Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹37.9 LAccepted-AOC AZAD COLONY B 90 FEET ROAD SOURA SRINAGAR J K 190011 | SRINAGAR | SRINAGAR | JAMMU AND KASHMIR | 190011 | L1 | Accepted-AOC Found in Order Lowest bidder | |
| 2 | L2₹38.8 L+₹89,580 (2.36%)Rejected-AOC BUDOOBAGH NOWPORA 0 KHANYAR SRINAGAR JAMMU KASHMIR 190003 | SRINAGAR | JAMMU AND KASHMIR | 190003 | L2 | Rejected-AOC Other than lowest bidder | |
| 3 | L3₹39.4 L+₹1.5 L (3.87%)Rejected-AOC | L3 | Rejected-AOC Other than lowest bidder |
Tender Value
Refer Docs
EMD Value
₹69,500
Closing Date
11 Sept 2021, 6:00 pmClosed
GE 874 EWS C/O 56 APO
GE 874 EWS C/O 56 APO
SPECIAL REPAIR FOR REPLACEMENT OF VARIOUS BER DC SOURCE OF DG SETS VCBS AND OCBS AND PROVN OF LT PANEL AT CHOWKIBAL AND TANGDHAR UNDER GE 874 EWS
2021_MES_441265_4
GE 874/EWS-18/2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Kupwara
As per NIT and tender documents
6 documents required · 6 mandatory
₹500
GE 874 EWS
₹69,500
Yes
29 Oct 2021
23 Aug 2021
13 Sept 2021
23 Aug 2021
11 Sept 2021
30 Aug 2021
Amount
E/M Portion
Supply and installation, testing and commissioning of 12 Volts 150 AH tubular battery for use in Generator Sets/ VCBs/ OCBs, etc with minimum warranty of 48 months (replacement/ free repair warranty) from date of installation, of make Exide/ Luminous/ Amco.
Supply and installation, testing and commissioning of battery bank of 110 Volts or 24 Volts containing 55 Nos (for 110V) or 12 Nos (for 24V) batteries (using copper conductors for connecting) using batteries (batteries to be measured and paid separately in Srl Item No. 3 here in after).
Valve Regulated Lead Acid Type, 2 Volt Batteries of 125 AH each for use in VCBs/ OCBs with minimum comprehensive warranty of 48 months (replacement/ free repair warranty) from date of installation of make Exide/ Luminous/ AMCO or equivalent as approved by engineer in charge. Note : Batteries should be compatible and chargeable by the battery charger being installed by the item No. 4 and 5 here in after.
Supply and installation, testing and commissioning of smart battery charger for charging battery pack, that can charge above battery packs (by charging individual batteries, simultaneously), provide DC output to VCBs, from 170 V to 220V AC supply when main supply is present and through battery when main supply is absent, with charger capable of providing output of 110 V DC or 24V DC or 12V DC or 230V AC or all four, with output supply stabilised with no variation more than 0.5V, with charger of make power control systems or equivalent as approved by engineer in charge.
Supply and installation, testing and commissioning of smart battery charger for charging 24V (and 12V) battery packs, that can charge above battery packs (by charging individual batteries, simultaneously), provide DC output to VCBs, from 170 V to 220V AC supply when main supply is present and through battery when main supply is absent, with charger capable of providing output of 24V DC or 12V DC or 230V AC or all four, with output supply stabilised with no variation more than 0.5V, with charger of make power control systems or equivalent as approved by engineer in charge.
Supply, installing, testing and commissioning, factory made and tested (prototype having been CPRI type test certified), Outdoor LT Panel, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated aluminium bus bars of 600 Amps rating, installed on polymer insulators. The bus bars should be covered with colour coded (depending on the phase) heat shrink sleeve. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and 40x40x6mm thick angle iron frame work, externally and internally powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front opening type, with aprons for cable entry, with two layers of Sheet Metal Cover (should have one set of doors on inside and one set of doors outside), capable of withstanding snow and rain at installation site with maintainence proof design, with double door shutter and locking arrangement (including provision of 65mm Godrej (Freedom) lock with 2 keys, having one chamber with door for each MCCB, having two empty chambers for future use, internal wiring 2.5 Sqmm with PVC insulated, solid copper conductor, FRLS cables, IS-694 marked of adequate size incl the provision of space to accommodate the under mentioned items. The cable coming in and out of the Panel will be laid in specially made PCC/ Brick Masonry Trenches/ Ducts of 30cm x 30 cm with sand cushioning till top and RCC/ Cast Iron lid cover for the trenches. The scope of work includes the following:-
(a) Incoming (i) On Load Panel Mounted 350A Changeover, 2 input and 1 output - 01 Nos (ii) MCCB 4 pole, 415 volts AC grade, 300 Amps rating and 36 KA rupturing capacity complete with microprocessor based OL protection - 01 No E15 (iii) Two empty space for future MCCB connection in input (before Changeover, for generator) - Short with bus bar. The space shall be closed with a bolted door (b) Outgoing (i) MCCB 4 pole, 415 volts AC grade, 100 Amps rating and 35 KA rupturing capacity complete with microprocessor based OL protection - 01 Nos (ii) MCCB 4 pole, 415 volts AC grade, 63 Amps rating and 35 KA rupturing capacity complete with microprocessor based OL protection - 04 Nos (c) Three Phase Digital Panel Ammeter with three displays to display all phases symulteneously - 05 Nos (d) Indicator lamp R Y G B Make Havells -01 set (e) Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone , 15 cm thick in foundation, brick work in CM 1:6 with sub class `B', old size bricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45cm above the nearest road/ ground/ floor level.
(f) Multifunction Electric Panel Meter, LCD, Make Secure Model Elite 445 - 01 Nos (The meter and RYB lamps shall be protected by a TPN MCB) (g) Current Transformers - As required (h) Schematic Drawing Plate, Rivetted to the panel - 01 No Note : (i) All out going feeders shall be connected by cable through suitable size gland plate / glands. (ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint.
Supply, installing, testing and commissioning, factory made and tested (prototype having been CPRI type test certified), Outdoor LT Panel, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated aluminium bus bars of 600 Amps rating, installed on polymer insulators. The bus bars should be covered with colour coded (depending on the phase) heat shrink sleeve. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and 40x40x6mm thick angle iron frame work, externally and internally powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front opening type, with aprons for cable entry, with two layers of Sheet Metal Cover (should have one set of doors on inside and one set of doors outside), capable of withstanding snow and rain at installation site with maintainence proof design, with double door shutter and locking arrangement (including provision of 65mm Godrej (Freedom) lock with 2 keys, having one chamber with door for each MCCB, having two empty chambers for future use, internal wiring 2.5 Sqmm with PVC insulated, solid copper conductor, FRLS cables, IS-694 marked of adequate size incl the provision of space to accommodate the under mentioned items. The cable coming in and out of the Panel will be laid in specially made PCC/ Brick Masonry Trenches/ Ducts of 30cm x 30 cm with sand cushioning till top and RCC/ Cast Iron lid cover for the trenches. The scope of work includes the following:-
(a) Incoming (i) On Load Panel Mounted 300A Changeover, 2 input and 1 output - 01 Nos (ii) MCCB 4 pole, 415 volts AC grade, 250 Amps (As specified by Engineer in Charge) rating and 36 KA rupturing capacity complete with microprocessor based OL protection - 01 No (iii) Two empty space for future MCCB connection in input (before Changeover, for generator) - Short with bus bar. The space shall be closed with a bolted door (b) Outgoing (i) MCCB 4 pole, 415 volts AC grade, 100 Amps rating and 35 KA rupturing capacity complete with microprocessor based OL protection - 01 Nos (ii) MCCB 4 pole, 415 volts AC grade, 63 Amps rating and 35 KA rupturing capacity complete with microprocessor based OL protection - 04 Nos (c) Three Phase Digital Panel Ammeter with three displays to display all phases symulteneously - 05 Nos (d) Indicator lamp R Y G B Make Havells -01 set (e) Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone , 15 cm thick in foundation, brick work in CM 1:6 with sub class `B', old size bricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45cm above the nearest road/ ground/ floor level.
(f) LCD Multifucntional panel type energy meter, with tamper detection, output for data savingand data logging Model Secure Elite 440 series or equivalent in L&T/ HPL - 01 Nos (g) Current Transformers - As required (h) Schematic Drawing Plate, Rivetted to the panel - 01 No Note : (i) All out going feeders shall be connected by cable through suitable size gland plate / glands. (ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint.
Supply, installing, testing and commissioning, factory made and tested (prototype having been CPRI type test certified), Outdoor LT Panel, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated aluminium bus bars of 400 Amps rating, installed on polymer insulators. The bus bars should be covered with colour coded (depending on the phase) heat shrink sleeve. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and 40x40x6mm thick angle iron frame work, externally and internally powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front opening type, with aprons for cable entry, with two layers of Sheet Metal Cover (should have one set of doors on inside and one set of doors outside), capable of withstanding snow and rain at installation site with maintainence proof design, with double door shutter and locking arrangement (including provision of 65mm Godrej (Freedom) lock with 2 keys, having one chamber with door for each MCCB, having two empty chambers for future use, internal wiring 2.5 Sqmm with PVC insulated, solid copper conductor, FRLS cables, IS-694 marked of adequate size incl the provision of space to accommodate the under mentioned items. The cable coming in and out of the Panel will be laid in specially made PCC/ Brick Masonry Trenches/ Ducts of 30cm x 30 cm with sand cushioning till top and RCC/ Cast Iron lid cover for the trenches. The scope of work includes the following:-
(a) Incoming (i) On Load Panel Mounted 150A Changeover, 2 input and 1 output - 01 Nos (ii) MCCB 4 pole, 415 volts AC grade, 150 Amps rating and 36 KA rupturing capacity complete with microprocessor based OL protection - 01 No E15 (iii) Two empty space for future MCCB connection in input (before Changeover, for generator) - Short with bus bar. The space shall be closed with a bolted door (b) Outgoing (i) MCCB 4 pole, 415 volts AC grade, 100 Amps rating and 35 KA rupturing capacity complete with microprocessor based OL protection - 01 Nos (i) MCCB 4 pole, 415 volts AC grade, 63 Amps rating and 35 KA rupturing capacity complete with microprocessor based OL protection - 02 Nos (c) Three Phase Digital Panel Ammeter with three displays to display all phases symulteneously - 03 Nos (d) Indicator lamp R Y G B Make Havells -01 set (e) Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone , 15 cm thick in foundation, brick work in CM 1:6 with sub class `B', old size bricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45cm above the nearest road/ ground/ floor level.
(f) LCD Multifucntional panel type energy meter, with tamper detection, output for data savingand data logging Model Secure Elite 440 series or equivalent in L&T/ HPL - 01 Nos (g) Current Transformers - As required (h) Schematic Drawing Plate, Rivetted to the panel - 01 No Note : (i) All out going feeders shall be connected by cable through suitable size gland plate / glands. (ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint.
Supply, installing, testing and commissioning, factory made and tested (prototype having been CPRI type test certified), Outdoor LT Panel, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated aluminium bus bars of 300 Amps rating, installed on polymer insulators. The bus bars should be covered with colour coded (depending on the phase) heat shrink sleeve. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and 40x40x6mm thick angle iron frame work, externally and internally powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front opening type, with aprons for cable entry, with two layers of Sheet Metal Cover (should have one set of doors on inside and one set of doors outside), capable of withstanding snow and rain at installation site with maintainence proof design, with double door shutter and locking arrangement (including provision of 65mm Godrej (Freedom) lock with 2 keys, having one chamber with door for each MCCB, having two empty chambers for future use, internal wiring 2.5 Sqmm with PVC insulated, solid copper conductor, FRLS cables, IS-694 marked of adequate size incl the provision of space to accommodate the under mentioned items. The cable coming in and out of the Panel will be laid in specially made PCC/ Brick Masonry Trenches/ Ducts of 30cm x 30 cm with sand cushioning till top and RCC/ Cast Iron lid cover for the trenches. The scope of work includes the following:-
(a) Incoming (i) On Load Panel Mounted 100A Changeover, 2 input and 1 output - 01 Nos (ii) MCCB 4 pole, 415 volts AC grade, 100 Amps rating and 36 KA rupturing capacity complete with microprocessor based OL protection - 01 No E15 (iii) Two empty space for future MCCB connection in input (before Changeover, for generator) - Short with bus bar. The space shall be closed with a bolted door. (b) Outgoing (i) MCCB 4 pole, 415 volts AC grade, 63 Amps rating and 35 KA rupturing capacity complete with microprocessor based OL protection - 02 Nos (ii) (From the above MCCBs) MCB SPN 32A, C Curve - 06 (03 x 2) (c) Three Phase Digital Panel Ammeter with three displays to display all phases symulteneously - 02 Nos (d) Indicator lamp R Y G B Make Havells -01 set (e) Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone , 15 cm thick in foundation, brick work in CM 1:6 with sub class `B', old size bricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45cm above the nearest road/ ground/ floor level.
(f) LCD Multifucntional panel type energy meter, with tamper detection, output for data saving and data logging Model Secure Elite 440 series or equivalent in L&T/ HPL - 01 Nos (g) Current Transformers - As required (h) Schematic Drawing Plate, Rivetted to the panel - 01 No Note : (i) All out going feeders shall be connected by cable through suitable size gland plate / glands. (ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint.
Supply, installing, testing and commissioning, factory made and tested (prototype having been CPRI type test certified), LT Panel, platform mounted, Outdoor Type, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated Aluminium bus bars of 500 Amps (or above) rating installed on porcelain insulators. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and 40x40x6mm thick angle iron frame work, externally powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front opening type, with aprons for cable entry, with two layers of Sheet Metal Cover (should have one set of doors on inside and one set of doors outside), capable of withstanding snow and rain at installation site with maintainence proof design, with 60cm tall ground clearance, with double door shutter and locking arrangement (including provn of 65mm Godrej (Freedom) lock with 2 keys, internal wiring 2.5 Sqmm with PVC insulated, solid copper conductor, FRLS cables, IS-694 marked of adequate size incl the provision of space to accommodate the under mentioned items. The scope of work includes the following:-
(a) Incoming (i) Onload Panel Mounted, 4 Pole Changeover, 2 input 1 output - 01 Nos (ii) MCCB 4 pole, 415 volts AC grade, 250 Amps rating and 36 kA rupturing capacity complete with adjustable OL tripping settings - 1 Nos (iii) Two empty space for future MCCB connection in input (before Changeover, for generator and transformer inputs) - Short with bus bar (iv) Multifunction Electric Panel Meter, LCD, Make Secure Model Elite 445 - 01 Nos (The meter and RYB lamps shall be protected by a TPN MCB) (v) Surge Protection Device, 20kA rating, TPN (vi) Indicator lamp R Y B Make Havells -01 set
(b) Outgoing (i) MCCB 4 pole, 415 volts AC grade, 100 Amps rating and 35 KA rupturing capacity complete with microprocessor based OL protection - 02 Nos (ii) MCCB 4 pole, 415 volts AC grade, 63 Amps rating and 35 KA rupturing capacity complete with microprocessor based OL protection - 02 Nos (iii) Three Phase Digital Panel Ammeter with three displays to display all phases symulteneously - 02 Nos (c) Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone , 15 cm thick in foundation, brick work in CM 1:6 with sub class `B', old size bricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 45cm above the nearest road level. Note : (i) All out going feeders shall be connected by cable through suitable size gland plate / glands. (ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint.
Supply, installing, testing and commissioning, factory made and tested (prototype having been CPRI type test certified), Outdoor LT Panel, platform mounted, Outdoor Type, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated aluminium bus bars of 250 Amps rating, installed on polymer insulators. The bus bars should be covered with colour coded (depending on the phase) heat shrink sleeve. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and 40x40x6mm thick angle iron frame work, externally and internally powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front opening type, with aprons for cable entry, with two layers of Sheet Metal Cover (should have one set of doors on inside and one set of doors outside), capable of withstanding snow and rain at installation site with maintainence proof design, with 60cm tall ground clearance, with double door shutter and locking arrangement (including provision of 65mm Godrej (Freedom) lock with 2 keys, having one chamber with door for each MCCB, having two empty chambers for future use, internal wiring 2.5 Sqmm with PVC insulated, solid copper conductor, FRLS cables, IS-694 marked of adequate size incl the provision of space to accommodate the under mentioned items. The cable coming in and out of the Panel will be laid in specially made PCC/ Brick Masonry Trenches/ Ducts of 30cm x 30 cm with sand cushioning till top and RCC/ Cast Iron lid cover for the trenches.The scope of work includes the following:-
(a) Incoming (i) On Load Panel Mounted 100A Changeover, 2 input and 1 output - 01 Nos (ii) MCCB 4 pole, 415 volts AC grade, 63 Amps rating and 30 KA rupturing capacity complete with Adjustable Overload and fixed Short Circuit protection - 01 No (placed after Changeover) (iii) Voltage Protector, Three Phase, with digital display, adjustable voltage setting for over voltage tripping and under voltage tripping, with auto recovery, 63A (iv) Two empty space for future MCCB connection in input (before Changeover, for generator) - Short with bus bar. The space shall be closed with a bolted door (v) Multifunction Electric Panel Meter, LCD, Make Secure Model Elite 445 - 01 Nos (The meter and RYB lamps shall be protected by a TPN MCB) (vi) Indicator lamp R Y G B Make Havells -01 set
(b) Outgoing (i) MCCB 4 pole, 415 volts AC grade, 40 Amps rating and 30 KA rupturing capacity complete with Adjustable Overload and fixed Short Circuit protection - 02 Nos (ii) (From the above MCCBs) MCB SPN 32A, C Curve - 06 (03 x 2) (iii) Three Phase Digital Panel Ammeter with three displays to display all phases symulteneously - 02 Nos (c) Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone , 15 cm thick in foundation, brick work in CM 1:6 with sub class `B', old size bricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 1.5mtr above the nearest road/ ground/ floor level. (d) Current Transformers - As required (e) Schematic Drawing Plate, Rivetted to the panel - 01 No Note : (i) All out going feeders shall be connected by cable through suitable size gland plate / glands. (ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint.
Supply, installing, testing and commissioning, factory made and tested (prototype having been CPRI type test certified), Outdoor LT Panel, platform mounted, Outdoor Type, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated aluminium bus bars of 250 Amps rating, installed on polymer insulators. The bus bars should be covered with colour coded (depending on the phase) heat shrink sleeve. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15 mm CRCA MS sheet and 40x40x6mm thick angle iron frame work, externally and internally powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front opening type, with aprons for cable entry, with two layers of Sheet Metal Cover (should have one set of doors on inside and one set of doors outside), capable of withstanding snow and rain at installation site with maintainence proof design, with 60cm tall ground clearance, with double door shutter and locking arrangement (including provision of 65mm Godrej (Freedom) lock with 2 keys, having one chamber with door for each MCCB, having two empty chambers for future use, internal wiring 2.5 Sqmm with PVC insulated, solid copper conductor, FRLS cables, IS-694 marked of adequate size incl the provision of space to accommodate the under mentioned items. The cable coming in and out of the Panel will be laid in specially made PCC/ Brick Masonry Trenches/ Ducts of 30cm x 30 cm with sand cushioning till top and RCC/ Cast Iron lid cover for the trenches.The scope of work includes the following:-
(a) Incoming (i) On Load Panel Mounted 200A Changeover, 2 input and 1 output - 01 Nos (ii) MCCB 4 pole, 415 volts AC grade, 100 Amps rating and 35 KA rupturing capacity complete with microprocessor based OL protection - 01 No (placed after Changeover) (iii) Two empty space for future MCCB connection in input (before Changeover, for generator) - Short with bus bar. The space shall be closed with a bolted door (iv) Multifunction Electric Panel Meter, LCD, Make Secure Model Elite 445 - 01 Nos (The meter and RYB lamps shall be protected by a TPN MCB) (v) Indicator lamp R Y G B Make Havells -01 set
(b) Outgoing (i) MCCB 4 pole, 415 volts AC grade, 63 Amps rating and 30 KA rupturing capacity complete with Adjustable Overload and fixed Short Circuit protection - 02 No (placed after Changeover) (ii) Voltage Protector, Three Phase, with digital display, adjustable voltage setting for over voltage tripping and under voltage tripping, with auto recovery, 63A - 02 Nos (iii) (From the above MCBs) MCB SPN 40A, C Curve - 06 (03 x 2) (iv) Three Phase Digital Panel Ammeter with three displays to display all phases symulteneously - 02 Nos (c) Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone , 15 cm thick in foundation, brick work in CM 1:6 with sub class `B', old size bricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for panel. The platform shall be such that it is of a height 1.5mtr above the nearest road/ ground/ floor level. (d) Current Transformers - As required (e) Schematic Drawing Plate, Rivetted to the panel - 01 No Note : (i) All out going feeders shall be connected by cable through suitable size gland plate / glands. (ii) The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint.
Re-painting of existing LT Panel with a thick coating of electrical insulating paint (such as insulect L), the paint box clearly stating the Paint as being Electrically insulating with atleast 1100 Volt insulation grade (measured per panel) complete all as directed by Engr-In-Charge.
Replacement of Unserviceable Voltmeter/ Ammeter with new Digital three phase Voltmeter/ three phase Ammeter, along with CT (each voltmeter or each ammeter is measured as one number) complete all as directed by Engr-In-Charge.
Replacement of existing Bus Bars of existing LT Panels with new Aluminium Bus Bars (covered with colour coded heat shrink insulation) of 600A Rating (measured in running meters) complete all as directed by Engr-In-Charge.
Replacement of existing Bus Bars of existing LT Panels with new Aluminium Bus Bars (covered with colour coded heat shrink insulation) of 500A Rating (measured in running meters) complete all as directed by Engr-In-Charge.
Supply, laying and testing cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 sqmm 3.5 core, burried in trenches/ floor/ Walls/ Ducted/ in GI Pipes complete including cutting/ chasing to any surface and making good distrubed surface to match existing surface complete all as directed by Engr-In-Charge.
Supply, laying and testing cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 70 sqmm 3.5 core, burried in trenches/ floor/ Walls/ Ducted/ in GI Pipes complete including cutting/ chasing to any surface and making good distrubed surface to match existing surface complete all as directed by Engr-In-Charge.
Supply, laying and testing cable XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 sqmm 3.5 core, burried in trenches/ floor/ Walls/ Ducted/ in GI Pipes complete including cutting/ chasing to any surface and making good distrubed surface to match existing surface complete all as directed by Engr-In-Charge.
Excavation in trenches in any type of soil n.exc 1.5m deep and not exc 1.5m wide for laying of under ground cable, electric pole and getting out complete all as directed.
Returning filling in including spreading leveling watering and well ramming 25cm in thickness in any type of soil.
Removing excavated material n.exc 50m and depositing where directed at a level n.exc 1.5m above the starting point.
M&L for dry sand cushioning to under ground cables provided with a layer of sand 8 cm deep before laying the cable, 15 cm depth after laying cable & stretching the cable all as specified and directed.
Supply and installation of 10 kVA (8000W) single phase Voltage Stabiliser 90V to 300V input and output stabilised at 300V, with bypass mechanism and Overcurrent protection, Air Cooled, Make of Aulten/ Vinitec/ Pulstron, complete as directed, specified and clarified by engineer in charge.
Supply and Laying Hot and Cold Water Dispenser, bottle type, with built in refrigeration cabinet, with bottle.
Supply and lay brick class ‘B’ covering as mechanical protection to cable with well burnt all as specified by engineer in charge.
M&L GI tubing light grade with all fitting and fixed in wall and floor or fixed to pole of size 40mm dia or more as required for covering the pipes.
Top Mind Industries Pvt Limited
Kesar Impex
Bidder Name
FG CONSTRUCTION
Top Mind Industries Pvt Limited
Kesar Impex
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .