Incharge. Concrete of M-25 grade
Concrete of M-30 grade
Concrete of M-35 grade
Providing Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding (with GI wire) all complete for all leads and lifts, all level, all floors, all height/ depth etc complete and as directed by Engineer in charge. Thermo-Mechanically Treated bars Fe 500 D
CENTERING AND SHUTTERING Providing and fixing formwork using any type of suitable material and/ or proprietary system formwork so as to give fair finish including centering shuttering strutting, propping and removal etc. height of propping and centering below supporting floor to ceiling not exceeding 4.00 Mt. and removal of the same for in-situ reinforced concrete and plain concrete work etc complate and as directed by engineer in charge. Foundations, footings, bases of columns, sides of raft, base PCC etc.
Wall shuttering with tie rod provision RCC walls of any thickness including attached pilasters, buttresses, plinth and string courses, etc including the cost of tie bolt and heavy duty PVC pipe sleeve (above plinth), left in concrete spring coil and plastic cone assembly/ water barrier tie rod assembly (below plinth, water retaining structures) and removing the PVC cone, spring, sleeve etc and grouting the same with non-shrink grout/ ready mix patch repair mortar for concrete complete as per the direction of Engineer-in-charge. Length and dia of tie rod assembly shall be as per thickness and height of wall. Contractor shall get prior approval of tie rod assembly and water barrier.
Suspended floors, roofs, landings, balconies and access platform.
Lintels, beams, plinth beams, girders, bressummers and cantilevers.
Columns, Pillars, Piers, Abutments, Posts and Struts.
Stairs, (excluding landings) except spiral-staircases.
Extra for additional height in centering, shuttering where ever required with adequate bracing, propping etc., including cost of intermediate staging (if required), de-shuttering and decentering etc at all levels, over a height of 4.5 m, for every additional height of 1.5 metre or part thereof (Plan area to be measured).
Extra for Providing and fixing formwork for exposed concrete surfaces with pattern (vertical or horizontal surface or any shape) for any elements in desired pattern and size as per drawing and specifications using any type of formwork material and system to achieve desired finish as per approved sample for RCC elements including neat cleaning the exposed concrete surface, as directed by the engineer-in-charge. Rate shall be applicable for all levels, all places and all shapes. The contractor shall submit shuttering pattern/ shop drawing including tie-rod hole position, architectural groove based on architectural conceptual design with control line. Item shall be executed only after shuttering pattern approved by Architect and engineer in charge. Same kind of shuttering material should be only used for standard and residual sizes. These areas shall be entirely free from honey combing, stains, fins, lipping, nail or screw marks, raised grain marks, air holes or any other imperfections; bulging, and also having even shade, texture, level throughout. Mock up for all exposed work to be prepared by contractor and got approved from architects in all respect prior to concrete production. Architect reserves right to reject part or all work of sub standard or not in confirmation to sample approved as per mock up. Contractor shall get prior approval for reuse the shuttering material for repetition from Engineer in charge. Rates shall also include the cost of providing architectural groove of required size, pattern in concrete work as per drawing, cut-out etc in formwork.
EXPANSION JOINT Providing and fixing premoulded compressible, high performance closed cell, bitumen free expansion joint filler board of specified thickness in black colour of approved make, having minimum density 95 Kg/ Cum, non staining with less than 0.08% water absorption & compression recovery of 92% (conforming to MORTH specification clause 1015) minimum as per specifications including cutting to required size and shape, at all levels/ all floors/ all heights, etc. complete, as per drawings/ specification and as directed by Engineer-in-charge. 50 mm thick filler board
Providing and fixing fire retardant Expanded Polystyrene Sheets (EPS) of any thickness for filler board as filling material of 32 Kg/cum density including cutting, joining of sheet to getting required thickness as per drawing/ specification for all level/ all height etc complete as directed by engineer in charge. LDPE sheet of 500GSM shall be laid over expanded polystyrene sheet to receive the concrete in case of sunken filling. Expanded polystyrene sheet shall be joined with other filler board in case on expansion gap filling.
Providing and fixing of pan/ tray type expansion/ seismic joint system of approved make related with floor location (floor to floor or floor to wall corner) with stone fixing arrangement (minimum 20mm recess depth for receiving stone) as per drawings and direction of Engineer-in-charge. The joints system will be of extruded aluminium base members, self aligning/ self centering arrangement and support plates etc. as per ASTM B221-02. The system shall be such that it provides floor to floor /floor to wall expansion control system for various vertical locations in load application areas that accommodates multi directional seismic movement without stress to it's components. System shall consist of metal profiles with a universal aluminium base member designed to accommodate various project conditions and match with finish floor treatments. The cover plate shall be designed of width and thickness required to satisfy projects movement and loading requirements and secured to base members by utilizing manufacturer’s pre-engineered self-centering arrangement that freely rotates/ moves in all directions. The self - centering arrangement shall exhibit circular sphere ends that lock and slide inside the corresponding aluminium extrusion cavity to allow freedom of movement and flexure in all directions including vertical displacement. Provision of moisture barrier membrane in the joint system to have watertight joint is mandatory requirement all as per the manufactures design and as approved by Engineer-in-charge. (Material shall conform to ASTM 6063). Product shall be with ASTM1399 E certification. Rate shall be inclusive of edge preparation, moisture barrier, polyester powder coating (min 50 micron) on aluminium of approved shade and make if required. Cost of flooring stone/ tile (which shall be fixed in tray of expansion joint cover) shall be paid in relevant tender item. Expansion joint system shall be as approved for all floor all level including scaffolding etc complete. Floor Joint upto 150 mm gap - tray type
Providing and fixing of expansion/ seismic joint system of approved make related with wall joint (internal wall to wall/ ceiling to ceiling/ wall to corner/ any angle) location as per drawings and direction of Engineer-In- Charge. The joints shall be of extruded aluminium base members, self aligning/ centering arrangement and support plates as per ASTM B221- 02. The material shall be such that it provides an expansion joints system suitable for vertical wall to wall/ wall or ceiling at corner/ ceiling application, with no slipping down tendency amongst the components of the joint system. The joint system shall utilize light weight aluminium profiles exhibiting minimal exposed aluminium surfaces mechanically snap locking the multicellular to facilitate movement. No screws shall be visible on centre plate (hidden fasteners). The centre plate can be individually designed to match the adjacent surface and can be printed in same adjacent wall texture. Expansion joint system shall be with all mandatory requirement as per the manufactures design and as approved by Engineer-in-charge. (Material shall conform to ASTM 6063). Rate shall be inclusive of edge preparation, moisture barrier, polyester powder coating (Minimum 50 micron) on aluminium of approved shade and make if required. Expansion joint system shall be as approved for all floor all level including scaffolding etc complete. Internal Wall/ ceiling Joint upto 150 mm gap
Providing and fixing of expansion/ seismic joint system of approved make related with External wall joint location (wall to wall/ wall to corner) as per drawings and direction of Engineer-In- Charge. The joints shall be of extruded aluminium base members, self aligning/ centering arrangement and support plates as per ASTM B221- 02. The material shall be such that it provides an Expansion Joints System suitable for vertical wall to wall/ wall or ceiling at corner/ ceiling application, with no slipping down tendency amongst the components of the Joint System. The Joint System shall utilize light weight aluminium profiles exhibiting minimal exposed aluminium surfaces mechanically snap locking the multicellular to facilitate movement. No screws shall be visible on centre plate (hidden fasteners). The centre plate can be individually designed to match the adjacent surface and can be printed in same adjacent wall texture. Provision of moisture barrier membrane through shaped EPDM sheet of minimum 1.0 mm thickness in the Joint System to have watertight joint is mandatory requirement all as per the manufactures design and as approved by Engineer-in-charge. (Material shall conform to ASTM 6063). Rate shall be inclusive of edge preparation, moisture barrier, polyester powder coating (Minimum 50 Micron) on aluminium of approved shade and make if required. Expansion joint system shall be as approved for all floor all level including scaffolding etc complete. External Wall Joint upto 150 mm gap
Providing and fixing of expansion joint system of approved make and manufactures for various roof locations as per approved drawings and direction of Engineer-in-charge. The joints shall be of extruded aluminium base members with, self aligning and self centering arrangement support plates as per ASTM B221-02. The system shall be such that it provides watertight roof to roof/roof to corner joint cover expansion control system that is capable of accommodating multidirectional seismic movement without stress to its components. System shall consist of metal profile that incorporates a universal aluminium base member designed to accommodate various project conditions and roof treatments. The cover plate shall be designed of width and thickness required to satisfy movement and loading requirements and secured to base members by utilizing manufacturer’s pre-engineered self-centering arrangement that freely rotates / moves in all directions. The Self centering arrangement shall exhibit circular sphere ends that lock and slide inside the corresponding aluminium extrusion cavity to allow freedom of movement and flexure in all directions including vertical displacement. The Joint System shall resists damage or deterioration from the impact of falling ice, exposure to UV, airborne contaminants and occasional foot traffic from maintenance personnel. Provision of Moisture Barrier Membrane in the Joint System to have water tight joint is mandatory requirement. (Material shall confirm to ASTM 6063). Roof Joint upto 150 mm gap
Providing and filling the expansion joints, with exterior grade one component PU sealant with application of primer including scraping/ removing the expansion filler materials from joints, cleaning, repairing of the edges with epoxy mortar of approved colour and make, placing of backup material (polyethylene baker rod), fixing of abro masking tapes on the edges to prevent the adjoining surface, at all levels/ all floors/ all height etc. complete as directed by Engineer-in-charge. The PU sealant shall have minimum tensile strength of 1.5 N/mm2, minimum 600 elongation at break, 75% elastic recovery (after 28 days), tear propagation resistance of 8 N/mm and resistant to water, diluted alkalis, cement grout, water dispersed detergents etc. The contractor shall furnish a performance guarantee of 10 years against leakage, debonding from the edges. Size of expansion joint 40 to 50mm x 20 mm
ALLIED ITEMS Providing and wet drilling accurate and clean holes of specified diameter in RCC walls, slabs, beam or any other RCC member without vibration by core cutting (diamond drilling) machine of approved make for laying service lines including scaffolding, safety majors, disposing the debris, cleaning, making good, providing epoxy mortar/ micro concrete/ patch repair mortar/ Non shrink grout for concrete for grouting the gaps around the pipes for all levels/ all height, after approval of engineer in charge. Measurement shall be taken for the depth of holes in running meter for specified diameter. Holes shall made by authorized approved agency. Scanning of reinforcement shall be carried out before core cutting if required and as suggested by Engineer in charge. Location of core cutting shall be approved by Engineer-in-charge. Core cutting - Up to 52 mm dia.
Core cutting - Beyond 52 mm dia. up to 102 mm dia.
Core cutting - Beyond 102 mm dia. up to 202 mm dia.
Providing in position rigid PVC pipe sleeves of 6Kg/cm2 and length as per design for following diameters for services wherever pipes pass through walls/ slabs/ beam before concreting. All pipes shall be accurately cut to the required sizes, laid as per drawing, kept in the position while laying reinforcement and shuttering, sleeves shall not get displaced while concreting, and burrs removed before laying. Open ends of the pipe shall be closed as the pipe is installed to avoid clogging while concreting. Measurement shall be taken up to two decimal. (minimum 0.01 mt.). Rate shall be inclusive of removal of sleeves before water proofing or grouting. For all floors/ all levels/ all heights. Location of sleeve shall be approved by Engineer-in-charge. PVC sleeve - 200 mm Diameter
PVC sleeve - 160 mm Diameter
PVC sleeve - 110 mm Diameter
PVC sleeve - 75 mm Diameter
PVC sleeve - 50 mm Diameter
Providing and fixing Medium duty injection adhesive for rebar of approved make in dry conditions for below specified dia including drilling hole to the required depth by rotary hammer drill, cleaning with brush and jet of clean air, filling resin and hardener with standard dispenser in hole and then fixing the rebar, The system shall be made of two foils consisting of resin and hardener foil pack. The installation and the setting instructions shall be strictly followed as per the manufacturers recommendations. Rate shall be inclusive of scaffolding and for all places and all heights etc. and work shall be carried out as per direction of engineer in charge. Reinforcements shall be paid in relevant tender item. (Pull out testing upto 1% of total rebar is to be produced by manufacturer) 8 mm dia - Medium duty injection adhesive for rebar
10 mm dia - Medium duty injection adhesive for rebar
12 mm dia - Medium duty injection adhesive for rebar
16 mm dia - Medium duty injection adhesive for rebar
20 mm dia - Medium duty injection adhesive for rebar
25 mm dia - Medium duty injection adhesive for rebar
32 mm dia - Medium duty injection adhesive for rebar
MASONRY WORK Providing and laying Conventional Brick masonry works in foundation ,substructure and upto Plinth using common burnt clay building bricks confirming to IS 1077-1992 having crushing strength not less than 35 kg/Sq.cm in cement mortar 1:5 (1 cement : 5 sand) in any shape, thickness and all depth including curing, scaffolding racking / flush jointing etc. complete, as per drawing and as directed by Engineer in Charge.
Providing and laying Conventional Brick masonry works in Superstructure using common burnt clay building bricks confirming to IS 1077-1992 having crushing strength not less than 35 Kg/Sq.cm., in cement mortar 1:5 (1 cement : 5 sand) in any shape, size and thickness including curing, scaffolding, racking/ flush jointing etc. complete for all levels, all floor, all height, as per drawing and as directed by Engineer in Charge.
Providing and laying Conventional half brick masonry in foundation substructure and upto Plinth with common burnt clay building bricks having compressive strength not less than 35 Kg/cm2 in cement mortar 1:4 (1- Cement : 4 - sand) including finishing, curing, scaffolding, racking/ flush jointing etc complete for all depth, all levels, as per drawing and as directed by Engineer in Charge.
Providing and laying Conventional half brick masonry in super structure with common burnt clay building bricks having compressive strength not less than 35 Kg/cm2 in cement mortar 1:4 (1- Cement : 4 - sand) including finishing, curing, scaffolding, racking/ flush jointing etc complete for all heights, all floor, all levels, as per drawing/ specification and/ or as directed by Engineer in Charge.
Providing and fixing 190 ± 5 mm x 190 ± 5 mm x 80 ± 5 mm glass bricks of approved make, shade, finish/ texture as per following : 1) Drilling hole of required dia in periphery of opening to fixed 5mm GI wire (2 no hole @ 200c/c in both direction). 2) GI wire shall be embedded in the hole and grouting with rebaring chemical of approved make. 3) 2 numbers of GI wires shall be provided with PVC spacers (for provision of groove) in each joint horizontal as well as vertical. 4) fixed the glass brick with suitable white/ transparent adhesive of approved make and/ or polymer based white cement mortar 1:2 (1 white cement: 2 sand + white marble dust), in approximate 10mm thickness. 5) The glass bricks shall be fixed with placing of GI wires vertically as well as horizontally after passing through the spacer and having minimum lap length of 200mm. 6) Joints along the periphery of glass bricks shall be filled with weather silicone sealant of approved make and colour. 7) All the grooves (both side) between the glass brick shall be smoothly finished with paste/ putty of white cement and polymer for water tightness.
Note - 1. Only Superior class wood shall be used for any kind of woodwork. All wood (kiln seasoned and termite treated) and wood base material shall be treated with anti-termite treatment as per relevant IS before use and after installation. The guarantee shall be furnished for 10 years in the prescribed format as directed by EIC. 2. Plywood (BWP grade IS – 710), laminate or other composite wood-based products shall be free of urea formaldehyde. 3. All veneer, wood shall be FSC (Forest Stewardship Council) & Green Guard Certified. 4. All loose sample of materials shall be approved by Engineer in charge. 5. All manufactured products shall conform to Green building norms. 6. All adhesives and sealants shall be with low VOC and lead free with acceptable VOC content as per GRIHA requirements. 7. Contractor shall prepare shop drawing based on intent/ concept drawing and get approval from Engineer-in-Charge. The contractor shall prepare mock-up doors, windows and other elements with all required hardware and approved by the Engineer-in-Charge before execution of work. Work shall be carried out as per the final approved shop drawing and approved mock up. Contractor shall responsible against stability, safety, leakage, etc all complete. Testing work shall be carried out by Contractor as suggested by Engineer in charge. (If required). 5. All type of locks shall be with computerized 4 No. keys (SS 304/ brass) and master keys (if mentioned in the nomenclature of the item). Grouping of master keys shall be as suggested by Engineer-in-Charge. Nothing extra shall be payable for master key provision. 6. Contractor shall provide test certification for all fire rated items. 7. Contractor shall make provision for access control system and other mechanical/ automation devices, co-ordinate with other services work and making good etc complete. 8. All Doors, windows and other elements shall be fabricated and finished at the factory/ workshop, and only fixing and final finishing shall be executed at site, unless otherwise approved by Engineer-in-charge. 9. Door, window and other elements work shall be carried out for all floor, all level, all height, all places including loading, unloading, stacking, transporting, hoisting, erecting by any means (mechanical or manual). 10. All silicone sealant shall be grey in colour or as directed by the Engineer-in-charge. 11. All types of coating (polyester powder coating, anodizing and PVDF coating for aluminium work shall have 20 years of life). DOOR WINDOWS WORK Providing and fixing factory made and pressed laminated/ veneer finish 35mm thick flush door shutter excluding thickness of veneer/ laminate, made of ISI marked non decorative type flush door shutters conforming to IS:2202 (Part I), core of block board construction with frame of 1st class hard wood, pine filler and well matched commercial 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters having laminates/ veneer of approved make, shade, finish (which paid separately) as approved by Engineer-in-charge on both faces of shutter fixed with phenol formaldehyde synthetic resin type adhesive conforming to IS 848 including providing and fixing 6mm thick peripherial external lipping made out of first class teak wood, on all edges of door shutter with specified polishing on all exposed faces of lipping including fixing shutters etc complete for all floor all level as per drawings and as directed by Engineer-in-charge. Rate shall be inclusive of flush shutter, lipping, PU polishing, necessary consumable, accessories etc but excluding the cost of veneer/ laminates, all required hardware, etc complete for all height as per drawing, design & direction by Engineer-in-charge. Out to out dimension including beading thickness shall be measured for payment.
Metal door with frame and shutter (Non fire rated) Providing and fixing of Hollow steel door from ISO 9001-2000 certified Manufacturer for all floor all height and as directed by architect and Engineer in charge. All hollow metal doors with or without vision panel Pressed Galvanized steel Single /Double leaf to required sizes of approved make which consists of frame, shutter, infill and finish as detailed below and conforming to IS 277. Door frame shall be single rebated profile of size 143 x 57mm with having 1.20 mm thick galvanized steel sheet (18 gauge) in approved shade. Frames should be Mitered and field assembled with self tabs. Frames should be fixed with back plate bracket and anchor fasteners of approved size and make for installation on any type of surface. Once frame installed should be grouted with approved material as per recommended by engineer incharge on the clear opening. Door shutter shall be of 46 mm thick, fully flush, double skin door with or without vision panel.Door shutter shall be manufactured from min 0.8mm thick (22 gauge) galvanized steel sheet. The internal construction of the door shall be rigid with steel stiffeners/ pads and reinforcement. The infill material shall be resin bonded honey comb core . Door frames and shutter shall be finished with powder coating in desired shade. All doors shall be factory prepped for receiving appropriate hardware and provided with necessary reinforcement for hardware i.e. hinges, locks, and door closers & frames with provision for required type and size of anchor bolt fixing to any surface . The edges shall be interlocked with a bending radius of 1.4mm. For pair of doors astragals has to be provided on the meeting stile for both active and inactive leaf. Vision lite wherever applicable shall be as per joinery details with a screw on glass beading on the inside. All door shutter and frames shall be finished with etched primer coating, stove zinc phosphate primer and thermosetting polyurethane aliphatic grade paint of approved colour. The door shutter and frame shall have passed minimum 250 hours of salt spray test. Rate shall include supply and installation of door shutter with frame, anchor, vision lite (if required) etc but exclude the cost of hardware etc complete as directed by engineer in charge. Out to out area of door shutter with frame shall be measured for payment.
Hollow Metal Door With Lead Layer Providing and fixing of Pre-painted galvalume Lead Line door (Frame and single/double leaf/Fixed shutter)(with or without vision panel) of any size, any shade, any finish at all levels from approved make which consists of frame, shutter, infill, necessary hardware and finish as detailed below and conforming to respective IS code. The door shutter shall be insulated with high quality PIR 40 per m3 with 2mm lead lining in Door shutter & door Frame, conforming AERB norms. Door frame shall be rebated alluminium profile of anodize/powder coated size - 80 x 60 mm with min 1.20 mm thickness and with 2mm thick Lead layer. Frames should be fixed with back plate bracket and anchor fasteners of approved size and make for installation on any surface. Once frame installed should be grouted with approved material as per recommended by engineer incharge on the clear opening. Steel door shutter shall be of 44 mm thick, fully flush,(with or without vision panel) double skin door shall be manufactured from 0.5mm thick PPGL sheet each side with 2mm thick Lead layer. The infill material shall be with PIR insulation 40kg per m3 +/- 3. Rate shall include for supply and fix required thickness base plates, all joints of frames with provision for anchor bolt fixing to any type of surface, reinforcement pad for fixing of required hardware, factory finish, pre-punched cut outs to receive hardwares, required thickness hinge plates predrilled to receive hinges for screw mounted fixing, dust proofing arrangement for complete door and door seal as per approved shop drawing etc complete for all floor all height and as directed by architect and Engineer in charge. Rate shall include supply and installation of door shutter with frame, anchor, cost of hardware i.e. Hinges, D hadle and Door Closer, tower bolt,Locking arrangement, lead line vision panel-Lead glass (wherever required with required size) etc complete as directed by engineer in charge. Out to out area of door shutter with frame shall be measured for payment.
Providing and fixing vision panel made out of 5 mm thick toughen glass of any shape any size in all type of flush doors (for non fire rated door). Glass shall be fixed with superior class teak wood beading on both side the door of required size as shown in drawing and direction of Engineer-in-charge. Rate shall be inclusive of the cost of making opening in door, provision of glass, superior class teak wood beading both side, extra batten support required around periphery of opening, cost of PU polishing etc complete. Installed glass area shall be measured for payment without considering any wastage.
Providing and fixing in position frames/ shutter for any type of aluminium work like aluminium door, composite door-window, window (sliding, openable, side hung, top hung, fixed etc.), casement window, aluminium partition, aluminium fixed louvers, fixed window with any type of aluminium sections of make Jindal/ Indal/ Hindalco as per approved make having minimum 50 micron pure polyester powder coating of approved shade, texture & colour of approved make for all floors/ all levels/ all heights/ all shapes/ all sizes including cutting, bending, crimping, fabricating in best workmanship manner etc as per the drawing, specification and as directed by Architect or Engineer-in-Charge. Rate shall be inclusive of providing aluminium sections (conventional and/ or Euro-profile sections), cutting, fabrication, errection and fixing to the best workmanship manner, including 1) Sheet metal screws and casted solid aluminum corner cleats fixed with external byttins with a spring for rapid and secure joint assembly for casement and sliding shutter and frame; 2) Glazing clips for receiving infill panel; 3) Best quality wool pile where ever shutter touches the frame and compatible microwave cured EPDM rubber; 4) Dash Anchor fasteners of HILTI or equivalent for fixing the frame assembly to the RCC or masonry surfaces. Minimum 1 anchor fastener shall be used for every 600 mm length of section for stability of frame. 5) 10mm GI tie rod for connecting vertical stile at top and bottom for aluminum door shutter and 4mm thick solid aluminium corner cleat of full thickness of section for connecting style and horizontal rails; 6) providing and fixing packing at every 600mm c/c of average 6 mm compact sheet of width (equal to section width less 30mm for backer rod and sealant); 7) Filling the gap between wall and frame on both sides (outside and inside) with polyethylene baker rod of avg. 10 mm thickness of approved make and color and then sealing the remaining gap with neutral grade G/M (Glazed & Metal) weather silicon sealant of approved make and color. 8) Termite treated seasoned teak wood as infill material to installe hardware in door shutter and frame as and when required but excluding. 1) necessary hardware; 2) Glazing or panelling material and shutter. Shop drawing shall be prepared and get approved from the consultants before procurement of material by the contractor. Work shall carried out as per the approved shop drawings and approved sample. Actual weight of installed Aluminium sections which are visible shall only be measured and shall be considered for the payment. Contractor shall provide guarantee for stability, water tightness etc for 12 months after defects liability period.
Air Transfer Grill for door shutter Providing and fixing powder coated (powder coating not less than 50 microns) non vision extruded aluminum "Air Transfer Grill” of approved make and of required sizes to be fixed in the opening made in the laminated/ veneer finished/ non decorative flush door shutters/compact sheet door. The frame of grill shall be approximate 1.20 mm thick, in approved size, shade, and pattern, shape, as per the drawing and as per directions of Engineer in charge. Rate shall be inclusive of cutting the door as per approved grill size, providing and fixing required depth of beading on the cutting edges of door shutter with finishing. The air transfer grill shall be of double frame and fixed flush with the surface of door shutter on both sides. Area of the Air Transfer Grill on one side of door shutter shall be measured for payment.
Providing and fixing glazing in door, window, ventilation, fixed glazing and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per drawings and directions of engineer-in-charge. (Cost of beading shall be covered in basic item). Glass shall be of any shade ,any size, any shape as per Drawing and conform to IS:2835 or IS:2553. Sample shall be approved before execution the work. Installed area shall be measured for payment without considering any wastage. a) With clear toughened glass panes of 6.0 mm thickness
b) With clear toughened glass panes of 8.0 mm thickness
c) With clear toughened glass panes of 12.0 mm thickness
f) 13.52mm thick laminated glass of approved make, shade and as per approved sample- 13.52mm thick clear laminated glass with (6mm toughen glass + 1.52mm thick PVB lamination + 6 mm toughen glass) in glazed panel door & Window.
Extra for providing frosting/ etching process on glass of any thickness in any pattern as per approved sample. Frosted/ etched area of glass shall be measured for payment.
Glass Film Providing and fixing in position Glass film of various type (i.e PVC Frosted film of 100 to 130 micron thickness or UV resistant solar control film) approved make (of any pattern, shade and type) on glass partitions, window and doors for internal/external use. Film shall be pasted on glass without any appearing air bubble. The rates shall be for all shapes and all heights with necessary scaffolding complete as per the architectural drawings and manufacturer's specification & instructions as directed by the Engineer-in-charge. Film shall be with 10 years warranty. Finished frosted film area on glass shall be measured for payment.
Mirror Providing and fixing 6mm thick superior quality wall hung mirror with modular aluminium frame. Mirror shall be extra clear, decorative type, best quality, bevelled edge at periphery and of approved make in any shape and sizes. Exposed edges of mirror shall be grinded and polished. The backing of mirror shall be 8mm thick Cement bonded particle board/ fibre cement board and fixed with silicon sealant/ double sided tape to mirror. Mirror shall be fixed on cement board with double sided tape and suitable adhesive etc complete in proper plumb and level etc complete at all floors/ all levels/ all heights as directed by engineer in charge. Rate shall be inclusive of mirror,cement fiberboard, adhesive, double sided tape, screw, fasteners and all required accessories. Out to out area of mirror with aluminium frame shall be considered for payment without any wastage.
Mirror with wooden frame Providing and fixing 6mm thick extra clear mirror (with low iron content) of approve make in any shape and sizes with kiln seasoned termite treated superior class teak wooden frame of size upto 100mm x 38mm and as per drawing. Wooden framing shall be with some carving, molding work as per intent and water based exterior grade PU polished. Cement bonded particle board/ cement fiber board of minimum 6 mm thickness shall be fixed to wall with SS 304 screw/ fastener in proper plumb and level. Mirror shall be fixed with silicon sealant/ double sided tape on cement board. Wooden frame shall be fixed at periphery of glass in good workmanship manner etc. complete at all floors, all levels, all heights as directed by Engineer-in-charge. Rate shall be inclusive of mirror, cement bonded particle board/ fiber cement board, wooden framing including moulding, carving, adhesive, double sided tape, screw, fasteners, PU polish and all required accessories. Out to out area of mirror with wooden frame shall be considered for payment without any wastage.
Internal Modular Glass partition system and door Providing and fixing Internal Modular Glass and aluminium partition system and door of approved make. Single glazed partition and door consist of aluminium extruded profile, infill panel and door shutter. Infill material for fixed panel shall be of glass (of required size & specified thickness) and/ or plywood. Door shutter shall be glazed shutter and/ or flush door shutter as specified and as per drawing. (Door shutter shall be paid separately). All aluminium profiles (peripheral and intermediate) shall be of size 100mm x 30 to 45mm having minimum 1.5mm thickness excluding of powder coating. Mullioin and transom in partition system shall be made of Aluminium sections of same size of 100mm x 30 to 45mm and location as per drawing. All aluminium profile shall have minimum 50 micron polyester powder coating/ minimum 20mm anodized finish of approved make and shade. All aluminium profile shall be with featured concealed sealing (No visible gaskets/ seals) with acoustic rating of 30 dB with third party test certificate. No visible clip lines to provide clutter free view at both side of section. The Glass to be offset mounted towards outer edge or centre mounted. It shall consist of profile bottom seal pair for additional acoustic. Following standards shall be applicable for partition system. • Structural stability test accordance to BS 5234: Part2:1992 & EN 1991-1-1:2002 • Acoustic test for sound insulation in accordance to DIN EN ISO 10140-2 ASTME - E90 • All aluminium profile shall be extruded and manufactured and tested in accordance to EN573-3, EN755-2, DIN EN 12020 T2, non-dimensions manufacturing tolerance deviation DIN ISO 2768-1 or DIN 18202, DIN 1249 DIN EN ISO 12543. Contractor shall prepare shop drawing including fixing arrangement based on concept drawing. If adjoining surface is not available to fixed the partition, the contractor shall provide fixing arrangement of partition as per manufacture's recommendation without any extra cost. Contractor shall prepare mock-up (for one module with infill, shutter and hardware) for approval. Partition system shall be fixed on any type of surface i.e. masonry, RCC, dry wall system, metal work etc) with required capacity of anchorage as per manufacturer's specification. Stability of partition system shall be responsibility of contractor. Contractor shall coordinate and execute any type of services in partition system. Work shall be carried out as per approved shop drawing, as per approved mock-up and as directed by Engineer-in-charge. Rate shall be inclusive of cost of minimum 50 micron polyester powder coated/ minimum 20 micron colour anodized aluminium framing system, fixing accessories, SS 304 fasteners, gaskets, sealants etc. all required to completely install the system. However, Infill material (glass, plywood, veneer), flush door shutter, glazed door shutter, hardware and MS for fixing the partition (if required) shall be paid in relevant tender items. Partition system shall be measured as per following 1) In case of fixed partition and partitions with door - Out to out dimension of frame shall be measured for payment. 2) In case of only door - Out to out dimension of door frame shall be measured for payment.
Single glazed aluminium door shutter in glass partition system Providing and fixing glass door with aluminium shutter profile in modular partition system (frame) to accommodate the glass of specified thickness. Glass door with aluminium shutter profile shall be suitable to modular partition system and of approved make (same as partition system), all complete with necessary arrangement for provision of hardware (door closer, hinge, lock, handle etc.), required to perform as per specification and approved shop drawing. The contractor shall submit shop drawing with all details for approval of Engineer-in-charge. The rate includes shutter frame, all accessories and hardware, labour, but except glazing which shall be paid under relevant item. Out to out area of shutter shall be measured for payment.
External fixed system window Design, fabricate, supply, installation, testing of fixed window/ door system with fixed and/or openable (hinged or sliding) panels of approved make, custom designed to with stand the design wind pressure confirming to IS -875 part III. The system shall have two barrier gasket system for weather sealing. Provision for drainage of uncontrolled water entering to 1st barrier gasket. Microwave cured EPDM gaskets to accommodate glass thickness as per structural requirement, weather sealants, SS 316 grade screws of approved make, all in complete required to perform as per specification and drawing in conjunction with BOQ. Complete system shall be warranted for minimum 10 yrs against design, material, hardware, system performance, water tightness & workmanship defects. The extruded aluminium sections of Alloy 6063 T5 / T6 & tolerances confirming to DIN/ EN standard, of approved architectural sizes. All the aluminium structural profiles shall have minimum 2.0mm wall thickness. All the internal and external visible and non visible surfaces shall have Super durable polyester Powder coating of 60 - 80 micron confirming to AAMA 2604. The contractor shall prepare design and shop drawing and submit along with methodology statement in line with manufactures specifications to Engineer-in-charge. The rate shall include all materials, hardware , SS 304 fasteners, any type reinforcment to strenghen the system, sealant (minimum 5 mm thick depth and 5 mm thick wide with PE backer rod on both faces) and labour. Aluminium shutter Profile of casement window/ door shutter, glass shall be paid under relevant tender item. All shade approval shall be as per Engineer In Charge Approval. The quote rate shall include all design, engineering & shop drawing approval from Engineer-in-charge. Out to out window frame (without sealant) including shutter opening (if any) shall be measured for payment purpose. TESTING – The system shall be demonstrated performance for air seal/ water seal/ structural/seismic requirement.
Extra for side hung/Top hung shutter in fixed system window Providing and fixing side hung/Top hung openable window/door shutter, with all required accessories and hardware i.e. heavy duty three leaf projected type hinges, multi point lock, window stay of required capacity, microwave cured EPDM gaskets etc. Shutter profile to accommodate the glass of specified thickness, weather sealants, SS 316 grade screws and fasteners of approved make, all complete required to perform as per specification and approved shop drawing. Shutter shall have crimped corners. The door shutter adaptor frame profile shall be fixed to the GCW profile system (system window frame) with necessary SS 316 screws and weather sealant applied from outside. The item includes all materials, accessories, hardware, labour etc as mentioned. The contractor shall prepare and submit shop drawing with all details for approval of Engineer-in-charge. The rate includes all material, labour, hardware, (i.e. Hinges, multi point lock, window friction stay, window restrictor stay etc) as above except glazing which shall be paid under relevant item. All the accessories-Hardware shall be system compatible accessories. Add on profile, if any, required for shutter along with necessary fixing accessories and EPDM gaskets are inclusive in the cost of this item. Out to out dimensions of shutter area shall be measured for payment.
Extra for sliding shutter in fixed system window Providing and fixing sliding openable window/door shutter, with all required accessories and hardware i.e. lever handles, Flush type locks, multi point lock, roller, etc. of required capacity, microwave cured EPDM gaskets etc. the gaskets used shall be made of EPDM peroxide cured glazing gasket ensures perfect water-tightness. Wool pile brush made of high quality polypropylene multifilament yarn and has a central polypropylene fin to be provided for additional protection for tightness. Wool piles shall be extended till the height of shutters. All the accessories-Hardware shall be system compatible accessories. Rollers shall be system based with suitable weight carrying capacity. Rollers shall be tested for 25000 cycles. Shutter shall be with two point/ multi point lock with mortise handle of approved shade and shape. Shutter profile to accommodate the glass of specified thickness, weather sealants, SS 316 grade screws and fasteners of approved make, all complete required to perform as per specification and approved shop drawing. Shutter shall have crimped corners. The door shutter adaptor frame profile shall be fixed to the GCW profile system (system window frame) with necessary SS 316 screws and weather sealant applied from outside. The contractor shall prepare and submit shop drawing with all details for approval of Engineer-in-charge. The item includes all materials, accessories, hardware, labour etc as mentioned above except glazing which shall be paid under relevant item. Add on profile, if any, required for shutter along with necessary fixing accessories and EPDM gaskets are inclusive in the cost of this item. Out to out dimensions of sliding shutter area shall be measured for payment. Water tightness and air permeability shall be as per relevant latest code.
Mosquito net Providing and fixing fly proof stainless steel net/ mesh grade 304 made out of wire gauge with 0.5 mm dia. wire and 1.4mm wide aperture in any type of door, window, ventilation shutter, behind louver etc as per drawing (Area of opening for panel inserts excluding portion inside grooves or rebates to be measured) with matching aluminium beading with required screw, nails, fastener etc. complete for all floor, all level, all height and as directed by engineer in charge. The rate shall be inclusive of SS mesh, with all required accessories but excluding the cost of aluminium work. Actual installed quantity shall be measured and paid. any type of wastage is not measured for payment.
Providing and fixing laminated 6mm thick Compact Sheet of any size, any shape, any colour, any texture as per approved sample (approved by architect) in aluminium frame and shutter work with necessary cutting of sheet, single side, double side coloured as per drawing & specifications including providing and fixing EPDM quality rubber/ silicon sealant/ adhesive tape/ screwing on the periphery of the sheet as per the required thickness etc. complete at all floors/ all levels/ all heights as per the drawing & as directed by EIC / Architect. Cut edges of the compact sheet shall be provided with masking tape. Actual installed quantity shall be measured and paid. any type of wastage is not measured for payment.
Aluminum Operable Louver Providing and fixing aluminum operable system (hand operated) louvers of approved make having 50 micron polyester powder coating of approved shade & colour and texture with operating mechanism frame louver with gasket and piles. The corner joints of the frame shall be made at 45 degree using die-cast solid aluminum corner cleats fixed with a spring for rapid and secure joint assembly. Gaskets shall be of EPDM material. Work shall be carried out in the existing door/ window frame as per sample approved by the Engineer-in-charge. Operating panel shall be provided as per drawing. Actual measurement of system with louvers shall be measured and paid in sqm. Rate shall be inclusive of aluminum frame for louver operating system.
Providing and fixing SS 304 grade 5 knuckle, 2 bearing butt hinge in satin stainless steel finish, as per EN 1935 of specified size of approved make as per approved sample with necessary SS 304 screws etc. complete for all floor all height all level as directed by Engineer-in-charge. a) 125 x 75 x 3 mm - with ball bearing
b) 100 x 75 x 3 mm - with ball bearing
Providing and fixing central pivot hinge for duct door shutter of required capacity and of approved make with necessary screws etc complete as directed by engineer in charge.
Providing and fixing set of dead lock for single/ double shutter door, including strike plate SS 304 as per DIN 18251-1, grade 2 and prepared for euro profile cylinder (EPC) including strike plate and EPC length 60/70 mm standard Euro profile Pin Cylinder of approved make with both side key/ one side key one side knob/ slot operation with pair of SS 304 Escutcheons (key hole plate) in round shape as approved for any type of doors with necessary SS Phillips head screws etc complete as per drawing and sample approved by Engineer-in-charge. Rate shall be for all heights, all floors and all places. The lock shall be with 4 number computerised keys. Provision of master key shall be as per client's requirement. No extra shall be paid for the same.
Providing and fixing SS 304 satin finished set of narrow stile dead lock of approved make including strike plate SS 304 as per DIN 18251-2, grade 2 and prepared for euro profile cylinder (EPC) including strike plate and EPC length 60/70 mm standard Euro profile Pin Cylinder of approved make with both side key/ one side key one side knob/ slot operation with pair of SS 304 Escutcheons (key hole plate) in round shape as approved for any type of doors with necessary SS Phillips head screws etc complete as per drawing and sample approved by Engineer-in-charge. Rate shall be for all heights, all floors and all places. The lock shall be with 4 number computerized keys. Provision of master key shall be as per client's requirement. No extra shall be paid for the same.
Mortise lock w/o handle Providing and fixing set of mortise latch and lock including strike plate SS 304 as per DIN 18251-1, grade 2 and prepared for euro profile cylinder (EPC) including standard Euro profile Pin Cylinder (with/ without latch) of approved make with both side key/ one side key one side knob operation with one pair of SS 304 Escutcheons (key hole plate) of approved for any type of doors with necessary SS Phillips head screws etc complete as per drawing and sample approved by Engineer-in-charge. The lock shall be with 4 keys. Provision of master key shall be as per client's requirement. Pair of lever handle shall be paid in relevant tender item.
Providing and fixing Mortise shaft dead bolt with key (Alen Key lock) with 57mm backset, 25mm square forend and Escutcheons (key hole plate) in stainless steel satin finish of approved make.
Providing and fixing SS 304 grade push-pull pair of handle made out of satin (brush) finish hollow pipe of minimum 1.0mm thick having offset (C or D shape)/ H-shape/ D-shape (dent free at bending point) of approved make with necessary screws etc. complete for wooden doors/ aluminium doors/ metal doors as per drawing as approved by Engineer-in-charge. Rate shall be for all heights, all floors and all places. The length of handle shall be perfect centre to centre as below specified. a) 200 mm long x 19 mm dia.
b) 300 mm long x 22 mm dia.
c) 450 mm long x 25 mm dia.
d) 600 mm long x 32 mm dia.
e) 1200 mm long x 32 mm dia.
Plain mortise lever handle Providing and fixing SS 304 grade satin/ brush finish pair of Mortise lever handle with cap of 150mm to 200mm long of any shape, size of approved make with necessary screws, escutcheons etc. complete for wooden/ aluminium doors as per drawing as approved by Engineer-in-charge. Rate shall be for all heights, all floors and all places.
Providing and fixing Stainless steel 304 Flush Pull Handle up to 200mm long (overall) with necessary screws etc. complete as approved by Engineer-in-charge. Rate shall be for all heights, all floors and all places.
Grab handle Providing and fixing 25mm diameter (minimum 1.0mm thick) SS 304 satin (brush) finish Grab handle for disabled toilet door of 600mm long of approved make with necessary SS 304 grade screws etc. complete as per drawing as sample approved by Engineer-in-charge. Rate shall be for all heights, all floors and all places.
b) 300 mm x 10 mm rod size
c) 450 mm x 10 mm rod size
Providing and fixing of SS 304 satin finish lever action Flush tower bolt with 19mm projecting bolt (extended rod of 600mm length) aluminium casted of approved make for double shutters aluminium door, with necessary screws etc. complete as approved by Engineer-in-charge. Rate shall be for all heights, all floors and all places.
Providing and fixing SS 304 brush finish for any type of door stopper/ buffer of approximate 70mm size (floor mounted, door/ wall mounted) with magnetic/ non magnetic type etc of approved make with necessary screws etc. complete as approved by Engineer-in-charge.
Providing and fixing SS 304 grade 1.2 mm thick kick plate of approved finish of size 1000mm (+/- 100mm) (W) x 300mm (H) for disabled toilet door/ kitchen door as per drawing of approved make including fixing with necessary material like adhesive, adhesive tape, SS screws etc complete as directed by Engineer-in-charge. Kick plate have cute corner and grinded edges as per approved sample.
Push Plate Providing and fixing SS 304 push plate (plain matt/ satin/ brush finish) of approved make and approximate size 300mm (min) x 100mm x minimum 1mm thickness with necessary screws etc. complete as approved by Engineer-in-charge. Rate shall be for all heights, all floors and all places.
Fire rated & Insulated glazed Partition system with double leaf swing type/sliding type door Supply and installation of tested fully glazed fire rated fixed partition system/ fixed window including swing type latched double shutter door/ sliding type double leaf door with 120 minutes of integrity and radiation control (EW 120) and Insulation of 30 minutes (EI 30) with symmetrical (Bi-Directional) fire protection. The frames for partitions as well as doors, shutter, beading shall be made out of cold rolled/ pressed galvanized steel profiles as per EN 10327 or IS 277. The door frames are cold rolled/ pressed galvanized steel from minimum 1.5 mm steel sheet to form a profile. Frame shall have minimum 48mm width and face width maximum 125mm and as per manufacturer’s specification. The doors frame profiles shall have groves to incorporate fire resistant gaskets. The system shall be tested as per EN 1634-1/ / ISO 834-1/ ISO 3009/ IS 16947:2019 in FRL CBRI or an accredited laboratory as approved by Engineer-in-charge. The glass shall be clear with minimum 11 mm thickness and 120 min fire rated for Integrity, radiation control (EW 120) and partial insulation (EI 30), non wired, interlayered with a light transmission of minimum 85%, and a sound reduction of 37 (±2) dB and manufactured in UL & TUV audited Facility. The glass for partitions as well as for doors shall be held in its place with the help of minimum 1.2 mm cold rolled/ galvanized steel beading and ceramic tape as per the test evidence. Beadings for doors and partitions shall be clipped using SS self-tapping screws. The glass panes in doors and partitions shall be supported on non-combustible 6 mm Calcium Silicate setting blocks. All provision shall be mortised, drilled and tapped for receiving appropriate hardware. The door frame profiles and partitions shall be fixed to the supporting construction by means of M10 or bigger SS 304 steel fastener as per system requirement. Partition system shall be fixed on any type of surface i.e. masonry, RCC, dry wall system, metal work etc. with required capacity of anchorage as per manufacturers specifications. Stability of door and partition system shall be responsibility of contractor Contractor shall prepare shop drawing including fixing arrangement based on concept drawing. In case, surface/member is not available abutting the partition and door system for fixing, contractor shall design and propose a subsystem/ MS frame for fixing arrangement as per manufacturers recommendation. Contractor shall prepare mock of system with all hardware for approval. Any sub structure/ MS framing for fixing the system, shall be paid in relevant tender item. All exposed system profiles shall be finished pure polyester powder coated and shall have passed minimum 500 hours of salt spray test. The specimen shall be tested in FRL CBRI or international test lab like TBWRL / IFTS / DMT. Rate shall be inclusive of frame and glass for fixed partition system (including side and top fixed panel of shutter), fasteners, finishing and all required accessories etc complete, but excluding the cost of swing type latched door shutter, sliding door shutter, required hardware and automatic system. MS work for subsystem/ fixing arrangement, if required, shall be paid in relevant tender item after approval of Engineer-in-charge. Contractor shall prepare mock up of system with all hardware for approval. Area of partition measuring out to out dimension of frame for partition without deducting the area of door opening shall be measured for payment.
Insulated Glazed Fire Door shutter - Swing type Door shutter Extra for Providing and fixing of double door shutter of approximate total door opening size 2400mm x 2400mm with fully glazed with shutter profile of size upto 60 x 120mm step box section for taking glass elements. Door leaf profile shall be manufactured from 1.2mm (18guage) minimum thick galvanised steel sheet. Glass shall be held in its place with 1.2mm x 19mm GI clip-on beading with a ceramic tape of size 4 x 13mm as per the test evidence. Concealed screws shall be 8 x 19mm, self tapping and fixed inside the beading at every 250 mm c/c. Internal construction of the door shall be rigid reinforcement pads for stability of profile & infill of high density mineral wool. All provision shall be mortised, drilled and tapped for receiving appropriate hardware. No visible cut-out or joints shall be allowed for hinges and other accessories. For pair of doors integral astragals has to be provided on the meeting stile. Shutter shall have all necessary hardware as mentioned below: SS 304 heavy duty butt hinge (minimum 4 nos per shutter) of size 100mm x 75mm x 3mm with ball bearing, 1 set of panic device for both shutter (one point and three point), external trim with lever handle, 1 set of two concealed door closers with integrated door coordinator etc The doors shutter shall have fire rated drop down seal at the bottom and peripherial seal. All hardware shall be of 120 minutes fire rating and third party approval certificate as directed by Engineer in charge. All exposed system profiles shall be finished pure polyester powder coated and shall have passed minimum 500 hours of salt spray test. The specimen shall be tested in FRL CBRI or approved test lab by Engineer in charge. Rate shall be inclusive of shutter frame, finishing, all required hardware, services connections etc complete.
Providing and fixing of Hollow metal 2 Hour fire rated metal doors (single / double shutter door with 120 minute integrity and 30 minute insulation) of approved make and in any shade any finish as per IS 3614 – 2021 for stability and integrity. Pressed Galvanized steel confirming to IS 277 with the following specification. Recommended fire door shall have doors tested at CBRI or ARAI for maximum rating of 2hrs with minimum 30 mins insulation with vision panel. Test certificates shall be available for vision liters/ panels as part of the fire door assembly. Independent glass test certificates will not be accepted. Manufacturer test certificate shall cover doors both single & double leaf doors and hardware shall be of 120 minutes Fire Rating and third party approval certificate from reputed agency such as CERTIFIRE / UL etc. Any deviation in specification and sheet thickness other than what is mentioned in the test certificates are not allowed. Proper label confirming the type of door and the hourly rating is mandatory. Approved manufacturer subject to Engineer-in-charge approval and shall be ISO certified company. Fire door system shall be fixed on any type of surface i.e. masonry, RCC, dry wall system, metal work etc. with required capacity of anchorage as per manufacturers specifications. Stability of door and partition system shall be responsibility of contractor Contractor shall prepare shop drawing including fixing arrangement based on concept drawing. In case, surface/member is not available abutting the door system for fixing, contractor shall design and propose a subsystem/MS frame for fixing arrangement as per manufacturers recommendation. Contractor shall prepare mock up of system with all hardware for approval. Any sub structure/ MS framing for fixing the system, shall be paid in relevant tender item. Fire rated Door frame shall be single rebate profile of size 125mm x 55 mm made out of 1.60mm (16 gauge) minimum thick galvanized steel sheet. Frames shall be as per tested design and field assembled with self tabs. All provision shall be mortised, drilled and tapped for receiving appropriate hardware. Frames shall have inbuilt grooved sealing system and shall be site fitted with EPDM smoke seal as per IS:3614-2021. Rubber door silencers shall be provided on the striking jamb. Frames shall be provided with back plate bracket and anchor fasteners for installation on a finished plastered masonry wall opening. Once frame installed shall be filled with PUF as recommended by the manufacturer or engineer. Door shutter and frames shall be finished with minimum 50 micron pure polyester powder coated and shall have passed minimum 500 hours of salt spray test as per the directions of Engineer-in-charge. Rate shall be inclusive of all above mentioned components including anchor fasteners. (Cost of SS ball bearing hinges is excluded). MS work for subsystem/fixing arrangement, if required, shall be paid in relevant tender item after approval of Engineer-in-charge.
Fire rated Door shutter shall be 46mm thick fully flush double skin metal door (single/ double shutter door) with or without vision lite. Door shutter shall be manufactured from 1.2mm (18 gauge) minimum thick galvanized steel sheet. The internal construction of the door shall be rigid reinforcement pads for receiving appropriate hardware. The infill material shall be high density insulation material with Intumescent seals and smoke seal as per IS:3614-2021. All doors shall be factory prepared for receiving appropriate hardware and provided with necessary reinforcement for hinges, locks, and door closers. The edges shall be interlocked with a bending radius of 1.4mm. For pair of doors astragals has to be provided on the meeting stile for both active and inactive leaf. Vision lite wherever applicable shall be provided for minimum 5mm thick fire rated glass as per manufacturer’s recommendation with a clip on arrangement. Door shutter and frames shall be finished with minimum 50 micron pure polyester powder coated and shall have passed minimum 500 hours of salt spray test. The cost includes all above material, labour, finishing, fixing except Vision panel, ball bearing butt hinges, mortise sash lock, hydraulic door closer, panic device and external trim with design liver handle, which shall be paid in relevant tender item. MS work shall be paid in relevant tender item, if required and after approval of Engineer-in-charge.
Providing and fixing fixed vision panel glass in any type of fire rated door having minimum 11 mm clear, 2 hour fire rated and insulated glass of approved make with a clip-on arrangement with ceramic/ fire rated gasket and as per manufacturers recommendation. Installed area of glass shall be measured for payment.
Rolling shutter Supplying and fixing rolling shutters of approved make, made of 80x1.25 mm M.S. laths with 1.25 mm thick top cover, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 - part 1 and M.S. top cover of required thickness including providing mechanical device chain and crank operation for operating rolling shutters, Inclusive for providing grilled rolling shutters manufactured out of 8 mm dia M.S. bar instead of laths as per design approved by Engineer-in- charge, (area of grill would be width of shutter and required height). Rate shall be inclusive of epoxy primer and PU paint of approved make and shade and thickness as per manufacturer specification on both side with guide channel and hood cover of rolling shutter. Out to out dimension of shutter including guide channel and hood cover shall be measured for payment.
Fire Rated Rolling Shutter Providing and fixing of motorized fire rated rolling shutter FRS120 as per IS3614 Part-1 and tested to ISO 834-1 or BS 476 Part 22 of approved make and in required size. Slats shall be made from galvanized steel 0.9 to 1.2mm (22/18 gauge) as per IS 277 of size approximate 80mm of approved make. Rolling shutter shall be tested & certified for stability and integrity for up to 120mins. Construction of the slats shall be of 0.8 10 1.2mm thick cold rolled galvalume steel/ GI sheets forming to the door height, the bottom rail formed from mild steel flat bar and angle of suitable size depending on door width. Mild steel angles of suitable size and thickness are bolted to U guide of 3mm thick, fitted with suitable steel bolts / Anchor fasteners to form a secure fix in the RCC/ Steel structure. minimum 0.8mm thick pressed galvalume steel hood box complete with reinforced bracket as required to suit the shutter width, finish with two coats of polyurethane spray paint of approved shade over one coat of epoxy primer. Motor capacity shall be min 0.5hp (370W) or as per manufacturer's recommendation, connecting volt shall be 230Volt, 50Hz, 1 phase and 415V 50Hz 3 phase for bigger sizes. 2 no. of Three station push button (Up, Stop, Down), IP 65. The current rating shall be 3.3 Amp for the sizes mentioned. Where fire shutters are needed to be activated by fire alarm signal, a dual fusible link (electric solenoid releaser) is used which releases the brake of the motor, upon receipt of a 24V DC, 400mA fire alarm signal. Standard size cable shall be provided by the manufacturer. The rolling shutter shall be of galvalume steel and provided with finish two coats of Polyurethane spray paint of approved shade over one coat of epoxy primer. The contractor shall provide mechanical operating arrangements (if the motor is not functioning) and locking arrangement etc as directed by engineer in charge. Space for head room area, side space for both sides based on door sizes and as per manufacturer's recommendation. Shutter box and guide rail shall be integrated. For payment out to out area of rolling shutter including hood cover and side channels shall be measured.
Providing & fixing Fire rated (120 minutes) hydraulic door closer having third party approval certificate from reputed agency such as CERTIFIRE / UL etc. with controlled adjustable closing speed and power adjustable with back check with track arm with screws to hinged door of approved make confirming EN grade 2-4 with minimum one year guarantee. All adjustment screws face fixed. Rate shall be inclusive of fixing with using the template as per manufacturer’s specification & maintain in good working condition. The door closer shall conform to EN 1154 standards and CE marked with necessary fittings etc. complete as recommended by manufacturer and as directed by Engineer in Charge.
Providing and fixing 120 min fire rated SS 304 Ball Bearing Butt Hinges 125mm x 75mm x 3 mm CE marked for fire rated metal door of approved make with necessary screws etc. complete as recommended by manufacturer and as directed by Engineer-in-charge.
Providing and fixing 120 min fire rated Mortise sash lock of approved make with 70 mm Cylinder with thumb turn & key operation, SS 304 pair of lever handle, and pair of SS 304 Escutcheons (key hole plate) etc having CE marked for fire rated metal/ wooden door of approved make with necessary fittings etc. complete as directed by Engineer-in-charge. The lock shall be with 4 keys. Provision of master key shall be as per client's requirement.
Providing and fixing 2 hour fire rated 1 point panic device in contour design, carry bar for fire and smoke check doors (single shutter door and active leaf of double shutter door), with steel latch, security anti thrust latch for door widths up to 1300mm, in silver finish having third party approval certificate from reputed agency such as CERTIFIRE / UL etc., as per EN 1125, CE marked of approved make etc. complete as recommended by manufacturer and as directed by Engineer-in-charge.
Providing and fixing 2 hour fire rated 2 point modular panic device on inactive leaf of approved make, carry bar for rebated double shutter fire and smoke check doors, with steel latch, security anti thrust latch in silver finish, having third party approval certificate from reputed agency such as CERTIFIRE / UL etc., as per EN 1125, CE marked with necessary fittings etc. complete as recommended by manufacturer and as directed by Engineer-in-charge.
External trim with lever Providing and fixing 2 hour fire rated External trim with design lever handle up to 200mm long of approved make suiting the panic bar for fire and smoke check doors. For max. 60mm thick door prepared for half euro profile cylinder and in Silver finish with necessary fittings etc. complete having third party approval certificate from reputed agency such as CERTIFIRE/ UL etc., as recommended by manufacturer and as directed by Engineer-in-charge.
Providing and fixing floor mounted (with bottom and wall support) toilet/ shower cubical systems of approved make in required size partition and door width with 18mm thick compact board which shall be antibacterial, antifungal (conforming to JIS Z2801:2010 and ASTM G 21-2015 standards respectively) with Green guard Certification, including doors, pilasters & intermediate panels, which shall be resistant to heat, bacteria, water, chemical, scratch, termite and impact. Compact board shall be resistance to water immersion through permissible increase on thickness and mass <0.60% and board density >1.35kg/cm3 and manufactured under EN438-2&3:2005 standard. Compact panel shall be of approved shade, texture and make. To strengthen and support the system, it shall be settled on end walls with MS member. Mid panels and Pilaster will be fixed with top support of SS (316 grade). The intermediate panels will be attached to the wall with the help of approved SS channels (grade316) and all required hardware, made up of stainless steel as per manufacturer’s specification. Pilaster shall be fixed to floor with SS 316 supports as approved by Engineer in charge. Door knob, gravity hinges, Thumb turn locksets with occupancy indicators, coat hooks with door stopper, U channel, top rail with corner connector, adjustable foot/ pedestal, bottom supports, rubber noise deafening tape, screw & wall plugs shall be as approved by Engineer-in-charge. All screws shall be of SS 316 grade in stain finish. The floor clearance shall be upto 110 mm. Cubical shall be procured and install from system manufacturers and assembled. Dimensions of the cubical system shall be as per conceptual drawing and as per site condition. Contractor shall prepare shop drawing with all hardware and accessories for approval before execution. Work shall be carried out as per approved shop drawing. Total Area of compact sheet (used in fixed partition, door shutter and divider) shall be measured for payment which will include cost of all SS 316 fittings, hardware and support system as mentioned in the item. MS work, for additional support, if required, for the cubicle system shall be paid in relevant tender item.
Note:- 1) Rate shall be inclusive of any type of groove and drip mould in all type of plaster work. 2) The rate shall be for all floor, all height, all level in any shape. 3) Contractor shall provide GI chicken mesh/ glass fiber mesh (with alkali resistant coating ) at all junctions, corner, services cut-out/ chasing, doors window joints etc. as per specification and as directed by Engineer in charge. 4) If plaster thickness shall be more than mentioned in BOQ description, contractor shall provide GI chicken mesh/ glass fiber mesh (with alkali resistant coating) in entire area. Gypsum suitable for spray application shall only be used. PLASTER WORK Providing and laying average 10 mm thick single coat cement plaster and finished with trowel, on ceiling, side and soffit of beam and stair etc in cement mortar 1:3 (1 cement : 3 coarse sand), in any shape, at all floors, all heights with necessary scaffolding, curing, making grooves, forming pattas, application of bonding agent/ hacking properly RCC surface etc. complete as directed by the Architect and Engineer-in-charge.
Providing and laying 12 to 15 mm thick single coat cement plaster and finished with trowel on sides of brick work/ blocks work/ RCC work etc in cement mortar 1:3 (1 cement : 3 Coarse sand) in any shape, at all floors, all heights with necessary scaffolding, finishing, curing, making grooves, forming pattas, hacking properly RCC surface/ application of bonding agent, provision of GI hexagonal chicken mesh of size aperture 20 mm x 20 mm of 22 gauge and minimum 200 mm wide at RCC & masonry junctions or between different materials and 145 GSM of minimum 150mm wide fiber glass mesh with alkali resistant coating shall be fixed at plumbing and electrical work chasing areas, at corner and doors and window joints as per manufacturer's specifications with GI nails, hacking of concrete/ application of bonding agent, etc. complete as directed by the Architect and Engineer-in-charge. Rate shall be inclusive of all labour and material including hacking of concrete/ bonding agent, chicken mesh, glass fiber mesh, provision of groove/ drip mould as per drawing, incidentals etc. complete and as directed by Engineer-in-charge.
Providing and laying 20mm thick double coat mala plaster and finished with trowel on sides of brick work/ blocks work/ RCC work consisting of average 12 mm thick backing coat of CM 1:4 (1 cement : 4 coarse sand) and average 8 mm thick uniform coat using steel trovel finish in CM 1:2 (1 cement : 2 sand), in any shape, at all floors, all heights (for internal and external surfaces) with necessary scaffolding, finishing, curing, making grooves, forming pattas, hacking properly RCC surface/ application of bonding agent, provision of GI hexagonal chicken mesh of size aperture 20 mm x 20 mm of 22 gauge and minimum 200 mm wide at RCC & masonry junctions or between different materials and 145 GSM of minimum 150mm wide fiber glass mesh with alkali resistant coating shall be fixed at plumbing and electrical work chasing areas, at corner and doors and window joints as per manufacturer's specifications with GI nails, hacking of concrete/ application of bonding agent, etc. complete as directed by the Architect and Engineer-in-charge. Rate shall be inclusive of all labour and material including hacking of concrete/ bonding agent, chicken mesh, glass fiber mesh, provision of groove/ drip mould as per drawing, incidentals etc. complete and as directed by Engineer-in-charge.
Providing & laying 12 to 15 mm thick water proof single coat smooth / wired finish cement plaster on sides of masonry work / block work / RCC work, in any shape, in CM 1:3 (1 cement : 3 fine sand) and water proofing compund of approved make in proportions recommended by the manufacturer, finishing the surface wired finish / smooth finish with a floating coat of neat cement slurry for all floors, all height including hacking to RCC surface, scaffolding, curing etc. complete as directed by engineer-in-charge.
Note:- 1) All the waterproofing treatment/ work shall be executed through an approved water-proofing agency of approved manufacturer. Contractor shall submit technical data sheet of each product, which will be used for execution. 2) Contractor shall submit methodology statement with all detail in illustrative sketch form and got approved by Engineer-in-charge. 3) A written guarantee bond on non-judicial stamp paper (tri-party) shall be submitted by the main Contractor and provided by principal manufacturer and applicator, who has carried out work.The gurantee bond shall be for a period of ten years from the certified date of completion of overall work. The gurantee shall be for composite warranty against leakages/seepage/dampness and for the satisfactory performance of the entire water-proofing system. 4) Water proofing shall be executed under supervision of technical team of manufacturer. Waterproofing shall be tested and approved by Engineer-in-charge before proceeding for subsequent activities. 5) Contractor shall repair the concrete element by injection grouting of suitable non-shrink grout and other suitable methods in case of defective concreting of retaining walls, water tanks, slabs, beams etc., for which nothing extra shall be payable. 6) Rate shall be inclusive of surface preparation, repairing, injection grouting, saw cutting of construction joints and filling with patch repair mortar, making polymer mortar /Polymer CC fillets at horizontal as well as vertical corners etc complete. Rate shall be inclusive of testing of elements and system before and after water proofing application. 7) Rate shall be inclusive of dewatering work (pumping out and removing slush) while execution in under water condition. 8) Latest technical system/ product shall be adopted at the time of execution after approval of engineer incharge. WATERPROOFING WORK Providing & laying under the RCC Raft Foundation, a HDPE based waterproofing white composite sheet membrane, at minimum 1.2mm thickness (bare sheet thickness), when tested as per ASTM D 3767, consisting of high density polyethylene film/ sand blasted surface, a pressure sensitive adhesive and a trafficable weather resistant coating. The membrane shall form an integral, adhesive and permanent bond to poured concrete to prevent water migration at the interface of the membrane and structural concrete and shall include with overlaps to be treated with hot air welding technology/ dual adhesive tape lap seam technology to complete the side laps and secure adjacent sheets. HDPE Membrane shall be applied with following steps and as per manufacturer recommendation: 1) Cleaning of PCC surface to remove dust, loose particles, etc with compressed air or any other suitable technique depending on site conditions, grinding any sharp edges, etc 2) HDPE membrance laid over PCC and continued over the side of raft, vertical portion of retaining wall and over the kicker joint, and terminated over the kicker joint, into a saw cut groove provided at an angle of 45 degrees to the vertical, to tuck in the HDPE membrane and sealed off with a PU sealant. The membrane shall have the following physical properties: 1) Lateral Water Migration Resistance of at least 70 m as per ASTM D 5385, of hydrostatic head pressure 2) An elongation of minimum 400% as per ASTM D 412. 3) Tensile Strength > 25 MPa as per ASTM D 412, 4) Peel Strength to Poured-in-Place Concrete after 7 days of water immersion: >800N/m – ASTM D 903 5) Lap peel adhesion minimum 1400 N/m; ASTM D1876 6) The membrane shall have a puncture resistance not less than 890 N as per ASTM E 154, 7) Water presence less than 0.1 perms as per ASTM E 96 Method B 8) Water absorption not exceeding 0.5% as per ASTM D 570. Contractor shall submit methodology statement with all detail in illustrative sketch form and get approved from Engineer-in-charge before start of work. Application shall be carried out by approved applicator of manufacture and as per recommended by manufacturer. Actual laid area of HDPE membrane (horizontal & vertical) shall be measured for payment without considering overlaps.
Retaining wall Treatment Providing and applying spray applied, 2-component Polyurea over retaining wall on thoroughly prepared and cleaned surface mechanically to remove all chipping and loose material and laitance by mechanical grinding, treatment of cracks and honey combing by suitable repairing method as approved by Engineer-in-charge as per site condition. Then application of 2-component Polyurea that shall be quick/ fast Setting, elastomeric waterproof, spray applied in two coat to acheive minimum 1.5 mm DFT by high-pressure spray application, heated two component, spray proportioning equipment. The proportioning equipment must be capable of supplying correct pressure and heat for the appropriate hose length on a consistent basis. The Polyurea coating system must deliver the following properties: Solids by Volume shall be 100%, Tensile strength ASTM D412 >10 MPa , Tear Resistance ASTM D624C shall be minimum 50 N/mm, Shore A Hardness (ASTM D2240) not less than 80, Elongation ASTM D412 > 400%, crack bridging ability of minimum 2 mm as per ASTM C1305, and resistance to fire to std (EN 13501-1) Class E. Protection Board in Verticals: Providing and installing of minimum 25 mm thick XPS protection board of approved quality over the layer of Polyurea/ Polyurethane using appropriate compatible adhesive to prevent any damage to membrane during backfilling. The protection board is to be spot-bonded on the applied waterproofing. Contractor shall submit methodology statement with all details in illustrative sketch form and get approved from Engineer-in-charge. Application shall be carried out by registered applicator of the manufacture and approved by the Engineer-in-charge. Cost shall include all materials, labour, T&P, wastage etc. as mentioned above in the item. Applied area of Polyurea coating as per approved methodology (horizontal and vertical) shall be measured for payment without any overlaps.
Supplying and laying M25 grade vibrated concrete screed in proper slope and gradient including saw cutting (approx. 6mm W x 30mm D) at 3m x 4m panels or less size, making angle fillet of 50mm x 50mm at the corners using M25 grade concrete and filling the groove with PU sealant (minimum 20 mm depth over PE backer rod). If Screed concrete shall be laid over on existing concrete surface, bonding agent shall be applied before laying of concrete. Cost includes all material, labour, T&P, wastage involved as mentioned in the item. Reinforcement if required shall be paid in relevant agreement items.
Providing and applying integral crystalline slurry of hydrophilic in nature for waterproofing treatment to the RCC structures like retaining walls of the basement, water tanks, roof slabs, podiums, reservoir, sewage & water treatment plant, tunnels/ subway and bridge deck etc., prepared by mixing in the ratio of 5 : 2 (5 parts integral crystalline slurry : 2 parts water) for vertical surfaces and 3 : 1 (3 parts integral crystalline slurry : 1 part water) for horizontal surfaces and applying the same from negative (internal) side with the help of synthetic fiber brush. The material shall meet the requirements as specified in ACI - 212-3R-2010 i.e. by reducing permeability of concrete by more than 90% compared with control concrete as per DIN 1048 and resistant to 16 bar hydrostatic pressure on negative side. The crystalline slurry shall be capable of self-healing of cracks up to a width of 0.50mm. The work shall be carried out all complete as per specification and the direction of the Engineer-in-charge. For vertical surface two coats @0.70 kg per sqm per coat
For horizontal surface one coat @1.10 kg per sqm.
Toilet, Wet area & Misc. areas Providing and applying Two-part acrylic polymer modified cementitious elastomeric waterproof coating of minimum 1.5mm thickness DFT having minimum 1 N/mm2 tensile strength, and shall cover 2.2 kg/sqm per mm of thickness. The coating shall have an elongation of a minimum of 80% when tested as per ASTM D 412 resisting 5 bars hydrostatic pressure as per DIN 1048 and having crack bridging ability of up to 2mm. Thorough surface preparation by mechanical means to level and plain the surface of walls and floors of the toilet areas. All cracks and crevices shall be filled and made good to receive waterproofing coating treatment The coating shall cover all the floor area of the wet area (toilet) and shall also be applied over on the vertical walls for minimum 300mm height above the floor in two or more coats to achieve required thickness. The periphery of the toilet floor shall be additionally reinforced with an extra third coat of the coating with a fiber band (glass fibre mesh of minimum 80 gsm) sandwiched between the first and the second coat, which shall also done around protrusions (pipes) meant for plumbing purpose. The last coat (second/ third coat) when wet, shall be sprinkled with clean and washed sand, to facilitate the floor screed or plaster. Pipes being fixed for plumbing shall be fixed in holes which are mechanically core cut, more than the dia of the pipes. Pipes shall be fixed by grouting the annular space with non-shrink cementitious grout of proprietary make. Before grouting, the pipes shall be wrapped with a two-way self adhesive tape at least 50mm wide and then grouted to fill in the grout, ensuring total watertight plumbing fittings. Contractor shall submit methodology statement with all detail in illustrative sketch form and get approved from Engineer-in-charge. Application shall be carried out by approved applicator of manufacture and as per recommended by manufacturer. Actual applied area on floor & wall shall be measured for payment. Cost includes all material (for surface preparation, coating and hole packing), labour, T&P, wastage involved as mentioned in the item.
Providing and filling light weight AAC bats (of size 40-60 mm) with cement mortar mixed in the ratio 1:3:6 (1 cement : 3 coarse sand : 6 block bats) including mixing of approved water proofing compound in recommended proportion. The laid AAC bat mix shall be well rammed and compacted as required. Further surfaces shall be screeded with cement concrete mix 1:1.5:3 (1 cement : 1.5 coarse sand : 3 stone grit of size 6 mm and below by volume) admixed with approved integral water proofing compound in recommended proportion, laid to an average thickness of 25mm and finished smooth or ready to receive finish material as specified. Care shall be taken prior to filling all pipes passing through sunk portion such that the pipes are pressure tested by maintaining pressure for 24 hours and junctions of pipes passing through walls, slabs are well grouted and sealed. This shall be tested by ponding water for required depth and maintaining for 72 hours. (Rate includes cost of AAC bats, cement mortar, top screed, labour charges for working at all levels, leads and heights). For payment the area of sunken slab and the depth of filling including the thickness of screed shall be measured.
Providing and applying of controlled swellable type water stop bar, of approximate size 20mm x 10mm, non-bentonite type (expansive nature) of approved make for construction joints treatment of RCC structure, such as raft slab, retaining walls, water storage tank and at the junctions of raft slab with the retaining walls etc. For provision of swellable bar, contractor shall provide shear key in wall and raft. After cleaning the shear key, one coat of required primer for swellable water stop tape shall be applied throughout the length of the joint as per manufacturer specification. Over the primed surface swellable type water stop bar shall be placed. The work shall be carried out all complete as per specification and the direction of the engineer-in-charge. The product performance shall carry guaranteed for 10 years against any leakage. Size of swellable bar shall be as per manufacturer’s recommendation and as per approved system by Engineer-in-charge.
Podium water proofing Providing and applying 2 component Root-Resistant hybrid Polyurea water proofing system over a thoroughly prepared surface of basement podium slab, top slab of tunnel/ under ground structure etc, cleaned mechanically, to remove all laitance by mechanical grinding, treatment of cracks and honey combing by suitable method etc. The suitable compatible primer for the polyurea system shall be applied earlier to reach a tack-free state. Then application of 2 component Polyurea in two or more layers that is quick / fast Setting, that is elastomeric waterproof, spray applied to achieve DFT recommended by manufacturer (minimum 1.5 mm) by spray application with a high-pressure, heated two component, spray proportioning equipment. The proportioning equipment utilized must be capable of supplying correct pressure and heat for the appropriate hose length on a consistent basis. The Polyurea coating system must deliver the following properties: Solids by Volume shall be 100%, Tensile strength ASTM D412 >10 MPa, Tear Resistance ASTM D624C shall be minimum 50 N/mm, Elongation ASTM D412 > 400%. The polyurea coating shall be applied over podium slab with vertical wall minimum 300 mm in height, after surface preparation. Supplying and applying protective geo textile fabric of 200 gsm over the entire membrane with proper overlaps of 100 mm. Over the geotextile fabric, concrete screed with saw cut and groove shall be provided in desired slope, which shall be paid under relevant tender item. Providing & placing polypropylene HDPE dimpled drain board (with inbuilt geo textile drainage membrane of 100 gsm at top), with minimum overlap of 100 mm, based on soil characteristics and height of soil overburden. Cost includes all materials, labour, T&P, wastage etc. as mentioned in the item except cost of protective concrete screed.Applied area of Polyurea coating as per approved methodology (horizontal and vertical) shall be measured for payment without any overlaps.
Terrace water proofing Providing and laying conventional (India Type) cement based brickbat coba water proofing treatment average 115mm thick and minimum thickness at khurra/ channel as 65 mm including preparation of surface as required for treatment on roofs, balconies, terraces etc. at all floors consisting of following operations and furnishing a guarantee bond in prescribe format of 10 years on Rs.100.00 stamp paper between main contractor, client and approved water proofing agency. 1) Cleaning and applying a cement slurry at the rate 2.75 Kg per sqm mixed with water proofing compound as manufacture's specification as directed by engineer-in-charge over the slab including adjoining walls upto 300mm height including testing the surface, grouting the cracks if leakage is found before the treatment . 2) Laying brick bats with mortar using broken bricks/ brick bats 25 mm to 115mm size with maximum 50% of cement mortar of mix 1:5 admixed with water proofing compound conforming to IS : 2645 in minimum 20 mm thick layer of beading cement mortar of mix 1:5 (1 cement :5 coarse sand ) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm height including rounding of junctions of walls and slabs. 3) After three days of proper curing applying a second coat of cement slurry at the rate 2.75 Kg per sqm admixed with water proofing compound conforming to IS : 2645 including laying glass fibre cloth of approved quality in top layer of plaster and finally Finishing the surface to make wired finish/ trowel finish with average 12-20 mm thick jointless cement mortar of mix 1:4 (1 cement :4 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge. 4) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test. All above operations to be done in order and as directed and specified by the Engineer-in-Charge. (Only plan area shall be measured, vata shall not be measured separately and paid for.)
Providing & laying china mosaic flooring for plain and curved surfaces, comprising of 20 to 25 mm size broken white/ colour pieces of ceramic/glazed tiles laid over 12 to 15mm thick cement mortar 1:6 (1 cement: 4 coarse sand) bedding including applying cement slurry at the rate of 2.75 kg per sqm on plain or sloped surfaces with joints not exceeding 5 mm, including filling the gaps with white cement mixture & mixing with synthetic polyester fibre, triangular in shape having specific gravity of 1.34 to 1.40, cross section size ranging from 10 to 40 micron & length upto 6mm, mixing fibre @ 125 grams per 50kg of cement in cement mortar, including providing and mixing water proofing material in mortar @ 1 kg per 50 kg of cement, all complete as per direction of Engineer-in-charge. The flooring shall be tampered with wooden rammer not exceeding 2 Kg in weight to bring the mortar up to the surface, including rounding of the junctions and extending them upto 15 cm. along the parapet wall. The rate shall include bands, if different colour is used, any pattern or design as per drawing and direction, making vata/ fillet, curing, cleaning with water and oxalic acid, etc. complete. Only Plan area shall be measured for payment.
Providing and laying 18 mm thick Granite stone of any finished i.e river wash, flamed finish, leather finish, linen finish, sandblasted finish or similar finish in any shade (uniform), any size and any shape for flooring in required design and patterns as per the drawings, laid over average bedding 40 mm thick cement mortar 1:4 (1 cement : 4 coarse sand), and jointed with groove or without groove with grey/white cement slurry mixed with pigment to match the shade of the slabs, including cleaning and curing etc. all complete as specified and as directed by the Engineer-in-Charge : Rate shall be inclusive of granite (as per approved sample), fixed with cement mortar bedding, cement slurry, matching pigment, all labour etc complete but excluding filling with epoxy grout which shall be payable under relevant item.
Providing and fixing 18 mm thick polished Granite stone slabs of any shade (uniform), any size and any shape in cladding, dado and pillars laid in any pattern over any type of levelled surface, fixed with minimum 6mm thick stone fixing adhesive as per IS-15477 of approved make and jointed with groove or without groove with grey/ white cement slurry mixed with pigment to match the shade of the slabs, including rubbing, curing, finishing, cleaning, protection, scaffolding, wastage and polishing etc. all complete as specified and as directed by Engineer-in-Charge. Exposed edge of granite stone shall be with pencil cornered and polished same as slab. Rate shall be inclusive of granite (as per approved sample), adhesive for fixing, cement slurry, matching pigment, all labour etc. all complete but excluding cement mortar plaster/ backing coat and filling with epoxy grout which shall be payable under relevant item.
Providing and fixing 8 to 10 mm thick polished Granite stone slabs of any shade (uniform), any size and any shape in skirting (flush with plaster or adjoining surface), laid in any pattern on any type of levelled surface, fixed with minimum 6mm thick suitable stone fixing adhesive as per IS-15477 of approved make and jointed with groove or without groove with grey/white cement slurry mixed with pigment to match the shade of the slabs, including providing 6 to 10mm wide groove between skirting and plaster, rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge. Length of stone for skirting shall be as per design to match the joint and pattern. Shade of skirting must be match with flooring stone. Rate shall be inclusive of granite (as per approved sample), adhesive for fixing, cement slurry, matching pigment, all labour etc complete but excluding filling with epoxy grout which shall be payable under relevant item.
Providing and laying polished Granite stone in single piece of any shade (uniform), any size and any shape in door & window sill - jambs as per the drawings. Granite stone slab having pencil corner and same polished at exposed edge in even and uniform thickness and laid over ant levelled surface, and fixed with minimum 6mm thick stone fixing adhesive as per IS-15477 of approved make, and jointed (paper joint) with grey/ white cement slurry mixed with pigment to match the shade of the slabs, including rubbing, curing and polishing etc. all complete and as directed by the Engineer-in-Charge. Joint with adjoining surface shall be finished as per drawing. Rate shall be inclusive of granite (as per approved sample), adhesive for fixing, cement slurry, matching pigment, all labour etc complete but excluding cement mortar bedding/ plaster which shall be payable under relevant item. 30 mm thick Granite stone
Providing and laying 25 mm thick machine cut polished Kota stone of any shade (uniform), any size and any shape for flooring in required design and patterns as per the drawings, laid over average bedding 50 mm thick cement mortar 1:4 (1 cement : 4 coarse sand), and jointed (paper joint) with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbing, curing and polishing etc. all complete up to the satisfaction and as directed by the Engineer-in-Charge : Rate shall be inclusive of kota stone (as per approved sample), fixed with cement mortar bedding, cement slurry, matching pigment, all labour etc complete but excluding filling with epoxy grout which shall be payable under relevant item.
Providing and laying 25 mm thick machine cut kota stone of any finished i.e river wash, flamed finish, leather finish, linen finish, sandblasted finish or similar finish in any shade (uniform), any size and any shape for flooring in required design and patterns as per the drawings, laid over average bedding 40 mm thick cement mortar 1:4 (1 cement : 4 coarse sand), and jointed (paper joint) with grey cement slurry mixed with pigment to match the shade of the slabs, including cleaning and curing etc. all complete up to the satisfaction and as directed by the Engineer-in-Charge : Rate shall be inclusive of kota stone (as per approved sample), fixed with cement mortar bedding, cement slurry, matching pigment, all labour etc complete.
Providing and fixing 25 mm thick machine cut polished Kota stone of any shade (uniform), any size and any shape in cladding, dado and pillars laid in any pattern over any type of levelled surface, fixed with minimum 6mm thick stone fixing adhesive as per IS-15477 of approved make and jointed (paper joint) with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbing, curing, finishing, cleaning, protection, scaffolding, wastage and polishing etc. all complete as specified and as directed by Engineer-in-Charge. Exposed edge of kota stone shall be with pencil cornered and polished same as slab. Rate shall be inclusive of kota stone (as per approved sample), adhesive for fixing, cement slurry, matching pigment, all labour etc. all complete but excluding cement mortar plaster / backing coat which shall be payable under relevant item.
Providing and fixing 8 to 10 mm thick machine cut polished Kota stone of any shade (uniform), any size and any shape in skirting (flush with plaster or adjoining surface), laid in any pattern on any type of levelled surface, fixed with suitable stone fixing adhesive as per IS-15477 of approved make and jointed (paper joint) with grey cement slurry mixed with pigment to match the shade of the slabs, including providing 6 to 10mm wide groove between skirting and plaster, rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge. Length of stone for skirting shall be as per design to match the joint and pattern of flooring. Shade of skirting must be match with flooring stone. Rate shall be inclusive of Kota stone (as per approved sample), adhesive for fixing, cement slurry, matching pigment, all labour etc complete.
Providing and laying machine cut polished Kota stone in single piece of any shade (uniform), any size and any shape in treads of steps, coping, seating, self etc. as per the drawings. Kota stone slab having pencil corner and same polished at exposed edge in even and uniform thickness and laid over average 20 mm thick base of cement mortar 1 : 4 (1 cement : 4 coarse sand), and jointed (paper joint) with grey cement slurry mixed with pigment to match the shade as per drawing, including rubbing, curing and polishing etc. all complete and as directed by the Engineer-in-Charge.Joint between tread and riser shall be finished as per drawing. Rate shall be inclusive of kota stone (as per approved sample), fixed with cement mortar bedding, cement slurry, matching pigment, all labour etc complete. 25 mm thick Kotastone
40 mm thick Kotastone
Providing and laying 25 mm thick machine cut polished Kota stone in single piece of any shade (uniform), any size and any shape in risers of steps laid in any pattern on 12 mm thick (average) cement mortar 1:3 (1 cement : 3 coarse sand) and jointed (paper joint) with grey cement slurry mixed with pigment to match the shade of the slabs, including finishing, rubbing, curing and polishing etc. all complete as specified and as directed by Engineer-in-Charge. Joint between tread and riser shall be finished as per drawing. Kotastone slab having pencil corner and same polished at exposed edge in even and uniform thickness (if required). Rate shall be inclusive of kota stone (as per approved sample), fixed with cement mortar, cement slurry, matching pigment, all labour etc complete.
Providing and laying machine cut polished Kota stone in single piece of any shade (uniform), any size and any shape in parapet top, coping and similar locations etc. as per the drawings. Kota stone slab having pencil corner and same bothside polished at exposed edge in even and uniform thickness and laid over average 20 mm thick base of cement mortar 1 : 4 (1 cement : 4 coarse sand), and jointed (paper joint) with grey cement slurry mixed with pigment to match the shade as per drawing, including providing 6 to 10mm wide groove between parapet top and plaster, rubbing, curing and polishing etc. all complete and as directed by the Engineer-in-Charge. Kotastone shall be secured to the base mortar (additional strengthen) by means of mechanical SS anchor fastener as per requirement and as directed by Engineer in charge. Rate shall be inclusive of kota stone (as per approved sample), fixed with cement mortar bedding, cement slurry, matching pigment, anchor fastener, all labour etc complete. 40 mm thick Kotastone
Providing and laying 18mm thick Italian Marble stone any shade (uniform), any size and any shape for flooring in required design and patterns as per the drawings, laid over existing bedding (cement mortar bedding), fixed with minimum 6mm thick high performance, polymer modified, non-slip, compatible white adhesive (IS-15477) of approved make, and jointed (paper joint) with white cement and matching pigment including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge : Italian Marble shall be laid in required pattern to match the natural grains and as per design intent. Rate shall be inclusive of Italian marble stone (as per approved sample), adhesive for fixing, white cement slurry, matching pigment, all labour etc complete but excluding cement mortar bedding which shall be payable under relevant item.
Providing and laying superior quality 18mm thick Italian Marble stone of any shade (uniform), any size and any shape in cladding, dado, skirting and pillars laid in any pattern over white cement mortar plaster / backing coat (levelled surface) fixed with minimum 6mm thick high performance, polymer modified, non-slip, compatible white adhesive (IS-15477) of approved make and jointed (paper joint) with white cement slurry mixed with pigment to match the shade of the slabs, including rubbing, curing, finishing, cleaning, protection, scaffolding, wastage and polishing etc. all complete as specified and as directed by Engineer-in-Charge. Exposed edge of marble stone shall be with pencil cornered and polished same as slab. Rate shall be inclusive of marble stone (as per approved sample), adhesive for fixing, white cement slurry, matching pigment, all labour etc. all complete but excluding white cement mortar plaster / backing coat which shall be payable under relevant item.
Extra for ornamental/ Intricate inlay flooring (With cutting of base stone as per design, not in full depth) Extra for Providing & laying ornamental/ Intricate Inlay designer flooring on base of marble flooring with specified inlay pattern/ border with different required shade of marble, sand stone, lime stone, Granite or other specified material per design. Inlay pattern shall be done with CNC cutting machine/ laser cutting/ manual or by any means as per concept image or drawing and as suggested by engineer in charge. Contactor shall prepare shop drawing base on concept drawing or image and get it approved. Contractor shall prepared mock-up as per approved shop drawing and suggested by Architect. Inlay : Providing and laying inlay pattern with specified stone over base stone flooring stone as per approved shop drawing and approved sample. Base stone and inlay marble shall be cut with CNC cutting machine/ hand cutting and making pattern as per approved shop drawing. Inlay shall be fixed with suitable adhesive on existing base flooring. The thickness of inlay material shall be of required thickness of base stone. While applying the adhesive for marble or other stone inlay, color of marble or other stone shall not get varied. After completion of laying of base and inlay, contractor shall finish entire floor (as specified) as per satisfaction of Architect and Engineer in charge. Rate shall be inclusive of inlay material, labor, adhesive, wastage, curing, polishing, cleaning with water jet, finishing, etc complete for all floor level and as directed by engineer in charge. Base stone flooring shall be paid in relevant tender item. Out to out dimension/ area of inlay work shall be measured for payment.
Providing and laying Vitrified tiles in any sizes with minimum 9 mm thickness (superior quality, full body, homogeneous tiles) with water absorption less than 0.08% and conforming to IS: 15622, of approved make, in any colours, shades, finish (anti skid/ satin/ polished etc) for flooring in required design and patterns as per the drawings, laid over average 40 mm thick base of cement mortar 1 : 4 (1 cement : 4 coarse sand) and jointed with groove or without groove with grey cement slurry mixed with pigment to match the shade of the tiles, including cleaning and curing etc. all complete as specified and as directed by the Engineer-in-Charge. Rate shall be inclusive of vitrified tile (as per approved sample), fixed with cement mortar bedding, cement slurry, matching pigment, all labour etc complete but excluding filling with epoxy grout which shall be payable under relevant item.
Providing and laying Vitrified tiles in any sizes with minimum 9 mm thickness (superior quality, full body, homogeneous tiles), with water absorption less than 0.08% and conforming to IS: 15622, of approved brand & manufacturer, in all colours, shade and finish (satin/ polished etc) in wall tile/ dado, riser of steps, skirting and pillars laid in any pattern over any type of levelled surface, in any pattern with suitable cement based high polymer modified quick set tile adhesive (water based) conforming to IS: 15477of approved make and jointed with groove or without groove with grey cement slurry mixed with pigment to match the shade of the tiles, including providing 6 to 10mm wide groove between wall tiles and plaster edge treatment, rubbing, curing, finishing, cleaning, protection, scaffolding and wastage etc. all complete as specified and as directed by Engineer-in-Charge. Length of tiles for dado shall be as per design to match the joint and pattern. Shade of dado must be match with flooring stone/tiles or as per approved shade. Rate shall be inclusive of vitrified tile (as per approved sample), adhesive for fixing, cement slurry, matching pigment, all labour etc complete but excluding filling with epoxy grout which shall be payable under relevant item.
Extra for Providing and Grouting the joints of any type of tile in flooring/ wall tiles of any size as specified having joints of up to 5 mm width in total thickness, using epoxy grout of approved make and shade including PVC spacer, filling/ grouting, protecting tile, abro-tap and finishing complete as per direction of Engineer-in-charge.
Extra for Providing and Grouting the joints of any type of stone of any size in flooring/ wall as specified having joints of up to 5 mm width in total thickness, using epoxy grout of approved make and shade including PVC spacer, filling/ grouting, protecting tile, abro-tap and finishing complete as per direction of Engineer-in-charge.
Providing and fixing Ceramic tiles 6 to 8 mm thick in floor and wall of water tank or similar laid on plastered wall with cement based high polymer modified quick set tile adhesive (water based) conforming to IS: 15477, in average 6 mm thickness, including finishing of joints, provision of groove of 3 to 5 mm, curing, grouting of joints etc. complete for all floors any heights/ depth, any lead and lift as directed by Engineer In charge. Backing coat plaster/ screed and grouting shall be paid in relevant tender item. Sample shall be approved before execution.
Concrete flooring: Providing and laying C.C. flooring of mix M-25 with ready mixed/ batch mixed concrete from batching plant with required finish (broom/ smooth finish). The ready mixed concrete shall be casted in panel and finished with screed board vibrator, vacuum dewatering process and finally finished by floating, brooming with machine, pumping from transit mixer to site of laying etc. complete as per specifications, for all heights and lifts and directions of Engineer in charge. If concrete flooring shall be laid over on existing concrete surface, bonding agent shall be applied before laying of concrete. Reinforcement if required shall be paid in relevant tender item. The rate shall include cutting of grooves and filling them with poly sulphide sealant and baker rod.
Cement concrete pavement/ flooring/ for additional floor screed with M10 grade, including spreading as per gradient, levelling and finishing complete as directed by Engineer in charge.
Floor bedding : Providing and laying cement mortar 1:4 (1 cement : 4 coarse sand) for additional thickness below flooring item required for gradient and as per drawing and as directed by engineer in charge including spreading as per gradient, levelling, finishing, curing etc complete as directed by Engineer in charge.
Providing and laying white cement mortar 1:3:2 (1 white cement : 3 coarse sand : 2 marble dust) for additional thickness below marble flooring and behind white marble wall dado/ lining work (if required) as directed by engineer in charge including spreading as per gradient, levelling, finishing, curing etc complete as directed by Engineer in charge.
Vinyl flooring Providing and fixing vinyl flooring of 2mm thick 100% recycled PVC flexible homogeneous and monolayer in construction of weight minimum 2600 g/m2 and should be manufactured by calendering and pressing process of size 2mt x 20mt in approved pattern, to ensure a dense, smooth surface and non-directional design, color dyed as a raw mixture to ensure even color throughout the thickness and its surface should be densely compacted for improving wear and ease of maintenance with Anti-bacterial and Fungicidal properties. The flooring shall incorporate a specially formulated Polyurethane reinforcement (PUR+) Iodine stain free - UV Protected (No bacterial growth). Surface Treatment having wear resistance of ≤ 4.0mm3 as per EN 660.2 and Wear Group T as per EN-649 and should have a residual indentation of −0.03mm confirming to EN-433. The laid flooring shall confirm the fire rating B1 class as per EN 13501-1. It should have low VOC contain as TVOC after 28 days <10 µg/m3 as per ISO 16000-6. The floor finish should terminate at the room perimeter passing over a concealed cove former and continuing up the wall for 100mm. The joints in the flooring should be sealed by using a PVC welding bar of matching colour to be supplied by the manufacturer, using a hot air gun for fusion of welding bar with flooring. The laid flooring shall confirm fire rating Bfl-s1 class as per EN 13501-1. The vinyl sheet shall be laid on existing leveled surface and fixed with water based adhesive of approved make as per manufacturer’s specification etc complete as per direction and the entire satisfaction of Engineer-in-charge. The rate shall include cost of surface preparation, all materials, wastages and labour charges for working at all levels, leads and heights. Sample and mock-up shall be approved before execution.
Providing and applying anti-skid car park flooring system of approved make and shade (single/ combination of shade and texture) for parking, drive way and ramp area to sound, moisture free concrete after proper surface preparation to make it free from loose concrete, dust, dirt, laitance, oil and grease etc., carry out repairs of cracks and dents on the floor (if any) using suitable epoxy putty or repair mortar, application and epoxy penetrating primer with blind primer coat with anti-slip grains as per manufacturer specification. After primer application, Intermediate coat of PU base car deck flooring system having Elongation of >300 % (ASTM D412), Tensile Strength – 4 N/mm2 (ASTM D 412), Tear Resistance (ASTM D624) – 15 N/mm, coverage @ 0.2-0.5 ltr/m2 using short hair lambs wool roller and finally application of wear course of PU car deck system as per manufacturer specification. After final coat, marking for lane, direction, parking allocation, symbols etc shall be carried out as per manufacturer specification and as per required. Rate shall be inclusive of surface preparation, crack repairs, primer, two coat with anti slip grains and lane marking, symbols, text, numbers as per car parking layout etc for all floor all level. Contractor shall submit shop drawing and get approved by Engineer in charge before application.
Providing roughened strip 2.5 cm wide to form antiskid surface on treads of stairs in any type of stone including forming straight deep curved gishi (groove), 6 mm wide & 4 mm deep on two sides of the roughened strip, etching/ blasting/ hammering/ chiselling between two groove, polishing the edges, sides and bottom of gishi etc. complete as per sample approved. Only one time length of tread of stair shall be measured for payment. All process for roughen strip shall be done at process unit/ work shop only.
Tile Trim Providing and fixing aluminium tile trim of approved make, shape, finish (minimum 20 micron anodized finish or min 50 mm thick polyester powder coating of approved shade) of size 8mm to 10mm with approximate 20mm to 25mm wide flange (with hole for screwing) for fixing with wall and 1.5 mm thickness including cutting in required length and fixing with adhesive and/ or SS 304 grade screw etc complete for all floor, all level as directed by Engineer In-charge. Sample shall be got approved before execution. Shade shall be matched with tile or as per approved by Engineer-in Charge. Rate shall be inclusive of adhesive screws etc.
Tile Trim Providing and fixing aluminium tile trim of approved make, shape, finish (minimum 20 micron anodized finish or min 50 mm thick polyester powder coating of approved shade) of size upto 20mm with approximate 20mm to 25mm wide flange (with hole for screwing) for fixing with wall and 1.5 mm thickness including cutting in required length and fixing with adhesive and/ or SS 304 grade screw etc complete for all floor, all level as directed by Engineer In-charge. Sample shall be got approved before execution. Shade shall be matched with tile or as per approved by Engineer-in Charge. Rate shall be inclusive of adhesive screws etc.
Threshold Providing and fixing aluminium threshold of approved make, shape, finish (minimum 20 micron anodized finish of approved shade or min 50 mm thick polyester powder coating) of approximate size 10mm with 1.5mm thick between two different flooring (compatible with Vinayle/wooden/stone/tile flooring) including cutting in required length and fixing with adhesive, double side tape and/or SS 304 grade screw etc complete for all floor, all level as directed by Engineer In-charge. Sample shall be got approved by Engineer-in Charge before execution. Rate shall be inclusive of adhesive, screws, double side tape etc.
Providing and fixing 18 mm thick gang saw cut, both side polished, premoulded and pre-polished, machine cut Granite of any size, any shape, any shade for urinal partition and similar locations of required size, approved shade, colour and texture fixed with cement mortar 1:2 (1 cement : 2 coarse sand), joints treated with white cement, mixed with matching pigment, including curing, rounded edges, champhering and edge mirror polishing etc. complete at all levels as directed by Engineer-in-charge. single side plan area of urinal partition shall be measured for payment. If required, metal framing/ supports shall be paid in relevant tender items.
Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and pre-polished, machine cut Granite of any size, any shape, any shade for vanity/ wash basin counters, and fascias and similar locations of required size, approved shade, colour and texture laid with 20 mm thick cement mortar 1:2 (1 cement : 2 coarse sand) where required, joints treated with white cement, mixed with matching pigment, epoxy touch ups, including all making holes & cutouts for SS sink, wash basin, Piller tap/ Bib tap, rubbing, curing, rounded edges, champhering and polishing to edges to give high gloss finish etc. complete at all levels as directed by Engineer-in-charge. All exposed edges of granite shall be rounded in uniform thickness and polished. Plan area of counter and elevation area of facia shall be measured for payment. If required, metal framing/ supports shall be paid in relevant tender items.
Sandwich Platform Providing & laying sandwich platform comprising of a) Sandwich of 18 mm thick single side polish Granite of approved size, shade and sample on top and 30 mm thick polished kota in bottom with 25mm thick cement mortar (1:4) in between b) At centre vertical sandwich supports of 30 mm thick two kota stone on sides and 20mm CM (1:4) in between and at both end walls vertical supports of 18 mm thick double side granite. c) 75 mm raised platform at bottom with kota on top in CM (1:4) at bottom, and 50mm high kota stone skirting as per design and approved sample. The rate includes rounding, champhering and mirror polishing of edges, facias of granite, MS support including necessary bonding adhesive (if required). Rate shall be also inclusive of all making holes & cutouts for SS sink, wash basin, Piller tap/ Bib tap etc. as directed by engineer in charge but fixtures shall be paid in relevant tender items.Only plan area of platform shall be measured for payment
Wall Guard at bottom level Providing and fixing polyamide vinyl wall guard having vinyl snap on cover (lead free) and rubber spacer of 2mm thickness each to absorb the shocks and aluminum retainer of 2mm thickness that shall be fabricated from 6063-T5 aluminum. Dimensions to be of 100mm height x 20mm depth. The polyamide vinyl profile shall resist an impact of 30.2 ft-lbs/inch as per ASTM D-256-90b and shall not support fungal or bacterial growth. Polyamide Vinyl Snap on cover of 2mm thickness shall be extruded from chemical and stain resistant poly vinyl chloride with the addition of impact modifiers. The system shall also conform to class B1 fire rating, chemical and stain resistance. Rate shall be inclusive of all required accessories like corner piece etc complete
Wall Guard at upper level Providing and fixing handrail of having vinyl snapon cover (lead free) of 2mm thickness and aluminum retainer of 2mm thickness that shall be fabricated from 6063-T5 aluminum. Dimensions to be of 145mm height x 85mm width and 38 mm gripping diameter. The system shall resist an impact of 45.5 ft-lbs as per ASTM F-476-84. The polyamide vinyl shall not support fungal or bacterial growth. Polyamide Vinyl Snap on cover of .080" (2mm) thickness shall be extruded from chemical and stain resistant polyvinyl chloride with the addition of impact modifiers. The system shall also conform to class B1 fire rating, chemical and stain resistance.
Corner Guard (internal area) Providing and fixing corner guard having vinyl snap-on cover (lead free) of 2mm thickness and aluminum retainer of minimum 1.4mm thickness that shall be fabricated from 6063-T5 aluminum. Dimensions to be of 76mm x 76mm wings and 90 degrees angle. The polyamide vinyl profile shall resist an impact of 30.2 ft-lbs/inch as per ASTM D-256-90b and shall not support fungal or bacterial growth. Polyamide Vinyl Snap on cover of .080" (2mm) thickness shall be extruded from chemical and stain resistant polyvinyl chloride with the addition of impact modifiers. The system shall also conform to class B1 fire rating ,chemical and stain resistance.
Note - 1. All adhesives, sealants & paint shall be with low VOC with acceptable VOC content as per GRIHA requirements and lead free. 2. Contractor shall prepare shop drawing base on concept design/ drawing for any type of fabrication work and get approved. Contractor shall prepare mock-up/ prototype (as suggested) as per approved shop drawing for approval. Work shall be carried out as per approved shop drawing, approved mock-up/ prototype and as suggested by Engineer in charge. 3. Rate shall be for all floor, all level all height. 4. The rate shall include cost of all types of fasteners (ETA approved) to be used for fixing. 5. Structural stability shall be responsibility of contractor for all kind of metal work. 6. All elements shall be factory fabricated and finished, only final finishing to be made on site with all precautions. 7. Contractor shall coordinate all services work (cut-outs and provisions) in metal work. All cut-out and services provisions shall be finished at factory/ work shop. 8. contractor shall provide PVC/ nylon seprator, where two different metals connect to avoid galvanic reactions. METAL WORK Providing, fabricating, assembling, hoisting, erecting and fixing in position structural steel work at all heights/ all levels/ all shapes & sizes by any means with all leads & lifts using any type of MS section like rolled steel sections, hollow sections, plates, chequered plates, bar, sheet, rod, threaded bolt etc. all confirming to latest relevant IS codes for the metal elements i.e. railings, signage pole, gates, screen wall, roofing structure, truss, commercial pole, grills, bracings, foundation plate & bolt, platforms, brackets, fencing pole, supports for false ceiling work, trap door, any type of services and medical electrical elements etc. including straightening, cutting, bending, bolting and welding the members all as per structural drawings and as per detailed specifications (for materials & workmanship) including profile cutting, smooth grinding, machining of edges/ faces, necessary welding (electric arc welding) for required weld lengths and sizes, machine drilling of holes for joining/ anchoring; necessary arrangements of templates to keep the foundation bolts in position dry sanding, degreasing (wet cleaning) & preparation of rust-free surface manually or mechanically, metal putty to make the surface even and smooth, necessary scaffolding/ staging, anchor fasteners for fixing etc complete. Contractor shop/ fabrication prepare shop drawing and get approved. The fabrication work shall start only after approval of the fabrication drawings. Fabrication shall be in a perfect Architectural workmanship manner and as provided in Section V & VI of IS 800 & IS 7215. The rate shall include for applying (on all surfaces of MS member) two or more coats PU paint (DFT min 40 micron per coat) of approved make and shade over two coat (DFT min 50 micron per coat) of anti corrosive epoxy base primer, as per approved make and manufacturer's specification, anchor fastener and other required acessories etc all complete.
SS modular system railing Providing and fixing stainless steel (Grade 304) Railing and baluster modular system of approved make stair railing, hand rail, bump rail, guard rail or similar with knock down system in liner or curveliner shape made of Hollow or solid section i.e. tubes, square, flat, plates, bar etc with base plate, cover cap, finishing accessories, in-filled holding brackets, fixing accessories etc. for any type of design, shape (plain/ curvature), size and finish as per drawing. Railing shall be top mounted or side/ wall mounted. Railing shall be fixed with SS 304 grade anchor fastener of required size and as per fixing position of approved make. Any kind of welding or fabrication shall not be allowed on site. Sample shall be approved before execution. Contractor shall submit the shop drawing base on concept drawing and as per site measurement. As per approved shop drawing, contractor shall arrange mock up of railing system (2 or 3 no) in required length as directed by Engineer in charge. Contractor shall protect railing system up till handling over the project. Rate shall be inclusive of fixing accessories and all type fasteners but for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.
Providing and fixing aluminum work for framing of cladding work, wall panelling, partition, false ceiling work, or any other interior work with extruded any type of built up sections/ bracket/ other sections of approved make conforming to IS: 733 and IS: 1285. All aluminum member shall be anodized finished of approved make and shade (anodized transparent or dyed to required shade according to IS: 1868, Minimum anodic coating of grade AC 15). The aluminum frame shall be fixed with adjustable aluminum member and SS 316 nuts, bolts and washer. The aluminum quality shall be as per grade 6063 T6 and BS 1474. Framing system shall be as per approved shop drawing. Framing shall be fixed with RCC/ masonry work or other metal work with required size and type of anchor fastener of approved make. Aluminum sections shall be smooth, rust free, straight, metered and jointed mechanically wherever required. Rate shall be inclusive of all of all heights & levels, all kind of anchor fastener, screw, accessories and consumable. Only weight (by theoretical means) of installed aluminum member for cladding, wall panelling, ceiling or any type interior work shall be paid in Kg. Contractor shall prepare shop drawing (which is part of cladding/ panelling/ ceiling work etc.) for approval before execution.
Note : 1) Contractor shall prepare shop drawing based on concept drawing/ design for all false ceiling, panelling and partition work co-ordinate with services and get approved by Engineer in charge before execution of work. 2) All veneer and wood shall be FSC (Forest Stewardship Council) & Green Guard Certified. 3) All Manufactured products shall be with at least 5% recycled content. 4) Sample of all loose material and mock-up shall be approved by Engineer in charge. 5) Any wood / wood base material / plywood / MDF Board shall be treated with antitermite treatment as per relevant IS before use. Rates are inclusive of anti-termite treatment of all such members. 6) Contractor shall co-ordinate for all services in wall panelling/ ceiling work i.e. making openings for light fittings, switch board, electrical points, grills, diffusers, cut-outs for any services, provision of addition framing member for strengthen, making good as per satisfaction of Engineer in charge. 7) All elements shall be factory fabricated and finished, only final finishing to be made on site with all precautions. 8) Contractor shall cordinate all services work (cutouts and provisions) in all type of wall panelling, false ceiling, partition, pelmet and other interior work. All cutout and services provisions shall be finished at factory/ work shop. 9)Rate shall be for all floor, all level all height for all elements in any shape, any size. CEILING & WALL PANELLING WORK Providing and fixing 9 mm thick ply BWP grade (IS – 710) of approved make having, density minimum 600 Kg/m3, emission levels as per E-1 formaldehyde, for any type of door-window and interior work (i.e. wall cladding, ceiling work, on flush door shutter, pelmet,access panel or similar location) in any design, any pattern, any shape with necessary screws, fastners etc for all height all level etc complete as directed by Engineer-in-Charge. Rate shall be inclusive of 6mm thick peripherial beading of all around to ply (width of beading as per ply + finish surface) as per drawing along with necessary screw, nails etc. accesories. Veneer, laminate and any other finishes over ply surface shall be paid in relevant tender item.
Providing and fixing 12 mm thick ply BWP grade (IS – 710) of approved make having, density minimum 600 Kg/m3, emission levels as per E-1 formaldehyde, for any type of door-window and interior work (i.e. wall cladding, ceiling work, on flush door shutter, pelmet,access panel or similar location) in any design, any pattern, any shape with necessary screws, fastners etc for all height all level etc complete as directed by Engineer-in-Charge. Rate shall be inclusive of 6mm thick peripherial beading of all around to ply (width of beading as per ply + finish surface) as per drawing along with necessary screw, nails etc. accesories. Veneer, laminate and any other finishes over ply surface shall be paid in relevant tender item.
Providing and fixing 19 mm thick ply BWP grade (IS – 710) of approved make having, density minimum 600 Kg/m3, emission levels as per E-1 formaldehyde, for any type of door-window and interior work (i.e. wall cladding, ceiling work, on flush door shutter, pelmet,access panel or similar location) in any design, any pattern, any shape with necessary screws, fastners etc for all height all level etc complete as directed by Engineer-in-Charge. Rate shall be inclusive of 6mm thick peripherial beading of all around to ply (width of beading as per ply + finish surface) as per drawing along with necessary screw, nails etc. accesories. Veneer, laminate and any other finishes over ply surface shall be paid in relevant tender item.
Providing and fixing decorative high pressure 1.0 mm thick standard laminates (factory pressed with door shutter or plywood) in plain/ wood grain in gloss/ matt/ suede/ satin finish of approved make and shade with high density protective surface layer and reverse side of adhesive bonding quality conforming to IS : 2046 Type S, including cost of adhesive of approved quality. Laminate shall be applied on door shutter, wall panelling, ceiling, pelmet or any interior work in any design, any pattern, any shape, any size etc as per drawing. Sample shall be approved by Engineer-in-charge before execution.
Providing and fixing 4 mm thick one side decorative veneer (factory pressed with door shutter or plywood) conforming to IS: 1328 (type-1), for lining/ cladding/ ceiling work/ on flush door shutter/ pelmet or any interior work in any design, any pattern, any shape, any size etc as per drawing with necessary screws, adhesive including priming coat on unexposed surface.Veneer shall be applied with use of adhesive of approved quality & make. The veneer shall have minimum 0.3 mm thick slice (of natural veneer) and back up ply BWP grade (IS – 710) with density 650 Kg/Cum. Veneer shall be fixed with or without groove as per drawing. Sample shall be approved by Engineer-in-charge.
b) Perforated Gypsum having micro perforation Fully Perforated Gypsum Plaster Board of size 1200 x 2400x12.5 mm having approx. 15% perforated area with perforation size and pattern as approved by the Engineerin- charge and as per manufacturer's specification, with all 4 side tapered and backed by acoustical tissue with NRC value not less than 0.60
Aluminum Open Cell ceiling Providing and fixing open/ linear cell ceiling of approved make and manufactured from Aluminium minimum 0.35mm polyester powder coated/ PVDF colour coated coils of approved shade. The assembled cell ceiling panels shall be in size of 600 x 600mm/ 600 x 1200mm comprising blade having minimum 10mm in width and minimum 35mm in depth for open cell size 75mm to 100mm x 75mm to 100mm. The tile shall be laid on Grid system with 15 mm wide T - section flanges colour (matching to tile colour) having double stroke rotary stitching on all T sections i.e. the main Runner, 1200 mm & 600 mm cross tees with a web height of 38mm (all sections). OR The assembled cell ceiling panels shall be clipped into U carriers, coated in black enamelled finished at 1200mm c/c. Wire clips shall hold the cell ceiling panels into the U carriers. Additional Cross bracings shall be installed at max 3000mm distance. The whole ceiling shall be suspended by M6 threaded rods installed at 1200mm c.c. All panel modules must be fully hinge-able through wire clips. The open cell ceiling along with suspension system used together shall carry a 10 year warranty against manufacturing defect and manufacturer shall provide a warranty certificate. Contractor shall prepare shop drawing with coordination of all services and opening/ excess. Sample, shop drawing and mock up shall be approved by Engineer in charge. Contractor shall made all services provisions for providing light, diffusers, AC grill, fire alarm, sprinkler system etc at factory and machine cut only as per manufacturer's recomendation. Out to out plan area of aluminium open cell ceiling system shall be considered for payment without any deductions of cell of ceiling plank, for lights, diffusers, columns etc. The rate includes all above material and labour as per directions of Engineer-in-Charge
Providing and Fixing 15 mm thick densified tegular edged eco friendly light weight calcium silicate false ceiling tiles of approved texture of size 595 x 595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanised steel sections (galvanising @ 120 grams per sqm including both side) consisting of main ‘T’ runner suitably spaced at joints to get required length and of size 24x38 mm made from 0.33 mm thick (minimum) sheet, spaced 1200 mm centre to centre, and cross “T” of size 24x28 mm made out of 0.33 mm (Minimum) sheet, 1200 mm long spaced between main’T’ at 600 mm centre to centre to form a grid of 1200x600 mm and secondary cross ‘T’ of length 600 mm and size 24 x28 mm made of 0.33 mm thick (Minimum) sheet to be inter locked at middle of the 1200x 600 mm panel to from grid of size 600x600 mm, resting on periphery walls /partitions on a Perimeter wall angle pre-coated steel of size(24x24X3000 mm made of 0.40 mm thick (minimum) sheet with the help of rawl plugs at 450 mm centre to centre with 25 mm long dry wall screws @ 230 mm interval and laying 15 mm thick densified edges calicum silicate ceiling tiles of approved texture in the grid, including, cutting/ making opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc., wherever required. Main ‘T’ runners to be suspended from ceiling using G.I. slotted cleats of size 25x35x1.6 mm fixed to ceiling with 12.5 mm dia of size 85 x 30 x 0.8 mm, spaced at 1200 mm centre to centre along main ‘T’, bottom exposed with 24 mm of all Tsections shall be pre-painted with polyster baked paint, for all heights, as per specifications, drawings and as directed by Engineer-in-Charge.
Providing & fixing suspended vertical linear baffle ceiling for all height made out of min 0.6mm powder coated roll formed aluminium U shape baffle in Aluminium alloy grade AA 3105. The baffle blade shall be in size of 150 x 50 x minimum 3000mm (except at openable portion and residue) in powder coated to Plain finish of approved shade with centre to centre spacing 100 to 150 mm. The baffle shall be electro statically polyester powder coated to a coating thickness of 60-80 micron. The baffle blade shall be suspended using slotted U-profile of required size and length (as per baffle length) having slots, torsion spring, baffle hanger, splice, threaded rod etc. Longer lengths of baffle to be connected by baffle Joiner and the ends to be fixed with end caps. Each hanger to be secured into position by inserting the locking clip or other approved method. For opening of baffle, locking clip or torsion spring shall be provided as per manufacturer's specification. Baffles blades are to be connected at ends with baffle Joiner, which are inserted into the top and bottom slots of the Baffle closed profile for alignment only. Total suspension system and installation method shall be approved by Engineer-in-charge. Installation shall be carried out by approved installer and as per manufacturer recommended procedure. The Baffle along with suspension system used together shall carry a 10 year warranty against manufacturing defect and manufacturer shall provide a warranty certificate. The supply shall be backed by a Manufacturing Test Certificate. Contractor shall prepare shop drawing with coordination of all services and opening/ excess of baffle. Sample, shop drawing and mock up shall be approved by Engineer-in-charge. Measurements shall be wall to wall without any deductions for lights, diffusers, columns etc. Nothing extra shall be paid for making provisions for providing light, diffusers, AC grill, fire alarm, sprinkler system and other such fittings.
WPC board Ceiling with paint finish Providing and fixing 12mm thick WPC board false ceiling with aluminium framing system along the perimeter of existing wall/ partition with the help of screws at 600mm centers. False ceiling shall be partly openable and parlty fixed. For fixed part, WPC board shall be fixed on framing system with suitable screw and joint filling material for all floors/ any height/ any levels as directed by Engineer in Charge. Work shall be carried out as per approved sample, Mock-up and shop drawing including all material and labour. Actual area of ceiling shall be measured for payment.
Providing and fixing 8 mm thick plain Cement fiber board as per IS: 14862 (High pressure steam cured) of approved make for partition (required for HVAC and other services work), and other similar location etc. fixed on existing frame work with suitable screws etc. complete for all height, all level as directed by engineer in charge. Installed area of cement fiber board shall be measured for payment. (frame work to be paid separately in relevant tender item).
Providing and fixing ready made powder coated Access panel/ trap door of approved make of required size as per drawing including aluminum outer and inner frame, door, push latch, safety cable, removable hinge, intermediate and perimeter channel etc for all floor, all height etc complete as directed by engineer in charge. Tile/board of access panel shall be matched with false ceiling board. Contractor shall submit the technical data sheet of product regarding loading capacity to engineer in charge. Loose and fixed sample/ mock-up of access panel shall be approved by engineer in charge. Contractor shall prepare shop drawing with coordination of all services and opening/ excess based on concept design including fixing arrangement, services and prepare mock-up of required area. As per approved shop drawing and mock-up, contractor shall start the work. Sample, shop drawing and mock up shall be approved by Engineer in charge. Contractor shall provide and execute all services provisions, fixing arrangement for providing light, diffusers, AC grill, fire alarm, sprinkler system etc at factory and machine cut only as per manufacturer's recomendation. Access panel system shall be fixed on any type of surface i.e. RCC, metal work etc) with required capacity of anchorage as per manufacturer's specification. Contractor shall provide fixing arrangement with adjoining false ceiling and bottom of slab. Stability of access panel system shall be responsibility of contractor. Out to out dimension including frame shall be measured for payment in Sqm.
Roofing Work Providing and fixing pre-coated galvanized iron profile sheets at all level (any size, any color, any shape and pitch of corrugation as approved by Engineer-in-charge)as per approved make with total coated thickness 0.50 mm (base metal of minimum 0.45 mm thickness with total coating thickness of 0.05 mm) with zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length up to 12 metre or as desired by Engineer-in-charge. The sheet shall be fixed using self drilling/self tapping screws of size (5.5 x 55 mm) with EPDM seal, complete up to any pitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required. contractor shall necessary prepare shop drawings with necessary structural detail and services coordination for approval of engineer incharge befor execution of work.
Providing and fixing pre-coated galvanized steel sheet roofing accessories i.e. Gutter (600 mm over all girth) at all level as per aproved make and any size, any color, any shapewith total coated thickness 0.50 mm (base metal of minimum 0.45 mm thickness with total coating thickness of 0.05 mm) with Zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns using self drilling/ self tapping screws complete. contractor shall necessary prepare shop drawings with necessary structural detail and services coordination for approval of engineer incharge befor execution of work.
Providing and fixing precoated galvanised steel sheet roofing accessories i.e. ridge - flashing at all level as per aproved make and any size, any color, any shape with total coated thickness 0.50mm (base metal of minimum 0.45mm thickness with total coating thickness of 0.05mm) with Zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns using self drilling/ self tapping screws complete. contractor shall necessary prepare shop drawings with necessary structural detail and services coordination for approval of engineer incharge befor execution of work.
Providing and fixing 2 hr fire rated 122mm thick double layered dry wall partition system of approved make which includes (on both faces/ elevations) inner layer of tapered edge minimum 12.5mm thick Fire Resistant Gypsum Board having density minimum 790 kg/m3 (conforming to IS 2095 Part 1 : 2011/ EN520::2004, TYPE-F/ ASTM C1396, TYPE X) and outer layer of tapered edge 12.5mm thick calcium sulphate dihydrate encased in high gsm paper liners with glass fibers and other additives for enhanced the fire, acoustics and impact performance, third party EPD Verified as per ISO 14025, having minimum density 900 kg/m3, with maximum allowable point load on single board 25 kg to 30kg without any ply backing, complies with BS EN 520:2004 – Type A, F, D, R, I, Thermal Conductivity: 0.24 w/mºK, Thermal resistance: 0.05 m2K/w. Framing system - GI framing system consists of Close stud/ C stud of size approximate 70 x34x36x 0.5mm confirming to IS 513 having Y/S-minimum 230 Mpa, and Finish - AZ150 (IS 15961). Stud shall be placed at 600mm c/c in 72x32x32x0.5mm (approx.) floor channel and 72X32x32x0.5 mm ceiling channel. Floor & Ceiling channel is anchored to the floor & ceiling using zinc coated Rawl plug of size Ø8x45mm and having Pull out Load -7.5 kN/ anchor fasteners of required capacity as per manufacturer's specification at 600mm c/c. Floor channel to be wrapped with 70µ Self Adhesive LDPE moisture barrier film to further improve corrosion resistance performance. Noggin channel of 70x40x0.5mm has to be provided at the horizontal joints of the two boards and top of the board in case the top is not going up to the ceiling channel. All frame members shall be connected to each other by using metal screws. 50mm Rock wool slab of density 24kg/m³ shall be placed in metal framework. Glass wool holding clip should be used to hold Glass wool slab in its position. Gypsum boards shall be fixed with drywall screws of 25mm/ 35mm at minimum spacing of 300mm at centre and 150mm at periphery. Boards shall be jointed and finished so as to have a flush look which includes filling and finishing with Jointing compound, Joint Paper tape, angle beads at corners. The junction of the partition with masonry/ RCC & all penetration through the partition has to be treated with fire and acoustic sealant of approved make. In case surface/member is not available abutting the door syustem for fixing, contractor shall design and propose, a sub-system/MS frame for fixing arrangement as per manufacturer's recommendation. Contractor shall prepare shop drawing based on concept drawing including fixing arrangement, services and prepare mock-up of required area. As per approved shop drawing and mock-up, contractor shall start the work. Contractor shall furnish certification of entire system for STC 48 and 120 minutes Fire rating. Dry wall system shall be fixed on any type of surface i.e. masonry, RCC, dry wall system, metal work etc) with required capacity of anchorage as per manufacturer's specification. Stability of door and partition system shall be responsibility of contractor. Contractor shall provide fixing arrangement for all elements, which to be fixed in dry wall system. Rate shall be included for the cost of making openings for light fittings, switch board, any other services cut-outs made with frame of perimeter member suitably fixed etc complete for all level all height and as directed by the Engineer in Charge but excluding the cost of painting work. All Openings cut outs & periphery shall be treated with Fire & acoustical sealant. Contractor shall be cut first layer of gypsum board for provision of skirting and, additional board shall be provide and top layer to be cut properly as per skirting detail. At the location of door frame in dry wall system, wooden member shall be fixed of required size and as per manufacturer's specification. Skirting and wooden work shall be paid in relevant tender items. Horizontal framing member shall be provided as per architectural requirement and as suggested by Engineer in charge. Out to out area of dry wall elevation on one side only shall be measured for payment after deducting for openings for doors/windows and service cut-outs of size more than 0.36 sqm etc, complete for all floors, all height. Any additional members, support members, fasteners, fixing details etc required to provided in designed dry wall system approved by Engineer-in-charge, shall also include in the rate of this item and nothing extra shall be payable for the same.
Providing and installing prepainted "Sandwich panels" for roofing, as per approved make with any size, color, shape etc. Panel skins shall be PPGL type, 35/250 profile sheet of SMP coated of 0.5 mm thickness (TCT) for external and SMP coated sheet of 0.50 mm thickness (TCT), light profiled, at the bottom with guard film on both sides. The insulation core shall be rigid PIR insulation of minimum density 40 Kgs/Cum and thickness of 50 mm minimum at the valley. The rate to include the cost of all necessary accessories like fasteners, washers, stitch rivets, laps sealant and fillers, gable and eaves flashing, using the same material as the panel skins, sealing laps with sealant and exposed ends protected, as directed by Engineer-in-charge. Approved color and brand to be procured. actual installed area without considering wastage shall be measured for payment. contractor shall necessary prepare shop drawings with necessary structural detail and services coordination for approval of engineer incharge befor execution of work. sample shall be approved before mass execution.
Providing and installing prepainted flat ridge sheet as per approved make with any size, color, shape etc with SMP coated of 0.5 mm thickness (TCT), of girth up to 610mm. The sheet shall be fully aligned with the roof slope. The rate to include the cost of all necessary accessories like fasteners, washers, stitch rivets, laps sealant and fillers, as directed by Engineer-in-charge. Approved color and brand to be procured. actual installed area without considering wastage shall be measured for payment.sample shall be approved before mass execution. contractor shall necessary prepare shop drawings with necessary structural detail and services coordination for approval of engineer incharge befor execution of work.
Note:- 1) All adhesives, sealants & paint shall be water based, with low VOC with acceptable VOC content as per Green Building Norms requirements and lead free. 2) Paint shall be applied after thoroughly brushing the surfaces, free from mortar dropping and other foreign matter, preparing the surface even and sand papered smooth etc, after applying every coat of putty and primer complete. 3) Contractor shall furnish warranty paper, wherever applicable. 4) If necessary more coats shall be applied till the surface presents a uniform appearance without any extra cost. 5) Paint shall be applied with any means (i.e. brush, roller, spray etc) 6) Contractor shall prepare sample of minimum three shades as suggested by engineer in charge for approval. 7) The rate shall be applicable for all floor, all level, all height by any means of scaffolding. PAINT WORK Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the any surface to prepare the surface even and smooth complete.
Applying priming coats with primer of approved brand and manufacture, having low VOC (Volatile Organic Compound) content : Modified acrylic, water-based alkali resistant primer with having low VOC
Providing and applying premium acrylic emulsion paint (superior quality) of interior grade Two coats of interior grade premium acrylic emulsion paint of approved make and shade with highly washable, Anti fungal, anti bacterial, scratch resistant and scrub resistance property, having VOC (Volatile Organic Compound) content less than 50 grams/ litre of approved brand and manufacture, on wall/ ceiling/ false ceiling/ partition etc including applying additional coats wherever required to achieve even shade and colour.
Finishing walls with 100% Acrylic Smooth exterior paint with exterior primer for New work (Two or more coat including priming coat of exterior primer as per manufacturer's specification) of approved make and shade - Product having minimum 7 years warranty (Two or more coat applied @ 1.67 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm), having VOC (Volatile Organic Compound) content less than 50 grams/ litre of required shade.
Providing and applying water based, low VOC, breathable and biodegradable, water, oil and stain repellent transparent fluorocarbon based coating with anti graffiti property on natural stone cladding (suitable product according to sand stone/ marble/ granite) and exposed RCC surface of approved make having fluoro carbon based nanotechnology at all heights & leads and wherever instructed by Engineer-In-Charge. The treatment shall be in two coats wet-on-wet or as recommended by approved manufacturer including preparation of surfaces by cleaning, curing, protecting, independent double legged scaffolding etc complete. The rate includes the cost of all materials, its application by specialized applicators by spray coating with airless sprayer, cleaning the substrate of all laitance, construction dust, contaminants, double scaffolding, labour etc., all complete and at all levels, leads and heights as per particular specification & directions of Engineer-in-Charge. Guarantee Bond in the prescribed proforma shall be executed by the contractor for the satisfactory performance of the application for 10 years. The look and feel of the natural stone surface shall not be affected by coating.
PU polish Providing and applying exterior grade water base Poly urethane (PU) clear matt finish/ glossy finish/ semi gloss finish polish of approved make and shade for external/ internal wooden & veneered surfaces. Polish work shall be carried out as following: 1) Surface preparation with sand papering with different grade of sand paper up to satisfaction of Engineer-in-Charge. 2) Base coat application with compatible wooden primer 3) Stainer coat application of approved shade (for polish with shade) 4) Minimum Three subsequent coat of PU polish followed by sand papering with fine sand paper. Polish application shall be for all floor all level all height as per manufacturer's specification and as per drawing and as directed by Engineer in charge. Sample shall approved by Engineer-in-Charge.
Providing and applying external finish of average 2 to 2.5mm thick acrylic polymer based texture of approved make and pattern with standard tool and applicator as specified by manufacturer on exterior surfaces at all heights including scaffolding to give even shades including thoroughly brushing the surfaces free from mortar dropping and other foreign matter and sand paper smoothed etc. complete as per the manufacture specifications and up to the satisfaction of Engineer in-charge/ Architect. The rate includes making of grooves, pattas and finishing as directed by Architect/ EIC. Paint shall be measured and paid in separate tender item. (Item should be executed by approved applicator only.)
Construction of granular sub-base (GSB) by providing close graded Material conforming to required grade with required size of aggregate (respective as per grade) having CBR Value as per respective grade specifications, mixing in a mechanical mix plant at OMC, carriage of mixed material by tipper to work site, for all leads & lifts, spreading in uniform layers of specified thickness with motor grader on prepared surface and compacting with vibratory power roller to achieve the desired density, complete as per MoRTH clause 401 and as directed by Engineer in charge.
Providing, laying, spreading and compacting graded stone aggregates of required sizes to wet mix macadam (WMM) in required thickness including premixing material with water at OMC in mechanical mix plant, carriage of mix material by tippers to site for all lead and lift, laying in uniform layers with mechanical paver finisher in sub base/ base course on well prepared surface and compacting with vibratory roller of required capacity to achieve the desired density etc complete as per MoRTH clause 406 and as directed by Engineer in charge.
Bituminous Concrete (Asphaltic Concrete) - Providing and laying bituminous concrete with 100-120 TPH batch type hot mix plant of grade VG30 producing an average output of 75 tonnes per hour using crushed aggregates of specified grading, premixed with bituminous binder @ 5.5 per cent of mix and filler, transporting the hot mix to work site, laying with a hydrostatic paver finisher with sensor control to the required grade, level and alignment, rolling with smooth wheeled, vibratory and tandem rollers to achieve the desired compaction as per related MORTH specification clause No. i.e. 507, 509 etc. as directed by Engineer in charge.
Primer Coat - Providing and applying primer coat with bitumen emulsion on prepared surface of granular base including clearing of road surface and spraying primer at the rate of 0.60 kg/sqm using mechanical means.
Tack Coat - Providing and applying tack coat with bitumen emulsion using emulsion pressure distributor at the rate of 0.20 kg per sqm on the prepared bituminous/granular surface cleaned with mechanical broom.
Providing and applying 2.5 mm thick Road Marking with hot applied thermoplastic paint (retro reflective) or graphic/ letter/ arrows etc of specified shade/ colour using hot thermoplastic material by fully/ semi automatic thermoplastic paint applicator machine fitted with profile shoe, glass beads dispenser, propane tank heater and profile shoe heater, driven by experienced operator on concrete/ tar road surface including cost of material, labour, T&P, cleaning the road surface of all dirt, seals, oil, grease and foreign material etc. complete as per direction of Engineer-in-charge and accordance with applicable specifications.
Asphalt Painting Providing and laying Asphalt painting on B.T. surface with bitumen grade 60/70 (VG-30) @ rate of 5 kg/ 10Sqm by Mechanical sprayer and spreading the stone dust on prepared surface at the rate of 0.03 cum/ 10Sqm and rolling with smooth wheeled and pneumatic roller and brushing etc. comp.
External Granite Paving Providing and laying textured finish Granite stone flooring (stone of required size, shape, of approved type, shade and finish) for driveway, plaza, tread of stair, coping with even thickness at exposed edges or similar, over 40 mm (average) thick base of cement mortar 1:4 (1 cement : 4 sand), side buttered with cement mortar 1:2 (1 cement : 2 sand) including provision of groove of minimum 5mm size, admixed with pigment to match the shade of stone and pointing with same mortar. No mortar is to be visible on the surface. Exposed edge of stone shall be with rounded corner treatment in even thickness and finished same as slab finish as per drawing and as approved and directed by Engineer in charge. Granite shall be used in single possible length for staircase trade. A) 30 mm thick textured finish Granite stone flooring
Providing and laying at or near ground level factory made kerb stone, road soulder, dustbin base, precast concrete block for base of any land scape elements of M-25 grade cement concrete of any shape, any size in position to the required line, level and curvature, jointed with cement mortar 1:3 (1 cement: 3 coarse sand)/ ready mix mortar, including making joints with or without grooves (thickness of joints except at sharp curve shall not to more than 5mm), including making drainage opening wherever required complete etc. as per direction of Engineer-in-charge. Precast elements shall be approved by Engineer-in-charge. Outer most dimensions of all three side of each piece of finished product (cube/ cuboid shape) shall be measured for payment. Contractor shall make provision in dustbin base for fixing dustbin metal structure as per design.
Paver Block - 80mm thk, M-40 Grade Providing and laying shot blasted finished, non- interlocking type, machine made, factory finished, square/ rectangle shape paver blocks of any sizes, any shade of approved make, having 80 mm thickness and minimum M-40 grade, for any areas as mentioned in the drawing. Including providing and laying 50 to 80 mm thick average bedding layer of coarse sand below paver block as per required grading and specification. Laid paver block shall be mechanically compacted. The work of the paving blocks shall be executed in line and level. Paver block shall be cut by mechanical means only, if required. Actual laid area shall be measured and paid without any wastage.
Paver Block - 60mm thk, M-35 Grade Providing and laying shot blasted finished, non- interlocking type, machine made, factory finished, square/ rectangle shape paver blocks of any sizes, any shade of approved make, having 60 mm thickness and minimum M-35 grade, for any areas as mentioned in the drawing. Including providing and laying 50 to 80 mm thick average bedding layer of coarse sand below paver block as per required grading and specification. Laid paver block shall be mechanically compacted. The work of the paving blocks shall be executed in line and level. Paver block shall be cut by mechanical means only, if required. Actual laid area shall be measured and paid without any wastage.
Providing and fixing Glow studs of size 100x20 mm made of heavy duty body shall be moulded ASA (Acrylic styrene Acryloretrite ) or HIP (High impact polystyrene) or ABS having electronically welded micro- prismatic lens with abrasion resistant coating as approved by Engineer in charge. The glow stud shall support a load of 13635 kg tested in accordance with ASTM D4280. The slope of retro- reflective surface shall be 35 (+/-5) degress to base .The reflective panels on both sides with at least 12 cm of reflective area up each side. The luminance intensity should be as per the specification and shall be tested as described in ASTM I: 809 as recommended in BS: 873 part 4 : 1973. The studs shall be fixed to the Road surface using the adhesive conforming to IS, as per procedure recommended by the manufacturer complete and as per direction of Engineer-in-charge.
Providing and erecting barricading (height upto 10.0 meter) at site; made out of MS panel/ profile sheet with MS angle/channel/hollow or other suitable sections as vertical posts/ horizontal members/ bracings/ end member covered with MS sheet/ profile sheet of required size and thickness including suitable foundation work as per approved structural design. The sheet shall be fixed with MS flat of required size by suitable welding/ riveting. Suitable arrangement shall be made to fix the barricading to avoid from overturning by providing expansion fasteners at both ends of required length. The work shall be executed as per direction of Engineer-in-charge which includes writing and painting, arrangement for traffic diversion such as traffic signals during construction at site for day and night, glow lamps, reflective signs, markings, flags, caution tape as directed by the Engineer-in-charge. The barricading provided shall be retained in position at site continuously i/c shifting of barricading from one location to another location as many times as required during the execution of the entire work till its completion. Rate includes its maintenance for damages, epoxy painting on steel members, all incidentals, labour materials, equipment and works required to execute the job. The barricading shall not be removed without prior approval of Engineer-in-charge. Elevation area of the metal Sheet Shall be measured for payment. Contractor shall design the barricading and foundation for specified height and desired wind load and got the same approved from the Engineer-in-charge before execution. The entire barricading, including the complete RCC foundation shall be dismantled and disposed off by the contractor after completion of the work as per direction of engineer in charge and site shall be levelled and made in original condition. Cost for steel frame work, M.S./ profile sheet, RCC foundation work, all ancillary works including it’s dismantling etc. is included in the rate and nothing extra shall be paid on any account. Contractor shall be responsible for stability and maintenance of barricading during entire construction period. All dismantled materials, like steel frame, profile sheet etc. shall be the property of contractor after completion of the work. (Note :- One-time measurement and payment shall be made for providing barricading work from the start to completion of work including temporary shifting (if required). The profile sheet shall be measured in sqm from bottom to top (elevation area) for payment. All barricading materials shall be the property of contractor after completion of the work).
Manhole cover Providing and fixing recessed manhole cover of approved make having capacity of 40 T made with corrosion resistant metal (i.e SS316 of approved) with clear opening upto 600mm x 600mm. Recessed manhole cover shall be with frame and double seal system. Recessed manhole cover shall be with four side lifting arrangement with minimal dimensions and two lifting keys. The cover shall be with proper drainage arrangement, if cover to be used for softscape/ lawn area. Recess depth shall be as per adjoining development material and as per approved shop drawing. The contractor shall submit a shop drawing of cover with test certificate. Cover shall be installed in proper level as per adjoining surfaces.
Providing and fixing 800mm dia Convex mirror made out of ABS/ PC plastic of approved make having viewing distance of 6.0 Mt. fixed on wall at basement ramp with wall bracket as per standard and as directed by Engineer in charge.
FRP Recessed Manhole cover Providing and fixing heavy duty double seal FRP recessed manhole cover with frame of 40MT capacity, in matching shade of surrounding pavement and design according to EN - 124:1994 of approved make and shade having clear opening size of 600mm x 600mm and recessed depth up to 80mm, with client's logo etc. complete for all lead and lift. Cover shall be with 4 number lifting key with proper lifting arrangement. Frame shall be embedded in concrete of required grade and top level of frame shall be flush with road level as per drawing and as directed by Engineer in charge. Sample shall be approved before execution.
Perforated Drain Cover Providing and placing in position 100 mm thick factory made machine batched & machine mixed perforated precast fair finish RCC covers on drains/ catch pit of footpath of various sizes, made of M-25 grade cement concrete for RCC work, including cost of mould/ formwork, reinforcement of 8 mm dia TMT bars of Fe 500 grade @ maximum 100mm c/c on both ways, neat cement punning on finished surface, properly encased on all edges with 1.6 mm thick, 100 mm wide MS sheet duly painted over priming coat , reinforcement to be welded at edges with MS sheet and providing 2 Nos. 12 mm dia bar for hooks etc i/c cost of cartage, all leads & lift, handling at site etc. all complete as per direction of Architect and Engineer-in-Charge. Contractor shall prepare sample and mock-up for approval from Architect and engineer in charge before execution.
Dustbin: Providing and fixing in position metal dustbin (readymade factory product) for external use, having capacity approximate 75 Litre each of approved make and as per approved sample. Dustbin shall be separate for dry and wet waste with logo of client. Both bin of dustbin shall have swing type arrangement for functioning of dustbin. Contractor shall prepare sample and mock-up for approval from Architect and engineer in charge before execution. (Basic rate - 21000/ set.)
Providing and placing in position exposed fair finish (factory made) Precast RCC elements i.e. light pole cover, light pole pedestal, bollard etc as per drawing. Rate shall be inclusive of concrete, reinforcements, necessary moulds, curing, all accessories required for fixing, transportation, loading and unloading; fixing, rendering (if required) necessary civil work for fixing, finish good etc complete as per drawing and as directed by engineer in charge. Contractor shall prepare sample and mock-up for approval from Architect and engineer in charge before execution.
Precast RCC Bench Providing, hoisting, stacking and arranging in position Precast RCC Bench of size 1500mm x 450mm x 380mm with 40mm thick top polished Kota laid on cement mortar with provision of up to 10mm groove as per drawing and as per approved sample. All exposed edges of Kota stone shall be uniform, rounded corner, even and both side polished. Contractor shall prepare sample and mock-up for approval from Architect and engineer in charge before execution.Rate shall be inclusive of reinforcement.
Providing and fixing rumblers strips of 500 x 200 x min 15 mm of any design, any colour, any pattern like bottom design, chequered design, anti skid pattern specially designed for road grip, to etc, as per approved sample, fixed on pavement as per manufacturer's specification and as directed by Engineer in charge by Engineer in charge.
Providing and fixing rubber corner guards of approved make in basement parking of size 825 x 65 x 65 x 6 mm with retro reflective tape marking in suitable colour. Corner guard shall be fixed with SS 304 grade fasteners and/ or adhesive as per manufacturer's specification etc complete as directed by Engineer in charge.
Providing and fixing car stopper/ parking block of size minimum 550 (L) x 110mm (W) x 100mm (H) made of synthetic plastic & rubber, including reflective tape for visibility, fixed with SS 304/ zinc coated MS screw etc complete and as directed by Engineer in charge.
Supplying and stacking sludge at site including royalty and carriage upto 20 km lead complete (sludge measured in stacks will be reduced by 8% for payment).
Supplying and stacking at site farm yard manure, compost or other specified fertilizer (as specified in specification) for all lead and lift, from approved source, and stack wherever required and as directed by Engineer-in-charge. (manure measured in stacks shall be reduced by 8% for payment):
Mixing earth and sludge or manure in the required proportion specified or directed by the Officer-in-charge.
Spreading/ filling of sludge, dump manure, good earth/ available excavated and/ or top layer of plot (as per surface excavation) for all lead (within plot/ side area) in required thickness as per direction of Engineer-in-charge (Cost of sludge, dump manure and / or good earth to be paid in relevant tender item).
Providing and laying Neelgiri/ Mexican grass turf and brought to site as carpet with earth 50mm to 60mm thickness on prepared ground with proper level and ramming with tools wooden (Dhurmos) and than rolling the surface with light roller make the surface smoothen and light watering with sprinkler and maintenance more till the grass establish properly, as per direction of officer-in-charge. Rate shall be inclusive of surface preparation/ rough dressing/ fine dressing/ ploughing/ clod breaking of the ground and anti-termite Treatment (vertically and horizontally) with the use of approved pesticides (neem cake oil or similar as suggested and approved by EIC) as per specification and as per manufacturer’s recommendation, fertilizers, but excluding the cost of good soil, sludge and manure, which shall be paid in relevant tender items. Rate shall be inclusive of establishment of lawn, gap filling between turf pecies and application of roller and maintenance for period of 365 days from date of substantial handover. All steps have to followed by contractor as specified in specification for proper establishment of lawn. From surface preparation to after lawn establishment, all steps are inclusive in this item.
Shrub/ Hedge/ Ground cover plantation or other plants Supplying well grown shrub plants/ Hedge plants and ground cover plants or other plants of specified species and height proposed planting pallete and planting in planter/ on land with good soil, manure, sludge, pesticide & insecticide/ anti termite, fertilizer etc. Plants shall be disease free and fungus free in polythene bag. Plastic bags or pots shall be removed carefully and soil around the roots shall not be dropped or disturbed much. Shrub shall be plant @ average c/c depend on type of species as per palette. Work shall be done as shown in the drawing or as directed and approved by architect and EIC. The ground coverage shall be dense and uniform throughout the planting area. Rates of mortality up to maintenance period to be inclusive, in that condition contractor has to replace the plant of same specification with out any extra cost. Rate shall be for in to in area of planter or ground area in square meter. Rate shall be for cost of shrub, loading, transporting, unloading, planting, pesticides, fertilizers, anti termite treatment, watering, maintaining, replanting (if plant will be died) etc but excluding the cost of soil, manure, sludge and it shall be paid in relevant tender item. Shrub plants/ Hedge plants and ground cover plants varieties shall be as per proposed planting pallete. Rate shall be inclusive of maintenance for period of 365 days from date of substantial handover. 1) Shrubs and ground covers shall be twin or multi‐stemmed, full and bushy. The form or shape of the plants shall be typical to its species. Height of the shrubs/ hedge and ground cover shall be as per proposed planting pallette. 2) The size, colour and appearance of leaves shall be typical for the time of year and stage of growth. The shrubs will be supplies in plastic bags of size 200mm x 200mm or 300mm x 300mm or as required with well developed root system or injury caused by mishandling during transportation. Petioles shall be cut clean and symmetrically at the trunk on any old leaf bases remaining. Shrub/ Hedge/ Ground cover plantation or other plants As per proposed planting palette at 100 mm C/C Distance
PLUMBING WORK-WATER SUPPLY Construction of 2 Bore Wells at Site: Boring / drilling bore well of 350mm dia for 250mm diameter casing / strainer pipe, by suitable method prescribed in IS: 2800 (part 1), including collecting samples from different strata, preparing and submitting strata chart / bore log, including hore & running charges of all equipments, tools, plants & machineries required for the job, Gravel packing in tubewell construction in accordance with IS: 4097, including providing Crushed stone aggregate for Hard Quality 20mm size, all complete as per direction of Engineer-in-charge, beyind 90 metre & up to 150 metre depth below ground level. - Rocky strata including Boulders - 350 mm diameter
Manufacture, supply & delivery of Electric Resistance Welded(upto 400mm) MS Pipe having beveled end plateor coil conforming to IS-3589-2001 or its latest revision / ammendment for 273mm outside diameter & 5mm thickness at store anywhere in Gujarat State including all taxes, insurance, transportaiion, freight charges, octroi, inspection charges, loading, unloading, conveyance to departental store, stacking, etc. all complete, plain ended casing pipes, conforming to IS: 4270, of reputed & approved make, all complete, for all depths, as per direction of Engineer-in-charge.
Lowering, laying, jointing and welding in position to correct line & level M.S. Pipe, the rate include conveyance from store to site of work loading, inloading, jointing, hydrotesting , etc. complete
Submersible Bore Well Pump of Capacity: Supplying submersible pump set for bore of 225 mm. dia. or more having 3 phase motor capacity about 60 H.P discharge capacity having - (B) (7 Stage) 2200 to 1600 L.P.M. discharge at the head 81 to 124 mtrs. suitable for 125 mm dia. Delivery pipe [Cat.III]
Lowering of submersible motor pump set at the depth of following ,complete with required. Nos. and size of casing pipes erected by means of proper chain pulley block & pipe wrenches after checking of threads of each pipe with coupling to take the load of the pump set and pipe assembly filled up with water, complete. (C) Above 120 mtr.
Supplying & erecting approved make Automatic liquid level controller 6A. with sensor testing as per instruction of Engineer in charge on site complete with wiring connection with existing wires , with copper conductor from pump to upper and lower tank.
Supplying of following size of HEAVY UPVC column pipe with coupler and wire lock [D] 80 mm dia
Supply of following size of TOP & BOTTOM accessories i.e. Adaptor set (CI) long, pump guard set, starter pipe Rubber ring for submersible pump & UPVC column pipe as directed by Engineer - in - charge with necessary plumbing as desired. [F] 80 mm dia
Supplying & erecting ISI Marked G.l. Union for pipe connections suitable for (F) 80 mm(3")
Supplying and erecting ISI marked sluice valve at position with necessary material for following size of pipe diameter. (F) 80 mm (3")
Supplying, & erecting C.I. swing, check type non-return (Reflux) Valve -ISI marked suitable for following size (C) 80 mm dia.
Providing, fixing, testing and commissioning C.I. body, Motorised Butterfly valve (PN10 rating) with quarter turn, on/off electric actuator, SG Iron disc with EPDM/Nitrile seat, wafer type,with panel, IP-67 water tight alluminium enclosure with postion indicator working on operated by float type level controller and manually, VOLTAGE 220V AC. Size: 65mm dia.
Providing, fixing, testing and commissioning C.I. body, Motorised Butterfly valve (PN10 rating) with quarter turn, on/off electric actuator, SG Iron disc with EPDM/Nitrile seat, wafer type,with panel, IP-67 water tight alluminium enclosure with postion indicator working on operated by float type level controller and manually, VOLTAGE 220V AC. Size: 50mm dia.
Providing and laying in position ISI Marked (Embossed) 100mm diameter of Heavy duty “C” Class G.I . pipes as per IS: 1239, including fittings, threading the joints, fixing the joints with Teflon tapes, testing of the laid pipes as per standards, and laying underground including one coat of anticorrosive primer and wrapping material of 4mm thick & 150 mm width protection coating as per IS:10221 by thermo fusion process,overlap shall be maintained at 15mm as per specifications complete, and as approved and directed by Engineer-in-charge. (Excavation and backfilling excluded and extra as per relevant items)
Providing and laying in position ISI Marked (Embossed) 80mm diameter of Heavy duty “C” Class G.I . pipes as per IS: 1239, including fittings, threading the joints, fixing the joints with Teflon tapes, testing of the laid pipes as per standards, and laying underground including one coat of anticorrosive primer and wrapping material of 4mm thick & 150 mm width protection coating as per IS:10221 by thermo fusion process,overlap shall be maintained at 15mm as per specifications complete, and as approved and directed by Engineer-in-charge. (Excavation and backfilling excluded and extra as per relevant items)
Providing and laying in position ISI Marked (Embossed) 65mm diameter of Heavy duty “C” Class G.I . pipes as per IS: 1239, including fittings, threading the joints, fixing the joints with Teflon tapes, testing of the laid pipes as per standards, and laying underground including one coat of anticorrosive primer and wrapping material of 4mm thick & 150 mm width protection coating as per IS:10221 by thermo fusion process,overlap shall be maintained at 15mm as per specifications complete, and as approved and directed by Engineer-in-charge. (Excavation and backfilling excluded and extra as per relevant items)
Providing and laying in position ISI Marked (Embossed) 50mm diameter of Heavy duty “C” Class G.I . pipes as per IS: 1239, including fittings, threading the joints, fixing the joints with Teflon tapes, testing of the laid pipes as per standards, and laying underground including one coat of anticorrosive primer and wrapping material of 4mm thick & 150 mm width protection coating as per IS:10221 by thermo fusion process,overlap shall be maintained at 15mm as per specifications complete, and as approved and directed by Engineer-in-charge. (Excavation and backfilling excluded and extra as per relevant items)
Excavation for pipeline trenches for water supply, sewerage line, manhole, etc. all with shoring and struting if required as per requird gradient and line including safety provisions using site rails and staking excavated stuff including up to all required lead cleaning the site etc. complete for all lifts and strata as specified - a) in all sorts of soil and soft murum - up to 1.5 meter depth.
Lowering, laying and jointing G.I. pipes with G.I. specials of 100mm diameter in proper position, grade and alignment as directed by Engineer-in-charge including conveyance from stores to site of work, labour, hydraulic testing, etc. complete.
Lowering, laying and jointing G.I. pipes with G.I. specials of 65mm diameter in proper position, grade and alignment as directed by Engineer-in-charge including conveyance from stores to site of work, labour, hydraulic testing, etc. complete.
Lowering, laying and jointing G.I. pipes with G.I. specials of 50mm diameter in proper position, grade and alignment as directed by Engineer-in-charge including conveyance from stores to site of work, labour, hydraulic testing, etc. complete.
Providing and fixing to wall and ceiling ISI Marked (Embossed) 100mm diameter of Medium Duty 'B' Class G.I. pipes as per IS: 1239, complete with cutting, threading, all fittings such as unions, bends, tees, etc, Teflon tape over threaded joints, Hilti anchor fasteners, G.I. threaded rods, double sided G.I. clamps, etc. including making good the wall and ceiling complete as directed by the Engineer-in-charge.
Providing and fixing 40mm diameter Bronze gate valve (screwed) with C.I. wheel of approved quality (screwed end).
Providing and fixing 50mm diameter Bronze gate valve (screwed) with C.I. wheel of approved quality (screwed end).
Providing and fixing 65mm diameter Bronze gate valve (screwed) with C.I. wheel of approved quality (screwed end).
Providing and fixing 80mm diameter Bronze gate valve (screwed) with C.I. wheel of approved quality (screwed end).
Providing and fixing 100mm diameter Bronze gate valve (screwed) with C.I. wheel of approved quality (screwed end).
Providing and fixing 80mm diameter C.I. Y Strainer (flanged).
Providing and fixing 65mm diameter C.I. Y Strainer (flanged).
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal Work - Exposed on wall - 20 mm nominal dia Pipes
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal Work - Exposed on wall - 25 mm nominal dia Pipes
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal Work - Exposed on wall - 32 mm nominal dia Pipes
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal Work - Exposed on wall - 40 mm nominal dia Pipes
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge. Internal Work - Exposed on wall - 50 mm nominal dia Pipes
Providing and fixing concealed center point to wall ceiling & floor CPVC (SDR 13.5) PIPE having National Sanitation Foundation (NSF) seal for potable water of following dia. nominal bore tube fittings and clamps including making good the wall, ceiling and floor etc. complete.[A] 15 mm.
Providing and fixing concealed center point to wall ceiling & floor CPVC (SDR 13.5) PIPE having National Sanitation Foundation (NSF) seal for potable water of following dia. nominal bore tube fittings and clamps including making good the wall, ceiling and floor etc. complete. [B] 20 mm.
Providing and fixing concealed center point to wall ceiling & floor CPVC (SDR 13.5) PIPE having National Sanitation Foundation (NSF) seal for potable water of following dia. nominal bore tube fittings and clamps including making good the wall, ceiling and floor etc. complete. [C] 25 mm.
Providing and fixing concealed center point to wall ceiling & floor CPVC (SDR 13.5) PIPE having National Sanitation Foundation (NSF) seal for potable water of following dia. nominal bore tube fittings and clamps including making good the wall, ceiling and floor etc. complete. [D] 32mm.
Providing and fixing concealed center point to wall ceiling & floor CPVC (SDR 13.5) PIPE having National Sanitation Foundation (NSF) seal for potable water of following dia. nominal bore tube fittings and clamps including making good the wall, ceiling and floor etc. complete. [E] 40mm.
Providing and fixing concealed center point to wall ceiling & floor CPVC (SDR 13.5) PIPE having National Sanitation Foundation (NSF) seal for potable water of following dia. nominal bore tube fittings and clamps including making good the wall, ceiling and floor etc. complete. [F] 50mm.
Providing and fixing chlorinated polyvinyl chloride (CPVC) Ball valves , having pressure bearing capacity up to 7.0 kg/cm² at 82°C, of the following sizes including cutting the pipes, solvent welding, complete as per the manufacturers standards and the direction of the Engineer-in-charge. Make: Prince / Astral / Supreme / Ashirvad. a) 15 mm nominal bore
Providing and fixing chlorinated polyvinyl chloride (CPVC) Ball valves , having pressure bearing capacity up to 7.0 kg/cm² at 82°C, of the following sizes including cutting the pipes, solvent welding, complete as per the manufacturers standards and the direction of the Engineer-in-charge. Make: Prince / Astral / Supreme / Ashirvad. b) 20mm diameter
Providing and fixing chlorinated polyvinyl chloride (CPVC) Ball valves , having pressure bearing capacity up to 7.0 kg/cm² at 82°C, of the following sizes including cutting the pipes, solvent welding, complete as per the manufacturers standards and the direction of the Engineer-in-charge. Make: Prince / Astral / Supreme / Ashirvad. c) 25 mm nominal bore
Providing and fixing chlorinated polyvinyl chloride (CPVC) Ball valves , having pressure bearing capacity up to 7.0 kg/cm² at 82°C, of the following sizes including cutting the pipes, solvent welding, complete as per the manufacturers standards and the direction of the Engineer-in-charge. Make: Prince / Astral / Supreme / Ashirvad. d) 32 mm nominal bore
Providing and fixing chlorinated polyvinyl chloride (CPVC) Ball valves , having pressure bearing capacity up to 7.0 kg/cm² at 82°C, of the following sizes including cutting the pipes, solvent welding, complete as per the manufacturers standards and the direction of the Engineer-in-charge. Make: Prince / Astral / Supreme / Ashirvad. e) 40 mm nominal bore
Providing and fixing chlorinated polyvinyl chloride (CPVC) Ball valves , having pressure bearing capacity up to 7.0 kg/cm² at 82°C, of the following sizes including cutting the pipes, solvent welding, complete as per the manufacturers standards and the direction of the Engineer-in-charge. Make: Prince / Astral / Supreme / Ashirvad. f) 50 mm nominal bore
Providing & fixing of Nitrile rubber closed cell (Thermo plastic elastomeric) insulation of 13 mm wall thickness CLASS-1 with ALUPET FOIL of the following diameter and thickness over hot water pipes and fittings, of minimum 45 kg / M³ density and having thermal conductivity 0.037W/MK or better at 20°C mean temperature, class 'O' insulation applied by suitable adhesive complete as per manufacturers specifications (for internal and external hot water supply) all complete as per directions of the Engineer-In-Charge. Rate includes cost of all materials including fixing the insulation with the pipes with tapes or adhesives, labour charges for working at all levels. leads and heights. Make: Astral / Supreme / Equivalent. a) For 15mm diameter pipes
Providing & fixing of Nitrile rubber closed cell (Thermo plastic elastomeric) insulation of 13 mm wall thickness CLASS-1 with ALUPET FOIL of the following diameter and thickness over hot water pipes and fittings, of minimum 45 kg / M³ density and having thermal conductivity 0.037W/MK or better at 20°C mean temperature, class 'O' insulation applied by suitable adhesive complete as per manufacturers specifications (for internal and external hot water supply) all complete as per directions of the Engineer-In-Charge. Rate includes cost of all materials including fixing the insulation with the pipes with tapes or adhesives, labour charges for working at all levels. leads and heights. Make: Astral / Supreme / Equivalent. b) For 20mm diameter pipes
Providing and fixing cast iron steps of size 500mm x 150mm x 22.5mm and painting with two coats of Anti-corrosive paint etc. complete.
Providing and fixing C.I. Manhole cover 0.60 M. x 0.45M. Size having weight not less than 35Kg.
Providing and fixing in location G.I. / MS Puddle flanges with Hot dip galvanizing work confirming to IS 4759/ 2629/ 2633 with zinc of 610 GSM thickness on the tubular sections. The rate shall include preparing the surface by shot blasting as per IS: 2629 prior to hot dip galvanizing, labor, tools, machinery etc complete. The puddle shall be as per IS: 6392 / 1538 / BS 4504 of 8mm thick M.S. plate with 4 to 6 holes of 8mm diameter each welded to the 300mm long MS Pipe of below mentioned sizes, with double welding using Arc Welding / Electrode Welding, the pipe shall be of Hot dip Galvanised MS material with 6mm thick Table 'F' Flanges made from M.S. material, Rubber Gaskets, and Rubber lining for preventing leakages. The scope includes Puddle, Pipe, Sleeve and Flanges of the following sizes: 200 mm diameter (for interconnection of tanks)
Providing and fixing in location G.I. / MS Puddle flanges with Hot dip galvanizing work confirming to IS 4759/ 2629/ 2633 with zinc of 610 GSM thickness on the tubular sections. The rate shall include preparing the surface by shot blasting as per IS: 2629 prior to hot dip galvanizing, labor, tools, machinery etc complete. The puddle shall be as per IS: 6392 / 1538 / BS 4504 of 8mm thick M.S. plate with 4 to 6 holes of 8mm diameter each welded to the 300mm long MS Pipe of below mentioned sizes, with double welding using Arc Welding / Electrode Welding, the pipe shall be of Hot dip Galvanised MS material with 6mm thick Table 'F' Flanges made from M.S. material, Rubber Gaskets, and Rubber lining for preventing leakages. The scope includes Puddle, Pipe, Sleeve and Flanges of the following sizes: 150 mm diameter (for interconnection of tanks)
Providing and fixing in location G.I. / MS Puddle flanges with Hot dip galvanizing work confirming to IS 4759/ 2629/ 2633 with zinc of 610 GSM thickness on the tubular sections. The rate shall include preparing the surface by shot blasting as per IS: 2629 prior to hot dip galvanizing, labor, tools, machinery etc complete. The puddle shall be as per IS: 6392 / 1538 / BS 4504 of 8mm thick M.S. plate with 4 to 6 holes of 8mm diameter each welded to the 300mm long MS Pipe of below mentioned sizes, with double welding using Arc Welding / Electrode Welding, the pipe shall be of Hot dip Galvanised MS material with 6mm thick Table 'F' Flanges made from M.S. material, Rubber Gaskets, and Rubber lining for preventing leakages. The scope includes Puddle, Pipe, Sleeve and Flanges of the following sizes: 100 mm diameter (for interconnection of tanks)
Providing and fixing in location G.I. / MS Puddle flanges with Hot dip galvanizing work confirming to IS 4759/ 2629/ 2633 with zinc of 610 GSM thickness on the tubular sections. The rate shall include preparing the surface by shot blasting as per IS: 2629 prior to hot dip galvanizing, labor, tools, machinery etc complete. The puddle shall be as per IS: 6392 / 1538 / BS 4504 of 8mm thick M.S. plate with 4 to 6 holes of 8mm diameter each welded to the 300mm long MS Pipe of below mentioned sizes, with double welding using Arc Welding / Electrode Welding, the pipe shall be of Hot dip Galvanised MS material with 6mm thick Table 'F' Flanges made from M.S. material, Rubber Gaskets, and Rubber lining for preventing leakages. The scope includes Puddle, Pipe, Sleeve and Flanges of the following sizes: 80 mm diameter (for interconnection of tanks)
Providing and fixing in location G.I. / MS Puddle flanges with Hot dip galvanizing work confirming to IS 4759/ 2629/ 2633 with zinc of 610 GSM thickness on the tubular sections. The rate shall include preparing the surface by shot blasting as per IS: 2629 prior to hot dip galvanizing, labor, tools, machinery etc complete. The puddle shall be as per IS: 6392 / 1538 / BS 4504 of 8mm thick M.S. plate with 4 to 6 holes of 8mm diameter each welded to the 300mm long MS Pipe of below mentioned sizes, with double welding using Arc Welding / Electrode Welding, the pipe shall be of Hot dip Galvanised MS material with 6mm thick Table 'F' Flanges made from M.S. material, Rubber Gaskets, and Rubber lining for preventing leakages. The scope includes Puddle, Pipe, Sleeve and Flanges of the following sizes: 65 mm diameter (for interconnection of tanks)
Providing and fixing in location G.I. / MS Puddle flanges with Hot dip galvanizing work confirming to IS 4759/ 2629/ 2633 with zinc of 610 GSM thickness on the tubular sections. The rate shall include preparing the surface by shot blasting as per IS: 2629 prior to hot dip galvanizing, labor, tools, machinery etc complete. The puddle shall be as per IS: 6392 / 1538 / BS 4504 of 8mm thick M.S. plate with 4 to 6 holes of 8mm diameter each welded to the 300mm long MS Pipe of below mentioned sizes, with double welding using Arc Welding / Electrode Welding, the pipe shall be of Hot dip Galvanised MS material with 6mm thick Table 'F' Flanges made from M.S. material, Rubber Gaskets, and Rubber lining for preventing leakages. The scope includes Puddle, Pipe, Sleeve and Flanges of the following sizes: 50 mm diameter (for interconnection of tanks)
Providing and fixing in location G.I. / MS Puddle flanges with Hot dip galvanizing work confirming to IS 4759/ 2629/ 2633 with zinc of 610 GSM thickness on the tubular sections. The rate shall include preparing the surface by shot blasting as per IS: 2629 prior to hot dip galvanizing, labor, tools, machinery etc complete. The puddle shall be as per IS: 6392 / 1538 / BS 4504 of 8mm thick M.S. plate with 4 to 6 holes of 8mm diameter each welded to the 300mm long MS Pipe of below mentioned sizes, with double welding using Arc Welding / Electrode Welding, the pipe shall be of Hot dip Galvanised MS material with 6mm thick Table 'F' Flanges made from M.S. material, Rubber Gaskets, and Rubber lining for preventing leakages. The scope includes Puddle, Pipe, Sleeve and Flanges of the following sizes: 25 mm diameter (for level sensors in tanks)
SANITARY INSTALLATIONS Providing & fixing Divyang toilet set with European Closet (P Trap) & wall mount wash basin & all divyang requirements with dual flush tank, seat & cover (heavy duty) with C.P. brass hinges,including WC connector of 110mm inlet x 110mm outlet, connecting the same with soil pipe using appropriate solvent cement, C.I. Brackets for wall mounting the basin, 32mm CP waste Coupling, 32mm size CP bottle trap, CP brass Spatula Faucet, etc. all Internal fittings complete with S.S grab rails etc. rubber buffers, C.P nuts, bolts etc making holes in walls & floors, & finishing for ready to use.The rate includes all necessary connection charges as per product detail to the satisfaction and as directed by the Engineer-in-charge. Make: Hindware - Matrix - 70002 + SPATULA FAUCET - F280001MD
Providing, fixing, testing and commissioning White Vitreous China wall mount one peice water closet (European type) of approved size and shape, with CP bolts, nuts, C.I. Chair bracket or other hanging arrangements, C.P. Brass screws, washer with all accessories, including seat and cover, including cutting and making good the walls, floors, slabs wherever required, including all necessary accessories and consumables, complete as per the specifications / drawings, and as directed by the Engineer In Charge. Make: Cera - S1043148
Providing and Fixing Vitreous china Counter Top Wash Basin as per IS: 2556 (Part 4) of size 550 x 400 x 140mm, in white colour of approved make and quality. All junctions shall be sealed with silicon sealant. Rate shall include 32 mm dia CP brass waste coupling, 32 mm dia CP cast brass bottle trap, union & extension piece of required length and CP wall flange complete including cutting & making good the walls where required and as directed by the Engineer-in-charge. Make: Wash Basin: Cera - S2020102 - For all Common Areas; Bottle Trap: Cera - F8060301; Waste coupling: Cera - F8050301
Providing and Fixing Vitreous china Counter Top Wash Basin as per IS: 2556 (Part 4) of size 440 x 440 x 135mm, in white colour of approved make and quality. All junctions shall be sealed with silicon sealant. Rate shall include 32 mm dia CP brass waste coupling, 32 mm dia CP cast brass bottle trap, union & extension piece of required length and CP wall flange complete including cutting & making good the walls where required and as directed by the Engineer-in-charge. Make: Cera - S2020155 - For Attached Toilets; Bottle Trap: Cera; Waste coupling: Cera
Providing and Fixing Vitreous china Counter Top Wash Basin as per IS: 2556 (Part 4) of size 340 x 300 x 120mm, in white colour of approved make and quality. All junctions shall be sealed with silicon sealant. Rate shall include 32 mm dia CP brass waste coupling, 32 mm dia CP cast brass bottle trap, union & extension piece of required length and CP wall flange complete including cutting & making good the walls where required and as directed by the Engineer-in-charge. Make: Cera - S2020109 - For Consultant Rooms; Bottle Trap: Cera; Waste coupling: Cera
Providing and fixing white vitreous china Urinal of size 350 X 340 X 615mm with rear side water inlet & waste outlet, including conecting the Urinal with inlet water supply pipe & waste pipe, completeincluding cutting & making good the walls where required and as directed by the Engineer-in-charge. Make: Cera - S4020113 / Equivalent
Providing and fixing white vitreous china sink for Sluice Room & Autopsy Room, with C.I. brackets, 40 mm PTMT waste coupling, 40mm PTMT bottle trap, complete, including painting of fittings and brackets, cutting and making good the wall wherever required as directed by Engineer. Sink for Sluice Rooms. Sink: Make: Cera – CATER 600 x 400 x 250 mm (660 x 460 x 250 mm including rim) Cat. No. S6010103; PTMT Waste Coupling - PolyTUF - 38/40 mm - 1003 (b); PTMT Bottle Trap - PolyTUF - 40mm - 1060.
Providing and fixing Stainless Steel AISI 304 (18/8) kitchen sink as per IS: 13983 with C.I. brackets and stainless steel plug 40mm, including painting of fittings and brackets, cutting and making good the walls wherever required. Kitchen Sink without drain board: Size: 610 x 510 mm bowl depth 200 mm.
Providing and fixing PTMT Waste Coupling for wash basin and sink, of approved quality and colour. Waste coupling 38mm dia of 83mm length and 77mm breadth, weighing not less than 60 gms. Waste Coupling - Make: PolyTUF - 1003(b) / Equivalent
Providing and fixing PTMT Bottle Trap for wash basin and sink, of approved quality and colour. Bottle trap 38mm dia single piece moulded with height of 270mm, effective length of tail pipe 260mm from the center of the waste coupling, 77mm breadth with 25mm minimum water seal, weighing not less than 263 gms. Bottle Trap - Make: PolyTUF - 1060 / Equivalent
Providing and fixing 8mm dia S.S. jet with flexible tube up to 1 meter long with S.S. triangular plate to European type W.C. of quality and make as approved by Engineer-in-charge. Jet Spray - Make: Chilly - TSJS-SPVC-100 / Equivalent
Providing & fixing C.P. brass Concealed type flush valve (Metropole Flush Valve) with, 32 mm dia C.P. flush pipe with clamp and adapter, rubber joint, C.P. brass wall flange, elbow complete with all other accessories. Make: Jaquar - FLV-1095N or Equivalent
Providing and Fixing in position CP brass Pressmatic Urinal Flush Valve Auto-closing system with built in Control Cock and Wall flange of approved or equivalent make, and including all necessary materials required for fixing. All complete as per directions of the Engineer-in-charge. Concealed Flush Valve - Make: Jaquar - PRS-073 / Equivalent
Providing and Fixing 15 mm dia. Wall mounted type CP brass pressmatic bib cock with Auto Closing System with Built-in Control Cock With Wall Flange complete, making all necessary connections etc. All complete as per directions of the Engineer-in-charge. i) 15mm dia. Make: Jaquar - PRS-043 / Cera - F9020151 / Equivalent
Providing and Fixing 15 mm dia. CP brass extended lever handle pillar cock with ceramic disc cartridge for all laboratory and sluice sinks or as directed by the Engineer-in-charge, complete, making all necessary connections etc of approved make.
Providing and fixing of 15mm nominal bore CP Brass Angle valve confirming to IS: 8931, for wash basins, water coolers, geyser points, etc of approved quality and as approved by and directed by the Engineer-in-charge. Make: Jaquar - VGP-81053 / Equivalent
Providing and fixing screw down bib taps of following size. (B) Brass chromium plated screws down Bib Tap. (i) 15mm dia.
Providing and fixing C.P. brass towel rail comlete with C.P. brass brackets fixed to wooden plugs with C.P. brass scews.(B) 600mm x 20mm size.
Providing and fixing C.P. brass shower rose with 15mm or 20mm inlet.(A) 100mm dia. Each
Providing and fixing 20mm diameter x 600mm long Stainless Steel Grab Bar. Make: Euronics / Dolphy / Equivalent
Providing and fixing Swing Grab Bar Material : 18-8 S, Type-304, Stainless Steel, Operation : Movable (Horizontally & Vertically), Diameter : 32mm. Make: Euronics / Jaquar / Equivalent
Providing and fixing C.P. brass Shower arm for over head shower of approved make and quality, and as approved by the Engineer-in-charge, and conforming to Manufacturers Standards. a) Size: Casted 190mm long light body round shape for wall mounted shower rose with flange, of approved make and as per the direction of the Engineer-in-charge. Make: Jaquar - SHA - 483 / Equivalent.
Providing and fixing C.P. brass Wall Mixer with provision For overhead shower with 115mm Long Bend pipe on upper side, connecting legs & wall flanges, complete as per approved make and as directed by the Engineer-in-charge. Make: Jaquar - Fusion - FUS 29147 / Equivalent.
Providing and fixing Heavy class SS grating of grade SS 304 of approved make and quality, and as approved by the Engineer-in-charge, weighing not less than 150 gms. including setting in floor with white cement to match with floor finish as per requirement complete as per directions of Engineer-in-Charge. I) Type 1 - Size 129mm x 129mm Square Matt finish with Cockroach trap consisting of 100mm x 100mm perforated top cover, 77mm Ø x 67mm high Cockroach Trap ideal for 100mm drain pipe. Make: Chilly; Model No. CCT-S-129 or Equivalent.
Providing and fixing Heavy class SS grating of grade SS 304 of approved make and quality, and as approved by the Engineer-in-charge, weighing not less than 150 gms. including setting in floor with white cement to match with floor finish as per requirement complete as per directions of Engineer-in-Charge. ii) Type 2 - Size 150mm x 150mm Square Matt finish with Cockroach trap consisting of 100mm diameter solid top cover, 77mm Ø x 70mm high Cockroach Trap ideal for 100mm drain pipe with floor trap cover as specified in approved make and quality. (For Urinal only) Make: Chilly - Lifestyle Square : Model No: CCTL-S-150 / Equivalent.
Providing and fixing SS Floor Cleanout (FCO) plug of approved brand and with SS Square Frame/ Round Frame with Flat Round Cover with Rubber Seal & SS Screw jointing as per manufacturer recommendation or per approval of the Engineer-in-charge. ii) 128mm x 128mm Square Top for 100 mm dia pipe. Make:Chilly; Model No. COS 128 or Similar or Equivalent Make.
Providing and fixing UPVC SWR WC Connector 130 x 110 mm dia. Socket type of approved make, fixed to outlet gaskets with UPVC Lubricant or Solvent Cement, all complete as per directions of the Engineer-in-charge. Make: Astral; Model No. F172005909 or Equivalent.
Providing, laying and jointing in true line and level 160 mm diametre U.P.V.C (Type B) conforming to IS 13592 with one end plain and other end socketed with rubber ring, & fittings conforming to ISI 14735 of approved make for drainage system pipe line, pipe shall be jointed with each other with rubber lubricant, pipe shall be fixed on wall using of PVC clamp of the size 160 mm diametre x 210 mm length x 196 mm heigh at every 2000 mm center to center or shall be concealed in walls as directed including necessary fittings such as bends, shoes etc. including testing of pipes and joints and jointed with adhesive solvent cement including cost of all materials.
Providing, laying and jointing in true line and level 110 mm diametre U.P.V.C (Type B) conforming to IS 13592 with one end plain and other end socketed with rubber ring, & fittings conforming to ISI 14735-1999 of approved make for drainage system pipe line, pipe shall be jointed with each other with rubber lubricant, pipe shall be fixed on wall using of PVC clamp of the size 110 mm diametre x 149 mm length x 145 mm heigh at every 2000 mm center to center or shall be concealed in walls as directed including necessary fittings such as bends, shoes etc. including testing of pipes and joints and jointed with adhesive solvent cement including cost of all materials.
Providing, laying and jointing in true line and level 75mm diametre U.P.V.C (Type B) conforming to IS 13592 with one end plain and other end socketed with rubber ring, & fittings conforming to IS 14735 of approved make for drainage system pipe line, pipe shall be jointed with each other with rubber lubricant, pipe shall be shall be concealed in walls as directed including necessary fittings such as bends, shoes etc. including testing of pipes and joints and jointed with adhesive solvent cement including cost of all materials.
Providing, laying and jointing in true line and level 50 diametre P.V.C (6kg/cm2) conforming to IS 4985 with single socket, & fittings of approved make for drainage system pipe line, pipe shall be jointed with each other with appropriate solvent cement, pipe shall be shall be concealed in walls as directed, including necessary fittings such as bends, shoes etc. including testing of pipes and joints, including cost of all materials. Make: Astral / Ashirvad / Prince.
Providing, laying and jointing in true line and level 40 diametre P.V.C (6kg/cm2) conforming to IS 4985 with single socket, & fittings of approved make for drainage system pipe line, pipe shall be jointed with each other with appropriate solvent cement, pipe shall be shall be concealed in walls as directed, including necessary fittings such as bends, shoes etc. including testing of pipes and joints, including cost of all materials. Make: Astral / Ashirvad / Prince.
Providing and fixing unplasticized PVC SWR as per IS: 13592 (Type B), P - Trap as approved and directed by the Engineer-in-charge. For 110 mm Dia pipe
Providing and fixing unplasticized PVC SWR as per IS: 13592 (Type B), vent cowl as approved and directed by the Engineer-in-charge. For 75 mm Dia pipe
Providing and fixing unplasticized PVC SWR as per IS: 13592 (Type B), vent cowl as approved and directed by the Engineer-in-charge. For 110 mm Dia pipe
Providing and fixing unplasticized PVC SWR as per IS: 13592 (Type B), vent cowl as approved and directed by the Engineer-in-charge. For 150 mm Dia pipe
Providing, laying and jointing in true line and level 150 diametre U.P.V.C (Type A) conforming to IS 13592 with one end plain and other end socketed with rubber ring, & fittings conforming to ISI 14735 of approved make for drainage system pipe line, pipe shall be jointed with each other with rubber lubricant, pipe shall be fixed on wall using of PVC clamp of the size 110 mm diametre x 149 mm length x 145 mm heigh at every 2000 mm center to center or shall be concealed in walls as directed including necessary fittings such as bends, shoes etc. including testing of pipes and joints and jointed with adhesive solvent cement including cost of all materials.
Providing and fixing on wall face unplasticised - PVC moulded fittings/ accessories for unplasticised-PVC rain water pipes conforming to IS : 13592 (Type A), including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion. Shoe Bend - 150mm dia pipe
Providing and fixing unplasticised -PVC pipe clips of approved design to unplasticised - PVC rain water pipes at an average distance of 1.2 meters centre to centre, by means of 50x50x50 mm hard wood plugs, screwed with M.S. screws of required length, including cutting brick work and fixing in cement mortar 1:4 (1 cement : 4 coarse sand) and making good the wall etc. complete.
MECHANICAL INSTALLATIONS Submersible Pressurized Pumping System - For Hospital Domestic Water Supply: Supplying & erecting approved make open well multi-stage submersible vertical motor and pump set of reputed make a pre-engineered, tested, fully integrated, highly efficient multi-stage pump system, with IE2 submersible type motors, having a Flow range - upto 457 cum/hr; Pressure range - 0.7 to 26. kgf/sq.cm. (10 to 375 psi / 0.68 Bar to 25.86 Bar); Ambient temperature - 0°C to +45°C; Water pH - 6.5 - 8, complete ready-to-connected in parallel, with high efficiency IE 2 motors, an air-cooled external variable frequency drive, intelligent multi-pump controller, the controller shall be mounted in a control cabinet with an IP 58 enclosure of suitable rating having Potential free contacts to monitor On/Off, Run & trip status with necessary sensors/switches; hot Dipped Galvanised suction and delivery manifolds; isolation ball valves on suction and discharge of each pump; non return valve on discharge side of each pump; complete. Complete (Skid mounted / wall mounted / floor mounted) electrical control panel comprising of all accessories such as PLCs, pressure switches, pressure transducers, control wiring and any other necessary imports etc. (list to be provided by the vendor). All installations such as electrical wiring from Electrical Panel to Pump panel, civil foundations, etc, set of accessories such as NRVs, isolating valves, pressure gauge, pressure switches, pressure transducers, inter connecting power and control cabling etc. is included in this scope. Motor type - Submersible rewindable motor; Ratings - 1 phase - 0.37 to 1.5 kW per pump &/or 3 phase - 0.37 to 26 kW per pump; Rated speed - 2900 rpm; Enclosure class - IP 68; Nominal voltage - 1 phase - 220, 230 V / 3 phase - 380, 400, 415 V; Supply frequency - 50 Hz; Duty / Rating - S1 / Continuous; Direction of rotation - Clockwise as seen from the pump coupling side. For Soft Water Supply - Set consisting of 4 pumps (3 working + 1 standby); Flow Rate (Each pump): 250 LPM; Flow Rate (System): 1000 LPM (60 Cu. Mtr / Hr); Pressure Vessel = 1 x 100 Ltrs; Head (each pump): 55 Mtrs.
Submersible Pressurized Pumping System - For Dormitory Domestic Water Supply: Supplying & erecting approved make open well multi-stage submersible vertical motor and pump set of reputed make a pre-engineered, tested, fully integrated, highly efficient multi-stage pump system, with IE2 submersible type motors, having a Flow range - upto 457 cum/hr; Pressure range - 0.7 to 26. kgf/sq.cm. (10 to 375 psi / 0.68 Bar to 25.86 Bar); Ambient temperature - 0°C to +45°C; Water pH - 6.5 - 8, complete ready-to-connected in parallel, with high efficiency IE 2 motors, an air-cooled external variable frequency drive, intelligent multi-pump controller, the controller shall be mounted in a control cabinet with an IP 58 enclosure of suitable rating having Potential free contacts to monitor On/Off, Run & trip status with necessary sensors/switches; hot Dipped Galvanised suction and delivery manifolds; isolation ball valves on suction and discharge of each pump; non return valve on discharge side of each pump; complete. Complete (Skid mounted / wall mounted / floor mounted) electrical control panel comprising of all accessories such as PLCs, pressure switches, pressure transducers, control wiring and any other necessary imports etc. (list to be provided by the vendor). All installations such as electrical wiring from Electrical Panel to Pump panel, civil foundations, etc, set of accessories such as NRVs, isolating valves, pressure gauge, pressure switches, pressure transducers, inter connecting power and control cabling etc. is included in this scope. Motor type - Submersible rewindable motor; Ratings - 1 phase - 0.37 to 1.5 kW per pump &/or 3 phase - 0.37 to 26 kW per pump; Rated speed - 2900 rpm; Enclosure class - IP 68; Nominal voltage - 1 phase - 220, 230 V / 3 phase - 380, 400, 415 V; Supply frequency - 50 Hz; Duty / Rating - S1 / Continuous; Direction of rotation - Clockwise as seen from the pump coupling side. For Soft Water Supply - Set consisting of 4 pumps (3 working + 1 standby); Flow Rate (Each pump): 250 LPM; Flow Rate (System): 1000 LPM (60 Cu. Mtr / Hr); Pressure Vessel = 1 x 100 Ltrs; Head (each pump): 55 Mtrs.
Submersible Pressurized Pumping System - For Dormitory Recycled Water Supply: Supplying & erecting approved make open well multi-stage submersible vertical motor and pump set of reputed make a pre-engineered, tested, fully integrated, highly efficient multi-stage pump system, with IE2 submersible type motors, having a Flow range - upto 457 cum/hr; Pressure range - 0.7 to 26. kgf/sq.cm. (10 to 375 psi / 0.68 Bar to 25.86 Bar); Ambient temperature - 0°C to +45°C; Water pH - 6.5 - 8, complete ready-to-connected in parallel, with high efficiency IE 2 motors, an air-cooled external variable frequency drive, intelligent multi-pump controller, the controller shall be mounted in a control cabinet with an IP 58 enclosure of suitable rating having Potential free contacts to monitor On/Off, Run & trip status with necessary sensors/switches; hot Dipped Galvanised suction and delivery manifolds; isolation ball valves on suction and discharge of each pump; non return valve on discharge side of each pump; complete. Complete (Skid mounted / wall mounted / floor mounted) electrical control panel comprising of all accessories such as PLCs, pressure switches, pressure transducers, control wiring and any other necessary imports etc. (list to be provided by the vendor). All installations such as electrical wiring from Electrical Panel to Pump panel, civil foundations, etc, set of accessories such as NRVs, isolating valves, pressure gauge, pressure switches, pressure transducers, inter connecting power and control cabling etc. is included in this scope. Motor type - Submersible rewindable motor; Ratings - 1 phase - 0.37 to 1.5 kW per pump &/or 3 phase - 0.37 to 26 kW per pump; Rated speed - 2900 rpm; Enclosure class - IP 68; Nominal voltage - 1 phase - 220, 230 V / 3 phase - 380, 400, 415 V; Supply frequency - 50 Hz; Duty / Rating - S1 / Continuous; Direction of rotation - Clockwise as seen from the pump coupling side. For Recyled Water Supply - Set consisting of 3 pumps (2 working + 1 standby); Flow Rate (Each pump): 250 LPM; Flow Rate (System): 750 LPM (45 Cu. Mtr / Hr); Pressure Vessel = 1 x 200 Ltrs; Head (each pump): 65 Mtrs.
Submersible Pressurized Pumping System - For Recycled Water Supply to HVAC OHT: Supplying & erecting approved make open well multi-stage submersible vertical motor and pump set of reputed make a pre-engineered, tested, fully integrated, highly efficient multi-stage pump system, with IE2 submersible type motors, having a Flow range - upto 457 cum/hr; Pressure range - 0.7 to 26. kgf/sq.cm. (10 to 375 psi / 0.68 Bar to 25.86 Bar); Ambient temperature - 0°C to +45°C; Water pH - 6.5 - 8, complete ready-to-connected in parallel, with high efficiency IE 2 motors, an air-cooled external variable frequency drive, intelligent multi-pump controller, the controller shall be mounted in a control cabinet with an IP 58 enclosure of suitable rating having Potential free contacts to monitor On/Off, Run & trip status with necessary sensors/switches; hot Dipped Galvanised suction and delivery manifolds; isolation ball valves on suction and discharge of each pump; non return valve on discharge side of each pump; complete. Complete (Skid mounted / wall mounted / floor mounted) electrical control panel comprising of all accessories such as PLCs, pressure switches, pressure transducers, control wiring and any other necessary imports etc. (list to be provided by the vendor). All installations such as electrical wiring from Electrical Panel to Pump panel, civil foundations, etc, set of accessories such as NRVs, isolating valves, pressure gauge, pressure switches, pressure transducers, inter connecting power and control cabling etc. is included in this scope. Motor type - Submersible rewindable motor; Ratings - 1 phase - 0.37 to 1.5 kW per pump &/or 3 phase - 0.37 to 26 kW per pump; Rated speed - 2900 rpm; Enclosure class - IP 68; Nominal voltage - 1 phase - 220, 230 V / 3 phase - 380, 400, 415 V; Supply frequency - 50 Hz; Duty / Rating - S1 / Continuous; Direction of rotation - Clockwise as seen from the pump coupling side. For Soft Water Supply - Set consisting of 3 pumps (2 working + 1 standby); Flow Rate (Each pump): 250 LPM; Flow Rate (System): 1000 LPM (60 Cu. Mtr / Hr); Pressure Vessel = 1 x 100 Ltrs; Head (each pump): 55 Mtrs.
Water Treatment Plant: Design, supply, installation, testing and commissioning of pre-fabricated & packaged water treatment plant having Multigrade filter, Activated Carbon filters, Resin Treament, Anti-scalant treatment, to provide scaling free water to all buildings within the hospital, including centrifugal multistage water pump (1 working + 1 standby), connected plumbing work, control panel for auto cutoff, auto on, auto regeneration, auto rinse and auto filter mode with IP55 protection with all necessary equipment, piping and connected activities as per specification and operating conditions as mentioned by manufacturer or as directed by engineer in charge. System Capacity: 500,000 litres per day.
Hot Water Plant - for Dormitory: Supplying, installing, testing and commissioning of Electrically Operated Air-to-Water Heat Pump Hot Water System capable of heat output of COP in the range of 3.8 / 3.2 producing Hot water up to 60°C, at ambient temperature of 12°C to 45°C. Heat pump should have an IPX4 compatible control panel, designed and built in manufacturer's factory and compliant to norms for the same and compatible to support 8 units in parallel. Inbuilt 4 Ways valve for auto defrost function. The heat pump shall have an operational noise level of less than or equal to 65 dB(A). Model should be with tube in tube type heat exchanger Comprising of helical rotary inverter operated twin compressors with direct drive motor (the compressor speed shall not exceed 3000 RPM) with shell and tube type plain tube chiller as well as shell & insulated tube type integrally finned condenser, at working efficiency of minimum 80%, having heating capacity up to 60 degree centigrade, capable to withstand up to 300 ppm water hardness. The heat pump package shall include vibration mountings, copper refrigerant piping as per the latest applicable B.I.S. codes and standards, full refrigerant charge using CFC free gas, system control wiring and accessories, installed on a fabricated mild steel base frame assembled to form a compact assembly, complete with micro-processor based control panel comprising of adaptive controls, indication lights, Star-Delta / VFD starters, over-load and under-load protection, TPN isolator for termination of incoming power cable, necessary control wiring, disconnect switch, grooved (Victaulic couplings at inlet and outlet of both heat exchangers), DP switches for both heat exchangers, vibration isolation arrangements electrical panel with starter for Heat Pumps, testing of all systems post installation at Minimum Wet Bulb Temperature of 17.7 degree Celsius in January to deliver hot water at 60 degree Celsius. The scope also includes commissioning of the entire system, commissioning certificate in the name of the Engineer-in-charge, etc. complete as per manufacturing standards and to the complete satisfaction of the Engineer-in-charge. The scope includes pre-insulated S.S. storage tanks or M.S. storage tanks with ceramic lining, of capacity as mentioned below, including making inlet, outlet heavy gauge C.P. connection, temperature guages (at inlet and outlet of storage tank). The Storage Tanks duly painted with two coats of Red-Oxide and having PUF / Rockwool insulation, outer cladding of 22 guage Aluminum Sheet, control valves at inlet and outlet of Water tank, M.S. supports for the tanks with M.S. base plate, bolts and nuts for fastening the stands and support to Cement concrete blocks, testing the tanks and the entire hot water system at a constant water pressure of 5.0 Bar (50 Mtrs) each, testing of the entire system for a constant flow of hot water at 55 degree Celcius during peak winter when the Wet Bulb Temperature is 17.7 degree Celcius. Make: A O Smith / Benchmark / Jaquar / Mitsubishi. Total System Capacity: 115500 LPD; Heat Pump HWS: 6600 LPH (peak load) with 10,000 Ltr capacity S.S. storage tank. Heat pumps with electrical starter panels, level sensors, temperature sensors, thermostat, temperature gauges, pressure gauge, interconnecting G.I. 'C' class pipes with nitrile rubber cladding and aluminium cladding, complete.
Hot Water Re-circulating pumps: Supplying & erecting approved make self-priming domestic monoblock water pump with 1 H.P motor, suitable for operation on 230 volts, 50c/s. AC supply with metallic flange, and M.S. impeller delivery and following discharge: (b) 100 LPM at 14 mtrs. head suitable for 25 mm dia. delivery - Cat.III
Water Coolers: Providing & Erecting full SS Body (SS 304) Split type water cooler having storage capacity 160 to 175 Ltr.(Tank SS 304) & Cooling capacity 150 ltr. Per hour @ an ambient temp of 350 C.The outlet temp. of the water should drop by 150C within a hour,The water cooler should be comprising of hermetically sealed Reciprocating compressor with R134A, fan motor, Copper Condensing unit with company fabricated Outdoor Unit water tank surrounded by evaporating coil, thermostats, relay etc.complete with necessary copper tube & Insulation, M.S Chanel Stand with Painting for water tank & M.S. Powder Coated Stand for Outdoor unit with Installation. With DPELCB and 4 Way DB Box with accessory Three core Cord for connection.
Supplying & erecting 5 stage single reverse osmosis water purification system with M.S. powder coated frame, prefilter housing with 'O' ring presediment filter GAC filter, carbon filter suitable buster DC pump capacity 80 psi, mention with 40 psi inline type post carbon filter auto low & high pressure switches with following size of storage tank & LPH capacity & erected as directed. [C] 50 Ltr / Hr with 150 psi 2 nos booster pump
R.O. Plant for Cooling Towers & BMT Rooms + Scrubs: Supplying & erecting reverse osmosis (RO) water purification system with M.S. powder coated pedestal frame, prefilter housing carbon filter suitable buster DC pump, auto low & high pressure switches with following size of LPH capacity & erected as directed: [F] 500 LPH with 3 phase Raw water pump of 1000LPH @ 3.0 kg/cm2 (1No - Kirloskar /CRI /Lubi), Dual media filter 13"x54" - (1No), Micron catridge filter 20" x 4.0"-1No, High pressure pump 1000LPH @ 11kg/cm2 - (1No - lubi/ Shimge/ CRI), RO Membrane housing with RO membrane of 40*40 - (2 Nos), RO pressure tube 4" x 2E -(1No), 0-2400 LPH Rotameter ( 2Nos), , Dosing pump 0 -6 LPH - (1 No),. with 100 Ltr Dosing tank - (1 No), with Recovery Rate 50%.
DIALYSIS WATER TREATMENT PLANTS: Supply & fixing of extensive water purification system for Hemodialysis meeting AAMI Standard and Recommended Practices as per AAMI/RD 62:2001, The CARI Guidelines, and European Best Practice Guidelines (EBPG), consisting of Reverse Osmosis Membrane Technology which produces water with very low dissolved solids and which is also free from particulate, colloidal and organic matter and UF membrane advanced technology used for sterilization of pharmaceutical water separation of bacteria, microorganisms and Endotoxins.The system should use Hot water Sanitization Reverse Osmosis (HSRO) and state of the art Ultra Filtration (UF) membrane technologies to provide best results, UV system for permanent inactivation of microorganisms. The entire system should be on a Plug In & Plug Out Compact & portable, modular SS Skid made from SS 316L, semi-auto operated CIP and HWS, Control & Fault critical parameters with safety interlocks, Hot Water Sterilization for RO & UF Membranes, of capacity 1000 LPH. The feed water to this unit will be from the primary R.O. Treated Water Unit at terrace level, though the incoming water quality must be tested for further design of the unit as required. The scope includes - Cartridge Filter Housing; Cartridge; HPN System: Flow: 5.65 M3/Hr; Head: 12 Mtrs; M.O.C. SS 316L, operating on 415 V, 50 Hz, @ 4 kW/Hr and 2900 RPM; Secondary R.O. System having Hot Water Sanitizable Membranes & Pressure Tubes; Hot Water Sanitizable Ultra-filtration Membranes; All required instruments for the operation of the plant; All Pipes, Valves & Fittings made of SS 316L; One set of all chemicals required for the plant, etc.
Supplying and erecting approved make Instantaneous type water heater with 3Itr.capacity rust free container housed in ABS plastic body insulated with glass wool / puff insulation and 3 Kw heating elements,adjustable thermostat 300 C to 850 C with set to operate at 850 C (+ /-60 C ) auto reset indication lamps, thermal cut-out, safety valve fusible plug etc. (For Scrubs) - Premium Category (Racold,A.o.Smith,Venus)
Supplying and erecting horizontal / vertical mounting type storage water heater with copper container housed in M.S./S.S./ABS body insulated with glass wool/puff complete with heating elements,adjustable thermostats 300C to 850C, indicating lamp, safety valve, fusible plug, etc.complete erected with coach bolts, nuts. washers & cementation. (For Special Rooms only) - (B)15 Ltr-.with 2 /3K.W. heating element - Premium Category (Racold,A.o.Smith,Venus)
Supplying and erecting chromium plated heavy duty brass valve for inlet pipe of water heater 15 mm dia.)
Supplying and erecting 15mm brass non-return valve for inlet pipe of storage water heater.
Supplying and erecting dead pressure releasing valve for storage type water heater with necessary materials.
Providing & erecting fibre reinforced PVC flexible pipe with brass locking nuts & washers & clips at both ends complete erected without leakage
Drinking Water Fountains: Supply, installation, testing and commissioning of wall hanging Single level drinking water cooler & fountain with One Bottle Filling Station, having rated capacity of 8.0 GPH suitable to deliver cold water , shall include 100 micron strainer, 3 stage filtration system, single flexible bubbler guard, antimicrobial copper push pads, and and operation between 20-120 PSI, continuous chilling system suitable to R-134(a) refrigerant, adjustable thermostat control suitable for 220 - 230 V / 50-60 Hz, AC supply. Stainless Steel Brushed Finish Basin shall be designed to eliminate splashing and standing water. Water saver SS bubbler reduce waste water by 50%, with UV system of 50 LPH with G.I. Skid for mounting the UV lamp, and complete instrumentation. Cabinet finish shall be brushed stainless steel. The scope includes all necessary hardware like stop valve, trap, pipe connector to waste line and supply line.
Design, Supply, Installation, Testing and Commissioning of Sewage Treatment Plant of 400 kLD capacity based on Membrane Bioreactor Technology (MBR) with supply and erection of all Electro-mechanical and SCADA instrumentation & equipment as approved by the Engineer-in-charge. Scope also includes providing all relevant design basis reports for the system, general arrangement drawings, P&I Diagrams, Shop drawings, etc and getting approval of all prior to execution of the works,
Design, Supply, Installation, Testing and Commissioning of Effluent Treatment Plant of 50 kLD capacity based on Flocculation Technology with supply and erection of all Electro-mechanical and SCADA instrumentation & equipment as approved by the Engineer-in-charge. Scope also includes providing all relevant design basis reports for the system, general arrangement drawings, P&I Diagrams, Shop drawings, etc and getting approval of all prior to execution of the works,
Non Clog Sewage Submersible Pump - for Radioactive Waste: Providing, Supplying, installation, testing and commissioning of Non Clog Sewage Submersible Centrifugal Pump sets (water immersed, dry air filled, Class 'F' insulated TEWC motor integrally mounted on volute casing) for water duty, 3-phase, 50 Hz + 3%, 415V + 10% along with suitable foundation / installation device with cable length from pumps to panels of following: (Pump shall also have auto coupling) Material of Construction: Impeller - SS; Casing - ABS; Wearing Ring - SS; Mechanical seal - Teflon Coated; Bearing - CS / SS; Shaft with sleeve - SS; Strainer - SS, & ABS motor body. Q = 2 cum/hr; Head = 20 meter; Set comprises of 2 pumps (1 working + 1 standby).
DRAINAGE SUMP PUMP: Providing and fixing compact monoblock dry motor submersible pumps of suitable rating, with non-clog free flow open impeller, solid handling capacity of up to at least 30mm suitable for operation on 415 volts +10% , 3 Phase, 50Hz, A.C supply, speed 2900 RPM including oil chamber, guide wire for lifting & lowering of pump, M.S. galvanized lifting chain, duck foot bend complete. The pump sets shall be supplied with required accessories & as per specification with the following : (a) Water level sensing – switch type or hydraulic floats or pressure switch – with data accessible on IBMS platforms. (a) Complete piping 80 mm dia common delivery up to 12 m in heavy Duty Class 'C' G.I. – 10 meters length. (c) 80 mm dia Flap type Forged Brass Non-return valve. – 2 Nos. (d) 80mm dia Forged Brass Gate Valve. – 1 No. (e) Necessary cables from pump set to control panel (10 meters) – 1 Set (f) Electrical control panel having all necessary accessories & safety devices of standard specifications and suitable for receiving supply cable to connections within, and outlet connections for starters, and earthing outlets, complete. All best standards, as per ECBC & IS Codes to be followed and provided. Starters to be operated on cascading operations, so as to maintain maximum life cycle of each pump. – 1 Set. (g) Panels to have Modbus / BACnet connectivity, with pump performance data, pump fault data, On / Off operations, etc to be incorporated. (h) Each set consist of 2 nos. of pumps - 1 working & 1 stand by. Discharge: 25 Cu. Mtr / Hr. Head: 15 Meter (minimum).
ELECTRICAL ELW 01.00 HT PANEL Supplying, Testing & Commissioning of HT VCB panel consisting of 1 no. of 400A HT VCB as incoming and 3 nos of 400A HT VCB as outgoing. The panel should have tinned copper busbars and extensible type for future requirements. The Panel should be complete with metering and protection as per specification. (Extensible type)
ELW 02.00 TransformerSupplying, Testing, Commissioning & unloading at site, shifting to the erection site assembling, leveling, grouting, installing, field testing and commissioning of Dry type Cast resin 1600 kVA, 11KV / 415 Volts , 3 phase, 50 Hz, Dyn11 vector group, copper wound, class "H" insulation associated with winding temperature indicator / controller actuated by means of resistance temperature detector embedded in LV windings , indoor type distribution Transformer with approximately 5.5 % impedance (As per latest IS code) , tappings for On load operation with AVR - RTCC on HV side in steps of +/- 1.25 %, + 10 % & - 10 % having Suitable cu busbar connection between LV side & LT ACB with neutral brought out separately including supplying and laying copper conductor multicore control cable from transformer to HT breaker for safety tripping, suitably mounted on MS channel with all accessories and confirming to IS 11171:1985 complete with all fittings and accessories as per specifications attached etc. as required at site.
ELW 03.00 SANDWICH TYPE BUSDUCT WITH Aluminium BUSBAR Supplying, assembling, grouting in slab / wall / beam with hanging rods/ strips / supports, water proof, dust proof, vermin proof Sandwich Type busduct to be fabricated out of 14 gauge sheet. The busduct should be processed through 7 tank process. The busduct should be powder coated. All joints should be fitted with neoprene gasket. The busduct should confirm to IP 55 protection.The capacity of the busbar should be 2500 FP Amps. & should be of Aluminium, with necessary flexible, bends, reducer, expansion joints, supports and all assential accessories complete in all respect. Necessary certificate shall be required at the time of supply. The capacity of neutral bus should be equal to phase bus. (INDOOR DUTY).
Supplying, assembling, grouting in slab / wall / beam with hanging rods/ strips / supports, water proof, dust proof, vermin proof Sandwich Type busduct to be fabricated out of 14 gauge sheet. The busduct should be processed through 7 tank process. The busduct should be powder coated. All joints should be fitted with neoprene gasket. The busduct should confirm to IP 55 protection.The capacity of the busbar should be 1000 FP Amps. & should be of Aluminium, with necessary flexible, bends, reducer, expansion joints, supports and all assential accessories complete in all respect. Necessary certificate shall be required at the time of supply. The capacity of neutral bus should be equal to phase bus. (INDOOR DUTY).
Supplying, assembling, grouting in slab / wall / beam with hanging rods/ strips / supports, water proof, dust proof, vermin proof Sandwich Type busduct to be fabricated out of 14 gauge sheet. The busduct should be processed through 7 tank process. The busduct should be powder coated. All joints should be fitted with neoprene gasket. The busduct should confirm to IP 55 protection.The capacity of the busbar should be 630 FP Amps. & should be of Aluminium, with necessary flexible, bends, reducer, expansion joints, supports and all assential accessories complete in all respect. Necessary certificate shall be required at the time of supply. The capacity of neutral bus should be equal to phase bus. (INDOOR DUTY).
Supplying, assembling, grouting in slab / wall / beam with hanging rods/ strips / supports, water proof, dust proof, vermin proof Sandwich Type busduct to be fabricated out of 14 gauge sheet. The busduct should be processed through 7 tank process. The busduct should be powder coated. All joints should be fitted with neoprene gasket. The busduct should confirm to IP 55 protection.The capacity of the busbar should be 400 FP Amps. & should be of Aluminium, with necessary flexible, bends, reducer, expansion joints, supports and all assential accessories complete in all respect. Necessary certificate shall be required at the time of supply. The capacity of neutral bus should be equal to phase bus. (INDOOR DUTY).
Supply, testing & commissioning of Plug in Box with MCCB (MCCB,25KA WITH ROTARY HANDLE AND THERMAL MAGNETIC RELEASE UP TO 250A & ABOVE 250A CONSIDER MICROPROCESSOR BASED O/L, S/C, PROTECTION RELEASE.) SITC of 630A FP Plug in Box with MCCB
Supply, testing & commissioning of Plug in Box with MCCB (MCCB,25KA WITH ROTARY HANDLE AND THERMAL MAGNETIC RELEASE UP TO 250A & ABOVE 250A CONSIDER MICROPROCESSOR BASED O/L, S/C, PROTECTION RELEASE.) SITC of 500A FP Plug in Box with MCCB
Supply, testing & commissioning of Plug in Box with MCCB (MCCB,25KA WITH ROTARY HANDLE AND THERMAL MAGNETIC RELEASE UP TO 250A & ABOVE 250A CONSIDER MICROPROCESSOR BASED O/L, S/C, PROTECTION RELEASE.) SITC of 160A FP Plug in Box with MCCB
Supply, testing & commissioning of Plug in Box with MCCB (MCCB,25KA WITH ROTARY HANDLE AND THERMAL MAGNETIC RELEASE UP TO 250A & ABOVE 250A CONSIDER MICROPROCESSOR BASED O/L, S/C, PROTECTION RELEASE.) SITC of 125A FP Plug in Box with MCCB
Supply, testing & commissioning of Plug in Box with MCCB (MCCB,25KA WITH ROTARY HANDLE AND THERMAL MAGNETIC RELEASE UP TO 250A & ABOVE 250A CONSIDER MICROPROCESSOR BASED O/L, S/C, PROTECTION RELEASE.) SITC of 100A FP Plug in Box with MCCB
Supply, testing & commissioning of Plug in Box with MCCB (MCCB,25KA WITH ROTARY HANDLE AND THERMAL MAGNETIC RELEASE UP TO 250A & ABOVE 250A CONSIDER MICROPROCESSOR BASED O/L, S/C, PROTECTION RELEASE.) SITC of 80A FP Plug in Box with MCCB
Supply, testing & commissioning of Plug in Box with MCCB (MCCB,25KA WITH ROTARY HANDLE AND THERMAL MAGNETIC RELEASE UP TO 250A & ABOVE 250A CONSIDER MICROPROCESSOR BASED O/L, S/C, PROTECTION RELEASE.) SITC of 63A FP Plug in Box with MCCB
ELW 04.00 Substation Equipment and substaion Auxiliary SITC of 11 KV, 3 core Al. 240 sqmm H.T. XLPE armoured unearth cable.
SITC of H.T. cable indoor type end connection for 11 KV XLPE, 240 sq mm x 3 core cable with all accessories including lugs
Suppplying & Erecting automatic emergency light with maintenance free battery for 2 X 18 watts CFL tube. With exide make battery
Supplying & Erecting Rubber mat 1.1 KV grade ISI marked 1000 x 2000 x 6 mm size. as per IS 5424.
Supplying & Erecting Rubber mat 11 KV grade ISI marked 1000 x 2000 x 12 mm size. as per IS 5424..
Providing and erecting danger notice board for medium voltage installation to be erected as per I.S. The board should be 150 x 150 mm.
Providing and erecting danger notice board for high voltage installation to be erected as per I.S.
Providing and fixing printed instruction chart both in English & REGIONAL LANGUAGE & duly framed out on glass for treatment of person suffering from Electric shock.
Providing pair of rubber hand gloves suitable for working on 11 KV/22 KV supply.
Supplying and fixing Standard First aid box with all the Standard contents.
Supplying and instaling FIRE bucket round bottom of 9 litres capacity made out of 24 gauge G.I. sheet with extra handle at bottom duly painted white inside and Red out side with FIRE mark, filled with dry-sand and kept on existing stand provided or hung on wall hook..
Supplying & Erecting 1.5 mtr. (5') x 0.9 mtr. (3.1') x 0.6 mtr. (2.1') Floor mounted stand (For keeping 4 Nos.of buckets) made of 30 x 30 x 4 mm. angle iron welded with 4 hooks and duly painted with one coat of red lead & two coats of Approved enameled silver paints.
Supply installation testing and commissionning of Wall hooks of 22 to 25 cms. projection for keeping fire buckets made out of 15 mm. dia M.S. rod grouted in wall to a depth of minimum 15 cms.
ELW 05.00 MV Switch Gear and power Panel Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. SUBSTATION MAIN LT POWER PANEL As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. HOSPITAL NORMAL POWER PANEL As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. 325 KVAR RTPFC PANEL As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. LIFT PANEL As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. UPPER BASEMENT NORMAL POWER PANEL As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. LOWER BASEMENT NORMAL POWER PANEL As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. UPPER BASEMENT UPS POWER PANEL As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. LOWER BASEMENT UPS POWER PANEL As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. BUNKER AREA POWERPANEL As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. BUNKER AREA AHU POWER PANEL As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. BUNKER AREA UPS POWER PANEL As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. STACK PARKING PANEL-1 TO 4 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. EXTERNAL LIGHTING PANEL As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. UPS INCOMING POWER PANEL As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. UPS OUTGOING POWER PANEL As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. DORMITORY BLOCK LIGHTING POWER PANEL As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. DORMITORY BLOCK UPS PANEL As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. GROUND FLOOR NORMAL POWER PANEL-1 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. GROUND FLOOR NORMAL POWER PANEL-2 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. GROUND FLOOR NORMAL POWER PANEL-3 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. GROUND FLOOR NORMAL POWER PANEL-4 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. FIRST FLOOR NORMAL POWER PANEL-1 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. FIRST FLOOR NORMAL POWER PANEL-2 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. FIRST FLOOR NORMAL POWER PANEL-3 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. FIRST FLOOR NORMAL POWER PANEL-4 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. SECOND FLOOR NORMAL POWER PANEL-1 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. SECOND FLOOR NORMAL POWER PANEL-2 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. SECOND FLOOR NORMAL POWER PANEL-3 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. SECOND FLOOR NORMAL POWER PANEL-4 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. THIRD FLOOR NORMAL POWER PANEL-1 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. THIRD FLOOR NORMAL POWER PANEL-2 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. THIRD FLOOR NORMAL POWER PANEL-3 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. THIRD FLOOR NORMAL POWER PANEL-4 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. FOURTH FLOOR NORMAL POWER PANEL-1 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. FOURTH FLOOR NORMAL POWER PANEL-2 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. FOURTH FLOOR NORMAL POWER PANEL-3 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. FOURTH FLOOR NORMAL POWER PANEL-4 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. FIFTH FLOOR NORMAL POWER PANEL-1 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. FIFTH FLOOR NORMAL POWER PANEL-2 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. FIFTH FLOOR NORMAL POWER PANEL-3 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. FIFTH FLOOR NORMAL POWER PANEL-4 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. SIXTH FLOOR NORMAL POWER PANEL-1 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. SIXTH FLOOR NORMAL POWER PANEL-2 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. SIXTH FLOOR NORMAL POWER PANEL-3 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. SIXTH FLOOR NORMAL POWER PANEL-4 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. GROUND FLOOR UPS POWER PANEL-1 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. GROUND FLOOR UPS POWER PANEL-2 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. FIRST FLOOR UPS POWER PANEL-1 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. FIRST FLOOR UPS POWER PANEL-2 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. SECOND FLOOR UPS POWER PANEL-1 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. SECOND FLOOR UPS POWER PANEL-2 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. THIRD FLOOR UPS POWER PANEL-1 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. THIRD FLOOR UPS POWER PANEL-2 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. FOURTH FLOOR UPS POWER PANEL-1 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. FOURTH FLOOR UPS POWER PANEL-2 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. FIFTH FLOOR UPS POWER PANEL-1 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. FIFTH FLOOR UPS POWER PANEL-2 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. SIXTH FLOOR UPS POWER PANEL-1 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. SIXTH FLOOR UPS POWER PANEL-2 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. SIXTH FLOOR UPS POWER PANEL-3 As per Single line diagram
Supplying, unloading at site, shifting to site, assembling, leveling, grouting, erecting, Testing, & Commissioning compartmentalized type Panels with powder coated fabricated from CRCA sheet & folded channel totally enclosed cubical type with pad lock arrangement complete in all respect as per detail tedner specifications. The successful tenderer will have to prepare general arrangement with dimensions & get it approve through Engineer In charge / Consultant.Panels should be as per detail single line drawing with required nos of incoming and outgoing feeders and accessories complete in all respect. SIXTH FLOOR UPS POWER PANEL-4 As per Single line diagram
ELW 06.00 DG Set with AMF panel Supplying, installation, testing and commissioning of DG set of 2#2000 KVA with approximate 2655 BHP engine with enclouser & suitable alternator complete with all necessary fuel piping,Aluminium cladding, exhaust piping, control panel, Auto synchronizing, auto load sharing AMF Panel, silencer & its piping, Acoustic silencer, Alternator cable termination box suitable for Aluminium cables,initial battery charging,base frame, battery and charger complete in all respect. Scope also includes preparing necessary drawing submitting to authorities, getting their approval / sanction and final certificate including NOC from pollution board(if required) to energize the D G Set . (Rate Includes 2 Nos. of 2000 kVA Dg sets, 2 Nos. Control & AMF Panels and 1 No. of Auto synchronizing Panel etc.)
ELW 07.00 Distribution Board DISTRIBUTION BOARD Supplying, assembling, grouting, levelling, installation, Connecting,testing and commissioning of D.B of specified make but without MCB / ELMCB/MCCB etc but with all internal busbar as per requirement. TPN Distribution Board : Supplying, erecting, testing and commissioning of only TPN D.B. with space for FPMCB as incoming and space for DPELMCB and 12 SPMCB as outgoing per phase (i.e. 16 way TPN D.B.) with 16 way PPI kit
Supplying, assembling, grouting, levelling, installation, Connecting testing and commissioning of D.B of specified make but without MCB / ELMCB/MCCB etc but with all internal busbar as per requirement. Supplying, erecting, testing and commissioning of only TPN D.B. with space for FPMCB as incoming and space for DPELMCB and 8 SPMCB as outgoing per phase (i.e. 12 way TPN D.B.) with 12 way PPI kit
Supplying, assembling, grouting, levelling, installation, Connecting testing and commissioning of D.B of specified make but without MCB / ELMCB/MCCB etc but with all internal busbar as per requirement. Supplying, erecting, testing and commissioning of only TPN D.B. with space for FPMCB as incoming and space for DPELMCB and 4 SPMCB as outgoing per phase (i.e. 8 way TPN D.B.) with 8 way PPI kit
SPN Distribution Board : Supplying, erecting, testing and commissioning of SPN D.B. with space for DPELMCB as incoming and 12 SPMCB as outgoing per phase (i.e. 16 way SPN D.B.)
Supplying, erecting, testing and commissioning of SPN D.B. with space for DPELMCB as incoming and 8 SPMCB as outgoing per phase (i.e. 12 way SPN D.B.)
Supplying, erecting, testing and commissioning of SPN D.B. with space for DPELMCB as incoming and 4 SPMCB as outgoing per phase (i.e. 8 way SPN D.B.)
Supplying, erecting, testing and commissioning of SPN D.B. suitable for outdoor mounting IP 65 with space for DPMCB as incoming and 2 SPMCB as outgoing (i.e. 4 way SPN D.B.) equivalent to Hensel make cat No.. KV 7104
VTPN Distribution Board: Supplying,erecting, testing and commissioning of only VTPN D.B. having suitable space for 63 A FP MCB as incomer and 8 TP MCBs as outgoing
Supplying,erecting, testing and commissioning of only VTPN D.B. having suitable space for 100 A FP MCB as incomer and 12 TP MCBs as outgoing
MCB 's and its Accessories Supplying, Assembling, levelling, connecting & testing following MCB / RCCB / RCBO/MCCB etc in boards as specified in 7.1, 7.2, 7.3. Miniature circuit breaker single pole 6A to 32A. suitable to operate on 240V. A.C. system and having breaking capacity 10 KA to be erected in existing box. Confirming to IS 8828 / 1996 with ISI Mark.
Providing & erecting 240V MCB double pole switch for motor & inductive load (C Curve) having 10 KA breaking capacity & confirms to IS: 8828 in existing box having following capacity. 6 to 32 A DP MCB
SITC of 6A / 10A / 16A / 20A / 25A DP RCCB (30mA)
SITC of 40A DP RCCB (30mA)
SITC of 63A DP RCCB (30mA)
SITC of 6A / 10A / 16A / 20A / 25A DP RCBO (RCCB+MCB) (30mA)
SITC of 32 / 40 A DP RCBO(RCCB+MCB) (30mA)
SITC of 32 A DP RCBO(RCCB+MCB) (100mA)
SITC of 40 A DP RCBO(RCCB+MCB) (100mA)
SITC of 63 A DP RCBO(RCCB+MCB) (30mA)
SITC of 63 A DP RCBO(RCCB+MCB) (100mA)
SITC of 40 A FP RCBO(RCCB+MCB) (30mA)
SITC of 6 to 32 A TP MCB
SITC of 6 to 32 A FP MCB
SITC of 40 A FP MCB
SITC of 63 A FP MCB
SITC of Sheets steel powder coated enclosure suitable for incorporating One/Two nos. MCB.
Providing and erecting Sheet Steel powder coated MCB distribution board - flush / surface mounted fitted with busbar, neutral link, earth bar and DIN rail, Conforms to IS 8623-1 & 3, IEC 61439-1 & 3 without MCB to house appropriate nos. of MCBs Single doop IP30 4 way
Surge Protection Devices (SPD) Supplying, Assembling, levelling, connecting & testing following VSPs etc in boards 1.2KV Protection level FP, Class 's', (Imax-15KA, 8/20µS) Cat 003954
Surge Protection Devices (SPD) Supplying, Assembling, levelling, connecting & testing following VSPs etc in boards 1.2KV Protection level DP, Class 's', (Imax-15KA, 8/20µS) Cat 003974
SITC of Blank Plates
MCCB SITC of 100 A FP MCCB with Sheet steel metal enclouser
SITC of 125 A FP MCCB with Sheet steel metal enclouser
SITC of 200 A FP MCCB with Sheet steel metal enclouser
SITC of 250 A FP MCCB with Sheet steel metal enclouser
Caution Board : SITC of Caution boards of size 150 x 150 mm. to be supplied & fixed on the D.B.
ELW 08.00 CABLE TRENCH Excavation and back filling of cable trenches required for laying the cables directly buried in the ground. This includes supplying and providing cable markers at an interval of 90 Cms. The depth shall be app. 0.9mtr and the width shall be as per requirement.
Covering of cable with second class bricks or cement tiles laid cover the cable crosswise & also on both sides with covering of 7. 5 Cms. layer of sand above & below cable (16 bricks per meter)
ELW 09.00 MV Cabling Supply, testing and Laying and commissioning of XLPE steel wire/flat armoured cable of 1100 V grade of Aluminum Conductor of following sizes in ready made trench or mounted on wall with necessary clamping arrangement or in pre-laid RCC hume pipe with necessary cable identification mark to be provided at distance of 10 mt. The vertical cable on wall shall be drawn in prelaid conduit for vertical mechanical support. 300 Sq.mm x 3.5C Al. Cable
Supply, testing and Laying and commissioning of XLPE steel wire/flat armoured cable of 1100 V grade of Aluminum Conductor of following sizes in ready made trench or mounted on wall with necessary clamping arrangement or in pre-laid RCC hume pipe with necessary cable identification mark to be provided at distance of 10 mt. The vertical cable on wall shall be drawn in prelaid conduit for vertical mechanical support. 240 Sq.mm x 3.5C Al. Cable
Supply, testing and Layingand commissioning of XLPE steel wire/flat armoured cable of 1100 V grade of Aluminum Conductor of following sizes in ready made trench or mounted on wall with necessary clamping arrangement or in pre-laid RCC hume pipe with necessary cable identification mark to be provided at distance of 10 mt. The vertical cable on wall shall be drawn in prelaid conduit for vertical mechanical support. 150 Sq.mm x 3.5C Al. Cable
Supply, testing and Laying and commissioning of XLPE steel wire/flat armoured cable of 1100 V grade of Aluminum Conductor of following sizes in ready made trench or mounted on wall with necessary clamping arrangement or in pre-laid RCC hume pipe with necessary cable identification mark to be provided at distance of 10 mt. The vertical cable on wall shall be drawn in prelaid conduit for vertical mechanical support. 95 Sq.mm x 3.5C Al. Cable
Supply, testing and Laying and commissioning of XLPE steel wire/flat armoured cable of 1100 V grade of Aluminum Conductor of following sizes in ready made trench or mounted on wall with necessary clamping arrangement or in pre-laid RCC hume pipe with necessary cable identification mark to be provided at distance of 10 mt. The vertical cable on wall shall be drawn in prelaid conduit for vertical mechanical support. 70 Sq.mm x 3.5C Al. Cable
Supply, testing and Laying and commissioning of XLPE steel wire/flat armoured cable of 1100 V grade of Aluminum Conductor of following sizes in ready made trench or mounted on wall with necessary clamping arrangement or in pre-laid RCC hume pipe with necessary cable identification mark to be provided at distance of 10 mt. The vertical cable on wall shall be drawn in prelaid conduit for vertical mechanical support. 50 Sq.mm x 3.5C Al. Cable
Supply, testing and Laying and commissioning of XLPE steel wire/flat armoured cable of 1100 V grade of Aluminum Conductor of following sizes in ready made trench or mounted on wall with necessary clamping arrangement or in pre-laid RCC hume pipe with necessary cable identification mark to be provided at distance of 10 mt. The vertical cable on wall shall be drawn in prelaid conduit for vertical mechanical support. 35 Sq.mm x 3.5C Al. Cable
Supply, testing and Laying and commissioning of XLPE steel wire/flat armoured cable of 1100 V grade of Aluminum Conductor of following sizes in ready made trench or mounted on wall with necessary clamping arrangement or in pre-laid RCC hume pipe with necessary cable identification mark to be provided at distance of 10 mt. The vertical cable on wall shall be drawn in prelaid conduit for vertical mechanical support. 25 Sq.mm x 3.5C Al. Cable
Supply, testing and Laying and commissioning of XLPE steel wire/flat armoured cable of 1100 V grade of Copper Conductor of following sizes in ready made trench or mounted on wall with necessary clamping arrangement or in pre-laid RCC hume pipe with necessary cable identification mark to be provided at distance of 10 mt. The vertical cable on wall shall be drawn in prelaid conduit for vertical mechanical support. 16 Sq.mm x 4C CU. Cable
Supply, testing and Laying and commissioning of XLPE steel wire/flat armoured cable of 1100 V grade of Copper Conductor of following sizes in ready made trench or mounted on wall with necessary clamping arrangement or in pre-laid RCC hume pipe with necessary cable identification mark to be provided at distance of 10 mt. The vertical cable on wall shall be drawn in prelaid conduit for vertical mechanical support. 10 Sq.mm x 4C CU. Cable
Supply, testing and Laying and commissioning of XLPE steel wire/flat armoured cable of 1100 V grade of Copper Conductor of following sizes in ready made trench or mounted on wall with necessary clamping arrangement or in pre-laid RCC hume pipe with necessary cable identification mark to be provided at distance of 10 mt. The vertical cable on wall shall be drawn in prelaid conduit for vertical mechanical support. 6 Sq.mm x 4c CU. Cable
Supply, testing and Laying and commissioning of XLPE steel wire/flat armoured cable of 1100 V grade of Copper Conductor of following sizes in ready made trench or mounted on wall with necessary clamping arrangement or in pre-laid RCC hume pipe with necessary cable identification mark to be provided at distance of 10 mt. The vertical cable on wall shall be drawn in prelaid conduit for vertical mechanical support. 4 Sq.mm x 4c CU. Cable
Supply, testing and Laying and commissioning of XLPE steel wire/flat armoured cable of 1100 V grade of Copper Conductor of following sizes in ready made trench or mounted on wall with necessary clamping arrangement or in pre-laid RCC hume pipe with necessary cable identification mark to be provided at distance of 10 mt. The vertical cable on wall shall be drawn in prelaid conduit for vertical mechanical support. 6 Sq.mm x 3c CU. Cable
Supply, testing and Laying and commissioning of XLPE steel wire/flat armoured cable of 1100 V grade of Copper Conductor of following sizes in ready made trench or mounted on wall with necessary clamping arrangement or in pre-laid RCC hume pipe with necessary cable identification mark to be provided at distance of 10 mt. The vertical cable on wall shall be drawn in prelaid conduit for vertical mechanical support. 4 Sq.mm x 3c CU. Cable
ELW 10.00 Cable Termination SITC of Brass glands & making joint with necessary bi metalic crimping socket of long nack type connecting the same to various equipment/panel/DB etc. for the following sizes: 300 Sq.mm x 3.5C Al. Cable
SITC of Brass glands & making joint with necessary bi metalic crimping socket of long nack type connecting the same to various equipment/panel/DB etc. for the following sizes: 240 Sq.mm x 3.5C Al. Cable
SITC of Brass glands & making joint with necessary bi metalic crimping socket of long nack type connecting the same to various equipment/panel/DB etc. for the following sizes: 150 Sq.mm x 3.5C Al. Cable
SITC of Brass glands & making joint with necessary bi metalic crimping socket of long nack type connecting the same to various equipment/panel/DB etc. for the following sizes: 95 Sq.mm x 3.5C Al. Cable
SITC of Brass glands & making joint with necessary bi metalic crimping socket of long nack type connecting the same to various equipment/panel/DB etc. for the following sizes: 70 Sq.mm x 3.5C Al. Cable
SITC of Brass glands & making joint with necessary bi metalic crimping socket of long nack type connecting the same to various equipment/panel/DB etc. for the following sizes: 50 Sq.mm x 3.5C Al. Cable
SITC of Brass glands & making joint with necessary bi metalic crimping socket of long nack type connecting the same to various equipment/panel/DB etc. for the following sizes: 35 Sq.mm x 3.5C Al. Cable
SITC of Brass glands & making joint with necessary bi metalic crimping socket of long nack type connecting the same to various equipment/panel/DB etc. for the following sizes: 25 Sq.mm x 3.5C Al. Cable
SITC of Brass glands & making joint with necessary bi metalic crimping socket of long nack type connecting the same to various equipment/panel/DB etc. for the following sizes: 16 Sq.mm x 4C CU. Cable
SITC of Brass glands & making joint with necessary bi metalic crimping socket of long nack type connecting the same to various equipment/panel/DB etc. for the following sizes: 10 Sq.mm x 4C CU. Cable
SITC of Brass glands & making joint with necessary bi metalic crimping socket of long nack type connecting the same to various equipment/panel/DB etc. for the following sizes: 6 Sq.mm x 4C CU. Cable
SITC of Brass glands & making joint with necessary bi metalic crimping socket of long nack type connecting the same to various equipment/panel/DB etc. for the following sizes: 4 Sq.mm x 4C CU. Cable
SITC of Brass glands & making joint with necessary bi metalic crimping socket of long nack type connecting the same to various equipment/panel/DB etc. for the following sizes: 6 Sq.mm x 3c CU. Cable
SITC of Brass glands & making joint with necessary bi metalic crimping socket of long nack type connecting the same to various equipment/panel/DB etc. for the following sizes: 4 Sq.mm x 3c CU. Cable
ELW 11.00 Cable Tray Supply, Installation, testing and commissioning of hot dip GI ladder type cable tray with all accessories like coupler, GI nut bolts,bend, tee, reduser etc as per specification and drawings complete with all required hardware : 300 x 100 made out of 2 mm thick ladder type
Supply, Installation, testing and commissioning of hot dip GI ladder type cable tray with all accessories like coupler, GI nut bolts,bend, tee, reduser etc as per specification and drawings complete with all required hardware : 450 x 100 made out of 2 mm thick ladder type
Supply, Installation, testing and commissioning of hot dip GI ladder type cable tray with all accessories like coupler, GI nut bolts,bend, tee, reduser etc as per specification and drawings complete with all required hardware : 600 x 100 made out of 2 mm thick ladder type
Supply, Installation, testing and commissioning of hot dip GI perforated type cable tray with all accessories like coupler, GI nut bolts,bend, tee, reduser etc as per specification and drawings complete with all required hardware : 150 x 100 made out of 2 mm thick perforated type
Supply, Installation, testing and commissioning of hot dip GI perforated type cable tray with all accessories like coupler, GI nut bolts,bend, tee, reduser etc as per specification and drawings complete with all required hardware : 300 x 100 made out of 2 mm thick perforated type
Supplying , fabricating and installation of various sizes clamps for cable tray supports using available M.S. sections & rod as per drawings or instructions of engineer in charge or consultant including applying zinc chromate yellow oxide and two to three coats of required enamel paints with anchor fasteners etc.
ELW 12.00 Internal Wiring WITH MODULAR TYPE SWITCHES Wiring of points to be done in open/concealed manner in 25 mm dia medium guage Rigid PVC FRLS pipe. Wiring shall be done with FRLS type copper flexible wire of 650V/1100V. Separate pipe should be taken for circuit mains. Nos of ciruit of the same phases may be taken in same conduit .The circuit shall be laid in 25/40 mm dia medium guage rigid PVC FRLS pipe.The point rate shall include all the necessary piping and wiring from sub panel / Distribution board to switch board / Plug point & switch board to the batten holder / angle holder / connector / ceiling rose all inclusive except sub panel / Dist board. The wiring shall be done as per relevant prevailing standard. The looping of the wiring should be done in the switch boxes or light and fan point outlet boxes to avoid the junction boxes. The junction boxes and switch boxes for the ceiling light point, fan point etc shall be minimum 60/75 deep. All the necessary jarry in brick plastered walls should be done with machine cutter only , also jarry should be filled with cement, sand and wire mesh as required, the material cost for rough finish shall be included in point rate.Whenever pipes are required to be laid in flooring shall be of.Wiring should be done as per distribtion details. Each circuit should have dedicated phase, neutral & earth wire. Wire sizes to be used as under For Light Points /fan point/ wall fan / 6A 3 Pin Plug - DB to SB - 2.5sqmm for Phase & Neutral & 1.5 sqmm for Earth - SB to on board Point - 1.5 sqmm for Phase & Neutral & Earth For 6A Plug point. - 1.5 sqmm for Phase, Neutral & Earth For 6/10/16A general purpose plug point - 2.5 sqmm for Phase, Neutral & 1.5 sqmm Earth For 16A plug point for A/C, Geyser & Medical equipments - 4 Sqmm for Phase, Neutral & 2.5 sqmm Earth For 20/32A plug point - 6 sqmm for Phases, Neutral & 4 sqmm Earth No zarry will be allowed in expose brick work. The conduit shall be provided when the walls are under construction. The pipes in slab shall be laid before the slab is casted. One light point controlled by one single way 6 A switch.
Loop light point to be controlled from same switch.(Looping from first point), rate includes cost of pipe & wire as per above details.
One light point controlled by two, two way 6 A switch , rate includes cost of pipe & wire as per above details.
One ceiling fan outlet point controlled by one 6 A switch and hum free electronic type step regulator and cast iron fan box. , rate includes cost of pipe & wire as per above details.
One 6 A x 5 pin 250 Volt universal socket outlet point controlled by one 6 A switch located on switch board. , rate includes cost of pipe & wire as per above details.
6 A x 5 pin 250 Volt universal switched socket outlet point at convenient location., rate includes cost of pipe & wire as per above details.
6/16 A x 250 V switch socket point on one switch box with 2.5 sqmm flexible wires and phase and neutral and 1.5 sq nm flexible Cu. wire as earth wire. The rate should include conduiting upto DB. , rate includes cost of pipe & wire as per above details.
6/16A x 250 Volt switched socket outlet point for AC/GYSYER/MEDICAL EQUIPMENT NEAR BED with 4 sq.mm wire for phase and neutral & 2.5 sq.mm earth wire. , rate includes cost of pipe & wire as per above details.
-Do- as above but switch and socket at different location for Geyser
6/16A x 250 Volt switched socket outlet ON board point. , rate includes cost of pipe & wire as per above details.
Exhaust fan outlet point with 6A 5 pin socket controlled by one 5 single way switch located at different location. , rate includes cost of pipe & wire as per above details.
Bell point controlled by Bell push switch with Buzzer / bell of approved make. , rate includes cost of pipe & wire as per above details.
SITC computer power supply point with 2 nos of 6 amp 5 pin socket with 1 no. of 6/16 Amp. socket with 1 no 16 A Switch with indicator & wiring of computer point will be done through 2 nos.of 2.5 sq. mm Cu. wires as phase & Neutral and 1 nos. of 1.5 sq.mm.as earth wire. .( This cost includes the wiring from DB to Computer point.)
SITC of Outdoor Type 6/16A Socket with Switch, Suitable for outdoor appication (IP66)
20 A x 250 V plug & socket with interlocked switched socket, DP MCB and surface mounting box IP 66 with DIN rail for 2 module legrand make Cat no.056669 or equivalent but without cost of wiring and piping.
32 A x 250 V plug & socket with interlocked switched socket, DP MCB and surface mounting box IP 66 with DIN rail for 5 module legrand make Cat no.56669 or equivalent but without cost of wiring and piping.
32 A x 415 V plug & socket with interlocked switched socket, FP MCB and surface mounting box IP 66 with DIN rail for 5 module legrand make Cat no.56674 or equivalent but without cost of wiring and piping.
METAL CLAD SWITCH SOCKET SITC of Metal Clad Switch Socket with 10A SP MCB (2P+E)
SITC of Metal Clad Switch Socket with 20A DP MCB (2P+E)
SITC of Metal Clad Switch Socket with 20A FP ELMCB (2P+E)
SITC of Metal Clad Switch Socket with 32A FP ELMCB (P+E)
MAINS SITC of mains with 4 nos. of 10 sq mm Cu. PVC insulated FRLS flexible wire with ISI approval for 650 V/ 1100 V and 2 nos 4 sqmm Cu. PVC insulated flexible wires with ISI approval for 650 V/ 1100 V as earth wires to be drawn in 40 mm diameter rigid PVC conduit of medium guage having ISI and FIA approval with all necessary accessories.
SITC of mains with 4 nos. of 6 sq mm Cu. PVC insulated FRLS flexible wire with ISI approval for 650 V/ 1100 V and 2 nos 2.5 sqmm Cu. PVC insulated flexible wires with ISI approval for 650 V/ 1100 V as earth wires to be drawn in 25 mm diameter rigid PVC conduit of medium guage having ISI and FIA approval with all necessary accessories.
SITC of mains with 2 nos. of 4 sq mm Cu. PVC insulated FRLS flexible wire with ISI approval for 650 V/ 1100 V and 1 no 4.0 sqmm Cu. PVC insulated flexible wires with ISI approval for 650 V/ 1100 V as earth wires to be drawn in 25 mm diameter rigid PVC conduit of medium guage having ISI amd FIA approval with all necessary accessories.
SITC of mains with 2 nos. of 6 sq mm Cu. PVC insulated FRLS flexible wire with ISI approval for 650 V/ 1100 V and 1 no 4.0 sqmm Cu. PVC insulated flexible wires with ISI approval for 650 V/ 1100 V as earth wires to be drawn in 25 mm diameter rigid PVC conduit of medium guage having ISI amd FIA approval with all necessary accessories.
SITC of mains with 2 nos. of 10 sq mm Cu. PVC insulated FRLS flexible wire with ISI approval for 650 V/ 1100 V and 1 nos 6.0 sqmm Cu. PVC insulated flexible wires with ISI approval for 650 V/ 1100 V as earth wires to be drawn in 25 mm diameter rigid PVC conduit of medium guage having ISI and FIA approval with all necessary accessories.
SITC of mains with 2 nos. of 2.5 sq mm Cu. PVC insulated FRLS flexible wire with ISI approval for 650 V/ 1100 V and 1 no 2.5 sqmm Cu. PVC insulated flexible wires with ISI approval for 650 V/ 1100 V as earth wires to be drawn in 25 mm diameter rigid PVC conduit of medium guage having ISI amd FIA approval with all necessary accessories.
SITC of mains with 2 nos. of 1.5 sq mm Cu. PVC insulated FRLS flexible wire with ISI approval for 650 V/ 1100 V and 1 no 1.5 sqmm Cu. PVC insulated flexible wires with ISI approval for 650 V/ 1100 V as earth wires to be drawn in 25 mm diameter rigid PVC conduit of medium guage having ISI amd FIA approval with all necessary accessories.
Supplying , fabricating and installation of various sizes junction boxes made out to 14 gauge sheet with all necessary accessories & hardware etc All the necessary fabrication required will be included in the scope of contractor. Scope also includes two coat of primer and two coat of paining of each items on all the sides complete in all respect.
SITC of of 3 compatement 225 mm x 38 mm, 1.6mm thick, under floor metal trunking/race way with all accessories made out of hot dip pre galvanized metal coated steel sheet.
SITC of of 1 compartement 100 mm x 38 mm, 1.6 mm thick, under floor metal trunking/race way with all accessories made out of hot dip pre galvanized metal coated steel sheet.
SITC of 3 compartment Access outlet / service box of 250 x 250 x 60-75 mm with all accessories made out of high pressure die cast material suitable for above race ways .
SITC of 2 compatement 100 mm x 50 mm wall trunking/race way with cover and all accessories made out of PVC .
ELW 13.00Light Fixtures and Fans Supplying and erecting, testing and commissioning of COB based pendant downlight luminaire equilavent Regent make Rea 152 with system power: 25 W, Luminous flux of luminaire 2500 lm, 100 Lm/W, Colour temperature of 4000 K, Neutral white, SDCM 3, CRI > 80, 230 V constant current driver, 70% of luminous flux after 50,000 operating hours; Energy efficient LEDs, Direct light emission, Luminaire housing in aluminium, Polyester powder black coloured coat applied over a 5- stage pre-treatment, Clear glass cover, beam angle of 36°, ZHLS (ZERO HALOGEN LOW SMOKE) internal wiring, Electronic control gear, Protection class II, IP 20
Supplying and erecting, testing and commissioning of Ceiling mounting downlight equilavent Regent make Zing with LED (Light Emitting Diode), system power of 15W, luminous flux of luminaire 1650 lm, 110 Lm/W, colour temperature of 4000K, neutral white, CRI > 80, R9>20, THD<5%, P.F>0.95, Driver Efficiency>88%, SDCM<3, 70% of luminous flux after 50,000 operating hours, 230V constant current driver, direct light emission, housing in die-cast aluminium, polyester powder coated white applied over a 5 stage pre-treatment, opal protuded for uniform illumination, LG7 Complaince, integral electronic control gear, Protection class II , IP 20
Supplying and erecting, testing and commissioning of COB based pendant downlight equilavent Regent make WE-1 Rea 150 with HPE (HighPerformance Efficiency), system power: 25W, Luminous flux of luminaire 2250 lm, Colour temperature of 3000K, Warm white, CRI > 90, 230V constant current driver, 70% of luminous flux after 50,000 operating hours; energy-efficient LEDs, direct light emission, luminaire housing in aluminium, Polyester powder-black coloured coat applied over a 5-stage pre-treatment, clear acrylic with wall-washer aluminium reflector , control gear, Protection class I, IP 20
Supplying and erecting, testing and commissioning of 20W 4' Feet LED Wall / Surface / Ceiling/Pendent luminaire equilavent to Regent make Vela J with HPE (High-Performance Efficiency) LED (Light Emitting Diode) system power: 20 W, Luminous flux of luminaire 3000 lm, Colour temperature as per architect's input, Neutral white, CRI > 80, R9>20, THD<5%, P.F>0.95, Driver Efficiency>88%, SDCM<3, 230 V constant current driver, 70% of luminous flux after 50,000 operating hours; Energy efficient LEDs, Direct light emission, Luminaire profile in aluminium, Polyester powder white coloured coat applied over a 5- stage pre-treatment, snap-fit linear prismatic diffuser for a homogenous light distribution, UGR<19, ZHLS (ZERO HALOGEN LOW SMOKE) internal wiring, Electronic control gear, Protection class II, IP 40
Supplying and erecting, testing and commissioning of 36W 4' Feet LED Wall / Surface / Ceiling/Pendent luminaire equilavent to Regent make Vela J with HPE (High-Performance Efficiency) LED (Light Emitting Diode) system power: 36 W, Luminous flux of luminaire 5040 lm, Colour temperature as per architect's input, Neutral white, CRI > 80, R9>20, THD<5%, P.F>0.95, Driver Efficiency>88%, SDCM<3, 230 V constant current driver, 70% of luminous flux after 50,000 operating hours; Energy efficient LEDs, Direct light emission, Luminaire profile in aluminium, Polyester powder white coloured coat applied over a 5- stage pre-treatment, snap-fit linear prismatic diffuser for a homogenous light distribution, UGR<19, ZHLS (ZERO HALOGEN LOW SMOKE) internal wiring, Electronic control gear, Protection class II, IP 40
Providing and erecting PVC body surface or pendent mounting LED Bulk type 9 watt Lighting Fitting with electronic driver. And lumen output from luminaire 720lm , input voltage range 90-300VAC , 50Hz cool white(3000 to 6500k), inbuilt driver, -20degC to +60degC working temperature, AL frame with Beam Angle 120deg .
Providing and erecting Approved make Ceiling fan with double ball bearing ISI mark with BLDC Motor 1200 mm. sweep (Approx 35W) complete, canopy and 30 cms. down rod erected on existing hook or clamp with 24/0.2, 3 core flexible wire with earthing [ Make shall be approved by Engineer in charge] BEE 3 star rated.
Supplying and erecting 19/20mm. nominal bore Medium Class M.S. Pipe down rod erected duly painted for fan.
Supplying and erecting approved make low noise decorative exhaust fan having size 200mm with 1350 RPM with square frame.ABS body with inbuilt lowers & square frame.
Supplying and erecting single phase approved make industrial exhaust fan suitable for medium duty ring mounted low noise operation suitable for medium duty having following dia size and maximum speed in RPM. (A)305 mm dai 900 RPM (CAT-2)
Supplying and erecting single phase approved make industrial exhaust fan suitable for medium duty ring mounted low noise operation suitable for medium duty having following dia size and maximum speed in RPM. (B)380 mm dai 900 RPM (CAT-2)
Supplying and erecting single phase approved make industrial exhaust fan suitable for medium duty ring mounted low noise operation suitable for medium duty having following dia size and maximum speed in RPM. (C)380 mm dai 1400 RPM (CAT-2)
Supplying and erecting single phase approved make industrial exhaust fan suitable for medium duty ring mounted low noise operation suitable for medium duty having following dia size and maximum speed in RPM. (D)450 mm dai 900 RPM (CAT-2)
Supplying and erecting single phase approved make industrial exhaust fan suitable for medium duty ring mounted low noise operation suitable for medium duty having following dia size and maximum speed in RPM. (E)450 mm dai 1400 RPM (CAT-2)
Supplying and erecting single phase approved make industrial exhaust fan suitable for medium duty ring mounted low noise operation suitable for medium duty having following dia size and maximum speed in RPM. SITC of suitable M.S. louver shutter of the Exhaust fan.
ELW 14.00 EARTHING Supplying & erecting in earthpit of minimum bore dia. 225mm size approved make Safe Earthing Electrode consisting Pipe-in-Pipe Technology as per IS 3043-1987 made of corrosion free hot dipped G.I.Pipes having Outer pipe dia of 80 mm having 80-200 Micron galvanising, Inner pipe dia of 40 mm having 200-250 Micron galvanising, connection terminal dia of 14 mm with constant ohmic value surrounded by highly conductive compound with high charge dissipation suitable for following type of applications with chamber and heavy duty cover.(approved make OEM has to submit test certificate including value of earth resistane of installation. -Length of Pipe : 3 Mtrs. -Back filling Compound :2 nos Bags of 25 Kg
Supplying & erecting earth pit of minimum bore dia.150mm size approved make Earthing Electrode consisting Pipe-in-Pipe Technology as per IS 3043-1987 made of corrosion free hot dipped G.I.Pipes having Outer pipe dia of 50mm having 80-200 Micron galvanising, Inner pipe dia of 25 mm having 200-250 Micron galvanising, connection terminal dia of 12mm with constant ohmic value surrounded by highly conductive compound with high charge dissipation suitable for following type of applications with chamber and heavy duty cover.(approved make OEM has to submit test certificate) & having back filling compound of (B) Inner chemical (CCM Compound)- Resistivity:- 0.2 / meter testing as per IEC 62561-2017, Voltage drop:- < 1 volt at no load & dry form, Sulphar content:- <2%(C) Back fill Compound :- Earthing compound should be capable to retain moisture for long time Necessary test report must be submitted. -Length of Pipe : 3 Mtrs. -Back filling Compound :2 nos Bags of 25 Kg
Earth wire/strips : Supply and laying cu. earthing required size strips for interconnecting the earthing stations, panels, DB's etc. in built up trenches, on walls/ceiling, buried in ground generally as specified and shown on drawings complete with : a) Fixing accessories. b) Corrosion protection of buried conductors with bituminous coating and covered with PVC tapes. 25 x 3 mm/ 32X6mm / 50x6mm CU. strip/ 38x6 Cu earth link
SITC of No.8 gauge bare cu. earth wire Complete in all respect with all reuqired accessories.
ELW 15.00 Miscellaneous MISCELLANEOUS PVC PIPES Supplying and laying following sizes PVC pipe of approved make including excavation of trenches, laying the pipe as per layout and drawing and re-filling the trenches etc. complete as directed. Heavy gauge pipe in Open / Concealed manner minimum 25 mm dia with GI pulling wire.
Supplying and laying following sizes PVC pipe of approved make including excavation of trenches, laying the pipe as per layout and drawing and re-filling the trenches etc. complete as directed. Heavy gauge pipe in Open / Concealed manner minimum 32 mm dia with GI pulling wire.
Supplying and laying following sizes PVC pipe of approved make including excavation of trenches, laying the pipe as per layout and drawing and re-filling the trenches etc. complete as directed. Heavy gauge pipe in Open / Concealed manner minimum 40 mm dia.
Supplying and laying following sizes PVC pipe of approved make including excavation of trenches, laying the pipe as per layout and drawing and re-filling the trenches etc. complete as directed. Heavy gauge pipe in Open / Concealed manner minimum 50 mm dia.
Supplying and laying following sizes PVC pipe of approved make including excavation of trenches, laying the pipe as per layout and drawing and re-filling the trenches etc. complete as directed. Heavy gauge pipe in Open / Concealed manner minimum 75 mm dia.
Supplying and laying following sizes PVC pipe of approved make including excavation of trenches, laying the pipe as per layout and drawing and re-filling the trenches etc. complete as directed. Heavy gauge pipe in Open / Concealed manner minimum 90 mm dia.
Supplying and laying following sizes PVC pipe of approved make including excavation of trenches, laying the pipe as per layout and drawing and re-filling the trenches etc. complete as directed. Heavy gauge pipe in Open / Concealed manner minimum 110 mm dia.
Fire Stopper SITC of Equivalent to Hilti make Hilti Mineral Wool Board System Providing Fire resistant board system with minimum 2 hours fire rating when tested in accordance with BS 476 part 20 for horizontal openings in fire rated floors or slabs and vertical openings in walls for passing service shafts. The fire resistant board system shall comprise of a mineral wool board coated with an ablative coating CP 670 at 0.7mm dft. The mineral wool board should be of min.160 kg/m3 density. All contact surfaces and cavities shall be sealed with a joint filler CP 606. The service lines could be of various types like electrical cables trays, metal pipes, etc. The product shall be age tested for as per Dafstb and DIBT standards. The product should be tested for mold resistance rating of 0 as determined by ASTM G21-96 and should have a VOC content of approx. 38 g/l as per LEED 2009. The product shall bear the UL and FM approval logo on the packing where applicable.
SITC of Fire stop mortar system , with minimum 2 hours fire rating when tested in accordance with UL 1479/ASTM-E 814 standards, for horizontal openings in floors or slabs after passing service lines like cables/cable bundles, cable trays etc. The system shall be UL listed & classified and product shall bear the UL and FM approval logo on the packing. If none of UL test certificate comply with actual application, an EJ document (as per IFC Guidelines) prepared by a qualified personnel and based on nearest third party tested & approved systems like UL test certificates & in accordance with IFC guidelines shall be producted by manufacturer. A firestop submittal shall be produced by manufacturer , in accordance with approved passive fire protection method statement, for technical approval. Firestop installation shall be done by manufacturer's Accredited Firestop Speciality Contractor (HAFSC) and in accordance with manufacturer guidelines and UL system test certificates or approved EJ document. .
SITC of Provide expanding firestop foam on both sides of wall, with minimum 2 hours fire rating when tested in accordance with UL 1479/ASTM-E 814, for horizontal/ vertical openings in floors / wall or slabs made of concrete/ masonry or Gypsum after passing service lines like cable trays or cables/cable bundlesThe system shall be UL listed & classified and product shall bear the UL and FM approval logo on the packing. The system shall be UL listed & classified and product shall bear the UL & FM approval logo on the packing. If none of UL test certificate comply with actual application, an EJ document (as per IFC Guidelines) prepared by a qualified personnel and based on nearest third party tested & approved systems like UL test certificates & in accordance with IFC guidelines shall be producted by manufacturer.Firestop installation shall be done by manufacturer's Accredited Firestop Speciality Contractor (HAFSC) and in accordance with manufacturer's guidelines and UL system test certificates or approved EJ document.
SITC of intumescent based coating on cables/bunch cables & cable tray for at least 1 mtr in every 14 mtrs for horizontal runs and to entire length of vertical runs . The coating shall have a density in the range of 1.2 to 1.4 Kg/ L. The coating shall be non-toxic, asbestos and halogen free and shall have good mechanical strength. Firestop installation shall be done by manufacturer's Accredited Firestop Speciality Contractor (HAFSC) and in accordance with manufacturer's guidelines .
ELW 16.00 External Lighiting Poles Supply & installation of 3.6 Mtr long, 139 mm outer uniform dia. GI street light pole with medium class ( minimum 4.8 mm thick) GI pipe with zinc coating and two coats of paint / pu coats of approved shade complete as approved by architects with base plate as per requirement complete in all respect as per drawing. Junction box shall be in concealed manner (inside the pole)with one no 2A SP mcb and 5 way 16A Connector strip suitable to terminate armoured cables. Adequate size cutout with opeanable hinged door should be provided on pole with necessary gasket to ensure water tight arrangement for pulling cables and installation of mcb, connectors etc, complete in all respect as per requirement and instruction of engineer in charge and tender drawing.Scope also includes necessary foundation, Spiral earthing, cable entry pipes, minumum 2.5sqmmx 3 core round flexible wire from junction box to light fixture etc,.
Supply & Installation of GI Pole made out of B CLASS ERW G.I. PIPE for road having Height - 7.5 metre (Single Arm) having thickness of 4.5 mm, 139.7 mm outer uniform dia., with base plate of 450 x 450 x 16 mm with stiffener plate with 1 Nos Seprate integral type junction box ( For Street light) , with complete concrete foundation with necessary reinforcement, j bolt, necessary hardware as per detail, with necessary Reducer / Coupler / for fixing of light fixtures & Hinged access door with welded chain between pole and hinged door with Allen key require to access the integral junction box, Fabrication work complete in all respect as per given detail with one coat of zinc oxide complete in all respect as per Drawing. Rate shall be including two coats of PU paint of shade as per drawing or as directed by Architect ( effective length should be 7500mm above GF) (Sample to be approved) 1) with necessary 1 Nos 6 way connector, 1 Nos. 2A SP MCB with din rail channel, 8mm thk. Hylem sheet, 12x2 mm thk. GI Patti Clamp, with necessary required hardware, necessary welding & Fabrication work (if required) complete in all respect. 2) 40 mm diameter GI pipe for each cable entry . 3) Wiring up to the light fixture from the junction box using 3nos. x 1.5 sq.mm.flexible copper wires of specified make for each fixture. 4) Concrete foundationwith base plate. 5) Excavation for erection of poles as per drawing complete in all respect. 6) Pole Numbering to be carried out by contractor as instructed by Site in charge as per Client's requirement.
Supply & Installation of GI Pole made out of B CLASS ERW G.I. PIPE for road having Height - 7.5 metre (Double Arm) having thickness of 4.5 mm, 139.7 mm outer uniform dia., with base plate of 450 x 450 x 16 mm with stiffener plate with 1 Nos Seprate integral type junction box ( For Street light) , with complete concrete foundation with necessary reinforcement, j bolt, necessary hardware as per detail, with necessary Reducer / Coupler / for fixing of light fixtures & Hinged access door with welded chain between pole and hinged door with Allen key require to access the integral junction box, Fabrication work complete in all respect as per given detail with one coat of zinc oxide complete in all respect as per Drawing. Rate shall be including two coats of PU paint of shade as per drawing or as directed by Architect ( effective length should be 7500mm above GF) (Sample to be approved) 1) with necessary 1 Nos 6 way connector, 1 Nos. 2A SP MCB with din rail channel, 8mm thk. Hylem sheet, 12x2 mm thk. GI Patti Clamp, with necessary required hardware, necessary welding & Fabrication work (if required) complete in all respect. 2) 40 mm diameter GI pipe for each cable entry . 3) Wiring up to the light fixture from the junction box using 3nos. x 1.5 sq.mm.flexible copper wires of specified make for each fixture. 4) Concrete foundationwith base plate. 5) Excavation for erection of poles as per drawing complete in all respect. 6) Pole Numbering to be carried out by contractor as instructed by Site in charge as per Client's requirement.
STREET LIGHT FIXTURE Supplying, erecting, connecting, testing and commissioning of following type posttop Light Fixture with all necessary Hadware, Internal Wiring with Lamp,Ballast etc. all required accessories Complete in all respect. Posttop Light fixture-Keselec VALE 50W LED ASYM 3000K DECORATIVE Posttop IP 66 OPTIC LUMINAIRE WITH ALUMINIUM BODY CLEAR ACCYLIC
Supplying, erecting, connecting, testing and commissioning of following type street Light Fixture with all necessary Hadware, Internal Wiring with Lamp,Ballast etc. all required accessories Complete in all respect. Keselec VALE 50W LED ASYM 3000K DECORATIVE Suspended IP 66 OPTIC LUMINAIRE WITH ALUMINIUM BODY CLEAR ACCYLIC
Supplying, erecting, connecting, testing and commissioning of 1000 mm.height , 18W and above Bollard with all necessary Hadware, Internal Wiring with Lamp,Ballast etc. all required accessories Complete in all respect with base plate & foudation bolts Bollard -Make - Keselec make Vio or equivalent complete in all respect LED lamp, Integral Ballast, IP65, foundation, bolts etc.
ELW 17.00 Lighitning Protection SITC of 8 mm dia solid Aluminium Conductor for roof top mesh grid and tested as per IEC 62561- 2 conducted in the Govt. accredited thirty party laboratory to meet the requirement of IS/IEC 62305 with Required Accessories - Aluminium Holding clamp at every 1 mtr distance, Aluminium/SS cross splicer at every crossing of Alu. conductor, Expansion piece with connectors at every 20 mtr distance, Aluminium straight Splicer to connect conductors. All Accessories should be tested as per IEC 62561-1 2018 Cl. 6.3 for conditioning & Ageing Test & 6.4 for Lightning impulse current withstand test: 100 kA of 10/350µs waveform(Ageing & Electrical test ) conducted in a sequence manner & tested in the Govt. accredited Third party laboratory to meet the requirements of IS/IEC 6230
Supply, installation, testing and commissioning of test link complete with inter connections between aluminium round conductor & GI strip or GI strip to GI strip all fixing accessories etc required for complete installation, Complete in all respect with all required accessories.
SITC of Vertical Air Termination Solid aluminium with Base- 10 mm dia and 1000 mm long. Air Termination Base tested for conditioning, Ageing Test & Lightning impulse current withstand test: 100 kA of 10/350µs waveform in an accredited Third party laboratory as per 6.3 & 6.4 of IEC 62561-1 2017 protocol with MAST 34mm dia 3000 mm long- Cold Galvanized
Down Conductor System SITC of 10 mm MS Round Solid Conductor having smooth surface Should be tested and use exclusively for lightning protection (Vertical Riser/Down Conductor which shall be concealed in Column) to meet the requirement of IS IEC 62305 With Accessories - Earthing stud of dimension SS-75mm OD plate with 10mm dia tail connector used in structural steel ring earthing system to meet the requirements of IS/IEC 62305. (For Interconnecting the Column and the Terrace AL Conductor / Strip/Flat), SS Cross Connector to connect Earth fixing point to vertical raiser/Down conductor, SS Straight Splicer at every 4 Mtr to connect MS conductor in column, Bonding /Rebar Clamp at every 3 mtr suitable for interconnecting round conductor with reinforcement inside the concrete for structural earthing system, SS connector -To connect external conductor 8- 10 mm with earth fixing point. All Accessories should be tested as per IEC 62561-1 2018 Cl. 6.3 for conditioning & Ageing Test & 6.4 for Lightning impulse current withstand test: 100 kA of 10/350µs waveform(Ageing & Electrical test ) conducted in a sequence manner & tested in the Govt. accredited Third party laboratory to meet the requirements of IS/IEC 6230
SITC of Lightnig counter - To count no of lightning strike & it can record the date and time of the lightning incident also tested as per IEC 62561-6. Complete in all respect with all required accessories.
ELW 18.00 UPS Supplying and erecting approved make online Un-interruptible Power Supply system with IGBT Based rectifer and Inverter & sealed maintenance free batteries. Three phase Input and Three Phase output with Inbuilt Isolation transformer with Unity (KVA=KW) load power factor with battery, over under voltage output with over load & short circuit protection equipment. The system housed in CRC sheet duly powder coated paint with following capacity & with Following size of batteries for 30 Min Backup (Minimum 230400 VAh) 250 KVA UPS with 160 AH, 120 Nos. Battery (Including Five year free maintenance with guarantee)
Supplying and erecting approved make online Un-interruptible Power Supply system with IGBT Based rectifer and Inverter & sealed maintenance free batteries. Three phase Input and Three Phase output with Inbuilt Isolation transformer with 0.9 load power factor with battery, over under voltage output with over load & short circuit protection equipment. The system housed in CRC sheet duly powder coated paint with following capacity & with Following size of batteries for 30 Min Backup (Minimum 28800 VAh) 30 KVA UPS with 120 AH, 20 Nos. Battery (Including Five year free maintenance with guarantee)
ELW 19.00 Exit sign SITC of Self contained single sided exit sign for wall / ceiling / pendant cantilever mounting with 3 W LED tube for Non maintained battery backup emergency lighting for 2 hours duration.Prolite make or approved equal in quality and design.
SITC of Self contained double sided exit sign for wall / ceiling / pendant cantilever mounting with 3 watt LED tube, Non maintained battery backup 2 hours duration Prolite make or approved equal in quality and design.
ELW 20.00 Solar Plant Supply, Installation, Testing & Commissioning of following size of Grid Tied Solar Power Plant with Solar Panels (ALMM approved): Frame Material : Anodized Aluminum alloy Frame With Twin Wall Profile, Front Cover : High Transmission Low-Iron Tempered Glass (AR Coated), High efficency and positive power tolerance Pmax: 0/+5, Module Efficiency should be approx. 18%-21%, Normal operating temperature 45'C, Junction Box with Waterproof IP67 & MC4 Compatible and Enclosed with Bypass diodes, 100% Electroluminescence test to ensure error free Modules, Thep. temp. co-efficient of the PV module shall equal or better than -0.45%/degree C. Solar PV modules of minimum fill factor 75% to be used. Unit Production:- 4 to 5 Unit /kw /day (Actual)(1Year Avg) With 10 year Product warranty and 25 year Linear Power Warranty., Solar Inverter: MPPT Range: 80-1000 V, Max efficiency: 97.5% - 98.9%, O/p Frequency: 50/60Hz, Operating Altitude (m) ≤4000, O/p Power Factor: ~1, O/P THDi: <3%, Operating Tempreture Range: -25~60°C, Anti-islanding Protection: Integrated, Input Reverse Polarity Protection Integrated, Insulation Resistor Detection Integrated, Residual Current Monitoring Unit Integrated, Output Over Current Protection Integrated, Output Short Circuit Protection Integrated, Output Over Voltage Protection Integrated, Protection Degree: IP65, User Interface LCD & APP,Datalogger & Communication: GPRS / Wi-Fi, Module Mounting Structure: Seamless Box Pipe / 'C' Channel of suitable size for rooftop solar installations with good stability agaist wind & weight load., Hot Dipped Galvanized steel coils. suitable arrangement for base plate for foundation , solar panel mounting, the structure should be suitable for carry the load of solar panel,wiring, sprinkler system etc. with necessary foundation work/wall mount, j bolt, anchor fastner etc. the nut bolt used for installtion of stucture should be (SS 304) quality. and Balane of System with necessary Swithgears (Suitabel size and protection of ACDB & DCDB), inter connecting wiring, earthing system, lightining arrester system, all liasoning work with various gov. dipartment like state nodal agency,DISCOM & CEIG is included in agency scope (Excluding GEDA Application fees, Solar connectivity Charges, Meter connectivity Charges, Meter testing Charges.) Grid Tied Solar Power System: 101 - 250 kW (3 - phase)
ELV SYSTEMS Sec.1.0 Telephone and Data Networking Providing & erecting main Distribution (MDF) indoor type, back mounted frame as per DoT standard approved with krone strips (e) Suitable for 100 pair
Providing & erecting main Distribution (MDF) indoor type, back mounted frame as per DoT standard approved with krone strips (e) Suitable for 200 pair
Supply & fixing of 500 pair MDF unit with required modules in a fabricated CRCA powder coated junction box of size 450x250x100 with two no. of pad-lock, provision for earthing, as per technical specification etc. as required.
Supplying & erecting approved make Telephone Cable electrolytic copper conductor PE insulation twisted in two pairs & wrapped with FR PVC tape & sheathed with FR PVC or HFFR outer jacket suitable for telephone wiring & confirming to C-DOT erected in existing pipe. of following size of conductors & nos. of pairs. With necessary connections. A Conductor Size 0.5 mm. (b) Armoured. (Jelly Filled) (4) One Hundred Pairs.
Supplying & erecting approved make Telephone Cable electrolytic copper conductor PE insulation twisted in two pairs & wrapped with FR PVC tape & sheathed with FR PVC or HFFR outer jacket suitable for telephone wiring & confirming to C-DOT erected in existing pipe. of following size of conductors & nos. of pairs. With necessary connections. A Conductor Size 0.5 mm. (b) Armoured. (Jelly Filled) (3) Fifty Hundred Pairs.
Supply, Installation, Testing & Commissioning of CAT6 UTP 23AWG Solid: Per Meter (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of Jack Cat 6 Keystone UTP (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of Face Plate - Single (Keystone Jack,square) (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of Face Plate - Dual (Keystone Jack,square) (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of Patch Panel Cat 6 UTP Keystone Type- 24 Port-Fully Loaded (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of CAT6 UTP 24AWG PATCH CORD:1M,Plug 30U' Snag less (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of CAT6 UTP 24AWG PATCH CORD:2M,Plug 30U' Snag less (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of 12-core Outdoor Cable - Corrugated Steel tape Armored, Loose-tube, Gel-filled, 9/125 Single Mode OS2 Fiber Cabel where ever required in prelaid conduits / RCC hume pipes/HDPE/DWC, whichever maybe available, as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of 19-inch 24 Port LIU, rack mount patch panel, 1U, loaded with 2 X 12 Ports Adaptor Connector Panel & with Splice Tray, inclusive of all mechanical accessories with out pigtail, as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of PIGTAIL LC SM SIMPLEX LENGTH- 1m (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of PATCH CORD LC-LC SM DUPLEX LENGTH- 3m (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Networking Enclosures & Accessories Supply, Installation, Testing & Commissioning of ruggedized, IP54 rated outdoor Pole/Wall mountable 9U enclosure for housing power supplies, fiber LIUs, and industrial networking switch, with suitable provisions for DIN rails, cable management as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of 15U (600W X 600D)MM Wall mount closed rack with front glass door, fan tray on top, perforated rear doors, keyboard tray with shelf. Casters & 2 nos vertical power strip with std, as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of 24U (600W X 600D)MM Wall mount closed rack with front glass door, fan tray on top, perforated rear doors, keyboard tray with shelf. Casters & 2 nos vertical power strip with std, as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of 42U (800W X 800D) floor mount closed rack complied with UL, CSA, TUV, EIA 310, DIN 41494, DIN 41494, ISO 9001, ISO 14001, IEC 297 and current industry practices, CRCA Steel Door - Plain, Vented at Bottom, Fully perforated at front and rear side, with screw fitted side panels. 19" L type mounting angles at front and rear, top and bottom cover with cable entry provision, with required accessories as per technical specification etc. as required.
Active Components- Data & Voice Networking TYPE-1 Core Switch Layer 3 features switch: minimum 24 × 1/10G SFP+ slots, 6 × 40G QSFP+ slots With redudant power supply & standard mouting hardware & accessories. Core Switch for Server room complete as per technical specification etc. as required.
Type 2 Switch: 24 Port POE Supply, Installation, Testing & Commissioning of Layer 2 Manageable, Stackable Networking switch having 24 x 10/100/1000Tx ports, all 24 ports shall be capable of providing PoE+ as per 802.3at, switch having a PoE power budget of minimum 700 Watts, minimum 6 SFP+ ports complete as per technical specification etc. as required.
Type 3 Switch: 24 Port Non POE Supply, Installation, Testing & Commissioning of Layer 2 manageable networking switch, 24 x 10/100/1000Tx ports,minimum 6 SFP+ ports complete as per technical specification etc. as required.
Type 4 Switch: 48 Port POE Switch Supply, Installation, Testing and Commissioning of Layer 2 Manageable, Stackable Networking switch having 48 nos. 10/100/1000 Base-T ports, all ports capable of providing PoE+ as per 802.3at, switch having a PoE power budget of minimum 1400 Watts, additional minimum 6 SFP+ ports complete as per technical specification etc. as required.
Type 5 Switch: 48 Port Non - POE Supply, Installation, Testing and Commissioning of Networking Switch (Access Switch) having 48 nos. 10/100/1000 Base-T ports, stacking, additional minimum 6 SFP+ ports, with all licenses from day 1 and inclusive of dual redundant hot-swappable power supplies installed from day 1, complete as required and as per technical specifications.
Supply, Installation, Testing and Commissioning of 10G SFP+ LR singlemode transceivers, 1310nm, duplex LC termination supporting distance upto 10000 mtrs, inclusive of any hardware or interfaces such as modules for populating SM-LC transceivers complete as required.
Supply, Installation, Testing and Commissioning of Wireless indoor Access Point supporting Dual band with Wi-Fi 6 operation with MIMO support 4x4, 3 spatial streams, One 10/100/1000 BASE-TX auto-sensing (RJ45) PoE port, as per technical specification etc. as required.
Wireless Controller Supply, Installation, Testing and Commissioning of Wireless Controller & WIPS : Wireless controller alongwith WIPS capable of supporting min. 100 access points, inclusive of licence costs for supplied Access Points from day-1. Centralized Virtual Controller based architecture, complete as required and as per technical specifications
Supply, Installation, Testing & Commissioning of Digital / PCM / TDM EPABX System having SMT design, system with flexible universal slots. Inbuilt Auto attendant facility, Minimum 15 Nos. conference, Analog extension line, Calling GSM, E&M line, PRI / EI & VOIP program me through Analog telephone digital key from Ethernet, public address cord, shall have unrestricted simultaneous dialing facility, QSIG protocol on PRI, 95 / STD / ISD / Local-Locking, Class of Service, Quick Dial-Single Digit dialing of any two external number, Once only ring device, Boss/Secretary-Do not disturb Facility, Power Down Mode, Hot Line, Hot Outward Dialing, Day Night Mode, Auto Call Back, Barge-in, Call Pick Up & Call Transfer, Call transfer while Ringing with Voice Guide System, (DISA), Caller ID (CLI), CLI Base ECF, CLI Base routing Internet Ready Port, External Music Port, Call Budgeting, Call Most Calculation (ASMDR), DID Direct Inverse Dialing, External Music Input, Fax Homing, Global Directory Printing with following capacities [E] No of Extension 128, No of Junctions 24, No of expandable ports : 512, Operators Console - 01 Compatible : ISDN and Networking Note: Entire EPABX System proposed by contractor must be seamlessly integrate with existing 450 Bed EPABX System.
Supply, Installation, Testing & Commissioning of Additional Analog Extention Card for 336 Nos compatible with EPABX System.
providing and erecting add on Digital PRI T1E1 single card suitable for existing system of following ports suitable for 30 channel as per technical specification etc. as required.
Supply, Installation, Testing and Commissioning of User Call Control Application for all users/extensions, Voice Messaging Application inclusive of voice mail licences for users and inclusive of computer application and operating system, Emergency response services with voice messaging, inclusive of licences as per technical Specification.
Providing and erecting IP Phone with display with all IP system supported
Supplying & erecting push button type telephone instrument having speaker phone Caller ID & hands free dialing system & 30 memories with display system (a) Single line BEETEL/panasonic or equivalent make
Sec.2.0 IP Based Video Surveillance/CCTV System (Note : Entire CCTV Solution proposed by contractor must be seamlessly integrate with existing 450 Bed CCTV System) Supply, Installation, Testing and Comissioning of 4MP Varifocal Lens Bullet Camera, H.265 4MP IR Bullet N/W Camera, Manual Varifocal 2.8-12mm, 50M, Micro SD, DC12V/PoE, IP67/IK10, Basic IVA, 4MP resolution (2560 × 1440), True day/night, Digital WDR, 3D DNR, HLC & BLC, Triple streams, Smart codec by ROI, Cyber Security, Basic intelligent video analytics, NDAA Compliance, UL, CE, FCC Certified (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Installation, Testing and Comissioning of 4MP Varifocal Lens Dome Type Camera, H.265 4MP IR Turret Dome N/W Camera, Manual Varifocal 2.8-12mm, 50M, Micro SD, DC12V/PoE, IP67/IK10, Basic IVA, 4MP resolution (2560 × 1440), True day/night, Digital WDR, 3D DNR, HLC & BLC, Triple streams, Smart codec by ROI, Built in MIC, Cyber Security, Basic intelligent video analytics, Audio In, NDAA Compliance, UL, CE, FCC Certified (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Installation, Testing and Comissioning of 2 MP IR IP PTZ, 32x Optical Zoom, 16x Digital Zoom Up to 150m IR distance, 1/2.8’’ Progressive Scan CMOS sensor, Up to 1920x1080P @ 25/30FPS, Smart Event, Smart Tracking, WDR @ 120dB, ONVIF S,G,T, Ultra-low illumination, HLC, BLC, Defog, WDR, EIS, 3D DNR, Alarms I/O, 24 VAC & Hi-PoE, Supports H.265+/H.265, SD Card up to 256 GB Support, Cyber Security, IP66 & IK10, UL, CE, WEEE, REACH, FCC certified, Opp Temp - 30 °C to 60 °C (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Installation, Testing and Comissioning of Professional VMS Software, High Video Throughput With Minimal CPU And RAM Requirements, Powerful Search Capabilities In An Intuitive Interface, Exacq Replay Provides Instant Replay Of Events, Step-By-Step Online System Configurator Calculates Storage And Bandwidth Requirements, Client-Side Fisheye Camera De-Wrapping Provides Distortion-Free Images, Cybersecurity Features Include HTTPS Encryption, Complex Passwords, And User Lockout, Compatible With Over 5000 Models Of IP Cameras And Encoders, Including The H.265 Codec, Constantly Expanding Functionality With Included Software Updates, Windows & Linux Server Compatibility, Free Windows, Linux & Mac Clients, Browser-Based Viewing Of Live/Stored Events, Compatible With Free Exacq Mobile App, Easy Connect To Compatible IP Cameras, Fisheye/Panoramic Lens Support (Live & Recorded), Client Bandwidth Throttling, Pre/Post Alarm Recording, Soft Triggers, Time-Lapse Recording, Extended Storage, Archiving, Per-Camera Min/Max Retention, Audit Trail, Custom User Groups, Third-Party Integrations, Email Notification For System Health Events, Exacqvision Surveillance Keyboard Support The proposed VMS should support integrated Solution of CCTV + NVR, Access Control and Intrusion Detection from the same OEM. (Including Five year free maintenance with guarantee) For details specification refer tender technical specification etc. as required.
Supply, Installation, Testing and Comissioning of Rack Mount Network Video Recorder (NVR Server without HDD and Camera License) for 128 Camera, CPU: Intel Xeon processor or better, RAM : 32 GB or better ,OS Drive : 256GB SSD or better, HDD Storage support Up to 96TB with RAID5/RAID 6 configuration. Operating System : Windows & Linux, NIC : 2 x 1 Gbps, USB Port : 6, RS485, Video storage rate up to 800 mbps, Max 2 simultaneous display monitor, Dual Power supply Regulatory Approvals : UL , cUL, , CE, FCC, BIS & NDAA Compliance (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supplying, installation, testing and commissioning of 10 TB HDD Enterprice Garde as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of Client PC - Industry standard Intel based platform computer system. Intel Core i7 latest generation, 4 GB of RAM DDR3 ,1 TB SATA II hard drive for OS and VMS applications, NVidia card 1 GB graphics card , 1600 x 1200 or higher screen resolution, 1 X 1000Mbps ethernet network interface card ,16x DVD+/- RW Drive alongwith appropriate licenced Operating System, licenced applications suites from OEM and application licences as per the technical specifications etc. as required.
Supplying, installing, testing and commissioning of 65-inch, LED Panel, 16:9 Aspect ratio, 350 cd/m2 Brightness, Anti-glare panel surface with viewing angle 176 degree, 4K pixels resolution, Video Input Interfaces : HDMI Type A Connector x 2, Mini D-sub 15-pin x 1, 20 Watt Built in Speakers with wall mount bracket as per technical specification etc. as required.
Sec.3.0 Addressable Type Fire Detection & Alarm System (Note : Entire Fire Alarm & Detection System proposed by contractor must be seamlessly integrate with existing 450 Bed Fire Alarm & Detection System) Supply, Installation, Testing & Commissioning of FireNET FACP 2 Loop Red UL 864 9th Edition listed Multi-loop (1-2) analog-addressable,127 addressable points per SLC loop Up to 500 Cause & Effect Built-in help & alarm information screens Up to 5,000 ft. wire length per SLC loop Network-able up to 64 Panels Configurable through keypad 3 Programmable Form C relays rated 1 Amp at 30VDC, 2 Programmable Notification Appliance Circuits Power per NAC: 2.3 Amps Max Switchable 120/240VAC 50/60 Hz Power supply,Programmable Input and Output modules on SLC Loop Programmable Function button, Fire Drill button, Day and night sensitivity settings, Power Supply: 5.25 Amp, regulated & integrated, (2) 360mA auxiliary power available rated at 24VCD, LCD Display: 8x40 (320 character), Programmable NAC Cadence Patterns: Temporal, Continuous or March and Auxiliary Power options: Continuous Reset-able or Door Holder Power One man walk test – Fire Test Mode (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of Intelligent Addressable Fire Alarm Control Panel. The Fire Alarm Control panel shall have expandable capacity from 2-16 SLC loops with each supporting 127 devices of any combination, and 127 analog sounder bases. It shall have UL listed 10th edition, 4 programmable class B (style Y) NAC circuits rated 2.5 Amps each, Class B or 2 Class A with internal synchronization. The user shall have a choice of using the panel with 5.25 A (charges up to 60 Ah) or 10.25 A (charges up to 100 Ah) power supply. The Panel shall have 3 voltage-free programmable inputs and 5 programmable relay outputs 30 V DC 1 Amp, 7 inch full-color resistive touch screen with intuitive user interface, Up to 24 programmable soft “function keys”, Up to 64 user login accounts, Hard-wired fire and trouble routing inputs and outputs, Modular and expandable electronics, 400 sub address points per loop (800 per loop module), Option to “invert” inputs and outputs. The panel shall support up to 5000 programmable Cause and Effects entries; over 40,000 inputs and outputs, 10,000 events log @ 1 second resolution, 2000 software zones, 5000 software groups, 2 AUX 24V output each rated at 900 mA, Can be networked with programmable functionality, Programming via USB port to PC or memory stick. The Panel shall have dedicated RS232 serial port for optional printer, UL approved (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of Network Vision Annunciator. The Annunciator shall have Full color 7” (800 x 480 pixel) interface, Replicates information displayed at the FACP, Automatic display brightness adjustment, Internal buzzer, Connects via control panel network terminals, Low current, 24V DC powered, Configurable functionality, Enable key-switch, Sheet steel enclosure, UL approved (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of Network Module. The Module shall connect Panels and Repeator Panels through RS485. The Module shall use RS485 data at a Baud rate of 115200 Bauds. The Network Module must be configured Master/Slave, Multiple Master/Slave and Peer to Peer networking. Approved by UL and FM (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of Analog Multi-Criteria Sensor Features, Low profile - only 2" high including base, variable sensitivity from 0.7 to 4% obs/Ft Simple and reliable device addressing, Automatic compensation for sensor contamination , Built in Fire test feature, Two built-in power/alarm LEDs, programmable non-polling LEDs, Non-directional Smoke chamber, Vandal resistant security locking feature, Approved by UL and FM (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of Fixed Temperature/Rate of Rise sensor, Low profile-only 2.00" high, including base, simple and reliable device addressing method, Rate of rise temperature threshold = 15° F/Min, Adjustable threshold temperature = 135° - 190°, Approved by UL and FM (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of Short Circuit Isolator. The device shall have ability to locate between any devices on the SLC loop, Indicate of a single short circuit by a yellow LED, UL Approved (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of Analog Duct Detector ability to detect and limits the spread of smoke throughout building HVAC ducts, Installs quickly and easily, No screens or filters to clean, Rugged gray steel back box with clear cover, Remote LED alarm indication capability, Meets UL 268A requirements. Approved by UL (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of Class A Supervised Output Module. The Module shall have Flexible application, Quick response to emergency conditions, Contacts are rated 2.0 Amps@ 24VDC, Programming is highly flexible providing 16 priority states plus zoning capability, Approved by UL and FM (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of Fast Response Contact Monitoring Module. The Module shall have UL 864 9th Edition Listed, Single Input contact monitor, can be programmed to monitor Normally Open (NO) or Normally Closed (NC) contacts, operates on Class A or Class B SLC loop, Accepts up to 12 AWG wire. Approved by UL and FM (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of Dual Relay Module 2A @ 30 VDC/.5A @ 120 VAC. The Module shall have two independently configurable Form C contacts per address, Visible Bi-colored LED is software controlled and can be programmed to blink red or green when polled. The LED can be latched on when activated, Yellow LED indicates a short circuit condition, Programming is highly flexible providing 16 priority states plus zoning capability, operates on Class A or Class b SLC loop, UL 864 Listed. Approved by UL and FM (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of Projected Beam Smoke Detector. The device should have standard features including Microprocessor based for Reliability, Simple setup and alignment with signal strength LEDs, Provide 60 feet on center linear protection at a range of 32.8 feet to 328 feet, Automatic compensation for signal drift or dirty lens, Three field adjustable sensitivity settings, form A alarm and Form B trouble contacts, Color coded emitter (red) and receiver (green) labels for easy recognition, Adjustable to one of the three obscuration settings of 25%, 50% or 70% per span, voltage and RF transient protection, External red LED when alarm condition is indicated. Approved by UL and FM (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of Response Indicator - Dual LED (Metal square plate type) (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of Addressable Single Action Manual Pull Station features including Addressable integrated design, All metal construction, Extremely easy to operate, Bi-colored status LED indicates standby and Alarm conditions, Address is programmable in EEPROM, Enclosed switch with glass rod, Terminals accept up to 14AWG wire, ADA compliant. Approved by UL and FM (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of low profile Horn/Strobe. The device shall have Nominal voltage 24VDC. The device shall produce 100 dBA @ 10ft and has a minimum flash rate of 1Hz regardless of input voltage. The device approved by UL and CSFM (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Sec.4.0 Digital Evac / Public Address System. (Note : Entire Digital EVAC / Public Address System proposed by contractor must be seamlessly integrate with existing 450 Bed Digital EVAC / Public Address System) Supply, Installation, Testing & Commissioning of Controller Heart of the Plena Voice Alarm System EN 54‑16 certified Built-in message manager and 240 W amplifier Six‑zone outputs 6 emergency and 6 business triggers (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of Router Expand the Plena Voice Alarm System with six zones EN 54‑16 certified 12 additional input contacts Six volume override output contacts Supervision within the Plena Voice Alarm System (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of Power amplifier, 480W (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of Ceiling speaker, 6W, metal (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of Metal fire dome (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of Cabinet loudspeaker 6W, white (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of Horn loudspeaker 30W, circular, ABS (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of Volume control unit, 36W (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of Music source, USB/SD/Tuner MP3 playback from SD card and USB inputs FM tuner with RDS, presets and digital control Simultaneous operation of SD/USB-player and FM tuner Separate outputs for digital source and FM tuner as per technical specification etc. as required.
Supplying & laying of 2x1.5 sqmm fire alarm armoured cable with annealed copper conductor having XLPE insulation, steel wire armouring & FRLS outer sheath complete as required.
Supplying and drawing of cable Fire Retardant PVC insulated copper conductor cable in the existing surface / recessed steel conduit of following pairs, cores and size including connections and interconnections etc. as required. (A)Speaker cable Single pair, 2-core, 1.5 sqmm.
Sec.5.0 Access Control System (Note : Entire Access Control System proposed by contractor must be seamlessly integrate with existing 450 Bed Digital Access Control System) “Providing & erecting approved make Fingerprint and card based premium Door controller with LCD and Keypad having following features.”(A) Optical Fingerprint and card based Reader (Card personality Module not included) “(B) Dot – Matrix LCD and Touch sense Keypad “(C) Built-in interfaces like door lock, door sense exit Reader, Exit switch, Ethernet RS485, Aux Input & aux output port “(D) 5000 Events, access Control, Time Attendance, Tamper Detection “(E) 4 LEDS and Buzzer” as per technical specification etc. as required.
“Providing & erecting approved make Card Reader having following features. “[A] Wiegand/ RS232 Interface “(B) Power supply from COSEC Door controller or through Separate Adaptor “(C) Compatible with any COSEC Door controllers “(D) 4 LEDs (Status, Alarm, Allowed and Denied) and Buzzer “(E) Tamper Detection” as per technical specification etc. as required.
“Providing & erecting approved make Card Personality Module (CPM) having following features “(A) EM proximity Card Reader Module [Low Frequency] “(B) Compatible with any COSEC Door Controllers and COSEC Reader CA “(C) Supports EM Proximity Card” as per technical specification etc. as required.
Providing & erecting approved make Panel Controller for Multiple Door Controllers having following feature (A) Controls up to 16 Door Conditioners (B) Ethernet RS485, USB,Aux Input and Aux Output Port (C) 10000 Users Capacity and 100000 Events Storage (D) 32-bit processor, 32 MB RAM and 32MB Flash (E) Compact and Elegant Design as per technical specification etc. as required.
Providing & erecting approved make Application Software Platform for 500 Users having following features (A) With 100 Users (B) Expandable up to 500 Users with COSEC USER100 (C) Supports up to 16 Door Controllers (D) Basic Access Control, Basic Time Attendance and Enrolment Management (E) Compatible with all COSEC Hardware (F) Add Other COSEC software Modules on requirement. as per technical specification etc. as required.
Providing & erecting approved make Time Attendance Module (TAM) having following features (A) Comprehensive Time Attendance and Leave Management Software Module (B) For 500 Users [AS per COSEC GE PLATFORM USERS] (C) Attendance and Leave Policy Creation (D) Integration with payroll and HRM (E) Shift Schedule, Holiday Schedule and Past Adjustment (F) Manually Attendance Correction (G) Leave / Tour Application and Approval (H) Report and Charts Generation as per technical specification etc. as required.
Providing & erecting approved make Access Control Module (ACM) having following features (A) Comprehensive Access Control Management (B) For 500 Users [AS PER COSEC GE PLATFORM users] (C) Time, User and Zone Based Access Control (D) Access Zones, Access Modes and Access Levels (E) Advanced Access Control Feature like 2-person rule, First in user rule, Antipas Back, Guard Tour, Duress Detection and More (F) Various Reports Generation as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of Drop Bolt Or EM Door Lock as per Door type & site Location requirement as per technical specification etc. as required.
Sec.6.0 Cable TV Distribution System Providing following type of Modular Type Accessories mounted with pvc / metallic box covered with appropriate front plate modules erected with necessary connection. As desired by Engineer In charge. (4) TV Co-axial Socket outlet. Cat. III. as per technical specification etc. as required.
Providing & Erecting approved make following size of TV Co-axial flexible cable comprising inner conductor of solid bare copper insulated with Foam PE & Secondary conductor made of poly – Aluminium film bonded Al. Braids @ suitable coverage overall sheathed with black PVC insulation. (b) RG – 6 as per technical specification etc. as required.
Providing & Erecting approved make following size of TV Co-axial flexible cable comprising inner conductor of solid bare copper insulated with Foam PE & Secondary conductor made of poly – Aluminium film bonded Al. Braids @ suitable coverage overall sheathed with black PVC insulation. (e) RG – 11 as per technical specification etc. as required.
Sec.7.0 Audio Visual System Supply, Installation, Testing and Comissioning of 75" Smart Interactive 4K display |7H hardness toughen anti glared glass | In-built Android 8.0, RAM 3 GB, 16 GB ROM with 32 GB SD card)|10 Points Touch in Android and 20 points Touch in Windows | Smart Object recognition and responsive multi-touch | Multiple Inputs for connectivity | 15W x 2 Speakers | Inbuilt Screen Sharing Software | Slimmer Frame|Customize GUI| Broadcasting uto 200 Devices| Display Management (Including Five year free maintenance with guarantee) with required wall mount kit as per site requirement, as per technical specification etc. as required.
Supply, Installation, Testing and Comissioning of 65" Smart Interactive 4K display |7H hardness toughen anti glared glass | In-built Android 8.0, RAM 3 GB, 16 GB ROM with 32 GB SD card)|10 Points Touch in Android and 20 points Touch in Windows | Smart Object recognition and responsive multi-touch | Multiple (Including Five year free maintenance with guarantee) with required wall mount kit as per site requirement, as per technical specification etc. as required.
Supply, Installation, Testing and Comissioning of 85" Smart 4K Non-Touch display | In-built Android 8.0, RAM 3 GB, 16 GB ROM| 20W x 2 Speakers | 6 no. of Beam Forming Microphones with Echo Cancellation | 50000 Hours of Life | 500 nits Brightness| Multiple Inputs for connectivity | Inbuilt Screen Sharing Software | Slimmer Frame |OPS Slot for On-Board Computer Connectivity (Including Five year free maintenance with guarantee) with required mouting kit as per site requirement, as per technical specification etc. as required.
Supply, Installation, Testing and Comissioning of Intel SDM Module (Core i5 11th Gen Processor, 8Gx2 RAM, 256 GB Storage)with Dimension 175mm x 110mm (Intel SDM Large compliant) (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supplying, installation, testing and commissioning of Modular Pop-Up Box / Cable cubby Includes a Universal power outlet X 2 Nos. and space for four customer-supplied cables HDMI Port X 1nos, RJ-45 X 2 Nos, as per technical specification etc. as required.
Supply,Installation,Testing and Commissioning of 4x4 4K60 4:4:4 HDR AV Switcher Should have minimum 4xHDMI inputs and 4xHDMI outputs; Should support input signals up to HDR10, HDR10+, Dolby Vision, Deep Color, 4K60 4:4:4 or better; Should support output signals up to HDR10, HDR10+, Dolby Vision, Deep Color, and 4K60 4:4:4 or better; Should handles resolutions Up to 4096x2160@60Hz (DCI 4K60), 4:4:4 Video; Should be HDCP 2.3 compliant or better; Should have minimum 2xaudio de-embedding Port or better; Should provide 2-channel Stereo Audio output; Should support the audio formats like Dolby Digital, Dolby Digital EX, Dolby Digital Plus, Dolby TrueHD, Dolby Atmos, DTS, DTS-ES, DTS 96/24, DTS HD High Res, DTS-HD Master Audio, DTS:X, LPCM up to 8 channels; Should have minimum 1xUSB port for firmware loading and configuration management and to power a USB powered device; Should support 100/1000 Mbps, auto-switching, auto-negotiating, auto-discovery, full/half duplex, DHCP; Should support Web browser setup and control; Should have front Panel control for manual Switching; Should have compatibility with control systems of the same OEM; Should support IEEE 802.1X, Secure CIP, Authentication, SSH/SSL, TLS; Should have Enterprise-grade security; Should have EDID management option; Should have device control option via CEC; Should have built-in web interface; Should be 1U 19-inch rack-mountable; Should come with rack ears; Should be capable of Powered via a local power pack or a PoE+ compliant Ethernet switch or any approved third‑party PSE; Should be Bureau Veritas Listed for US & Canada, IC, CE, FCC Part 15 Class B digital device compliant; Should have an option of Cloud management via IoT based platform for remotely provisioning, monitoring, and managing devices across an enterprise or an entire client base by the same OEM (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supplying, installation, testing and commissioning of 4 in 1 Media processor - supports recording, switching, mixing and live streaming at 1080p, Supports 1080p 60/30fps video recording, Supports 4 HDMI Inputs and IP video sources, Should have minimum 1TB inbuilt storage. as per technical specification etc. as required.
Supplying, installation, testing and commissioning of Full HD 1080p, Minimum 20X Optical Zoom, 20 Presets, 30 Frames per Second, Ethernet Out, HDMI Out, 3G-SDI Out, Audio In, RS232/422 Controls, -170° ~ +170° Panning angle, -30° ~ +90° Tilting angle capturing presenter and students. as per technical specification etc. as required.
Supplying, installation, testing and commissioning of Joystick for PAN/Tilt/Zoom Cameras and Focusing, RS232C/RS455 Communication Interfaces, High Brightness OLED Display, Auto Backlit Keys.as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of Handheld Wireless Mic with Cardiod polar pattern,Dynamic microphone ,frequency response 80Hz-18kHz,RF sensitivity < 1.0 Uv,Image rejection>55dB,Dyanmic range >95dB and receiver having 30 or more channels possible,S/N ratio >100dB A,dynamic range >95db B,distortion <1 %,frequency band:618-634MHz,more than 12hrs battery life with AA battery.The transmitter & receiver should be of metal body (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of Wireless Mic Lapel with condenser,frequency response 100Hz-15kHz,Cardiod polar pattern,,RF sensitivity < 1.0 Uv,Image rejection>55dB,Dyanmic range >95dB and receiver having 32 channels possible,S/N ratio >100dB A,dynamic range >95db B,distortion <1 %,frequency band:618-634MHz,more than 12hrs battery life with AA battery.The transmitter & receiver should be of metal body (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supplying, installing, testing and commissioning of two way communication 10 x 8 Audio Digital Signal Processors, with Minimum 10 AEC balanced mic/line inputs, Minimum eight balanced mic/line outputs. as per technical specification etc. as required.
Supply, Installation, Testing and Commissioning of 600 mm beamforming microphone array Ceiling tile, Support beamforming from 100Hz to 20kHz, support AEC, Noise Cancellation, Gain & Level control, Mute on/off, Support Dante protocol, Coverage up to 24 feet redius, with required PoE / Non POE Power supply & mouting accessories from the ceiling as per site requirement, as per technical specification etc. as required.
Supply, Installation, Testing and Commissioning of DSP Mixer with 4 mic/line inputs (AEC), 8 mic/line outputs, built-in USB audio, VoIP conferencing interface , analog telephone interface, Dante protocol support, support SIP Based configuration, as per technical specification etc. as required.
Supply,Installation,Testing and Commissioning of 8x8 4K60 4:4:4 HDR AV Switcher Should have minimum 8xHDMI inputs and 8xHDMI outputs; Should support input signals up to HDR10, HDR10+, Dolby Vision, Deep Color, 4K60 4:4:4 or better; Should support output signals up to HDR10, HDR10+, Dolby Vision, Deep Color, and 4K60 4:4:4 or better; Should handles resolutions Up to 4096x2160@60Hz (DCI 4K60), 4:4:4 Video; Should be HDCP 2.3 compliant or better; Should have minimum 2xaudio de-embedding Port or better; Should provide 2-channel Stereo Audio output; Should support the audio formats like Dolby Digital, Dolby Digital EX, Dolby Digital Plus, Dolby TrueHD, Dolby Atmos, DTS, DTS-ES, DTS 96/24, DTS HD High Res, DTS-HD Master Audio, DTS:X, LPCM up to 8 channels; Should have minimum 1xUSB port for firmware loading and configuration management and to power a USB powered device; Should support 100/1000 Mbps, auto-switching, auto-negotiating, auto-discovery, full/half duplex, DHCP; Should support Web browser setup and control; Should have front Panel control for manual Switching; Should have compatibility with control systems of the same OEM; Should support IEEE 802.1X, Secure CIP, Authentication, SSH/SSL, TLS; Should have Enterprise-grade security; Should have EDID management option; Should have device control option via CEC; Should have built-in web interface; Should be 1U 19-inch rack-mountable; Should come with rack ears & power supply; Should be Bureau Veritas Listed for US & Canada, IC, CE, FCC Part 15 Class B digital device compliant; Should have an option of Cloud management via IoT based platform for remotely provisioning, monitoring, and managing devices across an enterprise or an entire client base by the same OEM (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply,Installation,Testing and Commissioning of 6.5” Two-way In-Ceiling Speaker - White Should be 2-way Two-way In-Ceiling Speaker Should have minimum 6.5" woofer with wide-dispersion dome or better Should have minimum 0.79" tweeter dome or better Should support 8 Ohms nominal with transformer set to 8Ω Should have built-in 30 Watt 70/100V multi-tap transformer or better Should support transfer tap 3.75W/7.5W/15W/30W at 70V; 7.5W/15W/30W at 100V Should support frequency response 95 Hz to 15 kHz (±3 dB) or better Should support frequency range 65 Hz to 20 kHz (-10 dB) or better Should support power handling of minimum 50 Watts @ 8 Ohms or better Should support sensitivity 91 dB @ 1W/1m or better Should have minimum coverage of 110˚ or better Should have perforated metal grille with push-on friction fit installation option Should have baffle made with ABS plastic with UL 94V-0 flame rated or better Should come with tile bridge for installation in a drop-tile ceiling Should have UL 1480 & UL 2043 device Compliance Should be available with White colour option (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply,Installation,Testing and Commissioning of 4” Two-way Surface Mount Indoor/Outdoor Speaker - Black Should be 2-way Two-way Surface Mount Speaker Should have minimum 4" polypropylene woofer with damped cloth surround for tight, controlled bass and clear midrange or better Should have minimum 0.79" titanium dome with 90˚ conical horn or better Should support 8 Ohms nominal with transformer set to 8Ω Should have built-in 30 Watt 70/100V multi-tap transformer or better Should support transfer tap 1.87W/3.75W/7.5W/15W/30W at 70V; 3.75W/7.5W/15W/30W at 100V Should support frequency response 100 Hz to 16 kHz (±3 dB) or better Should support frequency range 78 Hz to 18 kHz (-10 dB) or better Should support power handling of minimum 100 Watts @ 8 Ohms or better Should support sensitivity 89.5 dB @ 1W/1m or better Should be weatherproof IPx4 rated per IEC 60529 & withstand water splashing from any direction Should have aluminum powder coated grille & can be paintable to blend with the surroundings Should support mounting system to orient and aim the speaker, Yaw (horizontal) ±30°, Pitch (vertical) ±30°, Roll (rotation) 360° or external mounting should be supplied Should have rigid ABS plastic construction or better Should be available with Black colour option (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply,Installation,Testing and Commissioning of 2 Channel Power Amplifier Should have minimum 2x Balanced or unbalanced analog line-level input or more Should have minimum 2x speaker output or more Should have inbuilt support for 4/8 Ohm Impedance and 70/100Volt direct coupled or an external transformer taps should be supplied. Should be Bridgable with the adjoining channel Should support minimum ouptut of 2x210 watts per channel at 4 Ohms or better Should support minimum ouptut of 2x120 watts per channel at 8 Ohms or better Should support minimum bridge mode ouptut of 420 watts at 8 Ohms or better Should support frequency response of 20 Hz to 20 kHz ±0.5 dB at 4/8 Ohms or better Should support frequency response of 80 Hz to 20 kHz ±0/-3 dB at 70/100V or better Should have S/N ratio >103 db or better Should have minimum THD of 0.2% @ 20Hz to 20kHz, 210W at 4 Ohms or better should have minimum THD of 0.1% @ 20Hz to 20kHz, 120W at 8 Ohms or better Should be field configurable as single/dual chanel amplifer. Should have individual gain control for each output channel. Should feature inbuilt Thermal Protection to Protect the amplifier power supply and each channel against overheating or excessive temperature Should feature inbuilt Over Current protection circuit to Protect each channel individually against an excessive speaker load or shorted speaker line or an external amplifer protection device should be supplied Should feature inbuilt DC Offset to Protect each channel and speaker line against DC voltages sensed at each output Should have individual Power control option via jumper or remote Should have auto power-down after 30 minutes of no signal is present in input Should have an instant behavior with auto power-on when an input signal is detected Should have inbuilt power adapter or an external power supply should be supplied. Should be single-space 1U rack mountable Should be Rack-mountable with front rack ears and rear support brackets provided or additional mounting accessories should be supplied. Should be ENERGY STAR compliant (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply,Installation,Testing and Commissioning of Automation Control Processor Should have minimum 1 Bidirectional RS-232/422/485 or more; Should have minimum 2 Bidirectional RS-232 or a suitable control port expansion module to be provided separately; Should have minimum 8 IR/1-way Serial ports or a suitable control port expansion module to be provided separately; Should have minimum 8 Low Voltage Relay Ports or a suitable control port expansion module to be provided separately; Relay Port should be Rated minimum 1 Amp, 30 Volts AC/DC; Should have minimum 8 I/O Versiport or a suitable control port expansion module to be provided separately; Should have Onboard SDRAM minimum 2GB or more; Should have minimum 8 GB Flash memory or more; Should have memory card slot support SD/SDHC cards up to 32 GB or more; Should support Expandable storage up to 1TB or more; Should have minimum 1xHigh-speed USB 2.0 host port to support Mass Storage; Should support ethernet with 100/1000 Mbps, auto-switching, auto-negotiating, auto-discovery, full/half-duplex, industry-standard TCP/IP stack, UDP/IP, CIP, DHCP, SSL, TLS, SSH, SFTP (SSH File Transfer Protocol), FIPS 140-2 compliant encryption; It should support IEEE 802.1x Active Directory service authentication to ensure reliability and compliance with your organization’s IT policies; It should have Built-in SNMP support; Should have Enterprise-class network security and authentication with SNMP V3 remote IT management support; It should support web servers like HTTP/HTTPS & SMTP email client; Should have IPv4 & IPv6 Support; Should have Native BACnet/IP support or a suitable external interface to be provided; Should have a network bus control port for communicating and controlling with other devices of the same OEM; Should have Customizable user interface, capable of real-time feedback and Metadata; Should support minmum 10 programs to run simultaneously; Should be 1U rack-mountable with rack ears provided; Should be controllable thru PC thru application file; Should be able to be controlled thru Mobile Devices like I-pad, I-phone, Android without the need of any additional hardware; Should be UL Listed for US & Canada, CE, IC, FCC Part 15 Class B digital device compliant; Should have an option of Cloud management via IoT based platform for remotely provisioning, monitoring, and managing devices across an enterprise or an entire client base by the same OEM; Appropriate power supply for the controller should be included in the BOQ (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply,Installation,Testing and Commissioning of 7 in. Tabletop Touch Screen Should have TFT active matrix Colour LCD, 7in. Diagonal; Should have widescreen active-matrix color display and 1280 x 800 display resolution; Should control Custom-programmable virtual control buttons; Should supports HTML5 and Smart Graphics for custom user projects; Should have minimum 1280 x 800 pixels resolution or better; Should have minimum aspect ratio of 16:10 WUXGA or better; Should have minimum contrast of 850:1 or better; Should have minimum brightness of 350 nits or better; Should have viewing angle of ±80° horizontal, ±80° vertical or better; Should have Edge-lit LED with auto brightness control; Should have the minimum project storage of 600 mb or better; Should have 2 GB LPDDR3 RAM; Should support 100 Mbps, auto switching, auto negotiating, auto discovery, full/half duplex, TCP/IP, UDP/IP, CIP, DHCP, SSL, TLS, SSH, SFTP (SSH File Transfer Protocol); Should employ advanced security features and protocols like IEEE 802.1X, SNMP, IPv4 or IPv6, Active Directory® service authentication, HTTPS web browser setup, IEEE 802.3at compliant; Should support Wi-Fi communication with IEEE 802.11a/b/g/n/ac Wi-Fi; Should have built-in microphone and speakers; Should support onboard Voice Recognition; Should have SIP Intercom integration feature; Should support H.265, H.264, or MJPEG formats streaming video; Should support RTSP; should support streaming input resolution up to 1920x1080@30fps; Should have Capacitive touch screen display with 5-point multitouch capable; Should have Web, cloud, or device-based configuration; Should support native apps for Zoom Rooms conferencing control, Microsoft Teams online meeting solution, and various room scheduling services; Should have Enterprise grade security and authentication with 64 and 128-bit WEP, WPA and WPA2-PSK with TKIP and AES or better; Should have the built-in Bluetooth communications beacon; Should be powered via Single wire Ethernet connection with Poe or PoE+ only, should not have separate power supply; Should have built-in Table Top Docking Station; Should be available in Black color; Should be IC, CE, FCC Part 15 Class B digital device Compliance; Should have an option of Cloud management via IoT based platform for remotely provisioning, monitoring, and managing devices across an enterprise or an entire client base by the same OEM (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of Control unit (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of Participant device long mic, black (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of Chairperson device long mic, black (Including Five year free maintenance with guarantee)
Supply, Installation, Testing & Commissioning of EXTENSION CABLE ASSEMBLY - 2MTRS (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Installation, Testing & Commissioning of EXTENSION CABLE ASSEMBLY - 10 MTRS (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply,Installation,Testing and Commissioning of 4K60 4:4:4 HDR Network AV Encoder/Decoder Should have capacity of encoding or decoding up to 4K@60Hz, 4:4:4 color sampling video over standard 1 Gigabit / 10 Gigabit Ethernet; Should be a Trans-receiver configurable as an encoder or decoder; Should have both copper and fiber Ethernet connectivity; Should have minimum 1xHDMI Input or better; Should handles resolutions Up to 4096x2160@60Hz (DCI 4K60), 4:4:4 Video; Should have HDR (High Dynamic Range) video support HDR10, HDR10+ or better; Should support Dolby Vision and Deep Color Video Content; Should supports audio formats of Dolby Digital, Dolby Digital EX, Dolby Digital Plus, Dolby TrueHD, Dolby Atmos, DTS, DTS ES, DTS 96/24, DTS HD High Res, DTS HD Master Audio, DTS:X, LPCM up to 8 channels; Should support minimum 7.1 surround sound audio or better; Should have Analog audio port configurable as a balanced stereo input or output; Should have minimum 1xHDMI output or better with 4K60 4:4:4 video scaler with motion-adaptive deinterlacing, intelligent frame rate conversion, Deep Color support, HDR10 support & widescreen format B981:B983 embedding; Should have Audio breakaway capability; Should have JPEG 2000 video compression technique; Should have adaptive bit rate; Should have configurable bitrates option from minimum 200 to 950 Mbps or better; Should have No latency penalty for real-time video performance in either of the operation; Should be Minimum HDCP 2.3 compliant or better; Should have JITC Certified Data Encryption; Should support streaming protocols like RTP, SDP; Should use MPEG-2 transport stream and Session Initiation with Multicast via RTSP; Should have dual onboard RJ45 LAN ports for addressing and delivering/transferring content over ethernet; Should have 10/100/1000 Mbps, auto-switching, auto-negotiating, auto-discovery, full/half duplex, TCP/IP, UDP/IP, CIP, DHCP, SSL, TLS, SSH, SFTP (SSH File Transfer Protocol), IEEE 802.1X, IPv4, Active Directory authentication, variable Multicast TTL, HTTPS web browser setup; Should have one dedicated network port for audio network; Should have an optional Fiber-Optic network connection via SFP port; Should have compatibility with control systems of the same OEM; Should be adhere to Enterprise-grade security to protect integrity of the content; Should employ advanced security features and protocols like 802.1x authentication, Active Directory credential management, LDAP directory management, PKI certification, AES-128 encryption, TLS, SSH, and HTTPS; Should have RTSP, SDP, ONVIF, IGMPv2, IGMPv3, SMPTE 2022, FEC (Forward Error Correction); Should have an onboard video wall processing capacity up to 8 wide x up to 8 high; Should have static or dynamic text overlay option; Should have minimum 1xRS-232 and 2xIR control ports or better for remote control through automation controller; Should have CEC device control gateway; Should support USB 2.0 and KVM signal extension and routing; Should have dedicated USB 2.0 HOST and DEVICE ports for allowing a USB mouse, keyboard, or other peripheral device; Should have HTTPS web browser base setup and control option; Should be a Compact, surface-mountable form factor; Should handle minimum temperature of 32° to 104° F or better; Should handle minimum humidity of 10% to 90% RH (non-condensing) or better; Should be Intertek Listed for US and Canada, CE, IC, FCC Part 15 Class B digital device compliant; Should be capable of Powered via a local power pack or a PoE+ compliant Ethernet switch or any approved third‑party PSE; Should have an option of Cloud management via IoT based platform for remotely provisioning, monitoring, and managing devices across an enterprise or an entire client base by the same OEM (Including Five year free maintenance with guarantee), as per technical specification etc. as required.
Supply Installation Testing & Commissioning of Surgical Monitor having 24” Clinical Review Display with 1920x1200 native pixel resolution and LED backlight. Features high-quality/high bright LCD panel, 10-bit DICOM LUT, Front Consistency Sensor, QAWeb, Adjustable stand (height/tilt/swivel/pivot), Scratch-proof front glass, External power supply, White bezel. Including pendent mount. as per technical specification etc. as required.
Supply Installation Testing & Commissioning of 42'' Surgical Display, Resolution-1920 X 1080, Aspect Ration-16:9, Screen Technology- TFT AM LCD, Viewing angle H-V: 178, input: HDMI, DVI. Complaint-CE, ISO, RoHS. Including wall mount, as per technical specification etc. as required.
Supply,Installation,Testing and Commissioning of Media Presentation Wall Plate - HDMI Should be single-gang wall mount pasive device, functions as input/output for HDMI; Supports 4K60 4:2:0 and 4K30 4:4:4 digital video; Should support 10.2 Gbps TMDS bandwidth; Should support Supports 7.1 digital surround sound audio; Should be Gangable for custom wall, lectern, and rack mount applications; Should be available in white, black, or almond colors with Decorator style faceplates; Should supplies with matching color Faceplate; The faceplate should be Clean and elegant two-piece design with no visible screws (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Laying, Testing and Commissioning of Laptop with 10th Generation Intel® Core™ i5 processor. Windows 10 Pro 64,Intel® UHD Graphics 620, 8 GB DDR4-2666 SDRAM (1 x 8 GB), 512 GB SSD, inbuilt Wi-Fi, camera, network interface, 1GB Graphics card, as per technical specification etc. as required.
Supply, Laying, Testing and Commissioning of software base VC with annual license includes 10 virtual meeting rooms with IM/presence, Phone dial out and Channels. Each room supports up to 100 participants. Also includes shared 1 SIP/H.323 gateway license, 200 Phone Dialout minutes included. Managed using Admin portal, as per technical specification etc. as required.
Supply, Installation, Testing and Commissioning of Adapter for data sharing via external laptop or PC as per technical specification etc. as required.
Supply, Installation, Testing and Commissioning of Hub that connects USB camera, USB audio, room displays and laptop as per technical specification etc. as required.
Supply,Installation,Testing and Commissioning of 3 ft HDMI Interface Cable Should be 3ft Male to Male High-speed Category 2 HDMI cable; Should be 24k gold-plated 19-pin Type A connector; Should have High-flex CL3-rated jacket; Should Support 4K60 4:4:4 video; Should support 18 Gbps bandwidth; Should be RoHS compliant (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply,Installation,Testing and Commissioning of 6 ft HDMI Interface Cable Should be 6ft Male to Male High-speed Category 2 HDMI cable; Should be 24k gold-plated 19-pin Type A connector; Should have High-flex CL3-rated jacket; Should Support 4K60 4:4:4 video; Should support 18 Gbps bandwidth; Should be RoHS compliant (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply,Installation,Testing and Commissioning of 12 ft HDMI Interface Cable Should be 12ft Male to Male High-speed Category 2 HDMI cable; Should be 24k gold-plated 19-pin Type A connector; Should have High-flex CL3-rated jacket; Should Support 4K60 4:4:4 video; Should support 18 Gbps bandwidth; Should be RoHS compliant (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply,Installation,Testing and Commissioning of 30 ft HDMI Interface Cable Should be 30ft Male to Male High-speed Category 2 HDMI cable; Should be 24k gold-plated 19-pin Type A connector; Should have High-flex CL3-rated jacket; Should Support 4K30 4:4:4 and 4K60 4:2:0 video; Should support 18 Gbps bandwidth; Should be RoHS compliant (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply,Installation,Testing and Commissioning of HDbaseT Twisted Pair Cable 500 ft Spool Should be 24AWG solid copper twisted pair Cable; Should be available in minimum 500 ft. spool or better; Should be UTP with four twisted pairs, inner jacket, drain, overall foil shield, ripcord, and overall jacket; Should have minimum conductor Gauge of 26AWG solid tin/copper or better; Should have 100% shield coverage or Aluminum foil; Should be 350 MHz ultra-high-performance shielded CAT5e; Should have optimized for high-definition digital AV and Ethernet data networking applications; Should be precision manufactured and tested to exceed CAT5e specifications; Should be recommended Cable for HDbaseT; Should have minimum 17.1 pF/ft capacitance or better; Should have minimum 45 nS/100m propagation delay skew or better; Should have NEC Article 800; UL Subject 444, Type CM; CSA Type CMR; ANSI/TIA/EIA-568-B.2 Category 5e Rating (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply,Installation,Testing and Commissioning of Non-Plenum Control Cable - Teal, 250 ft Should have minimum 4 wires or more that provides bi-directional communication; Should be minimum 250 feet cable or more; Should support power and data within the same cable; Should have non-plenum PVC jacket or better; should be compatible with both homerun and daisy-chain wiring topologies; Should have 1x22 AWG shielded twisted pair for control data and 1x18 AWG pair for 24VDC; should have minimum nominal capacitance of 12.5 pF/ft (41 pF/m) or better; Should have various colour for easy identification of different types; should suport cable length of 3000 feet (915 meters) per run or more; Should be NEC Article 800, UL Subject 13, Type CM, CSA Type CMG, RoHS compliant (Including Five year free maintenance with guarantee) as per technical specification etc. as required.
Supply, Laying, Testing and Commissioning of Ultra Flexible High Speed HDMI Cables HDMI Cable 15 Meter HDMI 2.0 Cable Male to Male, support Deep Color, 4K 4096 x 2160 @60Hz; 3840 x 2160 @ 60Hz 4:4:0, Minimum conductor gauge - 30AWG, gold Plating, as per technical specification etc. as required.
Supply, Laying, Testing and Commissioning of Ultra Flexible High Speed HDMI Cables HDMI Cable 20 Meter HDMI 2.0 Cable Male to Male, support Deep Color, 4K 4096 x 2160 @60Hz; 3840 x 2160 @ 60Hz 4:4:0, Minimum conductor gauge - 30AWG, gold Plating, as per technical specification etc. as required.
Supply, Laying, Testing and Commissioning of Two 16 AWG conductors non- plenum Speaker Cable, for High performance cable for audio signals as per technical specification etc. as required.
Supply, Installation, Testing and Commissioning of 30 feet (10 meters) long USB 3.0 Cable, to connect a Laptop as per technical specification etc. as required.
Sec.8.0 Nurse Calling System (Note : Entire Nurse Call System proposed by contractor must be seamlessly integrate with existing 450 Bed Nurse Call System) Supply, Installation, Testing and Commissioning of Nurse Calling System: Management Server: System Server used for uploading the firmware and the system configuration, for operating interfaces to foreign systems, for logging of all system events and as a central location for system configuration and remote maintenance and is an interface to all other foreign systems. The Server specification should be:-CPU: Intel Xeon Dual core 2.3 GHz, RAM: 4GB DDR2-800, 1xSATA HDD (2 TB), 2xPCI, 2x1GB LAN, Case for fitting in a 19” cabinet, Operating system: Linux (SUSE Server 10.x), Pre-installed system software as per technical specification etc. as required.
Supplying, installation, testing and commissioning of USB -Dongle for License Storage as per technical specification etc. as required.
Supply, Installation, Testing and Commissioning of Floor Switch: Uplink connections: 2 x 1Gb uplink ports, RJ45 (GBIC capable, possibility for LWL) Connections downlink: 24 x 100Mb downlink ports, RJ45 as mentioned as per technical specification etc. as required.
Supply, Installation, Testing and Commissioning of System Switch / Ward Controller: forms a decentralised communications node for exchanging data between the connected system devices and the rest of the communications system. It should have , - 1 x RJ45 socket, 100Mb IP Uplink Port galvanically isolated conformant with EN 60950 and VDE 0834 - 7 x RJ45 sockets, each with a 100Mb POE port - 1 x RJ45 socket, 100Mb IP POE Port (IEEE802.3 100BaseTX) for connecting Staff Room Devices - 2 x RJ45 sockets for connecting the external data bus including 230VAC / 24DC , 5 A power supply as per technical specification etc. as required.
Supply, Installation, Testing and Commissioning of Bedside Module with Call/ Cancel Button, The module should have membrane key pad with Call button (red) and Cancel button (Green) with Nurse symbol on Call button, 1xRJ45 connection for Patient Handset , 1 DIN socket and 2xRJ 45 connection for DATA BUS. Module must have antimicrobial coating on the surface and confirms to VDE 0834 as per technical specification etc. as required.
Supply, Installation, Testing and Commissioning of Patient Handset, The module will be connected with Bedside module with Intelifix connection features. The handset should have call button with Nurse sysmbol, membrane keypad with call button. optional Room or reading light control, 2.8 m cord. Handset must have antimicrobial coating on the surface and confirms to VDE 0834 as per technical specification etc. as required.
Supply, Installation, Testing and Commissioning of Pull cord, The Module should consist of finder / reassurance light with 2 mters pull cord with the grip and nurse symbol on it, with mounting frame for srew free installation as per technical specification etc. as required.
Supply, Installation, Testing and Commissioning of Call / Cancel button The module should consist of finder / reassurance light with membrane keypad includes call button with Nurse symbol, cancel button (green). The button must have antimicrobial coating on surface and confims to VDE 0834 as per technical specification etc. as required.
Supply, Installation, Testing and Commissioning of Indication Lamp The module should have LED indication of calls, presences and reminders in the relevant colours conforming to VDE0834, consist of White,RED, Blue and Green LED chamber each with 3 ultrahigh LEDS up to 10,000 operating hours as per technical specification etc. as required.
Supply, Installation, Testing and Commissioning of Nurse Station It should have 6.5" TFT wide viewing angle resolution of 800 x 480 touchscreen display. It should show all the call according to VDE 0834 and option of Collective announcements; Staff announcements, ward interconnection. It should be connected to System switch with TCP/IP POE inteface. The module must support VoIP speech comuunication. It should be connected to connection module with intelifix connection. It must fufill all the requirement mentioned in tender document as per technical specification etc. as required.
Supply, Installation, Testing and Commissioning of Software - License for event database Software pack on the Management Center for automati-cally handling of all events in the entire communications system, e.g. calls, presences, call acknowledgements, presences etc. This indication and analysis of the data is through a browser which has password-protected access to the XML data on the server. Various filters make it easily to find and display the required information as per technical specification etc. as required.
Sec.9.0 iBMS System (Note : Entire iBMS System proposed by contractor must be seamlessly integrate with existing 450 Bed iBMS System) Supplying, installation, testing and commissioning of Intel Core I7 Processor with EISA bus and with 3GHz minimum clock speed, minimum of 8 GB RAM , 512 KB cache, Minimum of 1TB storage, optical Mouse, 104 keys key board, with 10/100 Mbps Ethernet card (Min. of 3 slots) & internal modem. Server shall be RAID 5 configured. The system shall be provided with 21" TFT monitor for viewing GUI application. The back up server takes over in case the master server fails. This will be a redundant server configuration. with 21" LED / LCD Colour Monitor. as per technical specification etc. as required.
Supplying, installation, testing and commissioning of Laser Jet B/W Printer - A4 Size. as per technical specification etc. as required.
Supplying, installation, testing and commissioning of IBMS Server Software suite: This Web technology based software suite shall have unlimited concurrent user login licences. The client license provided shall display actual graphics as represented in the server machine. Shall be capable of interfacing with Bacnet/IP based DDC controllers, Bacnet/IP or modbus RTU 3rd party interface. Complete with Webserver for IBMS interface on Internet / Intranet. License for minimum hard/soft I/Os to be considered as per I/O Summary. Software should have the following Key features: 1. User Defined dashboard. Any Number of dashboard can be added by user. 2. Scalar/Vector Graphics to be supported. 3. Monthly Calender Dashboard: Monitor the demand/ consumption pattern for all days in a a month in a single screen. 4. Software shall be able to communicate with bacnet/ lonworks/ modbus simultaneously. 5. Mobile Platform: IPAD/ Android Compatible. 6. Software shall be Forword & Backward Compatible with 10 Years Obselation Support from OEM. 7. Display of HTML 5 Pages fromm company intranet or Internet for full smart device compatibility - with NO Java Dependancy in the Browser. 8.Database supported by software should be either SQL/oracle/db2. Also software should support 128 bit ssl encryption. Note: All required Software with original license competent with BMS software
Supply, Installation, Configuration, Programming of Web Based Energy Management & Reporting Tool software for Monitoring Building efficiency & Customization of Energy Management (For 40 Meters) Application that will Communicate with the Main Framework having Capability of Energy Profiling, Energy Mapping, Load Calculations, Predictive Energy Analysis, Energy Spectrum Analysis etc as per Functional Specifications of the Bid for 50 points. Bidders Must Consider all Application Modules and Licenses to be Part of the Bid. as per technical specification etc. as required.
Supply, Installation, testing, commissioning of UL listed, BTL approved IP BASED Open protocol INTEGRATOR with Inbuilt web browser & with max 150 device capacity, multiprotocol supported & should be of the same make as the DDC : INTEGRATION OF FOLLOWING SYSTEMS ON MODBUS-rtu / BACNET: The corresponding mentioned third party vendor shall be responsible to provide serial converter [RS 485 to RS 232] and the BMS vendor to accommodate the software address required for integration. including all necessary mounting hardware and accessories. as per technical specification etc. as required. for Chiller Units Soft Data Integration on Modbus / Bacnet Over IP as per technical specification etc. as required.
Supply, Installation, testing, commissioning of UL listed, BTL approved IP BASED Open protocol INTEGRATOR with Inbuilt web browser & with max 150 device capacity, multiprotocol supported & should be of the same make as the DDC: INTEGRATION OF FOLLOWING SYSTEMS ON MODBUS-rtu / BACNET: The corresponding mentioned third party vendor shall be responsible to provide serial converter [RS 485 to RS 232] and the BMS vendor to accommodate the software address required for integration. including all necessary mounting hardware and accessories. as per technical specification etc. as required. software interface for Secondry Pump Soft Data Integration on Modbus / Bacnet Over IP as per technical specification etc. as required.
Supply, Installation, testing, commissioning of UL listed, BTL approved IP BASED Open protocol INTEGRATOR with Inbuilt web browser & with max 150 device capacity, multiprotocol supported & should be of the same make as the DDC: INTEGRATION OF FOLLOWING SYSTEMS ON MODBUS-rtu / BACNET: The corresponding mentioned third party vendor shall be responsible to provide serial converter [RS 485 to RS 232] and the BMS vendor to accommodate the software address required for integration. including all necessary mounting hardware and accessories. as per technical specification etc. as required. software interface for Cooling Tower Soft Data Integration on Modbus / Bacnet Over IP as per technical specification etc. as required.
Supply, Installation, testing, commissioning of UL listed, BTL approved IP BASED Open protocol INTEGRATOR with Inbuilt web browser & with max 150 device capacity, multiprotocol supported & should be of the same make as the DDC : INTEGRATION OF FOLLOWING SYSTEMS ON MODBUS-rtu / BACNET: The corresponding mentioned third party vendor shall be responsible to provide serial converter [RS 485 to RS 232] and the BMS vendor to accommodate the software address required for integration. including all necessary mounting hardware and accessories. as per technical specification etc. as required. software interface for AHU's VFD Soft Data Integration on Modbus / Bacnet Over IP as per technical specification etc. as required.
Supply, Installation, testing, commissioning of UL listed, BTL approved IP BASED Open protocol INTEGRATOR with Inbuilt web browser & with max 150 device capacity, multiprotocol supported & should be of the same make as the DDC : INTEGRATION OF FOLLOWING SYSTEMS ON MODBUS-rtu / BACNET: The corresponding mentioned third party vendor shall be responsible to provide serial converter [RS 485 to RS 232] and the BMS vendor to accommodate the software address required for integration. including all necessary mounting hardware and accessories. as per technical specification etc. as required. software interface for Heat Pump (HVAC)'s VFD Soft Data Integration on Modbus / Bacnet Over IP as per technical specification etc. as required.
Supply, Installation, testing, commissioning of UL listed, BTL approved IP BASED Open protocol INTEGRATOR with Inbuilt web browser & with max 150 device capacity, multiprotocol supported & should be of the same make as the DDC: INTEGRATION OF FOLLOWING SYSTEMS ON MODBUS-rtu / BACNET: The corresponding mentioned third party vendor shall be responsible to provide serial converter [RS 485 to RS 232] and the BMS vendor to accommodate the software address required for integration. including all necessary mounting hardware and accessories. as per technical specification etc. as required. software interface for Energy Meter's Soft Data Integration on Modbus / RTU. as per technical specification etc. as required.
Supply, Installation, testing, commissioning of UL listed, BTL approved IP BASED Open protocol INTEGRATOR with Inbuilt web browser & with max 150 device capacity, multiprotocol supported & should be of the same make as the DDC : INTEGRATION OF FOLLOWING SYSTEMS ON MODBUS-rtu / BACNET: The corresponding mentioned third party vendor shall be responsible to provide serial converter [RS 485 to RS 232] and the BMS vendor to accommodate the software address required for integration. including all necessary mounting hardware and accessories. as per technical specification etc. as required. software interface for UPS's Soft Data Integration on Modbus / RTU. as per technical specification etc. as required.
Supply, Installation, testing, commissioning of UL listed, BTL approved IP BASED Open protocol INTEGRATOR with Inbuilt web browser & with max 150 device capacity, multiprotocol supported & should be of the same make as the DDC : INTEGRATION OF FOLLOWING SYSTEMS ON MODBUS-rtu / BACNET: The corresponding mentioned third party vendor shall be responsible to provide serial converter [RS 485 to RS 232] and the BMS vendor to accommodate the software address required for integration. including all necessary mounting hardware and accessories. as per technical specification etc. as required. software interface for Breaker's Soft Data Integration on Modbus / Bacnet Over IP as per technical specification etc. as required.
Supply, Installation, testing, commissioning of UL listed, BTL approved IP BASED Open protocol INTEGRATOR with Inbuilt web browser & with max 150 device capacity, multiprotocol supported & should be of the same make as the DDC: INTEGRATION OF FOLLOWING SYSTEMS ON MODBUS-rtu / BACNET: The corresponding mentioned third party vendor shall be responsible to provide serial converter [RS 485 to RS 232] and the BMS vendor to accommodate the software address required for integration. including all necessary mounting hardware and accessories. as per technical specification etc. as required. software interface for Fire Alarm System Soft Data Integration on Bacnet Over IP. as per technical specification etc. as required.
Supply, Installation, testing, commissioning of UL listed, BTL approved IP BASED Open protocol INTEGRATOR with Inbuilt web browser & with max 150 device capacity, multiprotocol supported & should be of the same make as the DDC : INTEGRATION OF FOLLOWING SYSTEMS ON MODBUS-rtu / BACNET: The corresponding mentioned third party vendor shall be responsible to provide serial converter [RS 485 to RS 232] and the BMS vendor to accommodate the software address required for integration. including all necessary mounting hardware and accessories. as per technical specification etc. as required. of software interface for Access Control System . as per technical specification etc. as required.
Supply, Installation, testing, commissioning of UL listed, BTL approved IP BASED Open protocol INTEGRATOR with Inbuilt web browser & with max 150 device capacity, multiprotocol supported & should be of the same make as the DDC : INTEGRATION OF FOLLOWING SYSTEMS ON MODBUS-rtu / BACNET: The corresponding mentioned third party vendor shall be responsible to provide serial converter [RS 485 to RS 232] and the BMS vendor to accommodate the software address required for integration. including all necessary mounting hardware and accessories. as per technical specification etc. as required. of software interface for DGs Soft Data Integration on Modbus / RTU. as per technical specification etc. as required.
Supply, Installation, testing, commissioning of UL listed, BTL approved IP BASED Open protocol INTEGRATOR with Inbuilt web browser & with max 150 device capacity, multiprotocol supported & should be of the same make as the DDC : INTEGRATION OF FOLLOWING SYSTEMS ON MODBUS-rtu / BACNET: The corresponding mentioned third party vendor shall be responsible to provide serial converter [RS 485 to RS 232] and the BMS vendor to accommodate the software address required for integration. including all necessary mounting hardware and accessories. as per technical specification etc. as required. of software interface for STPs Soft Data Integration on Modbus / RTU. as per technical specification etc. as required.
Supply, Developing, Testing, Commissioning of IP based 32 bit dual core microprocessor, minimum 128 MB RAM & 64 MB flash memory, true peer to peer communication,DDC to support NTP synchronization,DDC should be modular & expandable in steps for future expansion requirements, DDC with 230 VAC +_ 10 % powered will be preferrable , DDC shall have inbuilt web browser and support XML, along with DDC Panel for Chiller Plant Room - as per IO Summary and as per technical specification etc. as required.
Supply, Developing, Testing, Commissioning of IP based 32 bit dual core microprocessor, minimum 128 MB RAM & 64 MB flash memory, true peer to peer communication,DDC to support NTP synchronization,DDC should be modular & expandable in steps for future expansion requirements, DDC with 230 VAC +_ 10 % powered will be preferrable , DDC shall have inbuilt web browser and support XML, along with DDC Panel for Heat Pump (HVAC) - as per IO Summary and as per technical specification etc. as required.
Supply, Developing, Testing, Commissioning of IP based 32 bit dual core microprocessor, minimum 128 MB RAM & 64 MB flash memory, true peer to peer communication,DDC to support NTP synchronization,DDC should be modular & expandable in steps for future expansion requirements, DDC with 230 VAC +_ 10 % powered will be preferrable , DDC shall have inbuilt web browser and support XML, along with DDC Panel for AIR HANDLING UNITS WITH VFD BASED (4 NOS MODULATING DAMPERS) - as per IO Summary and as per technical specification etc. as required.
Supply, Developing, Testing, Commissioning of IP based 32 bit dual core microprocessor, minimum 128 MB RAM & 64 MB flash memory, true peer to peer communication,DDC to support NTP synchronization,DDC should be modular & expandable in steps for future expansion requirements, DDC with 230 VAC +_ 10 % powered will be preferrable , DDC shall have inbuilt web browser and support XML, along with DDC Panel for AIR HANDLING UNITS WITH VFD BASED (WITH VAV BOX SYSTEM + 2 NOS MODULATING DAMPERS) - as per IO Summary and as per technical specification etc. as required.
Supply, Developing, Testing, Commissioning of IP based 32 bit dual core microprocessor, minimum 128 MB RAM & 64 MB flash memory, true peer to peer communication,DDC to support NTP synchronization,DDC should be modular & expandable in steps for future expansion requirements, DDC with 230 VAC +_ 10 % powered will be preferrable , DDC shall have inbuilt web browser and support XML, along with DDC Panel for AIR HANDLING UNITS WITH VFD BASED- as per IO Summary and as per technical specification etc. as required.
Supply, Developing, Testing, Commissioning of IP based 32 bit dual core microprocessor, minimum 128 MB RAM & 64 MB flash memory, true peer to peer communication,DDC to support NTP synchronization,DDC should be modular & expandable in steps for future expansion requirements, DDC with 230 VAC +_ 10 % powered will be preferrable , DDC shall have inbuilt web browser and support XML, along with DDC Panel for AIR HANDLING UNITS WITH WITH FIRE EXHAUST PRO- as per IO Summary and as per technical specification etc. as required.
Supply, Developing, Testing, Commissioning of IP based 32 bit dual core microprocessor, minimum 128 MB RAM & 64 MB flash memory, true peer to peer communication,DDC to support NTP synchronization,DDC should be modular & expandable in steps for future expansion requirements, DDC with 230 VAC +_ 10 % powered will be preferrable , DDC shall have inbuilt web browser and support XML, along with DDC Panel for FLOOR MOUNTED AIR HANDLING UNITS RECYCLE WITH HEPA & HOTWATER - as per IO Summary and as per technical specification etc. as required.
Supply, Developing, Testing, Commissioning of IP based 32 bit dual core microprocessor, minimum 128 MB RAM & 64 MB flash memory, true peer to peer communication,DDC to support NTP synchronization,DDC should be modular & expandable in steps for future expansion requirements, DDC with 230 VAC +_ 10 % powered will be preferrable , DDC shall have inbuilt web browser and support XML, along with DDC Panel for FLOOR MOUNTED AIR HANDLING UNITS RECYCLE - as per IO Summary and as per technical specification etc. as required.
Supply, Developing, Testing, Commissioning of IP based 32 bit dual core microprocessor, minimum 128 MB RAM & 64 MB flash memory, true peer to peer communication,DDC to support NTP synchronization,DDC should be modular & expandable in steps for future expansion requirements, DDC with 230 VAC +_ 10 % powered will be preferrable , DDC shall have inbuilt web browser and support XML, along with DDC Panel for EXHAUST FANS / VENTILLATION FANS / JET FANS - Smoke Exhuast , Evacuation Fans, as per IO Summary and as per technical specification etc. as required.
Supply, Developing, Testing, Commissioning of IP based 32 bit dual core microprocessor, minimum 128 MB RAM & 64 MB flash memory, true peer to peer communication,DDC to support NTP synchronization,DDC should be modular & expandable in steps for future expansion requirements, DDC with 230 VAC +_ 10 % powered will be preferrable , DDC shall have inbuilt web browser and support XML, along with DDC Panel for Electrical Ststem - as per technical specification etc. as per IO Summary and as per technical specification etc. as required.
Supply, Developing, Testing, Commissioning of IP based 32 bit dual core microprocessor, minimum 128 MB RAM & 64 MB flash memory, true peer to peer communication,DDC to support NTP synchronization,DDC should be modular & expandable in steps for future expansion requirements, DDC with 230 VAC +_ 10 % powered will be preferrable , DDC shall have inbuilt web browser and support XML, along with DDC Panel for Plumbing System - as per IO Summary and as per technical specification etc. as required.
Supply, Developing, Testing, Commissioning of IP based 32 bit dual core microprocessor, minimum 128 MB RAM & 64 MB flash memory, true peer to peer communication,DDC to support NTP synchronization,DDC should be modular & expandable in steps for future expansion requirements, DDC with 230 VAC +_ 10 % powered will be preferrable , DDC shall have inbuilt web browser and support XML, along with DDC Panel for Water Tanks - as per IO Summary and as per technical specification etc. as required.
Supply, Developing, Testing, Commissioning of IP based 32 bit dual core microprocessor, minimum 128 MB RAM & 64 MB flash memory, true peer to peer communication,DDC to support NTP synchronization,DDC should be modular & expandable in steps for future expansion requirements, DDC with 230 VAC +_ 10 % powered will be preferrable , DDC shall have inbuilt web browser and support XML, along with DDC Panel for Fire Fighting Ststem - as per IO Summary and as per technical specification etc. as required.
Supply, installation, testing and commissioning of hand held portable operator terminals.(POT) touch screen type, shall be able to view graphs , alarms , parameters etc These shall be required if the Controllers and Integration Units do not have a built in keypad on the facia . With required connectors etc. - 4inch. as per technical specification etc. as required.
Supply, Installation, Testing, Commissioning of Outdoor type Ambient Temperature with Humidity Sensor with radiation shield , IP65 rated(Temp Range -30 to +50 °C, RH : 0-100 %). as per technical specification etc. as required.
Supply, Installation, Testing, Commissioning of Air Differential Pressure switches the for indicating the Blower status in Air able to measure pressure at 100-1000 pascal pressure. as per technical specification etc. as required.
Supply, Installation, Testing, Commissioning of Air Differential Pressure switches the for indicating the Filter status in Air able to measure pressure at 40-400 pascal pressure. as per technical specification etc. as required.
Supply, Installation, Testing, Commissioning of Temperature with Humidity Sensor, IP65 rated with RH accuracy 3 %, temp accuracy +_ 0.7 deg (0 to 70 Degree), as per technical specification etc. as required.
Supply, Installation, Testing, Commissioning of Air Type Differential Pressure Transmitter as per technical specification etc. as required.
Supply, Installation, Testing, Commissioning of Water Type absolute Pressure Transmitter as per technical specification etc. as required.
Supply, Installation, Testing, Commissioning of Water Type Differential Pressure Switch as per technical specification etc. as required.
Supply, Installation, Testing, Commissioning of Immersion Temperature Sensor,IP 65 rated thermister type Range of temp -10 to 50) with Thermowell, as per technical specification etc. as required.
Supply, Installation, Testing, Commissioning of Ultrasonic type Flow Meter as per technical specification etc. as required.
Supply, Installation, Testing, Commissioning of Ultrasonic type Level Switch as per technical specification etc. as required.
Supply, Installation, Testing, Commissioning of CO Sensor as per technical specification etc. as required.
Supplying, laying , testing and commissioning of 2 Core X 1.0 Sqmm Shielded Flexible Copper Cable (per I/O points hard wired to DDC). as per technical specification etc. as required.
Supplying, laying , testing and commissioning of 4 Core X 1.0 Sqmm UnShielded Flexible Copper Cable (per I/O points hard wired to DDC). as per technical specification etc. as required.
Supplying, laying , testing and commissioning of 2 Core X 1.5 Sqmm Shielded Flexible Copper Cable (per Soft I/O points to DDC). as per technical specification etc. as required.
Supplying, laying , testing and commissioning of 3 Core X 1.5 Sqmm Flexible Cable (per DDC to UPS Power Supply). as per technical specification etc. as required.
FFTG Supply, Installation, Testing and Commissioning of Electric driven fire pump (Hydrant Pump) suitable for automatic operation and consisting of following: complete in all respect as required. a) Horizontal, centrifugal end suction back pull out pump to ensure a minimum pressure of 3.5 kg / sq.cm. at highest and farthest outlet at specified flow of 2850 lpm at 100 m. head conforming to IS standards. b) Casing - CI, Impeller - Bronze, Shaft- SS 410, Mechanical Seal c) Squirrel cage induction motor with suitable HP with synchronous speed , Suitable for operation on 415 volts, 3 phase 50 Hz. AC with IP 55 protection for enclosure, IE-2, horizontal foot mounted type with Class-F insulation, Conforming to IS standards. d) Common Base plat for Pump and motor and coupling, coupling guard, foundation bolt and other accessories as required for complete Installation of pump set. e) Provide foundation details complete with anti-vibration arrangement etc.
Supply, Installation, Testing and Commissioning of Electric driven fire pump (Sprinkler Pump) suitable for automatic operation and consisting of following: complete in all respect as required. a) Horizontal, centrifugal end suction back pull out pump to ensure a minimum pressure of 3.5 kg / sq.cm. at highest and farthest outlet at specified flow of 2850 lpm at 100 m. head conforming to IS standards. b) Casing - CI, Impeller - Bronze, Shaft- SS 410, Mechanical Seal c) Squirrel cage induction motor with suitable HP with synchronous speed , Suitable for operation on 415 volts, 3 phase 50 Hz. AC with IP 55 protection for enclosure, IE-2, horizontal foot mounted type with Class-F insulation, Conforming to IS standards. d) Common Base plat for Pump and motor and coupling, coupling guard, foundation bolt and other accessories as required for complete Installation of pump set. e) Provide foundation details complete with anti-vibration arrangement etc.
Supply, Installation, Testing and Commissioning of Diesel Engine Driven standby pump suitable for automatic operation and consisting of following: complete in all respect as required. a) Horizontal, centrifugal end suction back pull out pump to ensure a minimum pressure of 3.5 kg / sq.cm. at highest and farthest outlet at specified flow of 2850 lpm at 100 m. head conforming to IS standards. b) Casing - CI, Impeller - Bronze, Shaft- SS 410, Mechanical Seal c) Diesel Engine with suitable HP with synchronous speed 2000 rpm, diesel tank, battery, battery cable, exhaust pipe with insulation with all required accessories. d) Common Base plat for Pump and motor and coupling, coupling guard, foundation bolt and other accessories as required for complete Installation of pump set. e) Provide foundation details complete with anti-vibration arrangement etc.
Supply, Installation, Testing and Commissioning of Electric driven hydrant Jockey pump suitable for automatic operation and consisting of following: complete in all respect as required. a) Vertical inline pump to ensure a minimum pressure of 3.5 kg / sq.cm. at highest and farthest outlet at specified flow of 180 lpm at 100 m. head conforming to IS standards. b) Casing - SS 304, Impeller-SS 304, Shaft - SS 304, Mechanical seal c) Squirrel cage induction motor with suitable HP with synchronous speed 2900 RPM, Suitable for operation on 415 volts, 3 phase 50 Hz. AC with IP 55 protection for enclosure, horizontal foot mounted type with Class-F insulation, Conforming to IS standards. d) Common Base plat for Pump and motor and coupling, coupling guard and other accessories as required for complete installation of pump set. e) Cement concrete foundation with cement concrete plaster will be in civil scope. Contractor has to provide foundation drawing to civil contractor.
Supply, Installation, Testing and Commissioning of Electric driven Sprinkler Jockey pump suitable for automatic operation and consisting of following: complete in all respect as required. a) Vertical inline pump to ensure a minimum pressure of 3.5 kg / sq.cm. at highest and farthest outlet at specified flow of 180 lpm at 100 m. head conforming to IS standards. b) Casing - SS 304, Impeller-SS 304, Shaft - SS 304, Mechanical seal c) Squirrel cage induction motor with suitable HP with synchronous speed 2900 RPM, Suitable for operation on 415 volts, 3 phase 50 Hz. AC with IP 55 protection for enclosure, horizontal foot mounted type with Class-F insulation, Conforming to IS standards. d) Common Base plat for Pump and motor and coupling, coupling guard and other accessories as required for complete installation of pump set. e) Cement concrete foundation with cement concrete plaster will be in civil scope. Contractor has to provide foundation drawing to civil contractor.
Supply, Installation, Testing and Commissioning of Electric driven fire pump (Water Curtain Pump) suitable for automatic operation and consisting of following: complete in all respect as required. a) Horizontal, centrifugal end suction back pull out pump to ensure a minimum pressure of 3.5 kg / sq.cm. at highest and farthest outlet at specified flow of 2280 lpm at 70 m. head conforming to IS standards. b) Casing - CI, Impeller - Bronze, Shaft- SS 410, Mechanical Seal c) Squirrel cage induction motor with suitable HP with synchronous speed , Suitable for operation on 415 volts, 3 phase 50 Hz. AC with IP 55 protection for enclosure, IE-2, horizontal foot mounted type with Class-F insulation, Conforming to IS standards. d) Common Base plat for Pump and motor and coupling, coupling guard, foundation bolt and other accessories as required for complete Installation of pump set. e) Provide foundation details complete with anti-vibration arrangement etc.
Supply, Installation, Testing and Commissioning of Electric driven Terrace pump (For Dormitories) suitable for automatic operation and consisting of following: complete in all respect as required. a) Horizontal, centrifugal end suction back pull out pump to ensure a minimum pressure of 3.5 kg / sq.cm. at highest and farthest outlet at specified flow of 900 lpm at 40 m. head conforming to IS standards. b) Casing - CI, Impeller - Bronze, Shaft- SS 410, Mechanical Seal c) Squirrel cage induction motor with suitable HP with synchronous speed , Suitable for operation on 415 volts, 3 phase 50 Hz. AC with IP 55 protection for enclosure, IE-2, horizontal foot mounted type with Class-F insulation, Conforming to IS standards. d) Common Base plat for Pump and motor and coupling, coupling guard, foundation bolt and other accessories as required for complete Installation of pump set. e) Provide foundation details complete with anti-vibration arrangement etc.
Supply, Installation, Testing and Commissioning of 150 mm dia. Pressure Gauge (for all pipes) of range 0 - 21 Kg / cm² Polished Stainless Steel Case with positive seal against weather, moisture & dust, with Glycerine filled, screwed, nipple, isolation valve, U-type stainless steel siphon tube and complete with necessary as required.
Supply, Installation, Testing and Commissioning of Pressure Switches for automation of fire pumps. Pressure switches shall be SPDT type suitable for single phase supply with diaphragm, IP 67 protection as required.
Supply, Installation, Testing and Commissioning of the following sizes of flange jointed / screwed / welded, M.S. Pipes Above ground of Class C (Heavy class) ISI marked including accessories such as MS bracket, U clamps with Anchor fasteners, tees / elbows / reducers / couplings / unions / bends / flanges etc., and laying on the surface including painting with two coats of anticorrosive primer and two coats of approved red enamel paint after laying and testing after Installation etc. as per specifications complete as required.(IS:1239 / 3589) All fittings up to 50mm shall be forged and above 50mm shall be butt welded. 250 mm dia. (wall thickness 6.3 mm)
Supply, Installation, Testing and Commissioning of the following sizes of flange jointed / screwed / welded, M.S. Pipes Above ground of Class C (Heavy class) ISI marked including accessories such as MS bracket, U clamps with Anchor fasteners, tees / elbows / reducers / couplings / unions / bends / flanges etc., and laying on the surface including painting with two coats of anticorrosive primer and two coats of approved red enamel paint after laying and testing after Installation etc. as per specifications complete as required.(IS:1239 / 3589) All fittings up to 50mm shall be forged and above 50mm shall be butt welded. 200 mm dia. (wall thickness 6.3 mm)
Supply, Installation, Testing and Commissioning of the following sizes of flange jointed / screwed / welded, M.S. Pipes Above ground of Class C (Heavy class) ISI marked including accessories such as MS bracket, U clamps with Anchor fasteners, tees / elbows / reducers / couplings / unions / bends / flanges etc., and laying on the surface including painting with two coats of anticorrosive primer and two coats of approved red enamel paint after laying and testing after Installation etc. as per specifications complete as required.(IS:1239) All fittings up to 50mm shall be forged and above 50mm shall be butt welded. 150 mm dia.
Supply, Installation, Testing and Commissioning of the following sizes of flange jointed / screwed / welded, M.S. Pipes Above ground of Class C (Heavy class) ISI marked including accessories such as MS bracket, U clamps with Anchor fasteners, tees / elbows / reducers / couplings / unions / bends / flanges etc., and laying on the surface including painting with two coats of anticorrosive primer and two coats of approved red enamel paint after laying and testing after Installation etc. as per specifications complete as required.(IS:1239) All fittings up to 50mm shall be forged and above 50mm shall be butt welded. 100 mm dia.
Supply, Installation, Testing and Commissioning of the following sizes of flange jointed / screwed / welded, M.S. Pipes Above ground of Class C (Heavy class) ISI marked including accessories such as MS bracket, U clamps with Anchor fasteners, tees / elbows / reducers / couplings / unions / bends / flanges etc., and laying on the surface including painting with two coats of anticorrosive primer and two coats of approved red enamel paint after laying and testing after Installation etc. as per specifications complete as required.(IS:1239) All fittings up to 50mm shall be forged and above 50mm shall be butt welded. 80 mm dia.
Supply, Installation, Testing and Commissioning of the following sizes of flange jointed / screwed / welded, M.S. Pipes Above ground of Class C (Heavy class) ISI marked including accessories such as MS bracket, U clamps with Anchor fasteners, tees / elbows / reducers / couplings / unions / bends / flanges etc., and laying on the surface including painting with two coats of anticorrosive primer and two coats of approved red enamel paint after laying and testing after Installation etc. as per specifications complete as required.(IS:1239) All fittings up to 50mm shall be forged and above 50mm shall be butt welded. 65 mm dia.
Supply, Installation, Testing and Commissioning of the following sizes of flange jointed / screwed / welded, M.S. Pipes Above ground of Class C (Heavy class) ISI marked including accessories such as MS bracket, U clamps with Anchor fasteners, tees / elbows / reducers / couplings / unions / bends / flanges etc., and laying on the surface including painting with two coats of anticorrosive primer and two coats of approved red enamel paint after laying and testing after Installation etc. as per specifications complete as required.(IS:1239) All fittings up to 50mm shall be forged and above 50mm shall be butt welded. 50 mm dia.
Supply, Installation, Testing and Commissioning of the following sizes of flange jointed / screwed / welded, M.S. Pipes Above ground of Class C (Heavy class) ISI marked including accessories such as MS bracket, U clamps with Anchor fasteners, tees / elbows / reducers / couplings / unions / bends / flanges etc., and laying on the surface including painting with two coats of anticorrosive primer and two coats of approved red enamel paint after laying and testing after Installation etc. as per specifications complete as required.(IS:1239) All fittings up to 50mm shall be forged and above 50mm shall be butt welded. 40 mm dia.
Supply, Installation, Testing and Commissioning of the following sizes of flange jointed / screwed / welded, M.S. Pipes Above ground of Class C (Heavy class) ISI marked including accessories such as MS bracket, U clamps with Anchor fasteners, tees / elbows / reducers / couplings / unions / bends / flanges etc., and laying on the surface including painting with two coats of anticorrosive primer and two coats of approved red enamel paint after laying and testing after Installation etc. as per specifications complete as required.(IS:1239) All fittings up to 50mm shall be forged and above 50mm shall be butt welded. 32 mm dia.
Supply, Installation, Testing and Commissioning of the following sizes of flange jointed / screwed / welded, M.S. Pipes Above ground of Class C (Heavy class) ISI marked including accessories such as MS bracket, U clamps with Anchor fasteners, tees / elbows / reducers / couplings / unions / bends / flanges etc., and laying on the surface including painting with two coats of anticorrosive primer and two coats of approved red enamel paint after laying and testing after Installation etc. as per specifications complete as required.(IS:1239) All fittings up to 50mm shall be forged and above 50mm shall be butt welded. 25 mm dia.
Supply, Installation, Testing and Commissioning of the following sizes of flange jointed / screwed / welded, M.S. Pipes Under ground of Class C (Heavy class) ISI marked including accessories such as MS bracket, U clamps with Anchor fasteners, tees / elbows / reducers / couplings / unions / bends / flanges etc., and wrapping coating as per IS:10221, after laying and testing after Installation etc. as per specifications complete as required.(IS:1239) All fittings up to 50mm shall be forged and above 50mm shall be butt welded. 150 mm dia.
Supply, Installation, Testing and Commissioning of the following sizes of flange jointed / screwed / welded, M.S. Pipes Under ground of Class C (Heavy class) ISI marked including accessories such as MS bracket, U clamps with Anchor fasteners, tees / elbows / reducers / couplings / unions / bends / flanges etc., and wrapping coating as per IS:10221, after laying and testing after Installation etc. as per specifications complete as required.(IS:1239) All fittings up to 50mm shall be forged and above 50mm shall be butt welded. 100 mm dia.
Supply, Installation, Testing and Commissioning of the following sizes of flange jointed / screwed / welded, M.S. Pipes Under ground of Class C (Heavy class) ISI marked including accessories such as MS bracket, U clamps with Anchor fasteners, tees / elbows / reducers / couplings / unions / bends / flanges etc., and wrapping coating as per IS:10221, after laying and testing after Installation etc. as per specifications complete as required.(IS:1239) All fittings up to 50mm shall be forged and above 50mm shall be butt welded. 80 mm dia.
Supply, Installation, Testing and Commissioning of C.I. Y type Strainer with S.S. Screen/SS 304 having 1.2mm perforation with require accessories. 250 mm Dia.
Supply, Installation, Testing and Commissioning of C.I. Y type Strainer with S.S. Screen/SS 304 having 1.2mm perforation with require accessories. 100 mm Dia.
Supply, Installation, Testing and Commissioning of C.I. Sluice valve (IS: 14846,PN 16) with flanges, nut bolts, gaskets complete as required. 250 mm dia.
Supply, Installation, Testing and Commissioning of C.I. Sluice valve (IS: 14846,PN 16) with flanges, nut bolts, gaskets complete as required. 200 mm dia.
Supply, Installation, Testing and Commissioning of C.I. Sluice valve (IS: 14846,PN 16) with flanges, nut bolts, gaskets complete as required. 150 mm dia.
Supply, Installation, Testing and Commissioning of C.I. Sluice valve (IS: 14846,PN 16) with flanges, nut bolts, gaskets complete as required. 100 mm dia.
Supply, Installation, Testing and Commissioning of C.I. Sluice valve (IS: 14846,PN 16) with flanges, nut bolts, gaskets complete as required. 80 mm dia.
Supply, Installation, Testing and Commissioning of C.I. Sluice valve (IS: 14846,PN 16) with flanges, nut bolts, gaskets complete as required. 65 mm dia.
Supply, installation, testing and commissioning of C.I. Butterfly valve (PN 16) with flanges, nut bolts, gaskets complete as required. 150mm dia.
Supply, installation, testing and commissioning of C.I. Butterfly valve (PN 16) with flanges, nut bolts, gaskets complete as required. 100mm dia.
Supply, installation, testing and commissioning of C.I. Butterfly valve (PN 16) with flanges, nut bolts, gaskets complete as required. 80mm dia.
Supply, installation, testing and commissioning of C.I. Butterfly valve (PN 16) with flanges, nut bolts, gaskets complete as required. 65mm dia.
Supply, Installation, Testing and Commissioning of Cast iron Dual plate Check valve (PN 1.6) 250 mm dia.
Supply, Installation, Testing and Commissioning of Cast iron Dual plate Check valve (PN 1.6) 150 mm dia.
Supply, Installation, Testing and Commissioning of Cast iron Dual plate Check valve (PN 1.6) 100 mm dia.
Supply, Installation, Testing and Commissioning of Cast iron Dual plate Check valve (PN 1.6) 65 mm dia.
Supply, Installation, Testing and commissioning of Air vessel of size 450 x 2000 mm long fabricated from min. 8 mm thick or more M.S Plate and installed vertically on suitable legs with necessary accessories as required for complete Installation. (Test Pressure 15kg/cm²)
Supply, Installation, Testing and Commissioning S.S. Fire Hydrant Single Landing Valve with 80 mm N.B. flanged inlet, SS spindle controlled 63 mm dia female instantaneous outlet type. SS coupling, blank cap, chain, twist release type lug & all accessories Conforming to IS:5290. Including fixing with anchor fastener and flanged tapping from wet riser complete as required.
Supply, Installation, Testing and commissioning of 63 mm dia instantaneous pattern SS short branch pipe, 20 mm dia nozzle conforming to IS 903, suitable for inter connection to hose pipe coupling complete as required by the Local Fire Authority.
Supply, Installation, Testing and Commissioning of Fire Hose Cabinet wall mounting type 16swg (750 mm x 600 mm x 250 mm deep) with required accessories as per specification.
Supply, installation, testing and commissioning non-percolating rubber reinforced lined Fire Hose pipe (as per IS : 636) of 63 mm dia and 1x15 mtrs long. The hose shall be rated for burst pressure of 38 kg/sqcm. Hose shall be complete with ISI marked SS male & female coupling (IS:903) bound as per specification.
Supply, installation, testing and commissioning of First- Aid Hose Reel equipment with M.S. construction spray painted in post office red, conforming to IS:884 with up to date amendments, complete with the following as required. (a) 36 m. long, 25 mm dia. water hose thermoplastic (Textile reinforced) Type-2 as per IS:12585. (b) S.S. 304 shut off nozzle (c) Drum and swinging type fixing brackets on the wall. (d) Connections from riser with isolation valve
Supply, installation, testing and commissioning of forged brass Ball Valve. (PN 25) 25mm dia
Providing and fixing standard fireman Axe with heavy duty insulated rubber handle as per IS: 926 with clamps.
Supply, installation, testing and commissioning of Cast Iron Four Way Fire Brigade Inlet as per IS: 904 having 63 mm dia inlet with blank cap and chain with necessary fittings, flanges, nut bolts etc. complete as required.
Supply, installation, testing and commissioning of Cast Iron Two Way Fire Brigade Inlet as per IS: 904 having 63 mm dia inlet with blank cap and chain with necessary fittings, flanges, nut bolts etc. complete as required.
Providing & fixing CI Draw-out connection with foot valve with strainer with 2 nos 63 mm dia instantaneous type male couplings complete as per specification/drawings and as directed by Engineer In Charge.
Supply, Installation, Testing and Commissioning of Gun Metal Air Release Valve with necessary fittings. Size: 25 mm (For Riser)
Supply, Installation, Testing and commissioning of Quartzoid Bulb type Sprinkler Heads. Pendent Sprinkler 68°C - K-80 - standard response - UL listed
Supply, Installation, Testing and commissioning of Quartzoid Bulb type Sprinkler Heads. Upright Sprinkler 68°C - K-80 - standard response - UL listed
Supply, Installation, Testing and commissioning of Quartzoid Bulb type Sprinkler Heads. Sidewall Sprinkler 68°C - K-80 - standard response - UL listed
Providing, installation, testing & commissioning of adjustable rosette plate chrome finish (UL listed & FM approved)complete as required.
Supply, Installation, Testing and Commissioning of Brass Sprinkler test and Drain Valve (300 PSI) assembly with all required fittings as per drawing and as directed.(UL listed & FM approved) 50mm dia.
Supplying, installation, testing & commissioning of sprinkler braided flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stockbar of following sizes complete as required. 700mm
Supplying, installation, testing & commissioning of sprinkler braided flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stockbar of following sizes complete as required. 1000mm
Supplying, installation, testing & commissioning of sprinkler braided flexible pipe (UL Listed) of stainless steel complete with 15 NPT on reducer thread with maximum working pressure of 175 PSI test pressure of 875 PSI (Burst) with branch line (Inlet) 25mm NPT male thread to sprinkler head (Outlet) 15mm NPT female thread with reducer, nipple, 2 side brackets, center bracket, stockbar of following sizes complete as required. 1200mm
Supply, Installation, Testing and commissioning of Vane type Flow Indicating Switch with fittings, Flanges, nut-bolts, washers etc. as per requirement. (UL listed & FM approved) 150 mm dia.
Supply, Installation, Testing and commissioning of Vane type Flow Indicating Switch with fittings, Flanges, nut-bolts, washers etc. as per requirement. (UL listed & FM approved) 100 mm dia.
Supply, Installation, Testing and commissioning of crome plated brass Water Curtain Nozzle. (K-48@ 1.4 bar, UL listed)
Supply, Installation, Testing and Commissioning Cast Iron Deluge Valve for Water Curtain system with required panel, cable, isolation valves, solenoid valve, panel,accessories & integration with other service. a) 150 mm Dia
Providing, fixing, testing & commissioning of Installation control valve of cast iron body, brass/bronze working parts comprising of water motor alarm, bronze seat clapper, clapper arm and hydraulically driven mechanical gong bell to sound continuous alarm when the sprinkler system activates, pressure gauges, emergency releases, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves, MS pipe of required size, flanges, orifice plate, gasket etc of following sizes as required : Size: 150mm dia
Supplying and fixing orifice plate made out of 6 mm thick stainless steel (Grade 304) with orifice of required size to be fitted between flange & landing valve to reduce pressure at the outlet to the level of 3.5 kg/cm2 complete as required.(For hydrant & sprinkler tapping line, wherever require.)
Supply, installation, testing and commissioning of Carbon Dioxide (Co2) type Fire Extinguisher of 4.5 kg confirm to IS:15683, stored pressure, squeeze type with ISI marked fitted with required accessories including wall suspension brackets.
Supply, installation, testing and commissioning of ABC (MAP 90%) type 6 kg stored pressure, squeeze type confirm to IS:15683, with ISI marked fitted with required accessories including wall suspension brackets.
Supply and fixing of Clean Agent HCF236fa, 10 Kg modular type ceiling mounted Fire extinguisher , Stored pressure type with pressure gauge.
Supply, installation, testing and commissioning of 2 hrs Fire stop cement for Fire shaft cut-outs as per specifications.
Providing, fixing AUTO GLOW photo luminescent Signage's as per IS standard in Block / Small Letters on rigid sheet with necessary wall or Ceiling fittings as Specified Sizes: Fire lift: size: 100 X 300mm
Providing, fixing AUTO GLOW photo luminescent Signage's as per IS standard in Block / Small Letters on rigid sheet with necessary wall or Ceiling fittings as Specified Sizes: In case of Fire, do not use lift, use staircase: 200 X 200mm
Providing, fixing AUTO GLOW photo luminescent Signage's as per IS standard in Block / Small Letters on rigid sheet with necessary wall or Ceiling fittings as Specified Sizes: Fire Equipment : size: 100 X 300mm
Providing, fixing AUTO GLOW photo luminescent Signage's as per IS standard in Block / Small Letters on rigid sheet with necessary wall or Ceiling fittings as Specified Sizes: Floor indication signage : size: 300 X 300mm
Providing, fixing AUTO GLOW photo luminescent Signage's as per IS standard in Block / Small Letters on rigid sheet with necessary wall or Ceiling fittings as Specified Sizes: Assembly Point : 600 X 600mm
Providing, fixing AUTO GLOW photo luminescent Signage's as per IS standard in Block / Small Letters on rigid sheet with necessary wall or Ceiling fittings as Specified Sizes: Emergency Escape Plan : A3 (297 X 420mm) Contractor should prepare the drawings.
Providing, fixing AUTO GLOW photo luminescent Signage's as per IS standard in Block / Small Letters on rigid sheet with necessary wall or Ceiling fittings as Specified Sizes: Fire Action : 600 X 450mm
Supply Of Self Contained Rechargeable SWGS Emergency Egress Routes Lighting With the 1X 3 W LED Lamp. The equipment Shall Surface/hanging mounted with all require Accessories with requirement for the Fire and Safety code of practice with 3 Hours backup. Nominal Input Voltage 230 +-10 % to 240V A.C. +-10 % 50 Hz +-10 % as specified in specification. (Size:300 x 180mm)
Supply, installation, testing and commissioning of Pump on/off Remote switches to each internal hydrant valve with required accessories. (For Dormitories)
Supply, installation, testing and commissioning of XLPE insulated FRLS copper armoured Cable with conduit from each Pump on/off switches to Panel with all necessary accessories. Size: 4 core x 2.5 sq. mm
Getting Approval/NOC of Fire protection system (Hydrant, Sprinkler etc..) from local fire authority and any other relevant statutory authority at initial and various other stages of work, including preparation of report/drawings as per fire authority.
Autotube cleaning system for each chiller complete with Maniifold / Pumping / Sensors / Moving tube spong/ewq material cleaning balls / electrical works as requried
Supply Programming & Integration of Chiller Master Controller (CPM) supporting BACNet protocol housed in IP42 Panel duly internally wired, tested, designed&configured for integrated Control of Five Chillers, 5 CHWP Pumps, 5 SCHW Pumps / 5 CDS Pumps, 4 Cooling Towers with Auxillaries as shown in Plant Room Layout; the Master Controller (CPM) shall be integrated with 1 sets of Variable Speed Controllers seamlessly and finally with Central BAS system including authorization of Read/Write facility provided by Chiller Manufacturer
Supply, Programming, Installation, Testing and Commissioning of Integrated Variable Speed Pumping Control System PANEL comprising of 1 Set Pump Logic Controller designed for 5 Drives, 5 Nos Pump Starters and 5 Sets of matching Variable frequency drives (with individual isolator & bypass arrangement) duly internally wired and tested (parallel pumping software downloaded); Controller shall support BACNetIP
Condenser Cooling Water Pumping System with accessories Supply, Installation, Alignment, Testing and Commissioning of HSC / End Suction (Better Effi at Duty point among the two) design, Centrifugal type Condenser Cooling water pumps as specified complete with mechanical seal, CI casing and Bronze Impeller - designed to operate at minimum 80% overall efficiency; the pump shall be dynamically balanced and supplied with 4 Pole TEFC IP 55 IE 3 Induction Motor, Flexible coupling with Guard, Corrossion resistant painted factory supplied MS baseframe with necessary vibration isolators and Rubber flexible bellows at suction and discharge nozzels; Centrifugal Pump with above accessories and Cooling water Flow rate = 2250 USGPM / 24 M WC (4 Working 1 SB)
FRP Induced draft cooling tower Supply, installation, testing and commissioning of CTI Certified 650 TR FRP Induced draft TWIN CELL Design Cooling tower as specified; Tower shall be MS HDG Frame work, Access ladder & Supports; FRP Casing and FRP Basin with makeup including Float valve, PVC fills, Distribution system with PP Nozzels, Axial Flow Direct drive Fan with PVC Blades & Al Alloy Hub driven by TEFC weather proof low RPM Dual IE 3 Speed motor for compliance with GRIHA requirement, suitable for 415±10% V, 50 Hz, 3 phase supply; power / control wiring, earthing, drain, make up, quick fill connection / HiLow Sump Level switch fixing provision and vibration isolation etc. as recommended by mfr. not less than tender specified requirements; Tower Design Capacity shall be designed for 2250 USGPM Cooling water Flow to achieve Water Leaving temp = 32 deg C at 29.5 deg C design WBT; Performance Charts and Paramters as specified to be submitted during detailed engg. Stage; 4 Working 1SB
Pressurized expansion Tank for chilled Water Design, Supply, installation, testing and commissioning of instulated pressure type expansion tank to be located within First Floor Plant Room complete with MS HDG supports = Tanks shall be of size suitable for expansion provision of water occupying total pipe volume as per sizes shown in layouts complete with integral heavy duty rubber diaphragm, system pressure 125 psig and temperature difference of 10 deg F; tank sizing calculations to be submitted by HVAC Contractor during detailed engg stage
Supply installation and commissioning of PVC fill tank of 1000 liters capacity with Pressurization / Makeup Pumps for Required Flow USGPM (1+1) flow rate coupled with suitable rating motor, relief valve, pressure gauge, cotrol panel, pressure switch, drain pipe, fittings, valves; Pump shall be sized to creat the required pressure in the system and complete with check valve, Y strainer, butter fly valve at suction/dischagre 25 mm dia.; IP 55 pump electrical panel for operation on pressure switch inclucing supply of Pressure switch
Air Separators Supply, installation, testing and commissioning of Insulated (to 32 mm thick & balance CHW Piping Insulation specifications) common air separator on the return water line located at the pump suction and suitable for cumulative Secondary pump water flow; the separator shall be complete with high capacity air vent, service valve, non return valve, isolation butterfly valve for makeup water inlet
MS Fabrication
Air Source Heatpump without external HW Pump connectivity feature as specified in Tender and further HEAT PUMP shall have standard hermetic/semi-hermetic rotary screw/scroll compressors, electronic expansion device (EEXV), shell & tube/ Plate type heat exchanger, air-cooled fin & tube condenser section, R134a /R410a/R407c refrigerant, lubrication system, motor starting components, suction line shut-off valve, discharge line shut-off valve, control system and all components necessary for safe and stable unit operation. The unit will be factory assembled on a robust base-frame made of zinc coated steel, protected by epoxy paint Rating: 175 kW Heat Rating; HW Leaving temperature 60 deg C
Hotwater recirculation Primary Pumps with accessories Supply, Installation, Alignment, Testing and Commissioning of HSC / End Suction (Better Effi at Duty point among the two) design, Centrifugal type Condenser Cooling water pumps as specified complete with mechanical seal, CI casing and Bronze Impeller - designed to operate at minimum 80% overall efficiency; the pump shall be dynamically balanced and supplied with 4 Pole TEFC IE 3 Induction Motor, Flexible coupling with Guard, Corrossion resistant painted factory supplied MS baseframe with necessary vibration isolators and Rubber flexible bellows at suction and discharge nozzels; Centrifugal Pump with above accessories and Cooling water Flow rate 135 USGPM / 18 M WC (2W 1SB)
Hotwater recirculation Secondary Pumps with accessories Supply, Installation, Alignment, Testing and Commissioning of HSC / End Suction (Better Effi at Duty point among the two) design, Centrifugal type Condenser Cooling water pumps as specified complete with mechanical seal, CI casing and Bronze Impeller - designed to operate at minimum 80% overall efficiency; the pump shall be dynamically balanced and supplied with 4 Pole TEFC IE 3 Induction Motor, Flexible coupling with Guard, Corrossion resistant painted factory supplied MS baseframe with necessary vibration isolators and Rubber flexible bellows at suction and discharge nozzels; Centrifugal Pump with above accessories and Cooling water Flow rate 135 USGPM / 28 M WC (2W 1SB)
HW System Plate heat Exchanger with 140 USGPM RATING Primary (HOT) & Secondary (COLD) side HW Circuit designed for 1 deg C Leaving Temp Diff (HOT In to COLD Out); 60 deg C HW IN Primary; 55 deg C HW Return PRIMARY; 59 deg C HW Out secondary; 54 deg C HW Return to Secondary; complete with factory MS HDG FOundation / supply installation & commissioning of required Accessories; Both SIdes shall have Single Pass / 304SS Eq Plate material 0.5 mm thk / NBR Gasket / IS2062 Frame material withsynthetic enamel and CS Nutbolts (1 W 1 SB)
B1FMAHU03-04+FIEX
B1FMAHU05+FIEX
B1FMAHU06
B1FMAHU07
B1FMAHU08
B1CSAHU01
B1FMAHU09
B1FMAHU11
B1CSAHU02
B1CSAHU03
B1CSAHU04
B1CSAHU05+FIEX
GFMAHU03
GFMAHU08-09
GFMAHU10VAV
GFMAHU11VAV
GFMAHU12
GFMAHU13VAV
GFMAHU14VAV
GFMAHU15VAV
GFMAHU16VAV
GFMAHU18
GFMAHU19
GFMAHU21
GFMAHU22
1STFMAHU04-05
1STFMAHU06VAV
1STFMAHU07VAV
1STFMAHU08VAV
1STFMAHU09VAV
1STCSAHU01-04
2NDFMAHU04-05
2ND FMAHU06VAV
2NDFMAHU07VAV
2NDFMAHU08
2NDFMAHU09VAV
2NDCSAHU01-04
3RDFMAHU04-05
3RDFMAHU06VAV
3RDFMAHU07VAV
3RDFMAHU08
3RDFMAHU09VAV
3RDCSAHU01-04
4THFMAHU04-05
4THFMAHU06VAV
4THFMAHU07VAV
4THFMAHU08
4THFMAHU09VAV
4THCSAHU01-04
5THFMAHU04-05
5THFMAHU06VAV
5THFMAHU07VAV
5THFMAHU08
5THAHUFM09VAV
5THCSAHU01-04
6THFMAHU04-05
6THFMAHU06-07VAV
6THCSAHU01
6THFMCSAHU02
6THCSAHU03
B1FMAHU10
B1FMAHU12
B1FMAHU13
GFMAHU01
GFMAHU02
GFMAHU17
GFMAHU20
1STFMAHU01
1STFMAHU02
1STFMAHU03
2NDFMAHU01
2NDFMAHU02
2NDFMAHU03
3RDFMAHU01
3RDFMAHU02
3RDFMAHU03
4THFMAHU01
4THFMAHU02
4THFMAHU03
5THFMAHU01
5THFMAHU02
5THFMAHU03
6THFMAHU01
6THFMAHU02
6THFMAHU03
6THFMAHU08VAV
6THFMAHU09VAV
SAME AS 8.3.1 BUT DEISIGNED FOR TERMINAL HEPA FILTERS; GFMAHU04VAV
GFMAHU05OT
GFMAHU06OT
GFMAHU07OT
TER-AHUSTRCOR
TER-OTAHU1
TER-OTAHU2
TER-OTAHU3
TER-OTAHU4
TER-OTAHU5
TER-OTAHU6
TER-OTAHU7
TER-OTAHU8
TER-OTAHU9
TER-OTAHU10
TREATED CHW FRESH AIR HANDLING UNITs Ceiling Suspended/Floor Mounted double skinned insulated with 43 mm thk 40 kg/m3 density PUF (or simialr non hygroscopic equivalent U value insulation) TFA Air Handling Unit supplied with (Bottom Access Doors for all Ceiling Units) & reqired Spring isolators; 22G inner/outer skin and Frame work with thermal break Al profile / SS 304-20G Drain tray insulated with 13 mm Nitrile insulation and drain Trap; 100% Fresh Air Intake with MERV 8 (10 Micron) Fresh Air Filter in a GI leakproof Framed Structure / 8 Row deep Chilled Water Coil section with AHRI certified Coil (0.15mm AL 13 FPI fins / 12.7 mm OD 27 SWG Cu Tube)/ Fan section with AMCA/Eq. PLUG Fan with drive package having spring mounted IP55/4P/TEFC/EFF1 Motor/ Balance specifications as per tender & Performance as per paramters mentioned under Design Schdeule against each AHU Tag No appearing below. Price should include additional external insulation for all exposed-to-atmosphere & above Ceiling AHUs using 25mm Nitrile Rubber insulation with UV & mechanical protection. For each model, Vendor shall provide Casing performance Certification Class complied for Casing Deflection (CD) / Air leakage (CL) / Thermal Transmitance (CT) w.r.t AHRI 1350 Standards producing Type Test Certificates to support the same in their data sheets B1-CSTFAU-1350 CFM/55 MM WC
B1-CSTFAU-400 CFM / 55 MM WC
GF-TFAU-560 CFM/55 MM WC
FF-TFAU-710 CFM/55 MM WC
FF-TFAU-600 CFM/55 MM WC
FF-TFAU-1100 CFM/55 MMWC
6THTFAU-1100 CFM/55 MM WC
Double Skinned Chilled Water Fan Coil Units Double Skinned 25 mm thick sandwitch insulated Fan Coil Units as specified with Cu Winding Motor / 10M Filter/Filter section / 4R Deep CHW Coil / Fan section complete in Powder coated finish with factory assembled and tested 2 way PIBCV valve with On/Off Actuator including pair of brass ball valve + inlet strainer; Price should include additional external insulation for all FCUs using 13mm Nitrile Rubber insulation _ 400 CFM / 1 TR
600 CFM / 1.5 TR
800 CFM / 2 TR
1000 CFM / 2.5 TR
1200 CFM / 3 TR
CHW Ductable FCU / CS AHU for following ratings with Double Skinned 25 mm thick sandwitch insulated 1Ph ductable Fan Coil Units / CSAHU as specified with Cu Winding Motor / 10M Filter/Filter section / 4R Deep CHW Coil / Fan section complete in Powder coated finish with factory assembled and tested 2 way PIBCV valve with On/Off Actuator including pair of brass ball valve + inlet strainer; Price should include additional external insulation for all FCUs using 13mm Nitrile Rubber insulation 1000 CFM / 8 MM ESP
1200 CFM / 10 MM ESP
2000 CFM / 12 MM ESP
Drain Pump for Condensate Drain line complete with installation and fixtures for FAN Coil Units
All Fibre body FCU Thermostat comprising of setpoint knob, power On/Off, 3 speed Switch and Digital Temp Display, 10 RMT control wiring laid in ready conduits; rates shall include fixing of thermostat as per architects requirement including all accessories as required
Exhaust Air Flow Regulators for TOI Exhaust in IP Rooms 75 CFM Range
Chilled Water Cassette Units Chilled Water Ceiling Suspended Cassette Units with Display as specified with built in drain pump / cordless remote with battery & all standard functions with all display / including factory assembled and tested 2 way PICBV with On/Off Actuator including pair of brass ball valve + inlet strainer; fresh air intake provision with butterfly damper and Flow sensor, decorative fibre grille to suite color as per architects approval, removal pre filter; shall also be supplied with temp control thermostat with Display, power On/Off, 3 speed switch (in the form of battery powered Cordless Remote (or corded if required by clients) and its wall mounted Fibre stand matching interior shade Price should include additional external insulation on CHW Inlet side face of cassette using 13mm Nitrile Rubber insulation _ 400 CFM / 1 TR
600 CFM / 1.5 TR
B2TAFA01-04_WITH MERV 8 HDPE FILTERS COMPLETE WITH DUCTING/TRANSFORMATION PIECES/CANVASS
B2TAEX05-08
B2TAFA05-08_WITH MERV 8 HDPE FILTERS COMPLETE WITH DUCTING/TRANSFORMATION PIECES/CANVASS
B2TAEX09-12
B2TAFA09-12_WITH MERV 8 HDPE FILTERS COMPLETE WITH DUCTING/TRANSFORMATION PIECES/CANVASS
B1TAEX01-04
B1TAFA01-04_WITH MERV 8 HDPE FILTERS COMPLETE WITH DUCTING/TRANSFORMATION PIECES/CANVASS
B1TAEX05-08
B1TAFA09-12_WITH MERV 8 HDPE FILTERS COMPLETE WITH DUCTING/TRANSFORMATION PIECES/CANVASS
TAF FOR B1FMAHU01_6000 CFM / 25 MM WC
TAF FOR B1FMAHU03-04_3600 CFM / 25 MM WC
TA FAN FOR B1FMAHU05_3600 CFM / 25 MM WC
TA FAN FOR B1CSAHU05_25 MM / 3600 CFM
TA FAN - ALL ICU SMOKE EXTRACT_9800 CFM / 28 MM WC_Excl Isolation ICUs
TA FAN_REFUGE CORRIDOR EXTRACT_7000 CFM / 22 MM WC
LIFT PRESSURIZATION TUBE AXIAL FANS WITH MERV 8 FILTERS / DUCT TRANSFORMATION PIECE_16500 CFM / 22 MM WC
STAIR PRESSURIZATION TUBE AXIAL FANS WITH MERV 8 FILTERS / DUCT TRANSFORMATION PIECE_14500 CFM / 22 MM WC
Attrium Exhaust Fans _ 30000 CFM_18 MMWC
ATTRIUM FA FANS _ 30000 CFM_22 MM WC
Exhaust Air Cum Fire rated Exhaust fans for ISOLATION ICUs on VFD operation_with PRE FINE HEPA Filter bank duly fabricated at works_8000 CFM_25 MM WC
Exhaust Air Cum Fire rated Exhaust fans for BMW Room on VFD operation_with PRE FINE HEPA Filter bank duly fabricated at works_1000 CFM_25 MM WC
Dry Ventilation Units Normal Mode (Exhaust / Fresh air) located in layouts, design parameters as per Design Schedule and as below Supply, Installation, Testing and Commissioning of Double Skinned MS Powder coated Low noise Cabinet Type BWC Centrifugal Ventilation Fan as specified with IP55 IE 3 TEFC Motor, Drive Package; Rain Protection Cowl and Bird Screen as specfied; All floor mounted units as per layout shall be provided with vibration isolators as required; Fan with motor equal or more then 0.75 kW shall be with VFD based Starters Cabinet type doube skinned Isolation Exhaust Units and as per balance Ratings mentioned below not less than 68% volumetric efficiency (Filter type in Fan as per Design Schedule and Tag Nos.; Filter Velocity not exceeding 400 FPM) Fan exit velocity not exceeding 1600 FPM : _12500 CFM / 25 MM WC (V1 SHAFT)
11500 CFM_25 MM WC_V1.1 SHAFT
5000 CFM_25 MM WC_V2 SHAFT
15000 CFM_25 MM WC_V3 SHAFT
6500 CFM_25 MM WC_V4 SHAFT
Supply, installing, testing and commissioning of Dual Speed IP54 H class insulated Motor Aerodynamic Centrifugal impeller Low Sound CE certified Jet fans complyig to EN60045-5/IEC 85 / EN-12101-3; having IP-65 elect isolator; thrust force equivalent to 400 M2 coverge area for car park areas with Adjustable Exhaust Direction. Complete fan assembly with its Casing, impeller & motor shall be sourced from one manufacturer and certified as tested for 250 degC for 2 hours operation. Casing shall have an inlet guard, shall be made Galvanized Aluminium or Equivalent MoC as per approved make. The system shall serve both CO-evacuation and smoke extract functions
Supply, Installation, Cablibration & commissioning of of UL/ANSI listed, Solid state, ABS enclosure with IP-65 protection, high CO measurement accuracy at low concentration conditions; with low sensitivity to alcohol vapor; Detection range 0-250 ppm @ +/-5% accuracy; Sensors with manufacturer recommended fixtures and as per layout, Testing Calibration and Commissioning of CO sensors as specified complete with Mounting Fixtures on the Column/Wall as pet layouts
KITCHEN VENTILATION SYSTEMS # Double Skinned Sandwitch insulated Direct indirect Evaporative cooling units in sectionalized construction comprising of: Fresh air Filter section MERV 11 HDPE Washable Media, Air-water Cross Flow Plate type Polymeric heat exchanger with approximately 18-20 deg C sensible pre Cooling in Summer & 5 deg C in monsoon / Direct Evaporative Cooling Section with Cell deck eq. COoling pads - circulation piping - pumps - storage tank with drain/makeup/quickfill/overflow; Fan section with AMCA/Eq. PLUG Fan with drive package having spring mounted IP55/4P/TEFC/EFF1 Motor/ Balance specifications as per tender & 25000 CFM / 65 MM WC
EXHAUST AIR SCRUBBERS FOR KITCHEN # Two stage Electrostatic air filtration based Dry scrubber in 16G Zn coated steel cabinet, Metal mesh or perforated plate type prefilter, Electrostatic Air cleaners section with Al Ionizing Repelling and Collector plates, Ionizing electrodes powered by solid state moisture resistant PSU with short circuit arc protection duly interlocked, operable upto 140 deg C, dry type air cleaner for oil/smoke/fume removal, Odore neutralizer, Double skin cabine DIDW BWC Centrifugal fan unit with drive package Class F IE-2 motor; cost to include exhaust cowl/birdscreen per unit_30000 CFM/80 MM WC
Supply, Installation, testing & commissioning of MICROPROSSER BASED Air cooled inverter Condensing unitsThe outdoor (condensing unit) shall be of Corrosion resistant Galvanized powder coated or equivalent Sheet steel low vibration assembly installed on suitable vibration isolators and comprising of energy efficient Scroll compressor with controls such as thermal protector, HP/LP cutouts, Pressure relief valve; the outdor unit shall also comprise of finned Cu tube air cooled condenser and condenser fan unit; the units shall have integral refrigerant copper piping within compressor and condenser and accessories such as refrigerant shutoff valves at compressor / compressors and liquid refrigerant outlet if required & filter dryer; Cu Cooling Coil with fans shall have protective metal frame. Unit shall be complete with factory supplied and tested PU Control Panel; The Outdoor units shall be installed on contractor supplied MS angle iron frame duly corrossion proof painted and supplied as welded structure which shall be securely grouted on floor and duly painted with anti-corrosive paint; the frame shall be isolated from floor through adequate vibration isolation; price shall be inclusive of all requried MS supports; Design, Supply, Installation Testing and Commissioning of Refrigerant copper piping for below units duly charged with Approved Green Refrigerant Gas (Qty to be measured form Layout as per ODU location from AHU) Refrigerant insulated with manufacturer recommended thickness closed cell electrometric Nitrile Rubber covered with Aluminum Foil interconnecting indoor & outdoor unit and accessories such as refrigerant shutoff valves at compressor and liquid refrigerant outlet. Metallic foil membrane shall be applied to provide resistance against breakdown due to UV radiation for exposed portion of the Rubber Insulation. Al power cabling between PU Control panel for Compressor motor, condenser fan and interlocking with CHW AHU Common Fan; the scope shall also cover supply and laying of Cu control wiring, 6 SWG G.I wire loop earthing on surface along with other cable as required, external wiring, between AC unit starters, indoor unit & condensing units. Control wiring required from IDU and ODU shall be laid with proper supports along with the refrigerant piping route; The unit shall be suitable for 415 ± 10 % volts, 50 Hz, 3 phase AC supply and IP55 Protection.; 5.5 TR ODU with 5 RMT copper Piping duly insulated & associated DX Coil / Distributor & EXPV
8.5 TR ODU with 5 RMT copper Piping duly insulated & associated DX Coil / Distributor & EXPV
BEE Approved DX Air Cooled Split units with Inverter Compressor Supply installation testing and commissioning of precharged Split units, required 16A MCB, accessories, fixtures including wooden framing on wall for IDU; unit shall be supplied with indoor units, outdoor condensing units, 10 RMT refrigerant piping insulated with Nitrile Rubber insulation (covered with UV barrier for exposed piping) including Control cabling between Indoor and Outdoor units complete with wired remote control having 10 rmt lead wire; 1Ph 2.0 TR HiWall Split Type unit
1Ph 1.5 TR HiWall Inverter Split Type unit
1Ph 1.5 TR Cassette Type Inverter Split Unit
Supply, installation, leak testing, air balancing, and commissioning of GSS Air Distribution System ducting for following gauges as specified (Contractor to keep all duct ends covered during installation to prevent ingress of dust and derbis); Supply and installation of GSS, Pre fabricated from CNC Machines & RTV Sealed rectangular ducts (for entire project except suite-pieces/connection pieces) supplied as per IS:277 (MIn 120 GSM) and fabricated as per IS:655, complete with MS flanges and bracing (as specifed), Trapeeze type MS Angle Supports for Ducting using fully threaded GI roads (as directed with bottom horizontal support Angles and Rods adequately sized to prevent sagging under all conditions) and anchor bolts, supply air collars, vanes, splitters dampers duly painting of the ducts and as per specification for 1.2 mm Thick GSS ducting (above 2250 mm duct sizes) Factory-fabricated ducting should come in box section & not in L sections joined at site.
1.0 mm Thick GSS ducting (upto 2250 mm duct sizes)
0.8 mm Thick GSS ducting (upto 1500 mm duct sizes)
0.63 mm Thick GSS ducting (upto 750 mm duct sizes)
Rates for RTV sealed GSS Ducting fabricated at site - fabrication as per IS655 as specified only for Suite-pieces & Connection Pieces 1.2 mm Thick GSS ducting
1.0 mm Thick GSS ducting
0.8 mm Thick GSS ducting
0.63 mm Thick GSS ducting
Round Ducting
Supply and installation of Aluminium Ducting, Pre fabricated from CNC Machines & RTV selaed for Operation theaters Sterile Areas and MRI at site rectangular ducts (for entire project except suite pieces / connection pieces) supplied as per IS:277 and fabricated as per IS:655, complete with Hot Dip Galvanized MS flanges and bracing (as specifed), necessary HDG MS Angles and fully threaded GI roads (as directed) and anchor bolts (Angles and Rods sized to avoid sagging of supports under all conditions), supply air collars, vanes, splitters dampers duly painting of the ducts and as per specification; Ducting shall be applied with RTV sealant; AL ducting shall be fabricated out of prime quality sheets. Complete with necessary supports, expansion fasteners, etc.: Rates to include necessary splitters/turning vanes, leak testing of ducting. 1.2 mm Thick Al ducting (Above 1250 mm sizes)
1.0 mm Thick Al ducting (751-1250 mm Ducting)
0.8 mm Thick Al ducting (upto 750 mm Ducting)
150mm dia flexible, sandwich-insulated duct complete with air-tight clamping arrangement at both ends. Rate should include square/round volume control damper and square/round GI connection for connecting flexible duct with SA duct.
Flexible Fire Retardant Duct Connectors for Seismic Isolation in Various Sizes
HEPA Plenum/Laminar Flow Units of 5000 CFM capacity, comprising of SS 304 structure & 18G SS 304 casing insulated with 25mm Class O Armacell closed-cell elastomaric nitrile rubber insulation of 40-60 kg/cumt density, EU 13 (MERV17) Terminal HEPA Filters of 99.97% efficiency down to 0.3 Micron particle size installed in zero leakage SS framewoek, with SS perforated plate type SA grille. Provide flanges for SA duct connection and dampers (operable from OT) for each SA connection. HEPA Plenum should have air-tight provision for passing OT Light pendant. Rate to include suspension/ supporting arrangement from slab. Filter Panel 8'x6' Size arranged in 4x3 (=12 Nos total) HEPA Filters each 600*600*300 rated for 5000 CFM
HEPA Plenum/Laminar Flow Units of 2400 CFM capacity rest same as above' Filter panel in 2x3 array size with 6 HEPA Filters each of 600*600*300
Supply, installation, testing and Commissioning of Terminal HEPA Box with HEPA Filter / VCD - balance as specified above for Sterile Corridors and BMT Antiroom 450x450x200 mm
OT/BMT Return air Readymade Risers (In case of exposed riser option) 16G GI Return Air Risers for Operation Suites with workmanship & finishing quality suitable for 1250 CFM return per riser for exposed installation in Pre-Fab Rooms/Modular OT. Risers should be without joint (i.e. single piece in height up to RA duct connection). Powder coated as per approved colour shade. RA grille should be easily removable to facilitate cleaning. Riser should be independently supported, and should touch the partition panel at the back. (For Any Rooms With Exposed Risers - applicable if SS Wall Hollow Risers are not adopted)
Same as above but for 600 CFM for each Riser
Supply Installation Testing Commissioning & balancing of Al extruded Powder coated Anti smudge SA Diffusers with VCD (each unit with 600x600 overall size and Neck size as per CFM demand); Shade and Finish of the diffusers and Grillers to be approved by Architech before supply by Contractor to site; samples to be submitted for approval of Architech
Al Extruded Powder coated RA Anti smudge Diffusers without VCD having 600x600 overall size & Neck size as per CFM demand
Aluminium Extruded Powder coated Supply air / TFA Grilles with Volume Control Damper
Aluminium Extruded Powder Coated Return air / Exhaust Grilles without Volume Control Dampers
Aluminium Extruded Powder Coated Continuous SA RA Grilles with/without End flanges as per interior designs
Supply, Installation, testing, commissioning of wall / duct dampers as specified and as below Al aerofoil opposed blade Volume control Dampers and PVC Gears for smooth operation for volume control at unit discharge and duct branches
Collar Dampers for SA collars
Two Position VAV Boxes complying to AHRI 880-2017 22G or better constrcution with 230v PSU, integral attenuator complete as specified with Integrated Room Control Unit, potentiometer, DPT, Actuator. fixing and accessories_600 CFM
Motorized Fire&Smoke Galvanized Steel Dampers with factory mounted Sleeves/actuators listed for UL-555S / AMCA certified / Leakage Class I / 3 hr fire rating flanged Dampers 14G Frame with GI linkage & Flanged bearings concealed in frame having minimum 0.3 mm SS flexible metal compression type Jamb seals & Silicon edged sealed aerofoil blades; designed to remnain closed in dynamic systems with 2000 FPM air velocity & pressure of 4" WC installed vertically at Wall crossings in SA/ RA ducts & Fan Discharge with certified for permissible hrs of Fire rating (minimum 2 hr @ 250 deg C) as per UL-555 & with Class-1 leakage as per UL-555S
As above but with fusible Linc with all regulatory approvals as required
Fire rated Actuators qualified for UL555S ready to mount on Fire Dampers with required linkages & having Torque upto 16 Nm designed to operate from external FAS Panel signal
EXPOSED DUCT Thermal Insulation Works with Approved make Elastomeric nitrile rubber 40-60 kg/m3 with thermal conditivity < 0.035 W/m°K at an average temperature of 0°C; Fire Propagation compliance as per BS476 Part 6 to meet the Class ‘O’ Fire category (without Al/outer metalic foil); Water vapour permeability shall not exceed 0.017 Perm inch (2.48 x 10-14 Kg/m.s.Pa), Non VOC Water based Adhesive and the entire process of Application shall be as recommended by Mfr. 50 mm thick insulation for Supply air Ducting covered with Factory Laminated GC 200 GSM GC barrier for UV and Mechinical Protection applied with approved make adhesive / additionally sealed with 75mm x 3 mm self adhesive tape on top at longitudinal and transverse joints simultaneously AND further covered with anti fungal lag coating
INDOOR DUCT Thermal Insulation Works with Approved make Elastomeric nitrile rubber 40-60 kg/m3 with thermal conditivity < 0.035 W/m°K at an average temperature of 0°C; Fire Propagation compliance as per BS476 Part 6 to meet the Class ‘O’ Fire category (without Al/outer metalic foil); Water vapour permeability shall not exceed 0.017 Perm inch (2.48 x 10-14 Kg/m.s.Pa), Non VOC Water based Adhesive and the entire process of Application shall be as recommended by Mfr. 50 mm thick insulation for Supply air Ducting covered with Factory Laminated GC 200 GSM GC barrier for UV and Mechinical Protection applied with approved make adhesive / additionally sealed with 75mm x 3 mm self adhesive tape on top at longitudinal and transverse joints simultaneously
EXPOSED 15 mm thick insulation for Exhaust air Ducting (Toilet/Sluice/DU/Autoclave etc) additionally sealed with 75mm x 3 mm self adhesive tape on top at longitudinal and transverse joints simultaneously covered with Factory Laminated GC 200 GSM GC barrier for UV and Mechinical Protection applied with approved make adhesive / additionally sealed with 75mm x 3 mm self adhesive tape on top at longitudinal and transverse joints simultaneously AND further covered with anti fungal lag coating
INDOOR 15 mm thick insulation for Exhaust air Ducting (Toilet/Sluice/DU/Autoclave etc) additionally sealed with 75mm x 3 mm self adhesive tape on top at longitudinal and transverse joints simultaneously covered with Factory Laminated GC 200 GSM GC barrier for UV and Mechinical Protection applied with approved make adhesive / additionally sealed with 75mm x 3 mm self adhesive tape on top at longitudinal and transverse joints simultaneously
Supply and fixing of acoustic lining inside sheet metal ducts using 140-180 kg/m3 Approved Make with Microban, having thickness specified below, conforming to Class 1 - BS 476 applied with Approved make adhesive (having less then max. permissibleVoC content as per GRIHA/Green Rating System) as specified with15 mm thick Armasound with Microban Upto 8 RMT of SA and Return Ducting for ICU / Sterile / Comfort Areas; Duct acoustic lining should be done while the ducts are still on floor, not after installing ducts in position
8 mm thick acoustic lining with Approved Make with Microban Upto 8 RMT of Supply Ducting of FCU and Exhaust ducting for Toilet / Sluice / DU Areas applied with adhesive having less then permissible VoC Content as per GRIHA/Green Rating System; Duct acoustic lining should be done while the ducts are still on floor, not after installing ducts in position
Slab Under deck insulation as per latest CFO circular # Approved make 50 mm thick (2 layers of 25 mm each) Elastomeric nitrile rubber 40-60 kg/m3 with thermal conditivity < 0.035 W/m°K at an average temperature of 0°C; Fire Propagation compliance as per BS476 Part 6 to meet the Class ‘O’ Fire category (without Al/outer metalic foil); Water vapour permeability shall not exceed 0.017 Perm inch (2.48 x 10-14 Kg/m.s.Pa), Non VOC Water based Adhesive and the entire process of Application shall be as recommended by Mfr. NOTE: Necessary re-work/repair/plugging of holes & cutouts in insulation will have to be carried out as required, after completion of ducting, false ceiling, lighting, etc." in HVAC scope
AHU Room Insulation Supply and fixing of acoustic lining inside AHU Room for with 20 mm thk 140-180 kg/m3 Approved make acoustic insulation with Microban conforming to Class 1 - BS 476 applied with Mfr recommended adhesive as specified complete with required framed structure
Fresh Air Arrangements Supply, installation, testing and commissioning of fresh air / Exhaust air arrangements with Al rain Louvers / Damper / SS Bird screen for AHU/FFU Fresh Air intake / Exhuast Air and finally comprising of For Fresh air including supply/fixing of MERV 6 (20 micron) Filter (400 FPM Area) per each Unit as per layouts; Required finishes for Fascad Exposed Fresh/Ex Air assemblies shall be provided as per Architects shall be included in cost
For Exhuast air without Filter as per layouts
INSULTAED CHILLED WATER PIPING with VALVES / ACCESSORIES as per IS-1239 upto 150 mm NB and 6 mm thick for 200 mm NB or above as applicable- CHILLED WATER PIPES Supply, installation, pressure testin & Insulation of MS C Class (or thickness as Specified) insulated with 32 mm Class O Nitrile Rubber for Pipe Sized upto 100 mm NB and (38 mm for Pipes Sized > 100 mm NB) Closed cell nitrile elastomeric rubber with thermal properties as specified; the pipe shallbe applied with red oxide followed with recommended adhesive through the specified application process; insulaiton shall be covered with Colored Woven Fibreglass fabric sheet of 0.18 mm thickness coated with acrylic co polymers or blends with self adhesive backing of 60 GSM for UV & Mechanical Protection; Prices shall include Corrossion proof painted MS structural supports / seasoned PVC gutty covering 50% of pipe exposed surface as required at intervals as specified - to be considered on RMT basis in respective sizing rates (refer Notes on BOQ below); Fittings / valves installed in line with above piping shall be insulated/finished similar to above specifications with removable GI jacket boxes; All piping shall have valves and fittings rated for PN 16 Ratings 500 MM NB / 8 mm thk
400 mm NB / 8 mm thick
350 mm NB / 8 mm thick
250 mm NB/6 mm thick
200 mm NB/6 mm thick
Supply and fixing of Insulated Manual Balancing Valves with pair of flanges/nutbolts/neporene at Floor Tapp-Offs / Heat Exchanger Outlets _ 450 MM NB
Hg Manometer with Tubing ready to connect to valve probes for site balancing - common for all balancing valves with all fixtures and balancing chart
Supply, installation, testing & commissioning of following sizes insulated GI heavy duty drain pipes from AHU drain pans to nearest floor drain and from CHW pump glands to the nearest drain complete with interconnection, flanges, elbows, tees, nuts, P-trap etc. The insulation and final finish should be 40 mm thick PUF with AL cladding 100 mm NB
Supply installation testing and commissioning of insulated Heavy class IS CPVC Drain Piping for Fan Coil Units / CSAHU duly insulated with 6 mm thick Nitrile Hollow tubes of following ID
CHW FCU / Cassette End Connections with 6MM insulated Kitceh Make Pipes complete with fittings as required 400 CFM 1 TR
600 CFM / 1.5 TR
800 CFM / 2 TR
1000 CFM / 2.5 TR
1200 CFM / 3 TR
S&I of insulated Chilled Water Non Return Valve specified with SS Jali for CHWP, CHWS Pumps and AHU inlet with pair of flanges/screws/ neoprene gasket complete 250 mm NB
S&I of insulated Chilled Water MS fabricated Insulated Y Strainers for Plant Room specified with SS Jali with pair of flanges/screws/ neoprene gasket complete 250 mm NB
S&I of insulated Chilled Water CI Insulated Y Strainers for Plant Room / AHU Inlet specified with SS Jali with pair of flanges/screws/ neoprene gasket complete 200 mm NB
S&I with Flanges/Nutbolts complete of Insulated Chilled Water Isolation type manual Al / CI Butterfly valves in PN16 rating with operating lever and graduated disc pair of flanges neoprene gasket complete _ 450 mm NB gear driven
250 mm NB Gear Driven
200 mm NB Gear Driven
32 mm NB SS Flanged ball valve (in lieu of BFV)
25 mm NB SS Flanged ball valve (in lieu of BFV)
ANSI compliant MS Dead Flange/SORF flange pair for header Terminations 250 mm NB complete with Butbolts Gasket Neoprene Rubber sealing
S&I with Flanges Nutbolts complete of Insulated Chilled Water Isolation type manual SS Ball Valve with SS Body and Working parts 50 mm NB
Supply and installation of Auto Air Vents with coupling / accessories and fixtures 25 mm NB
S&I with Flanges nutbolts complete of Insulated Auto Isolation (BFV) valve with On/Off actuator having matching torque with required electronics compatible for remote operation for chiller autoisolation 250 mm NB
S&I with Flanges / Nutbolt complete of Insulated Pressure Independent Control (PICV) valves at AHU Outlet with 100% authority with Modulating actuators complete as specified with Percentage Opening Status Feedback feature and Remote AO operation _ 100 mm NB
Measuring Instruments_Chilled Water Piping Insertion type ElectroMagnetic Flow meter as specified +/-2% accuracy with local display and Serial Communication Port supporting Universal Protocols For 450 mm NB Header
SS Bellows complete with double side flange for CHW pipes passing across the seismic barrier (@Expansion joint) within the building as specified
INSULTAED HOT WATER PIPING with VALVES / ACCESSORIES as per IS-1239 upto 150 mm NB # Supply, installation, pressure testin & Insulation of MS C Class (or thickness as Specified) insulated with 32 mm High Temp Insulation Class O Nitrile Rubber for Pipe Sized upto 100 mm NB with thermal properties withstanding upto 100 deg C as specified; the pipe shallbe applied with red oxide followed with recommended adhesive through the specified application process; insulaiton shall be covered with Colored Woven Fibreglass fabric sheet of 0.18 mm thickness coated with acrylic co polymers or blends with self adhesive backing of 60 GSM for UV & Mechanical Protection; Prices shall include Corrossion proof painted MS structural supports / seasoned PVC gutty covering 50% of pipe exposed surface as required at intervals as specified - to be considered on RMT basis in respective sizing rates (refer Notes on BOQ below); Fittings / valves installed in line with above piping shall be insulated/finished similar to above specifications with removable GI jacket boxes; All piping shall have valves and fittings rated for PN 16 Ratings 100 mm NB
Manual Balancing Valves as specified above but for HW 65 MM NB
Drain Ppg GI heavy class as specified above but for HW 65 mm NB
NRV as specified above above but for HW Pumps_100 mm NB
Y Strainers as specified above above but for HW_100 mm NB
Isolation type Al/CI Butterfly valves as specified above above but for HW_100 mm NB
Autoisolation valve with Actuator for Eq isolation as specigied above but for HW 80 MM
Autoair vents as specified above
PIBCV as specified above but for HW 80
Pressure Gagues as specified above but for HW
Temp Gauges as specified above but for HW
COOLING WATER PIPING with ACCESSORIES Supply, installation, pressure testing, of MS C Class Cooling Water Piping (IS:1239 / 6 mm thick for higher then 150 mm size) laid on Slab/Floor supported MS painted supports as required during detailed engineering and final Piping routes; pipes shall be applied with Anti corrosive primer and finally painted with color coded paint; pipes shall be complete with required elbows (short and long), Tees, Reducers, flanges, fittings as required _ 600 MM NB/ 8 mm Thick
300 mm NB/6mm thick
200 mm NB/6 mm thick
Cooling water Piping as above but applied with FRP Coating for following sizes with balance specifications unchanged 600 mm nb
400 mm NB / 8 mm thick
300 mm NB/6mm thick
200 mm NB/6 mm thick
S&I of Non Return Valve with pair of flanges neoprene gasket complete 300 mm NB NRV
CI POT Strainers with SS Jali 600 mm NB (one S/B in ByPass Line) on Terrace
S&I with Flanges nutbolts complete of BFV with On/Off actuator having matching torque with required electronics compatible for remote operation for Condenser Outlet autoisolation 300 mm NB
Supply and fixing of Manual Balancing Valves with pair of flanges/nutbolts/neporene at Heat Exchanger Outlets 300 mm NB (includes one each at Condenser Outlet)
S&I with Flanges/Nutbolts complete of Isolation type manual Al / CI Butterfly valves in PN16 rating with operating lever and graduated disc pair of flanges neoprene gasket complete 600 mm NB
400 mm NB / Gear Driven
300 mm NB Gear Driven
200 mm NB Gear Driven
ANSI compliant MS Dead/SlipOn pair Flanges in nutbolts neoprene gasket complete at header dead end 4 sides_600 mm NB
S&I of dial type Pressure Gauge 100 mm size with SS needle valve and fittings 0-10 kg/cm2 range installed as per P&I Diagram For CDS Shell, Pumps and Towers
S&I of dial type Temperature Gauge 100 mm size with SS thermowell/coupling/glycerine or eq. conductive fulid and fittings 0-50 C range installed as per P&I diagram For CDS Shell and Towers
S&I of Magnahelic Gauges with all tubing fixtures / site calibration of Mangehelic gauges for OT / BMT HEPA Tent
3 WAY CONTROL VALVE WITH ACTUATORS 100 mm NB
Painting work for Equipments / Pipes / Ducting including Taging of equipments under the scope of this tender with color shades as per code specified. All exposed metallic surfaces shall be painted with corrossion proof paint; work shall include Tagging of all Equipment with area codes / water flow directions on CHW HW CDW Piping etc as required by site incharge
HVAC electrical panel boards for Chiller,pumps,cooling towers, AHUs, re-heaters, ventilation units, TFA and Condensing Unit etc. Complete with incoming and outgoing feeders with ACB/MCCB, VFD (where marked on SLD) Aluminium busbars, indicating lamps, digital type voltage, current & energy meters, etc. Necessary contactors, relays, changeover switches, etc. for interface with AHU Controller/Control System (BMS) to be provided as required All small Panels must have minimum spare feeders as per Schematic Electrical Drawing. All Panels shall be fuseless type. All Pump Feeders / Tower Fan Feeder / AHU/TFA Fan & AHU Heater feeders shall be BAS Integration compatible as per IO summary enclosed and comprising of following but not limited to: a. ONOFF Status signal (Potential free) / b. TRIP (potnetial free) / c. 2Way 2Pole Switch (AUTO/MANUAL provision) with status / d. Remote Operation (relay based) provision / e. All Heater feeders (Reheat Panels) shall be with built in Power controller / f. Plant Room Panel should also include interlocking of CHW/CDW shut-off valve to stop flow of chilled water from idle Evaporator/Condenser. / (Refer Schematic Drawing for Feeders) Each AHU/Ventilation Panel should have feeders as per no. of AHUs installed in the repsective AHU Room. Each panel should be complete with: Incoming MCCB, Aluminium busbars, incoming indicating lamps, digital type voltage & current meters, etc. Outgoing MCBs & VFDs for AHU motors as per schematic electrical drawing, ougoing indicating lamps, digital Voltage & Current meters, control & safety interlocking, etc. Panel price should include VFDs for AHUs / custom designed Power Supplies for Flow Control Valves / Power supply & MCB for each UVGI as required; VFDs should be housed in the AHU panel with necessary cooling fan & filter; Interface with surgical control panel in respective Modular OT for control of temerature & RH to be included in Panel price. Ougoing feeders for DX Units of OT AHUs complete with MCB, ammeter, indicating lamps and DDC control interface (onoff /trip /AM status and Remote On/Off command) with DX unit panel to be included in respective AHU panel price. Outgoing feeders for Fresh Air/Exhaust Air fans with necessary MCB, DOL, indicating lamps, etc to be included in respective panel price. Necessary contactors, relays, changeover switches, Auto/Manual change-over provison to be included in panel price. All VFDs should have appropriate RFI Filters to avoid conducted RFI to and from the Hospital equipment. Care must also be taken to prevent radiated RFI- like locating all VFDs away from RFI sensitive areas, and by providing additional shielding. AHU/Fan motors with VFD; VFD should be a dedicated HVAC VFD with in-built harmonic filters & DC chokes & IP20 enclosure. VFD should have built-in under- and over-voltage, over-current protection and phase-loss protection, PF correction, display of key parameters, etc. VFD shall have EMC compliance complying with IEC 61800-3 requirement and conforming to category C1-50mts motor cable. VFDs should be manually operated but should be networkable / compatible with BMS. Outgoing feeder for DDC Controller and CHW & HW control valves with necessary MCB, transformer, converter, etc. to be included in respective AHU panel price. All Terrace monuted and Exposed panel boards Shall be IP-66 protection enclosure (Double door) and further installed below Weather Protection Canopy on four sides - Panel 1.1 (Chiller Distribution panel) for 5 Nos. 530 TR Chillers (4W 1 SB)
Panel-P1A (Plant Room Panel) for Primary CHW Pumps, Secondary CHW Pumps, CDW Pumps, Cooling Towers, Pressurized Expansion Tank, etc
Panel for HW Heat Pump / Recirculation HW Pumps
Starter Panels as specified above for below AHUs / Ventilation Units / Kitchen Ventilation Units as per kW mentioned against respectiev Tags B1FMAHU02
B1FMAHU03-04+FIEX
B1FMAHU05+FIEX
B1FMAHU06
B1FMAHU07
B1FMAHU08
B1CSAHU01
B1FMAHU09
B1FMAHU11
B1CSAHU02
B1CSAHU03
B1CSAHU04
B1CSAHU05+FIEX
GFMAHU03
GFMAHU08-09
GFMAHU10VAV
GFMAHU11VAV
GFMAHU12
GFMAHU13VAV
GFMAHU14VAV
GFMAHU15VAV
GFMAHU16VAV
GFMAHU18
GFMAHU19
GFMAHU21
GFMAHU22
1STFMAHU04-05
1STFMAHU06VAV
1STFMAHU07VAV
1STFMAHU08VAV
1STFMAHU09VAV
1STCSAHU01-04
2NDFMAHU04-05
2ND FMAHU06VAV
2NDFMAHU07VAV
2NDFMAHU08
2NDFMAHU09VAV
2NDCSAHU01-04
3RDFMAHU04-05
3RDFMAHU06VAV
3RDFMAHU07VAV
3RDFMAHU08
3RDFMAHU09VAV
3RDCSAHU01-04
4THFMAHU04-05
4THFMAHU06VAV
4THFMAHU07VAV
4THFMAHU08
4THFMAHU09VAV
4THCSAHU01-04
5THFMAHU04-05
5THFMAHU06VAV
5THFMAHU07VAV
5THFMAHU08
5THAHUFM09VAV
5THCSAHU01-04
6THFMAHU04-05
6THFMAHU06-07VAV
6THCSAHU01
6THFMCSAHU02
6THCSAHU03
5M AHU PANELS B1FMAHU01+FIEX
B1FMAHU10
B1FMAHU12
B1FMAHU13
GFMAHU01
GFMAHU02
GFMAHU17
GFMAHU20
1STFMAHU01
1STFMAHU02
1STFMAHU03
2NDFMAHU01
2NDFMAHU02
2NDFMAHU03
3RDFMAHU01
3RDFMAHU02
3RDFMAHU03
4THFMAHU01
4THFMAHU02
4THFMAHU03
5THFMAHU01
5THFMAHU02
5THFMAHU03
6THFMAHU01
6THFMAHU02
6THFMAHU03
6THFMAHU08VAV
6THFMAHU09VAV
SAME AS 8.3.1 BUT DEISIGNED FOR TERMINAL HEPA FILTERS; GFMAHU04VAV
GFMAHU05OT
GFMAHU06OT
GFMAHU07OT
TER-AHUSTRCOR
TER-OTAHU1
TER-OTAHU2
TER-OTAHU3
TER-OTAHU4
TER-OTAHU5
TER-OTAHU6
TER-OTAHU7
TER-OTAHU8
TER-OTAHU9
TER-OTAHU10
TFAU PANELS B1-CSTFAU-1350 CFM/55 MM WC
B1-CSTFAU-400 CFM / 55 MM WC
GF-TFAU-560 CFM/55 MM WC
FF-TFAU-710 CFM/55 MM WC
FF-TFAU-600 CFM/55 MM WC
FF-TFAU-1100 CFM/55 MMWC
6THTFAU-1100 CFM/55 MM WC
TAF FOR B1FMAHU01_6000 CFM / 25 MM WC
TAF FOR B1FMAHU03-04_3600 CFM / 25 MM WC
TA FAN FOR B1FMAHU05_3600 CFM / 25 MM WC
TA FAN FOR B1CSAHU05_25 MM / 3600 CFM
TA FAN - ALL ICU SMOKE EXTRACT_9800 CFM / 28 MM WC_Excl Isolation ICUs
TA FAN_REFUGE CORRIDOR EXTRACT_7000 CFM / 22 MM WC
LIFT PRESSURIZATION TUBE AXIAL FANS WITH MERV 8 FILTERS / DUCT TRANSFORMATION PIECE_16500 CFM / 22 MM WC
STAIR PRESSURIZATION TUBE AXIAL FANS WITH MERV 8 FILTERS / DUCT TRANSFORMATION PIECE_14500 CFM / 22 MM WC
Attrium Exhaust Fans _ 30000 CFM_18 MMWC
ATTRIUM FA FANS _ 30000 CFM_22 MM WC
Exhaust Air Cum Fire rated Exhaust fans for ISOLATION ICUs on VFD operation_with PRE FINE HEPA Filter bank duly fabricated at works_8000 CFM_25 MM WC
Exhaust Air Cum Fire rated Exhaust fans for BMW Room on VFD operation_with PRE FINE HEPA Filter bank duly fabricated at works_1000 CFM_25 MM WC
Dry Ventilation Units Normal Mode STARTER PANEL: _12500 CFM / 25 MM WC (V1 SHAFT)
11500 CFM_25 MM WC_V1.1 SHAFT
5000 CFM_25 MM WC_V2 SHAFT
15000 CFM_25 MM WC_V3 SHAFT
6500 CFM_25 MM WC_V4 SHAFT
BASEMENT VENTILATION SYSTEM AT B1 (ONE POINT POWER DIST BOARD FOR ALL BASEMENT VENT/36 JET FANS/PSU FOR 36 CO SENSORS
BASEMENT VENTILATION SYSTEM AT B2 ONE POINT POWER DIST BOARD FOR ALL BASEMENT VENT/ 33 JET FANS / PSU FOR 33 CO SENSORS
SPARE VFDs Spare VFDs covering all AHU motor ratings for immediate replacement in case of failure/breakdown of any installed AHU 2.2KW
POWER CABLING Armoured Aluminium/Copper power cabling between HVAC equipment, controls, controllers, HVAC panel boards; including terminations:All Cables should be XLPE type. NOTE: TPNE Power cabling & Earthing up to Chiller Terminal Box to be provided by electrical agency. Power cabling & Earthing from Terminal Box to chiller mounted panel to be provided by HVAC Contractor 3.5C x 185 sqmm.ALU. (For Chiller)
3.5C x 150 sqmm.CU. (For Chiller)
3C x 2.5 sqmm Cu.
3C x 4 sqmm Cu.
3C x 6 sqmm Al.
3C x 10 sqmm Al.
3C x 16 sqmm Al.
3C x 25 sqmm Al.
3C x 35 sqmm Al.
4C x 4 sqmm Cu.
4C x 6 sqmm Cu.
4C x 10 sqmm Cu.
7C x 1.5 sqmm Cu.(For FCU/CHW Cassette/CHW Split)
CONTROL CABLING (Other than Control Cabling covered under Control System/BMS) Armoured copper control cabling between HVAC panel boards, cabling for cutouts & interlocking, cabling for local isolators, push-buttons, thermostats, humidistats, sensors, switches, actuators, Local Control Panel, etc. _ 2CX1.5 MM2
3 C X 1.5 SQMM
3 C X 2.5 SQMM
EARTHING GI double earthing for HVAC equipment & controls 25x3 mm strip GI
12SWG Copper
10SWG Copper
8SWG Copper
CABLE TRAYS 14 SWG GI perforated cable trays for laying power & control cables between HVAC panel boards & equipment; including hardware, accessories like bends, tee’s, supports, etc. All cables should be installed in overhead cable trays to keep movement space clear. Tray rates should be inclusive of the same. 300mm Wide Tray
200mm Wide Tray
150mm Wide Tray
100MM Wide Tray
LOCAL PUSH BUTTONS / ISOLATORS FOR SAFETY IP-55 Weather-proof local ON-OFF push button stations or local isolators with lockable OFF button complete with mounting arrangement, for equipment located away from the respective panel boards (e.g. ventilation units, cooling towers, OT AHU,ICU AHU,TFAs installed outdoors, etc). (Control cabling between push-buttons and respective panel board to be included in Control Cabling item)
FIRE BARRIER SYSTEMSupply, installation, testing and commissioning of following fire barrier systems for HT and LT cable systems passing through shafts, trenches, ducts etc. ; Providing & Fixing Fire Barrier mortar with minimum 2 hours fire rating when tested in accordance with BS 476 part 20 nd UL 1479 for horizontal openings in fire vertical openings in walls for passing service shafts.The mortar shall have minimum hardended of 0.8 g/cm3 .The service lines could be of various types like electrical cables trays,metal pipes, GI ducts for AC. ETC.
Supply application of intumescent based coating on cables/cable tray along the horizontal runs, every 5m in case of vertical runs and tee-offs shall have a density in the range of 1.2 to kg /L.The coating shall be in non toxic , asbetos and halogen free and shall have good mechanical strength.
Minor civil works required to complete the HVAC job. Includes core cutting in RCC for Pipe sleeve provision / Mounting, grouting, MS supports, making breaking of cutouts for ducts, Indoor unit Supports, MS channel / angle for frame structure for installations of all equipments, parts, etc. and further. NOTE: HVAC Contractor should include without any extra cost to Client, any repairs required in civil works caused on finished surfaces/floors due to HVAC activity. HVAC Contractor shall follow Client's instructions like POP covering of finished floor, etc. Core Cutting in RCC for pipe sleeve Provision 50 mm and below
Core Cutting in RCC for pipe sleeve Provision 80 mm
Core Cutting in RCC for pipe sleeve Provision 100 mm
Core Cutting in RCC for pipe sleeve Provision 150 mm and below
Making & Finishing holes (200 mm dia) Masonry
Making & Finishing holes (150 mm dia) Masonry
Making & Finishing holes (100 mm dia or lower) Masonry
Making & Finishing holes in 1000x1000 mm (in2in finished) Masonry or lower finished & covered with seasoned & termite proof painted Wooden Frames
Making & Finishing holes in 500x500 mm (in2in finished) Masonry or lower finished & covered with seasoned & termite proof painted Wooden Frames
WALL CHASE FOR ACCOMMODATING/CONCEALING A/C PIPING Making of wall chases for accommodating / concealing A/C piping should be carried out using cutter machine and filling of zari up to first coat of plastering. Typical width of the zari is 150mm.
SYSTEM MAINTENANCE: (Refer O&M Tender Volume for Scope) Bidder shall indicate their charges for the ollowing: Comprehensive preventive maintenance contract for the entire HVAC plant supplied by the HVAC contractor inclusive of all parts, consumables and labour for all equipment supplied as well as replacement of any equipment/component/part which cannot be repaired to the satisfaction of the Client. This contract will commence after completion of Defects liability period of 1 year of successful handing over of the system This rate shall be valid for 5 years from the date of successful Handing over of HVAC system (1st Year Cost of maintenance shall be inclusive in the DLP and no extra payment will be paid for the maintenance in the first year after handing over) Maintenance for 1st Year after DLP
Maintenance for 2nd Year After DLP
Maintenance for 3rd Year After DLP
Maintenance for 4th Year After DLP
Maintenance for 5th Year After DLP
OPERATING CONTRACT: (refer Tender for scope) Operation of the complete air conditioning plant as per the requirements of the owner on the basis of 24 hours/ day and 365 days/ year as per Tender The operation contract shall also include operation of entire chilled water plant The above rate shall be firm for a period of 6 years from date of handing over of the system (Cost of operation During DLP)_1st Year After DLP
2nd Year After DLP
3rd Year After DLP
4th Year After DLP
5th Year After DLP
PSP PROJECTS LIMITED
Malani Construction Co.
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid