Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹42.2 LAccepted-AOC 42 B INDRA NAGAR SRINAGAR J K 190004 | SRINAGAR | SRINAGAR | J K | 190004 | L1 | Accepted-AOC Accepted Being Lowest | |
| 2 | L2₹47.5 L+₹5.3 L (12.6%)Rejected-Finance | L2 | Rejected-Finance Being Other than Lowest | |
| 3 | L3₹47.8 L+₹5.7 L (13.5%)Rejected-AOC | L3 | Rejected-AOC Rejected being other than lowest |
| Sl No | Description | Qty | Unit | M/S ZENITH TRADE LINK L1 | M/S Tajamul Ah Buchh L3 | M/S NORTHERN ELECTRICAL WORKS L2 |
|---|---|---|---|---|---|---|
| 1.00 | Supply, Installation, testing and commissioning of silent type Diesel engine driven generating set with Governing class (as per ISO 8528 Part V) -G2 including sound reducing canopy ,(as per CPCB-IV Norms) 415 volts, 3 phase, 50 Hz supply complete with panel for automatic starting or main failure control panel suitable for giving an output of 40 KVA confirming to IS-1601 at 1800 metre altitude above mean sea level and capable of operating between temperature range (-20) degree C to 40 degree C (at Srinagar area of J & K) and alternator of suitable capacity and RPM coupled with each other and capable of taking 10% over load for one hours on every 12 hours (As per BS-5514/649) with flexible coupling mounted on common base plate on Antivibration pads on foundation as recommended by manufacture. The DG set shall comprising all standard fittings, fixtures, complete all as specified and directed. | 1 | EACH | 8,67,000 ₹8,67,000 Lowest | 9,15,500 ₹9,15,500 | 9,24,000 ₹9,24,000 |
| 1.01(a) Alternator : Directly coupled with Engine and suitable to produce 415 volts, 3 phase 4 wire system, 50 Hz 0.8 PF @1500 RPM of capacity 40 kVA all as per as per IS: 13364 and up to date amendments with H class insulation having efficiency 91% on 100% load at 0.8 PF, self excited, self regulated, screen protected drip proof type with two end shield ball/Roller bearing with damper winding in each pole faces as per IS-4722 or BS 2613-1970 complete all as specified and directed (b) Engine : Water cooled Deisel Engine (CPCB-IV Norms Compliance) developing Min 50 kW /66 BHP or as recommended by the manufacturer for 1800 mtr altitude having Self start engine (including batteries with provn of charging the batteries and leads) suitable to drive above specified alternator complete with foundation (foundation design as per OEM), as per IS:10001/ 10002, coupled directly through flexible coupling, multi cylinder four stroke, cold starting, 1500 RPM industrial type as per BS-649 or IS-1601 with AI electronic governer suitable to regulate speed of DG set from No load to full load completed with fuel tank of cap as per manufacturer recommendations, fuel lines, exhaust pipe duly insulated with asbestos rope and with support and silencer mufflers etc for continuous operation and standard accessories, sump pre heaters cold start kit etc, complete all as specified and directed. (c)Canopy : Acoustic enclosure shall be powder coated and fabricated out of 16 SWG CRCA MS sheet. The silent canopy shall be of nut bolt type construction. Critical processes of punching is done on CNC machines to maintain dimensional accuracy of holes within 0.1 mm. Powder coating is done after seven‐tank surface preparation process of sheet metal. Canopy panel and doors shall have inside lining of FIRE‐RETARDANT foam as acoustic material . Four hinged doors shall be provided to canopy, one door shall have glass window for control panel. | ||||||
| 1.02(d) Base Frame : Base frame is fabricated in sheet metal. The base frame will be primer coated and painted. The base frame is rugged n construction and designed for mounting engine and alternator close coupled, with cross members mounted on AVM. The base frame shall have provision for mounting of acoustic enclosure and control panel on in it. The base frame is having provision of lifting hook for convenient lifting of complete set, i.e. along with canopy, engine and alternator. (e) Generating Panel :- DG set should consist of standard Generating Panel. (f) Exhaust System: The exhaust system and noise suppressor shall be provided with thermal insulation by using fire retardant / non igniting foam conforming to BIS 7888/BS 4375 to prevent excess heat radiation on the engine and safe for operator. (g) Fuel Tank: Fuel tank shall be fabricated out of 16 SWG CRCA MS Sheet . It is duly painted and fitted with inlet and outlet connections. Float gauge and fuel float switch is provided. Fuel tank shall have guage duly calibrated at every 5 mtrs. daily service fuel tank of suitable capacity as per manufacturer's instruction of having min fuel storing cap of 12 hours for running DG set including fuel oil indicating gauge drain and vent plug etc complete on a common base within the acoustic enclosure. (h) Control Panel :- Alternator inbuilt control panel 415 Volt ,3 phase, 4 wire, 50 cycle fabricated out of 1.6mm thick MS sheet painted with internally/externally with two coats of synthic enamelled paing over one coat of primer complete with internal copper wiring sutiable for 40 KVA DG Set comprising of MCCB 4P,100 Amp 25KA 01 No((and recommended by manufacturer) with spreader link,Multifunctional meter suitable to indicate Volt,power factor,bty voltage,RPM frequency,temp, oil pressure,hours run,Current AMP,KW, KWH etc. | ||||||
| 1.03Note:- 1. Capacity of alternator at 1800 meters altitute -40 kVA, AC 3 Phase, 415 volts, 50 Hz. and as recommended by the manufacturer for above sized motor. 2. Place of installation- Near BB Cantt Srinagar. 3. PCC platform 1:2:4 600 mm thick using 40mm graded stone aggregate to suit base frame size 30 cms below and 45 cms above ground level. Grouting 08 bolts of 600mm x 30mm and fixing the engine and alternator with base frame on the platform. PCC shall be measured & paid. 4. Engine and alternator shall be assembled on common steel frame by the manufacturer itself and not by rep / authorised agent / sister concern etc. 5. Engine shall be designed keeping in consideration of de-rating factor for 1800 meters altitute. 6. Canopy and engine shall be of same 7. Installation, testing and commissioning of Gen Set shall be done in presence of maufacturer's Engineer and not by any authorised person / rep/sister concern etc 8. DG Set to be tested for 12 Hrs contineously on full load (Rated load) including 1 Hr at 110% load. All testing materials and fuel to be provided by the contractor. | ||||||
| 1.04complete unit/set shall be equipped with all standard fitting as per manufacture recommendations and mounted on common base frame with following fitting and rates shall be deemed to be inclusive of the same:- (a) Fly wheel with bousing (b) Cooling system : Mounted radioter with fan and belt (c) Cooling water pump : Centrifucal type belt driven (d) Exhaust gas (i) turbo charger type (ii) Exhaust mainfold, Silencer : (i) Residential type,(ii) Bellows (e) Fuel System: Fuel injection system with fuel injectors fuel injection solenoid switch/nozzle/governer electronic type capable for 1% speed/frequency reglation.fuel filters,fuel hoses (f)Lub oil System:(i) Lubricating oil filter (ii) Lubricating pump (g) Air intake System :(i) Air intake Manifold (ii) Air cleaner dry type (h) Governer : Electronic Governer with actuator (j) Starting System : Electric Self starter with maintenance free batteries including battery charging alternator. (k) Batteries : maintenenace free batteries of 12 Volt as per manufacturer direction complete with copper conductor multistranded lead of suitable length from self starter to the battery terminals complete with initial charge and initial fill of electronic all as specified. Starter gear ring, start and stop push button , ignition key/switch, (l) Handing and operation : Sailent features of accessories shall be as under :-Radiator with blower fan , Corrosion inhibitor coolent, paper element filter for fuel, lub oil and by pass, Elecronic governer controlled direct fuel injection system, Fly wheel housing and fly wheel. | ||||||
| 1.05(m) Generator Monitoring Panel : Comprising of following:- (i) Microprocessor based genset controller for metering, monitoring,governing and protection (ii) Engine protection for low oil pressure, high coolent temperature (alarm & shutdown) (iii) Alternator protection parameter like under voltage, over current, under frequency, over frequency, (alarm & shutdown) (iv) Relay drivers for remote annuciations (v) Cyclic cranking (vi) Auto/manual strat/stop (vii) Operator within a temperatur ( range (-20 to 60 degree C) and humidity upto 95% (viii) Remote monitoring capacity throught separate interface moudules (n) Genset metering parameters like lube oil pressure, coolent temperature, engine speed (RPM), run hours, DC voltage, intake manifold temperature, 3 phase volts and 3 phase amperes,frequency, KW,KVA, power factor. (o) Safety Controls :- Engine low lube oil pressure, high water temparature and over speeding of engine (p) Coupling arrangement : Flexible coupling, fly wheel to suit flexible coupling fly wheel housing (q) Accessories :- AVM pads builts or separately mounted to manufacture base frames. (r) Base frame : Stardy design made of MS channel with necessary reniforcement and predetermined holes. | ||||||
| 2.00 | Excavation in trenches, not exc 1.5 m wide and not exc 1.5 m in depth; for foundation,shafts,cesspits,manholes,pier holes,laying of cables, pipes etc. and getting out all excavated material in any type of soil, complete all as specified and directed. | 62.5 | CUBIC METRE | 150 ₹9,375 Lowest | 150 ₹9,375 Lowest | 200 ₹12,500 |
| 3.00 | Returning, filling in and including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick, complete all as specified and directed. | 50.5 | CUBIC METRE | 60 ₹3,030 Lowest | 70 ₹3,535 | 100 ₹5,050 |
| 4.00 | Removing of excavated surplus soil to a distance not exc 50 m and depositing where directed at a level not exc. 1.5 m above the starting point, complete all as specified and directed. | 24.5 | CUBIC METRE | 60 ₹1,470 Lowest | 100 ₹2,450 | 70 ₹1,715 |
| 5.00 | M&L for sand cushioning for underground cable provided with a layer of 8cm thick sand before laying cable and 15cm thick layer of sand after laying and stretching the cable complete all as specified and directed. Note - Punned thickness shall only be measured and paid. | 10 | CUBIC METRE | 500 ₹5,000 Lowest | 500 ₹5,000 Lowest | 600 ₹6,000 |
Tender Value
₹48.2 L
EMD Value
₹96,420
Closing Date
1 Oct 2025, 6:00 pmClosed
GE 864 EWS
GE 864 EWS C/O 56 APO
PROVISION OF SHIFTING OF AFNET EQUIPMENT ROOM, RCC UNDERGROUND WATER TANK AND SPECIAL REPAIR TO CEILING FAN AND ELECTRIC GEYSER AT BB CANTT, SRINAGAR
2025_MES_729185_1
864/WS-54(T)/2025-26
Open Tender
Civil Works
Item Rate
180 days
GE 864 EWS
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
Yes
GE 864 EWS
₹96,420
Yes
21 Oct 2025
3 Sept 2025
8 Oct 2025
3 Sept 2025
1 Oct 2025
17 Sept 2025
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .