| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.9 LAccepted-AOC | ₹9.9 L | L1 | Accepted-AOC selected through transparent lottery system |
| 2 | L1₹9.9 LRejected-AOC | ₹9.9 L | L1 | Rejected-AOC not selected through transparent lottery system |
| 3 | L1₹9.9 LRejected-AOC | ₹9.9 L | L1 | Rejected-AOC not selected through transparent lottery system |
| 4 | L1₹9.9 LRejected-AOC | ₹9.9 L | L1 | Rejected-AOC not selected through transparent lottery system |
| 5 | L2₹11.0 LRejected-Finance | ₹11.0 L | L2 | Rejected-Finance highest bidder |
Tender Value
₹11.7 L
EMD Value
₹11,670
Closing Date
8 Jan 2026, 5:00 pmClosed
EE RW Electrical Division Sambalpur
RURAL WORKS ELECTRICAL DIVISION, SAMBALPUR
Provision of 63KVA Transformer for the CCE office Building at Angul for the year 2025-26_building
2025_CERWI_123884_1
EE/RWELECT/SBP/28/2025-26
Open Tender
Electrical Works
60 days
Angul
Please refer to Tender Documents
2 documents required · 2 mandatory
₹6,000
₹11,670
Yes
5 Jun 2026
27 Dec 2025
9 Jan 2026
27 Dec 2025
8 Jan 2026
27 Dec 2025
MAIN DB Supply & fixing of 63A TPN Panel board 1. 63A 4P 30KA MCCB with Spreader,rotary handle, and UV relaease(Make- Legrand/Seimens/L&T/C&S)-2 No 2.63A Change over(Manual)-1 No 3. 63A COPPER bus bar- 2set 8. Phase indicating lamp eith toggle switch-6Nos 9. All accesories & Connection (Rating & Danger borad)
S/F of 4 awy (4+12) TPN MCB DB Single door(2.5.1)
S/F of 40A FP 415V AC 10KA C Curve MCB( Make - Havells /Equivalent)
S/F of 32A C series D.P. MCB (make: Legrand/Anchor/Havels/HPL)
Supply of 3.5core 35sqmm PVC insulated and PVC seathed / XLPE power cable of 1.1 KV grade Armoured cable ( MAKE-HAVELLS/polycab/RR Kable/Rhino cable/equivalent)
Laying of 35sq mm. 3½ Core cable on surface(5.5.2)
Laying of 35sq mm. 3½ Core cable in ground(5.1.2)
Supplying and making end termination with brass compression gland and aluminum lugs for 35sq mm. 3½ Core cable(5.8.21)
Wiring for circuit I sub main wiring alongwith earth wire with following sizes of PVC insulated single core multistrand copper conductor with ISI marked conforming to IS- 694/1990 in 20mm dia non metalic heavy duty flexible conduit 1.6mm in recessed PVC conduit as required ( Make of wire- Finolex/ / Anchor/ Havels/ V-guard / HPL / L&T / Gratewhite / Polycab). -do- 4x6sqmm +1x2.5sqmm ( 1.8.10 )
-do- 2x4 sqmm + 1 x 1.5 sqmm (1.8.3)
S/F of 15A modular socket on 2 Modular Metal box for A.C
S/F of 2000 VA Inverter with 2 nos. 180 Ah Tubular battery including trally arrangement (Make: Microtake/ Luminous/Exide)
S/F of 10 ltr. Geyser(Make:- Havells/equivalent)
S/F of 1.5 Ton 5 star Inverter type split A.C. M/C with 4 KVA Voltage Stabilizer(110V-300V) (Make - Microtek, V-Guard) and AC stand with all accessories and connections and installation (Make - HITACHI/ Bluestar/ Carrier)
Supply and installation of 6 mtr long hot dip galvanized Octagonal pole having base dia of 155 mm and top dia of 70 mm and plate thick ness of 4 mm or more complete with base plate 250x250x16mm and 4 nos. Jtype En 8 grade foundation bolts M24X750mm to withstand 180 KM / HR wind speed considering the weight & dimension of One no. Solar lights fixed on the top of the bracket . The Pole must be suiable to withstand 180 KM/Hr wind speed by considering the weight and wind expose area of one no Semi Integrated Solar lights at a height of 6 mtr above ground .Both the Octagonal Pole and EN8 grade fdn bolts must be manufactuered by Octagonal pole manufacturing company. Brackets & EN8 fdn bolts manufactured in third party Supplier/manufacturer shall not be acceptable.The necessary test reports of Octagonal Pole and EN8 grade fdn bolts must be submitted by the manufacturer for acceptance of product/TDS approval prior to start of the work.The pole manufacturer must submit the confirmation regarding 10 years or more design life of the pole. Construction of RCC foundation by using M20 grade RCC and Fe 415 grade reinforcement in the foundation by considering the SBC as 10 T per sq mtr and fixing the 4 nos. fdn bolts in that foundation for installation of pole with Solar light on that foundation. The work shall be excuted as per the direction of EIC Installation of 6 mtr pole and fixing the solar light on the top of the bracket so that all the solar lights shall be installed at a height of 6mtr above ground on that foundation by using suitable machinery by taking all safety precautions as per the direction of EIC. Make : - Utkarsh/RR Ispat/Vakrangee)
Supply,installation,testing and commissioning of 40 W AIO Solar street lights having 100 Wp or more highly efficient Monocrystalline PV module & 12.8 V 42 Ah or more ( Lithium Ferrophosphate (LiFePo4) Battery having BIS ) which shall be inside the extruded aluminium luminaire housing (Theft retardant type), MPPT charge controller having > 92% efficiency & PIR Sensor. The initial lumen output of AIO street light shall be> 6400 lumen or more in CCT 6000K (+/-500K) (Lumen efficacy of 160 lm/w ) as per LM 79 report of NABL lab . The LED chip will be of OSRAM/NISCHIA/CREE/SEOUL Semiconductor only and should be with lenses for effective lighting distribution. The complete system & BMS should be designed to provide 2 days (24 Hrs) back up in dimming mode by activating PIR sensor and battery should be kept inside the luminaire and Mono Crystalline Panel (Made in India ) to be mounted on the top of the luminaire housing. The luminaire must be having IP 66 protection for critical component like (LED compartment, Driver compartment & Battery) . The AIO street light is having IK 08 .The luminaire should have the provision the tiltable/ adjustable mounting bracket to mount it on the top of the pole directly. Warranty on the AIO street lights must be 5 years .The solar lighting company must submit the warranty certificate in the department by mentioning 5 years warranty on complete lighting system against manufacturing defects. Solar lighting company has to repair/replace the lighting system if required against the manufacturing defect till compleiton of warranty period. The Agency/Contractor has to maintain the lighting system till the completion of warranty period by considering the periodical maintenance like panel cleaning in regular interval and rectifying the defect by engaging labour/machinery to make the lighting system operative till warranty period. The agency/contractor must submit declaration for maintaining the system till warranty period . The following test reports/certifications must be submitted for the technical acceptance of the products . 1. LM 79 REPORT NABL lab ) , 2. IK 08 (Report of NABL lab ), 3. IP 66 Report of NABL lab (The necessary test reports of NABL lab against the above must be submitted for any wattage of Solar Street lights for acceptance of product/TDS approval prior to start of the work. All the test reports must be in the name of Solar Lighting Company (Make:Crompton/Havells/Panasonic/Philips/Wipro)
9 Mtr. long 300 Kg. PSC Pole
LT Stay set Complete
7/12 SWG GI stay wire, Grade -2
LT stay Clamp ( 1.40Kg/pair)
LT Stay insulator
Pole clamp for EYE hook for (XLPE Aerial bunched Cable)
EYE hook for XLPE Aerial bunched Cable
Dead End Clamp suitable for messenger XLPE Aerial bunched Cable
Suspension Clamp with EYE hook for ABC
4C×50 mm² (P)+1C×50 mm²(M)+1CX16 mm²(Street Light) (LT AB Cable)
GI Pipe Earthing (each 5th pole to earth)
Coil Earthing
No-8 GI wire (Dia 4.6mm) 0.131 KG/ Mtr.- 2 Mtr. For connecting pole with Coil earthing
Danger plate (LT)
Back Clamp for danger Plate 25X3 mm. Flat(GI), 0.59Kg/Mtr. Flat(GI) of 0.510mtr length 1 no's = (1x0.59x0.510)
GI barbed wire anticlimbing device 3 Kg. Per support
GI Nut , Bolt & Washer of different sizes (0.5 Kg/ Pole)
Black Paint(GIS Numbering & Zebra Stripping)
Yellow Colour Paint(GIS Numbering & Zebra Stripping) for Background
Fixing of LT Complete stay set includes 1) Turn Buckle Assembly 2) Stay Rod & Stay plate 3) Stay Insulator 4) Stay Wire. 5)Stay clamps with Nuts & bolts, including excvation, supply of 0.5Cum cement concrete foundation 1:2:4 size (500mmx500mmx800mm) using 20mm BHG metal with all labour and material (Excavation of earth will be done of size 500X500X1500 mm.)
Concreting ratio 1:1.5:3(M-20 Grade) (500mmX500mmX1500mm) = 0.375Cu.mtr(Per Pole)
Construction Earthing chamber including installation of earthing pipe.Making earthing chamber including excavation , soil treatment with bentonide powder , calculation of earth resistance, including Installation of 3Mtr GI Pipe 40mm/50mm including welding of Flat(GI) around pipe .
WPB (GI) Pole 160x152 (11Mtr. Long, 30.44KG/Mtr.)-DP (Total Pole Weight with Base Plate & Stiffner=334.84 KG+10.74 KG= 345.58 KG)
9 Mtr. long 300 Kg. PSC Pole
Pole clamp for EYE hook for (XLPE Aerial bunched Cable)
EYE hook for XLPE Aerial bunched Cable
Dead End Clamp suitable for messenger XLPE Aerial bunched Cable
GI Channel 100x50x6mm Channel
GI Flat 50x6mm
M.U Channel(GI) GI 75x40x4.8 mm (3000 mm long)(7.14Kg./Mtr., 2 No's.) (Each 2x3.000x7.14= 42.84 Kg)
Cantilever Support Angle(GI) 50 X 50 X 6MM GI (1282 mm long) (4.5Kg./Mtr, 2 No's.) (Each 2x1.282x4.5= 11.54Kg)
63 KVA , 11/ 0.4 KV (AL) Transformer, BIS Energy Loss level II, Ammendment-4
LT Distribution Box with MCCB, Aluminium Busbar of single Bay with kit kat fuse for 63 KVA S/S
55 SQ.MM. AAAC XLPE Covered Conductor
4 Cx 95 mm2 LT XLPE Cable(Armoured) - FOR 63 KVA Trf.
4 Cx 95 mm2 LT XLPE Cable(Armoured) - From LTDB to Pole
AB Switch(11KV,200A.3pole,50Hz)
H.G.Fuse( 11KV.200A.3Pole)
WEDGE CONNECTOR FOR 55 SQMM.CONDUCTOR
POLYCARBONATE BIRD GUARD
Disc insulator (B&S)70 KN polymer
H W fitting (B&S)70KN(3bolted)
Lightning Arrester(12KV,10KA) Station Class 2
11KV pin insulator polymer
HT stay set complete
HT stay Clamp (1.9Kg/pair)
HT stay insulator TYPE-C
7/10 SWG GI stay wire, Grade -2 (15Kg./ Set)
Concreting ratio 1:1.5:3(M-20 Grade) (500mmX500mmX1800mm) = 0.450Cu.mtr(Per Pole) (For WPB Pole)
Couping ratio 1:1.5:3(M-20 Grade) (500mmX500mmX450mm) = 0.113Cu.mtr(Per Pole)
PCC ratio 1:3:6(M-10 Grade) For DSS Area (5X3X0.1)= 1.5 Cu. mtr.
Fixing of stay set with 0.5Cum cement concrete foundation 1:3:6(M-10 Grade) size ( 900mmx600mmx900mm) using 40mm BHG metal with all labor and material except stay set , stay wire , stay insulator .
Construction Earthing chamber including installation of earthing pipe.Making earthing chamber including excavation , soil treatment with bentonide powder , calculation of earth resistance, including Installation of 3Mtr GI Pipe 40mm/50mm including welding of Flat(GI) around pipe .
Laying of 4 Cx 95 mm2 LT XLPE Cable
SITC and Erection of GI Fencing with Gate
Concreting ratio 1:1.5:3(M-20 Grade) (500mmX500mmX1500mm) = 0.375Cu.mtr(Per Pole) (For PSC Pole)
Supply of AL Lugs suitable for 95 sq mm cable/conductor, Crimping with cable and Fixing/connecting include supply and erection of PVC Tape as per voltage requirement.
Supply and erection of double Compression Flameproof Type Glanding for armored Cable 3.5/4C 50-95sqmm including making hole in Base plate and dressing of cable along with vermin proofing properly .Supply to be done as per TPCODL Spec and approved make dowells.
GI Flat 50x6mm
Straight Cross Arm 100X50X6mm, 9.56 KG/Mtr., each Channel(GI) length 0.306 mtr., 4 no's Channel(GI) required =( 4x9.56x0.306)
11 KV pin insulator polymer
H W fitting(B&S) 70KN, 3Bolt
Disc insulator (B&S) 70 KN polymer
NON METALLIC TIES -11KV 55SQMM CVRD AAAC
IPC for 55 sq.mm AAA conductor (For covered conductor)-11kV
AAAC 11KV XLPE insulated covered conductor
H.T. Stay clamp, 50x8 mm. Flat(GI), 3.14Kg/Mtr., 0.551 Mtr. Length, 2 no's qty. required ( 1 Pair)
H.T. Stay set (Complete )
H.T. Stay Insulator Type-C
7/10 SWG Stay Wire 15kg /stay
GI Nut , Bolt & Washer of different sizes (7.433 Kg each Cut Pole)
Black Paint(GIS Numbering & Zebra Stripping)
Yellow Colour Paint(GIS Numbering & Zebra Stripping) for Background
Fixing of complete 11KV line Complete stay set includes 1) Turn Buckle Assembly 2) Stay Rod & Stay plate 3) Stay Insulator 4) Stay Wire. 5)Stay clamps with Nuts & bolts BA will do the excvation including excvation, supply of 0.5Cum cement concrete foundation 1:2:4 size ( 500mmx500mmx800mm) using 20mm BHG metal with all labour and material as per TPCODL Drawing & Standard.
Please Enable Macros to View BoQ information
stage.html
html • 0.05 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_573493.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.78 MB
Tendernotice_2.pdf
PDF • 0.70 MB
BOQ_573493.xls
BOQ • 0.39 MB
Download all tender documents and submit your bid