| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹87.5 LAdmitted-Finance | L1 | Admitted-Finance | |
| 2 | L2₹93.5 L+₹6.0 L (6.87%)Admitted-Finance | L2 | Admitted-Finance | |
| 3 | L3₹95.4 L+₹7.9 L (9.06%)Admitted-Finance | L3 | Admitted-Finance | |
| 4 | Not Admitted-Fee/PreQual/Technical | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification | |
| 5 | Not Admitted-Fee/PreQual/Technical | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
| Sl No | Description | Qty | Unit | ZOON ENGINEERING TRADERS L1 | FIRE TECHNOS L3 | M/S NISHAT FIRE AND SAFETY SYSTEMS L2 |
|---|---|---|---|---|---|---|
| 1.01 | Supply, installation, testing & commissioning of Single headed, gunmetal ISI marked oblique pattern hydrant landing valve with 80 mm dia flanged inlet and 63 mm dia instantaneous type female outlet complete with plastic cap and GI chain, twist release type plug and all accessories as per IS:5290-1983 (Type 'A'). | 16 | No. | 8,500 ₹1,36,000 | 6,800 ₹1,08,800 Lowest | 10,000 ₹1,60,000 |
| 1.02 | Supply, installation of 75/100 mm thick Insulation and 0.6-0.7 mm Al cladding, Material: Closed-cell crosslinked polyolefin foam with alupet foil & self-adhesive backing, density: 25kg/m³ for external yard hydrants complete with Glue and vapour retardant. | 8 | No. | 1,500 ₹12,000 Lowest | 5,000 ₹40,000 | 4,000 ₹32,000 |
| 1.03 | Supply, installation, testing & commissioning of First-Aid fire hose reels wall mounting swinging type, fitted with of heavy duty mild steel construction with CI brackets, 25 mm dia. ball valve and 20 mm dia. x 36m long high pressure Hose Reel tubing as per IS:444 with Stainless Steel shut-off nozzle having 5 mm dia. orifice. The hose reel shall strictly confirm to IS:884-1985. | 8 | No. | 8,000 ₹64,000 Lowest | 9,500 ₹76,000 | 11,500 ₹92,000 |
| 1.04 | Providing and fixing 63mm dia 15m long non percolated rubberized fabric lined hose including gunmetal male and female instantaneous type coupling approved by fire authority, machine wound with copper wire complete in all respects, hose shall conform to IS:636 type II and coupling to IS:903-1975 (ISI marked) | 32 | No. | 6,000 ₹1,92,000 | 5,200 ₹1,66,400 Lowest | 6,200 ₹1,98,400 |
| 1.05 | Providing and placing in proper position gunmetal 63mm dia short size branch pipes with 20 mm dia nozzles with 63mm instantaneous coupling ISI marked (IS:903). | 16 | No. | 3,000 ₹48,000 | 2,800 ₹44,800 Lowest | 2,800 ₹44,800 Lowest |
| 1.06 | Providing and fixing standard fireman's axe with heavy insulated rubber handle conforming to IS: 926 complete. | 8 | No. | 600 ₹4,800 Lowest | 750 ₹6,000 | 1,300 ₹10,400 |
| 1.07 | Providing and fixing fully glazed MS fully welded construction double leaf door shutter for fire hydrant station fabricated from MS 50x50x6 mm angle iron frame, fixed to wall and hinged MS 40x40x5 mm angle iron door shutter with required MS sash bars for glazing complete with locking arrangements, stove enamelled fire red finish with 'FIRE HYDRANT' written in front. Approximate size 2100x1200 mm. | 8 | No. | 10,000 ₹80,000 Lowest | 27,000 ₹2,16,000 | 17,000 ₹1,36,000 |
| 1.08 | Providing and fixing Weather proof hose cabinets for yard hydrant fabricated from 16 g MS sheet with full glass door and locking arrangement, suitable to accommodate one hydrant valve, 2 nos.15m long hose, 1 No branch pipe and one fireman's axe. The cabinet shall be painted with one coat of primer and finished stove enamelled "Fire Red", "Fire Hose" written on front including suitably mounted on a raised masonry platform as required. (Approx 0.75m x0.6 mx 0.25 m). | 8 | No. | 4,000 ₹32,000 Lowest | 5,200 ₹41,600 | 6,200 ₹49,600 |
| 1.09 | Providing and fixing 4 way gunmetal fire brigade inlet breaching head as per IS:904 specification tested for 20Kg/sq-cm with 63mm dia instantaneous type inlet and 150/100mm dia flanged outlet with built in check valve for fire brigade connection to under ground tanks and fire risers including companion flanges including nuts, bolts & washers etc. | 1 | No. | 10,000 ₹10,000 Lowest | 11,500 ₹11,500 | 16,000 ₹16,000 |
| 1.10 | Supply, installation, testing & commissioning of Gun Metal Fire brigade suction hose coupling (Draw-out Connection) with nut for female coupling as per IS:902-1974 complete with 100 mm dia. GI suction pipe and 100 mm dia. 1 No. CI foot valve flanged (to be connected to static water tank). | 1 | No. | 8,000 ₹8,000 | 5,800 ₹5,800 Lowest | 12,000 ₹12,000 |
Tender Value
₹1.1 Cr
EMD Value
₹2.2 L
Closing Date
16 Jul 2024, 4:00 pmClosed
Executive Engineer PWD(RnB) Mech SK Anantnag
Executive Engineer PWD(RnB) Mechanical South Kashmir Anantnag
Supply, Installation, Testing and commissioning of Fire Fighting and Fire Alarm System (including Sprinkler System) for 50 Bedded Sub District Hospital at Pahalgam, Anantnag South Kashmir.
2024_PWDJK_250209_1
eNIT 01 of 2024-25
Open Tender
Civil Works - Others
Item Rate
120 days
Pahalgam
Please refer Tender documents.
2 documents required · 2 mandatory
₹2,500
Executive Engieer PWD (RnB) Mech Division SK Ang
₹2.2 L
13 Aug 2024
15 Jun 2024
17 Jul 2024
15 Jun 2024
16 Jul 2024
15 Jun 2024
Amount
Supply, installation, testing & commissioning of Single headed, gunmetal ISI marked oblique pattern hydrant landing valve with 80 mm dia flanged inlet and 63 mm dia instantaneous type female outlet complete with plastic cap and GI chain, twist release type plug and all accessories as per IS:5290-1983 (Type 'A').
Supply, installation of 75/100 mm thick Insulation and 0.6-0.7 mm Al cladding, Material: Closed-cell crosslinked polyolefin foam with alupet foil & self-adhesive backing, density: 25kg/m³ for external yard hydrants complete with Glue and vapour retardant.
Supply, installation, testing & commissioning of First-Aid fire hose reels wall mounting swinging type, fitted with of heavy duty mild steel construction with CI brackets, 25 mm dia. ball valve and 20 mm dia. x 36m long high pressure Hose Reel tubing as per IS:444 with Stainless Steel shut-off nozzle having 5 mm dia. orifice. The hose reel shall strictly confirm to IS:884-1985.
Providing and fixing 63mm dia 15m long non percolated rubberized fabric lined hose including gunmetal male and female instantaneous type coupling approved by fire authority, machine wound with copper wire complete in all respects, hose shall conform to IS:636 type II and coupling to IS:903-1975 (ISI marked)
Providing and placing in proper position gunmetal 63mm dia short size branch pipes with 20 mm dia nozzles with 63mm instantaneous coupling ISI marked (IS:903).
Providing and fixing standard fireman's axe with heavy insulated rubber handle conforming to IS: 926 complete.
Providing and fixing fully glazed MS fully welded construction double leaf door shutter for fire hydrant station fabricated from MS 50x50x6 mm angle iron frame, fixed to wall and hinged MS 40x40x5 mm angle iron door shutter with required MS sash bars for glazing complete with locking arrangements, stove enamelled fire red finish with 'FIRE HYDRANT' written in front. Approximate size 2100x1200 mm.
Providing and fixing Weather proof hose cabinets for yard hydrant fabricated from 16 g MS sheet with full glass door and locking arrangement, suitable to accommodate one hydrant valve, 2 nos.15m long hose, 1 No branch pipe and one fireman's axe. The cabinet shall be painted with one coat of primer and finished stove enamelled "Fire Red", "Fire Hose" written on front including suitably mounted on a raised masonry platform as required. (Approx 0.75m x0.6 mx 0.25 m).
Providing and fixing 4 way gunmetal fire brigade inlet breaching head as per IS:904 specification tested for 20Kg/sq-cm with 63mm dia instantaneous type inlet and 150/100mm dia flanged outlet with built in check valve for fire brigade connection to under ground tanks and fire risers including companion flanges including nuts, bolts & washers etc.
Supply, installation, testing & commissioning of Gun Metal Fire brigade suction hose coupling (Draw-out Connection) with nut for female coupling as per IS:902-1974 complete with 100 mm dia. GI suction pipe and 100 mm dia. 1 No. CI foot valve flanged (to be connected to static water tank).
Providing and fixing MS cabinet (to enclose above Draw-out/Fire brigade inlet connections) fabricated from 16g sheet with full front glass door and locking arrangement duly painted with one coat of primer and two or more coats of synthetic enamel paint of approved make and shade and suitably mounted on a raised masonry platform as required (Approx.0.6 m x 0.6 m x 0.45 m).
Supply, installation, testing & commissioning of pressure gauges with isolation cocks and chrome plated copper pipes as hydrant station to read pressure from 0-25 kg/cm2 complete and of dial dia 150 mm
Supply, installation, testing & commissioning of air cushion tank (air-vessel) 250 mm dia.x1.0 m high with dished top, made of minimum 6 mm thick MS pipe/plate complete with 25 mm dia. brass air valve (ball valve, pressure gauge type), 25 mm dia brass stop cock, nipple, tees, B46 elbow, pipe and all accessories as required including fixing brackets.
Internal piping Supply, installation, testing & commissioning of Black steel pipe (IS:1239 Part-I) heavy C-class including cutting, threading, welding etc. bends, elbows reducers, clamps, hangers etc. including cutting holes in brick or RCC walls/slabs and making good the same complete including the cost of structural work for supports fabricated from standard sections of required sizes and thickness e.g. MS rods, angles channels, slotted angle, etc., cutting to sizes, drilling welding fixing to insert plates, including painting with one coat of primer and two or more coats of synthetic enamel paint of approved make and red shade including all steel work. a)150 mm dia
100 mm dia
80 mm dia
65 mm dia
50 mm dia
40 mm dia
32 mm dia
25 mm dia
External Piping Supply, installation, testing & commissioning of mild steel black pipe (IS:1239/IS:3895) heavy C-class including cutting, screwing, welding etc. complete with fitting viz. tees elbow, bends, flanges, reducers etc. including providing anti-corrosive treatment (coating and wrapping) with 4 mm thick tape and holiday test check as per IS:10221 complete as required. A) 150 mm dia
B)100 mm dia
C)80 mm dia
Excavating trenches of required width for pipes, cables etc. including excavation for sockets and dressing of sides, ramming of bottom depth upto 900 mm including getting out the excavated soil rubble soling, sand filling upto 3" above the pipe and then returning the soil as required in layers not exceeding 20 cms in depth including filling fine sand alround, consolidating each deposited layer by ramming, watering etc. and disposing of surplus excavated soil as directed, in all soils. Pipes, cables etc. exceeding 80 mm dia but not exceeding 300 mm dia
Providing and laying cement concrete 1 : 3 : 6 (1 cement : 3 coarse sand : 6 graded stone aggregate of nominal size 40 mm in thrust blocks at bends, tees etc and alsos as support to vertical pipes of yard hydrants including excavation and refilling of earth work centering and shuttering for concrete complete in all respects.
Automatic Sprinkler System Supply, Installation, Testing & Commissioning of 15 mm dia. quartzoid bulb type GM Sprinkler head (K-5.6) suitable to operate at 68 degre C Standard Pendent/Upright type in brass/chrome finish.
Supply, installation, testing & commissioning of 25mm dia automatic air release valves sprinkler ring main as per standard fire practice.
Supply, installation, testing & commissioning of hydraulically Operated Alarm Check Valve 150mm dia with water alarm gong and complete with necessary fittings & supports
Providing, fixing, testing and commissiong of electrically operated flow indicating switches with threaded connection for a minimum flow of 90 lpm for indicating water flow in sprinkler branch line on each floor with necessary junction box installed in accessible place on 150/100 mm Line
Supply, installation, testing & commissioning of installation zonal control valve assembly comprising of vertical wet alarm valve, including the cost of butterfly valve, hydraulic alarm motor & gong, 15 mm dia. test valve, 50 mm dia. drain valve and all necessary trimming connections including 2 nos. pressure gauges as per manufacturer's catalogue to be installed in each floor.
Supply, installation, testing & commissioning of 25 mm dia inspecting & testing assembly with gunmetal isolation valve, gunmetal sight glass, bypass valve & connected to drain line complete (excluding the cost of drain pipe).
Supply, installation, testing & commissioning of gun metal ball valve 50mm dia for flushing connection.
Supply, installation, testing & commissioning of gun metal ball valve 25mm dia.
FIRE PUMPS, VALVES & ACCESSORIES Supply, Installation, Testing & Commitioning of Electrical Motor Driven Fire Pumping set (Factory Fitted) suitable for automatic operation consisting of the following as per the specifications. Providing and fixing horizontal End Suction multi stage, single outlet factory fitted pumping set with bronze impeller with gland capable of delivering 2280 LPM against a total head of 70 M with CI body and connected by a flexible coupling to a totally enclosed fan cooled induction motor mounted on a common structural baseplates with all pump accessories complete as per specifications including pressure gauge with gunmetal isolation valves and anti vibration pump, motor to be suitable for 415 volts, 3 phase, 50cycles A.C. supply ( specification as per fire fighting requirements and on the pattern of TAC OR LOCAL AUTHORITY APPROVAL) as per instruction of following specifications: b) Squirrel cage induction motor totally enclosed fan cooled type suitable for 415 volts ±15%, 3 phase, 50 Hz AC supply of suitable capacity for the above pump coupled with flexible coupling including earthing as per relevant Indian standard & specifications. c) Common bed plate for mounting pump and motor fabricated from suitable MS Channel as per manufacturer's recommendations. ) Suitable RCC pump-foundations as per manufacturer's design and 4 nos. dunlop (cushy foot) heavy duty antivibration mounting pads.
Supply, Installation, Testing & Commitioning. Of Diesel Engine Driven Fire Pumping set (Factory Fitted) suitable for automatic operation consisting of the following as per specifications: Providing and fixing horizontal split casing multi stage, single outlet pumping set with CI body and bronze impeller & with gland capable of delivering 2280 LPM against a total head of 70 M connected by means of a flexible coupling to a water cooled diesel engine mounted on a common structural base plate with antivibration pads and and foundation complete with electric panel, battery (including one spare battery), utomatic starting arrangement exhaust pipe of required length to discharge outside building with muffer, day oil tank mounted on suitaible structural supports complete in all respects as per specifications ready for use and as per latest requirement of fire autority regularities. b) Water cooled TAC approved Diesel Engine suitable for developing at least 90 BHP (Duty point) at 2000 RPM) compatible for above pump complete with automatic starting mechanism, batteries, automatic battery charger unit, flexible coupling with the pump, fuel tank, silencer, exhaust pipe with insulation approx. 25m length & all standard accessories as required as per TAC rules including earthing, mandatory spares and tool kit. c) Common bed plate for mounting pump and engine fabricated from suitable MS Channel as per manufacturer's recommendations. d) Suitable RCC pump foundations as per manufacturer's design 8 Nos Dunlop Anti-vibration (cushy foot) heavy duty mounting pads.
Supply, Installation, Testing & Commitioning. of Electrical Motor Driven Automatic pressurisation (Jockey) pumping set (Factory Fitted) consisting of the following as per specifications. Providing and fixing horizontal split casing single/multi stage, single outlet pumping set with bronze impeller & with gland capable of delivering 180 LPM against a total head of 70 M with C.I. body and connected by a flexible coupling to a totally enclosed fan cooled induction motor mounted on a common structural baseplates with all pump accessories complete as per specifications including pressure gauge with gunmetal isolation valves and anti vibration pump, motor to be suitable for 415 volts, 3 phase, 50cycles AC supply (specification as per fire fighting requirements and on the pattern of TAC OR LOCAL AUTHORITY APPROVAL) as per instruction of following specifications: b) Squirrel cage induction motor totally enclosed fan cooled type suitable for 415 volts ±15% 3 phase 50 Hz AC supply of suitable capacity (approx. 10 KW) for the above pump with synchronous speed of 1500/3000 RPM confirming to IS:325 & duly coupled with above pump coupled with flexible coupling including earthling as per relevant Indian Standard and specifications. c) Common bed plate for mounting pump and motor fabricated of suitable MS channel as per manufacturer's recommendations. d) Suitable RCC Pump foundations as per manufacturer's design 4 Nos Dunlop Anti-vibration (cushy foot) heavy duty mounting pads.
Providing, fixing, testing and commissiong of double flanged vertical air vessel fabricated from 10mm MS plate with dished ends from 10mm MS plate, outside with one coat of primer and two coats of synthetic enamel paint of approved shade, complete with approved quality of pressure switches, pressure gauge and all other required accessories to operate commonly main fire pump, sprinkler pump and Jockey pump at drop of pressure, automatically at required pressure setting Recommended dia. : 450mm Height of shell : 2000mm Working pressure : 5.5 kg/cm2 Test Pressure : 10 kg/cm2
Providing, fitting of total 20,000 ltr (5000 ltr x 4 No.) terrace HDPE tank with necessary connections to the Terrace pump Capacity.
Providing and fixing resilient rubber neoprene lined single arch vibration eliminators suitable for raw water upto 450C temperature working pressure 5.5 kg/cm2 and test pressure 10.0 kg/cm2 with unit control including nuts, bolts matching flanges (screwed or welded) complete with 1.5mm thick compressed asbestos gasket of same rating. Suitable for nominal bore for Jockey Pump
150 mm dia
Providing and fixing CI double flanges Y suction strainer (PN 2.0) “Y” type including, nuts, bolts matching flanges (screwed or welded) complete with 1.5mm thick compressed asbestos gasket of same rating . Suitable for nominal bore for Jockey Pump
150mm dia
Providing and fixing butterfly valves, wafer end type class PN 1.6 as per IS: 13095-1991 or BS: 5155, including necessary nuts, bolts, gaskets etc. complete (without gear box) & matching flanges (screwed or welded) complete with 1.5mm thick compressed asbestos gasket of same rating . 50mm dia nominal bore.
65mm dia nominal bore.
80mm dia nominal bore.
100mm dia nominal bore.
150mm dia nominal bore.
Providing and fixing CI double flanged horizontal/ vertical type non-return valve including nuts, bolts,matching flanges (screwed or welded) complete with 1.5mm thick compressed asbestos gasket of same rating, complete to IS:5312, part-I, swing type, class PN 1.6. a)Suitable for nominal bore for Jockey Pump
b)150mm dia nominal bore.
Providing and fixing of sluice valve of 1.6 PN rating flanged at both ends of following sizes including necessary nuts, bolts, gaskets etc. complete (without gear box) 150mm dia nominal bore.
Providing earthing station with GI Earthing Plate (600mm x 600mm) 8 mm thick for pumps and MCC panels including excavation, CI manhole cover and frame complete as per specifications and IE rules.
GI Strip of following sizes 25 x 6 mm G
Providing and fixing pressure switch (for operation at 0-25 kg/cm2) with required fittings and accessories complete.
Structural Steel like angles, channels etc at various locations for supporting Tanks, Valves etc
Providing and fixing liquid level controller for fire pump to cut off in case low level of water in tank including cables, pannel etc. and making necessary connection to panel and commissioning.
P/F of electrical cables from main control panel to outdoor units as per sizes given. A)4 Core x 185 Sq mm AL Cable
B)3 Core x 95 Sq mm Copper Cable
C)3 Core x 16 Sq mm Copper Cable
500mm width x 50mm depth x 2mm thick perforted M.S. cable trays including horizontal and vertical bends, reducers, tees, cross members and other accessories as required and duly suspended from the ceiling with M.S suspenders and including painting etc. as reqd.
Providing and Fixing of ISI marked (IS:15683:2006) protable CO2 type fire extinguisher type 4.5 kg capacity, including valve, discharge hose of not less than 10 mm dia and 1 metre long complete in all respects including initiall filled CO2 gas confirming to IS : 307 - 1966 & filled to a filling rate of not more than .667 and wall suspension bracket.
Providing and Fixing of ISI marked (IS:15683:2006) protable ABC type portable extinguisher of capacity 4 kg , dry powder type (Gas Cartridge) confirming to IS: 15683 : 2006 with cylinder initially fully charged with dry powder, ISI marked confirming to IS: 15683 : 2006 complete with stsndard discharge valve with tube , CI bracket for wall mounting.
Providing and fixing of fire bucket stands for 6 No Buckets at designated locations
Providing and fixing of fire buckets of 9 Litre capacity to the stands
Supply and fixing of illuminated Fire exit signages. This sign may be used to Indicate all exits which can be used in the event of an emergency. It shall be accompanied: by an arrow as per IS-12349(1988) standards
Fire Alarm Detection System Supply,Installation,Testing and Commissioning of microprocessor based 4 loop (Expendable upto 8 loop or above) capacity networkable analogue addressable type fire alarm panel central processing unit with the loop length upto 2 km,network communication card minimum 320 character graphic/ LCD display with touch screen or keypad and minimum 4000 event history log in the non-volatile memory (EPROM) power supply unit(230±V, 50 Hz) 48 hrs backup with 24 volt sealed maintinance free batteries with automatic charger. The panel shall have facility to connect printer to print out the log and evacuation system (which is part of schudule under SH: PA system0 and shall be compatable with all accessories. The panel shall be compitable for IBMS system with open protocol BACnet/Modbus over IP complete as per specifications.
SITC of Active Repeater panel 7" Color LCD touch screen display with bright colors to indicate alarms and events to be connected peer to peer with Main Fire Alarm panel. Accept, Reset functions shall be possible from the repeater panel. The user interface of Repeater Panel shall be identical to the Fire alarm Panel. All other specification shall remain unchanged like FACP. EN54-VDS/UL-FM Certification
Supply, Installation, Testing and Commissioning of addressable multisensor smoke detector including mounting base with LED… etc. complete as required with 2 inbuilt Isolators as per NFPA 72 style 7 wiring requirements (one for incoming and one for outgoing line) for maintaining operational availability of all elements in the loop in the event of a short circuit and to meet style 7 requirements; Drift Compensation feature & Automatic addressing. Detector should monitor Electromagnetic interference and report to the panel - current and average values.Detector should have IP40 or better protection rating. EMC safety for detector shall be 50 V/m. Shall be EN54-VDS/UL-FM certification. (Detectors without Inbuilt Isolators may be considered with an additional Isolator Module per detector)
Supply, Installation, Testing and Commissioning of wireless intelligent photo electric (optical) smoke detector with mounting based LED to be intregrated with the main system.
SITC of Addressable analogue type Heat Detectors with combination of fixed type and rate of rise of temperature feature. Detetctor should have inbuilt isolators as per NFPA 72 style 7 wiring requirements and have an option of both soft & hard addressing. Detector should monitor Electromagnetic interference and report to the panel - current and average values. EMC safety for detector shall be 50 V/m. Shall be EN54-VDS/UL-FM certification.(Detectors without Inbuilt Isolators may be considered with an additional Isolator Module per detector) EN54-VDS/UL-FM Certification
P/F of Response indicator for mounting on false ceiling at the entries of the cabin for indicating the operation for detectors in the above areas including Backbox
'SITC of Addessable Manual call point with break glass unit (Double action) with inbuilt isolators as per NFPA 72 style 7 wiring requirements, with flexible network structures & necessary fixing arrangements with key complete as required. Shall be EN 54-VDS/UL-FM Certification.
SITC of Loop Powered Strobe with inbuilt isolators as per NFPA 72 style 7 wiring requirements,with flasher having Synchronized flash rate of 1 Hz and Light intensity > 2 cd, should be programmed from the panel. Shall be EN54-VDS/UL-FM Certification
SITC of Addressable Control Relay Module with inbuilt isolators as per NFPA 72 style 7 wiring requirements .Relay Control module shall be used for emergency control functions including shutting down Fire dampers in AHU's, tripping of AHU's, Fresh air fans, Ventilation fans, tripping of Access control doors etc. Shall be EN54-VDS/UL-FM Certification
SITC of Addressable Monitor Module with Inbuilt isolators for flow switches, Panic Bars & other Third Party Inputs. The monitor module shall monitor potential free contacts or Line monitoring resistors. Shall be EN54-VDS/UL-FM Certification.
Supply,Installation,Testing and Commissioning of following size PVC insulated copper conductor armoured cable XLPE Insulation, Extruded LSZH Inner Sheath, Extruded LSZH (Low smoke zero Halogen) Compound Outer Sheathed Fire Survival Armoured Cable.. The job includes providing and fitting of saddles and hinges as required. a)LSZH- 2 C X 1.5 Sq mm armoured cable
b)LSZH- 4 C X 1.5 Sq mm armoured cable
Supplying and Fixing of Following sizes of PVC Conduit along with Accessories in surface/Recess including painting in case of surface conduit,cutting the wall and making good the same in case of recessed conduit as required. 25mm PVC Conduit
M/S NISHAT FIRE AND SAFETY SYSTEMS
FIRE TECHNOS
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.95 MB
SBDFireFighting.pdf
Additional Documents • 1.68 MB
BOQ_728214.xls
BOQ • 0.39 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .