| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹94.4 LAccepted-AOC 202 NEW RAM VIHAR COLONY PINTO PARK MORAR GWALIOR 474005 | GWALIOR | GWALIOR | MP | 474005 | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹1.5 Cr+₹57.2 L (60.5%)Rejected-Finance | L2 | Rejected-Finance Not being Lowest bidder |
| Sl No | Description | Qty | Unit | M/s Kohli Builders L2 | M/S AUTOMATION AND SWITCHGEAR CONTROL L1 |
|---|---|---|---|---|---|
| 1.00 | Supply, Installation, testing and commissioning Outdoor Type Compact Sub- Station (CSS) having 11 KV, 630A VCB, 63 KVA Copper Wound Off-Circuit Transformer & LT Side comprising of the following below mentioned accessories complete all as specified and as directed:-
(a) HT Section :- 01 No 11kV, 630A, RMU with one incoming and one outgoing with Horizontal Draw Out VCB -02 Nos and Manual/230V AC Motor Operated Spring Charging Mechanism with 24V DC Closing /Opening Shunt trip coils, Aux. Switch, Mechanical On/Off Push Button, mechanical Operating Counter with metering 1 No CT, PT, IDMT, Cubical Auxiliary Relay, 8 Window Annunciator Model No. SI-801, Battery Power Pack with 7AH Battery & in built charger for 24V Circuit.
(b) Transformer Section :- 63 KVA, 11/0.433 KV, Dry type Copper Wound Step Down “BIS Marked & BEE Star Labelled” Transformer having 7 position Off-Circuit tap changer with tapping range +7.5% in steps of 2.5% each with all standard fittings & accessories including WTI 1 No & Marshalling Box. as per IS-1180:2014 EEL- 3 with amendment no.- 4 Losses @50% Load – 270W, Losses @100% Load - 956W
c) LT Section :- LT Panel comprising of LV Side Incomer – 01 No. 125 Amp 4 Pole 25KA MCCB with thermal magnetic based release with O/L & S/C Protection.- RYB Indication, Digital Ammeter for each outgoing, Digital voltmeter in incoming, surge protection device with proper control wiring. | 1 | Each Job | 35,00,000 ₹35,00,000 | 17,00,000 ₹17,00,000 Lowest |
| 1.01Outgoings for Distribution Network MCCB 100 Amps, 16 KA 415V 4 Pole with thermal magnetic based release with O/L & S/C protection. -01 No.(O/G) for PAR Panel 03 set LED phase indicating lamp with 2A SP MCB. 03 set 63/5A Class-1, CT 01 set 0-63A Digital Multifunction meter Capacitor Panel (30 KVAR) 30 KVAR APFC Panel with MCCB, APFC relay & Capacitors bank with Suitable Switchgear Incomer 1 no. 63A 415V TP MCCB, 25KA with thermal magnetic based release with O/L & S/C protection. 1 Set ON/OFF/TRIP indicating lamps (LED). 1 Set ON/OFF push buttons. 1 Set LED phase indicating lamps with 2A SP MCB. 2 set 63/5A Class-1 CT 1 No. 0-500 V Digital voltmeter 1 Set 0-63A Digital ammeter 1 No. APFC relay Bus Bars-40 x 10 mm copper bus bar for 3 phase and neutral duly colour coded insulation. Outgoing 6 nos. 20 A, 3P MCB with capacitor duty contactor, ON/OFF push buttons and LED indicating lamps. 1 no. 20 A, 3P MCB without capacitor duty contactor, ON/OFF push buttons and LED indicating lamps. 6 set 05 KVAR capacitor banks (i) MS Steel Sheet enclosure suitable for Outdoor Installation with MS channels (Base) - 01 Set (ii) Provision for receiving Incoming and Outgoing cables through Bottom entry, excluding Termination Kit and Glands - 01 Set | |||||
| 2.00 | Supply, installation, testing & commissioning of 12kV, 630A, 21kA/3sec, non extensible type, Motorised, Outdoor Type IP-64, SF6 Gas Insulated Ring Main Unit with Three (3) Vacuum Circuit Breakers (VCB) (01 Nos Incomer + 02 Nos Outgoing) with Air Insulated Bus PT Panel 11 KV, inside robotically welded stainless steel (Non Ferrite Non Magnetic Grade) tank having minimum thickness 2.5 mm having IP 43 Degree of Protection. RMU should be provided with Copper bus Bar, Resin cast ring core protection CT on cables 150/5-5 Amp, Core I (5P10, 15 VA class 1.0) and core II (13 VA, Cl 5P10) - 01 Sets for incoming and Resin cast ring core protection CT on cables 100/5-5 Amp, Core I (5P10, 15 VA class 1.0) and core II (13 VA, Cl 5P10) - 01 Sets for outgoing - 1, Resin cast ring core protection CT on cables 50-25/5-5 Amp, Core I (5P10, 15 VA class 1.0) and core II (13 VA, Cl 5P10) - 01 Sets for outgoing - 2, padlock provision and complete with all accessories. The RMU Shall be type tested for internal arc test of 20 kA/0.1 Sec as per IEC 62271-200 for both tank and cable compartment. The unit shall include the all necessary standards fittings as required at site required or as specified and directed by OEM/ Engr-in-charge.
Note :- Detail specifications and standard fittings and accessories are specified below.
RMU Construction:
The switchgear and busbar shall all be contained in a stainless steel enclosure filled with SF6 at 0.3 bar (300 kPa) relative pressure to ensure the insulation and breaking functions. Sealed for life, the enclosure shall meet the "sealed pressure system" criterion in accordance with the IEC 62271-1 standard (§ 3.6.5.4): "a volume for which no further gas processing is required during its entire expected life”. In addition, manufacturer shall confirm that maximum leakage rate is lower than 0,1 % / year. It shall provide full insulation, making the switchgear insensitive to the environment (temporary flooding, high humidity...), IP67 degrees of protection in accordance with recommendation IEC 60529 § 14.2.7. Thus assembled, the active parts of the switchgear shall be maintenance-free and the switchboard shall be low-maintenance. The switchboards drives shall have an IP2X protection index. The tank shall be made of at least 2mm unpainted stainless steel. SF6 gas is the preferred dielectric medium for MV RMUs. Oil filled switchgear will not be considered. SF6 gas used for the filling of the RMU shall be in accordance with IEC 60376.Any accidental overpressure inside the sealed chamber will be limited by the opening of a pressure limiting device in the lower part of the enclosure. Gas will be released to the rear or the bottom of the switchboard away from the operator. Number of mechanical operations of Circuit breaker 2000 O/C , Number of electrical operations at full loop current for CB: 2000 O/C,. Manufacturer shall provide type test report to prove compliance with IEC 62271-200 Annex A, Internal arc classification class AFL with 21kA 1s for the SF6 enclosure. Make of the RMU, vaccum intrtupter , relay & meter shall be of same OEM. All the test certificate shall be in the name of the OEM only . | 1 | Each JOB | 14,00,000 ₹14,00,000 | 7,00,000 ₹7,00,000 Lowest |
| 2.01(a) 3 No. 630 Amp motorised vacuum circuit breaker, tripple pole, single break 3 position as incomer (On, Off and earth having STC capacity 20 KA for 3 seconds with copper bus bar and copper earth bar fitted with fixed type voltage indicator device as per IEC 61958-1, fully rated with earth switch, spring assisted mechanism, Red/Green Push Button for On/Off Operation, Arc proof hinged type cable cover interlocked with Earth Switch, Air insulated cable boxes and boots suitable for bottom entry front termination of 3 core cable 95/120/185 Sqmm. (b) 3O/C + 1E/F self powered relay with Low and High set for Over current and Earth Fault. Relay should have LCD ( 16 x 2). Relay should have facility to trip the breaker from remote commands without shunt trip coil, Last 5 Fault Record with Time stamp, battery pack replaceable from front, One No Master trip relay, Announciator panel etc (c) Transformer, VCB should be provided with protection scheme for transformer faults like OTI, WTI & Buchholz's relay alaram & trip, along with annunciation and lock-out function (d) Bus Connected PT Unit -1 No. for Metering consisting of following:- (i) Type M: Air Insulated metering module 12KV, 630A, 20KA for 3sec. (ii) 3 Voltage Transformers of the ratio 11kV/√3 / 110 V/√3, 25 VA, Class 1.0 with HT fuses on primary side and MCB on secondary side. (iii) 1 Digital MFM to measure Amps, Volts, Frequency, PF, KWH, KVAR. (iv) 1 CFL Illumination. (v) 1 Space Heater with thermostat. (vi) 1 RYB phase indications. (vi) 1 set Bushings for external busbar connection along with Busbar cover & Sleeved busbars for coupling. (vii) 2X12 V Battery with battery charger with suitable burden for motor operation. Input 230 V AC & Output 24 V DC. Battery make: EXIDE/HBL/Eqiv. | |||||
| 2.02(e)Programmable Logic Controller for Auto changeover scheme between two incomers shall comprise of following features :- (i) PLC Scheme (Incorporating Basic Auto & Manual feature for by-passing changeover scheme) for Auto Changeover - 1 Set (ii) Two Sets of Remote Control Kits for Motorised Isolator Operation (iii) One No. PLC Having Communication Ports for future integration with SCADA on MODBUS. (iv) One Factory Programmable Logic - Of - Operation permanentaly stored in PLC as per manufacturers instructions for autochangeover of feeders all as directed by GE, MES and programmable at site (v) Two Sets of Signal Convertors for PLC Operation. (vi)Safety Interlocks Shall be provided as per relevant IEC/IS Standards and Manufacturers directions. (vii)The Autochangeover of feeders shall be in minimum time not exceeding 10 to 15 seconds. (viii)LED based Capacitive voltage indication fixed type VPIS 9-15 kV (ix)Necessay interclocking arrangement for safety and operations (x)LBS shall be of ratings 12 KV, 630 A, 20 KA for 3 Sec. (xi) One No. Operationg Handle for Manual Operation. (xii) One No. Manometer. (f) Safety Interlocks Shall be provided as per relevant IEC/IS Standards and Manufacturers directions. (g) Above switchgear shall confirm to all relevant IEC/IS Standards. (h) Manual operation of Breaker should be possible without dismantling the motor from RMU. The motor should be fitted in such a way that it should not be outside front covers of RMU. (j) Coupling of RMU and Metering module should be with the help of Bolted type arrangement, so that the coupling at site shall be easy. Plug-in type bushing shall not be acceptable. (k) The Cable termination of RMU should be front accessible only. And minimum 3 module should accommodate in one tank to avoid multiple coupling at site. (l) PCC 1:2:4. type B1 using 20 mm graded aggregate for foundation of RMU as per recommendations of manufacturers or directed by EIC. (m) Two copper earthing for RMU shall be provided with copper strip and earth test point (wiil be mesured and paid separatley under Item no 14). Note :- 1. Any other parts/items not specified above but have been considered essential for smooth and safe functioning of the RMU system shall be included in the items and are covered against the quoted rate. 2. The cost of taking down the HT connections from the existing VCB and refixing at RMU panel with in the same Substation is deemed to be included in the quoted rate | |||||
| 3.00 | Supply, jointing, fixing or passing through pipe, trenches or ducts, commissioning and testing XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armored, electric power cables (Heavy duty) with the aluminum conductor, 11000 Volts grade, cross-sectional area 95 Sqmm, 3 core, suitable for 11 KV earthed system confirming to IS 7098 Part-2 for insulation and for conductors Class 2 to IS 8130-84, in trenches, floors, ducts passing through pipe for road crossing etc, including connecting & testing complete all as specified and directed. (From CCR Substation VCB to proposed RMU in CSS) | 1,180 | RM | 1,180 ₹13,92,400 Lowest | 1,200 ₹14,16,000 |
| 4.00 | All as per above Item No 3 but 3 core 240 Sqmm complete all as directed. (From proposed RMU panel incoming to Existing VCB Panel) | 20 | RM | 2,800 ₹56,000 | 2,000 ₹40,000 Lowest |
| 5.00 | Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc., or shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and getting out complete all as specified in any type soil | 409 | Cum | 150 ₹61,350 | 92 ₹37,628 Lowest |
| 6.00 | Returning, filling in, including spreading, levelling watering and well ramming in layers n.exc 25cm in soft/loose soil etc complete as specified and directed. | 358 | Cum | 70 ₹25,060 | 50 ₹17,900 Lowest |
| 7.00 | Removing of surplus excavated soil not exceeding 50 M distance and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed. | 51 | Cum | 80 ₹4,080 | 50 ₹2,550 Lowest |
Tender Value
₹87.6 L
EMD Value
₹1.6 L
Closing Date
3 Mar 2026, 6:00 pmClosed
CWE AF Gwalior
HQ CWE AF Gwalior
PROVN OF DEDICATED POWER SUPPLY TO PAR RADAR AND IMPROVEMENT TO ELECTRIC INFRASTRUCTURE AT TECH SITE FOR SRE RADAR AT AF STN GWALIOR
2025_MES_734153_3
86034
Open Tender
Civil Works
Item Rate
180 days
GE AF Tech Area
As per NIT and tender documents
9 documents required · 9 mandatory
₹1,000
GE AF Tech Area
₹1.6 L
Yes
7 May 2026
17 Feb 2026
10 Mar 2026
17 Feb 2026
3 Mar 2026
24 Feb 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, Installation, testing and commissioning Outdoor Type Compact Sub- Station (CSS) having 11 KV, 630A VCB, 63 KVA Copper Wound Off-Circuit Transformer & LT Side comprising of the following below mentioned accessories complete all as specified and as directed:-
(a) HT Section :- 01 No 11kV, 630A, RMU with one incoming and one outgoing with Horizontal Draw Out VCB -02 Nos and Manual/230V AC Motor Operated Spring Charging Mechanism with 24V DC Closing /Opening Shunt trip coils, Aux. Switch, Mechanical On/Off Push Button, mechanical Operating Counter with metering 1 No CT, PT, IDMT, Cubical Auxiliary Relay, 8 Window Annunciator Model No. SI-801, Battery Power Pack with 7AH Battery & in built charger for 24V Circuit.
(b) Transformer Section :- 63 KVA, 11/0.433 KV, Dry type Copper Wound Step Down “BIS Marked & BEE Star Labelled” Transformer having 7 position Off-Circuit tap changer with tapping range +7.5% in steps of 2.5% each with all standard fittings & accessories including WTI 1 No & Marshalling Box. as per IS-1180:2014 EEL- 3 with amendment no.- 4 Losses @50% Load – 270W, Losses @100% Load - 956W
c) LT Section :- LT Panel comprising of LV Side Incomer – 01 No. 125 Amp 4 Pole 25KA MCCB with thermal magnetic based release with O/L & S/C Protection.- RYB Indication, Digital Ammeter for each outgoing, Digital voltmeter in incoming, surge protection device with proper control wiring. | 1 | Each Job | - | - |
| 1.01 | Outgoings for Distribution Network
MCCB 100 Amps, 16 KA 415V 4 Pole with thermal magnetic based release with O/L & S/C protection. -01 No.(O/G) for PAR Panel
03 set LED phase indicating lamp with 2A SP MCB.
03 set 63/5A Class-1, CT
01 set 0-63A Digital Multifunction meter
Capacitor Panel (30 KVAR)
30 KVAR APFC Panel with MCCB, APFC relay & Capacitors bank with Suitable Switchgear
Incomer
1 no. 63A 415V TP MCCB, 25KA with thermal magnetic based release with O/L & S/C protection.
1 Set ON/OFF/TRIP indicating lamps (LED).
1 Set ON/OFF push buttons.
1 Set LED phase indicating lamps with 2A SP MCB.
2 set 63/5A Class-1 CT
1 No. 0-500 V Digital voltmeter
1 Set 0-63A Digital ammeter
1 No. APFC relay
Bus Bars-40 x 10 mm copper bus bar for 3 phase and neutral duly colour coded insulation.
Outgoing
6 nos. 20 A, 3P MCB with capacitor duty contactor, ON/OFF push buttons and LED indicating lamps.
1 no. 20 A, 3P MCB without capacitor duty contactor, ON/OFF push buttons and LED indicating lamps.
6 set 05 KVAR capacitor banks
(i) MS Steel Sheet enclosure suitable for Outdoor Installation with MS channels (Base) - 01 Set
(ii) Provision for receiving Incoming and Outgoing cables through Bottom entry, excluding Termination Kit and Glands - 01 Set | - | - | - | - |
| 2 | Supply, installation, testing & commissioning of 12kV, 630A, 21kA/3sec, non extensible type, Motorised, Outdoor Type IP-64, SF6 Gas Insulated Ring Main Unit with Three (3) Vacuum Circuit Breakers (VCB) (01 Nos Incomer + 02 Nos Outgoing) with Air Insulated Bus PT Panel 11 KV, inside robotically welded stainless steel (Non Ferrite Non Magnetic Grade) tank having minimum thickness 2.5 mm having IP 43 Degree of Protection. RMU should be provided with Copper bus Bar, Resin cast ring core protection CT on cables 150/5-5 Amp, Core I (5P10, 15 VA class 1.0) and core II (13 VA, Cl 5P10) - 01 Sets for incoming and Resin cast ring core protection CT on cables 100/5-5 Amp, Core I (5P10, 15 VA class 1.0) and core II (13 VA, Cl 5P10) - 01 Sets for outgoing - 1, Resin cast ring core protection CT on cables 50-25/5-5 Amp, Core I (5P10, 15 VA class 1.0) and core II (13 VA, Cl 5P10) - 01 Sets for outgoing - 2, padlock provision and complete with all accessories. The RMU Shall be type tested for internal arc test of 20 kA/0.1 Sec as per IEC 62271-200 for both tank and cable compartment. The unit shall include the all necessary standards fittings as required at site required or as specified and directed by OEM/ Engr-in-charge.
Note :- Detail specifications and standard fittings and accessories are specified below.
RMU Construction:
The switchgear and busbar shall all be contained in a stainless steel enclosure filled with SF6 at 0.3 bar (300 kPa) relative pressure to ensure the insulation and breaking functions. Sealed for life, the enclosure shall meet the "sealed pressure system" criterion in accordance with the IEC 62271-1 standard (§ 3.6.5.4): "a volume for which no further gas processing is required during its entire expected life”. In addition, manufacturer shall confirm that maximum leakage rate is lower than 0,1 % / year. It shall provide full insulation, making the switchgear insensitive to the environment (temporary flooding, high humidity...), IP67 degrees of protection in accordance with recommendation IEC 60529 § 14.2.7. Thus assembled, the active parts of the switchgear shall be maintenance-free and the switchboard shall be low-maintenance. The switchboards drives shall have an IP2X protection index. The tank shall be made of at least 2mm unpainted stainless steel. SF6 gas is the preferred dielectric medium for MV RMUs. Oil filled switchgear will not be considered. SF6 gas used for the filling of the RMU shall be in accordance with IEC 60376.Any accidental overpressure inside the sealed chamber will be limited by the opening of a pressure limiting device in the lower part of the enclosure. Gas will be released to the rear or the bottom of the switchboard away from the operator. Number of mechanical operations of Circuit breaker 2000 O/C , Number of electrical operations at full loop current for CB: 2000 O/C,. Manufacturer shall provide type test report to prove compliance with IEC 62271-200 Annex A, Internal arc classification class AFL with 21kA 1s for the SF6 enclosure. Make of the RMU, vaccum intrtupter , relay & meter shall be of same OEM. All the test certificate shall be in the name of the OEM only . | 1 | Each JOB | - | - |
| 2.01 | (a) 3 No. 630 Amp motorised vacuum circuit breaker, tripple pole, single break 3 position as incomer (On, Off and earth having STC capacity 20 KA for 3 seconds with copper bus bar and copper earth bar fitted with fixed type voltage indicator device as per IEC 61958-1, fully rated with earth switch, spring assisted mechanism, Red/Green Push Button for On/Off Operation, Arc proof hinged type cable cover interlocked with Earth Switch, Air insulated cable boxes and boots suitable for bottom entry front termination of 3 core cable 95/120/185 Sqmm.
(b) 3O/C + 1E/F self powered relay with Low and High set for Over current and Earth Fault. Relay should have LCD ( 16 x 2). Relay should have facility to trip the breaker from remote commands without shunt trip coil, Last 5 Fault Record with Time stamp, battery pack replaceable from front, One No Master trip relay, Announciator panel etc
(c) Transformer, VCB should be provided with protection scheme for transformer faults like OTI, WTI & Buchholz's relay alaram & trip, along with annunciation and lock-out function
(d) Bus Connected PT Unit -1 No. for Metering consisting of following:-
(i) Type M: Air Insulated metering module 12KV, 630A, 20KA for 3sec.
(ii) 3 Voltage Transformers of the ratio 11kV/√3 / 110 V/√3, 25 VA, Class 1.0 with HT fuses on primary side and MCB on secondary side.
(iii) 1 Digital MFM to measure Amps, Volts, Frequency, PF, KWH, KVAR.
(iv) 1 CFL Illumination.
(v) 1 Space Heater with thermostat.
(vi) 1 RYB phase indications.
(vi) 1 set Bushings for external busbar connection along with Busbar cover & Sleeved busbars for coupling.
(vii) 2X12 V Battery with battery charger with suitable burden for motor operation. Input 230 V AC & Output 24 V DC. Battery make: EXIDE/HBL/Eqiv. | - | - | - | - |
| 2.02 | (e)Programmable Logic Controller for Auto changeover scheme between two incomers shall comprise of following features :-
(i) PLC Scheme (Incorporating Basic Auto & Manual feature for by-passing changeover scheme) for Auto Changeover - 1 Set
(ii) Two Sets of Remote Control Kits for Motorised Isolator Operation
(iii) One No. PLC Having Communication Ports for future integration with SCADA on MODBUS.
(iv) One Factory Programmable Logic - Of - Operation permanentaly stored in PLC as per manufacturers instructions for autochangeover of feeders all as directed by GE, MES and programmable at site
(v) Two Sets of Signal Convertors for PLC Operation.
(vi)Safety Interlocks Shall be provided as per relevant IEC/IS Standards and Manufacturers directions.
(vii)The Autochangeover of feeders shall be in minimum time not exceeding 10 to 15 seconds.
(viii)LED based Capacitive voltage indication fixed type VPIS 9-15 kV
(ix)Necessay interclocking arrangement for safety and operations
(x)LBS shall be of ratings 12 KV, 630 A, 20 KA for 3 Sec.
(xi) One No. Operationg Handle for Manual Operation.
(xii) One No. Manometer.
(f) Safety Interlocks Shall be provided as per relevant IEC/IS Standards and Manufacturers directions.
(g) Above switchgear shall confirm to all relevant IEC/IS Standards.
(h) Manual operation of Breaker should be possible without dismantling the motor from RMU. The motor should be fitted in such a way that it should not be outside front covers of RMU.
(j) Coupling of RMU and Metering module should be with the help of Bolted type arrangement, so that the coupling at site shall be easy. Plug-in type bushing shall not be acceptable.
(k) The Cable termination of RMU should be front accessible only. And minimum 3 module should accommodate in one tank to avoid multiple coupling at site.
(l) PCC 1:2:4. type B1 using 20 mm graded aggregate for foundation of RMU as per recommendations of manufacturers or directed by EIC.
(m) Two copper earthing for RMU shall be provided with copper strip and earth test point (wiil be mesured and paid separatley under Item no 14).
Note :- 1. Any other parts/items not specified above but have been considered essential for smooth and safe functioning of the RMU system shall be included in the items and are covered against the quoted rate.
2. The cost of taking down the HT connections from the existing VCB and refixing at RMU panel with in the same Substation is deemed to be included in the quoted rate | - | - | - | - |
| 3 | Supply, jointing, fixing or passing through pipe, trenches or ducts, commissioning and testing XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armored, electric power cables (Heavy duty) with the aluminum conductor, 11000 Volts grade, cross-sectional area 95 Sqmm, 3 core, suitable for 11 KV earthed system confirming to IS 7098 Part-2 for insulation and for conductors Class 2 to IS 8130-84, in trenches, floors, ducts passing through pipe for road crossing etc, including connecting & testing complete all as specified and directed. (From CCR Substation VCB to proposed RMU in CSS) | 1,180 | RM | - | - |
| 4 | All as per above Item No 3 but 3 core 240 Sqmm complete all as directed. (From proposed RMU panel incoming to Existing VCB Panel) | 20 | RM | - | - |
| 5 | Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc., or shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and getting out complete all as specified in any type soil | 409 | Cum | - | - |
| 6 | Returning, filling in, including spreading, levelling watering and well ramming in layers n.exc 25cm in soft/loose soil etc complete as specified and directed. | 358 | Cum | - | - |
| 7 | Removing of surplus excavated soil not exceeding 50 M distance and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed. | 51 | Cum | - | - |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.47 MB
Tender86034.pdf
Tender Documents • 1.15 MB
BOQ_843553.xls
BOQ • 0.37 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .