Electrical work in connection with the work of "Replacement of old FOB by 6.10M wide new FOB with Ramp for recoupment of Divyangjan Facility at Rura (RURA) station of PRYJ Division. Electrical work in connection with the work of "Provision of Ramp at FOB for divyangjan at BPU (Bhaupur) under CNB-TDL section."Electrical work in connection with the work of " Maitha Raising of platform no. 1 & 2 height upto High Level at Maitha station."
ELG-34-2627
ELG-34-2627
Open
6 Months
Auraiya, Uttar Pradesh
₹0
₹1.9 L
3 Jul 2026
3 Jul 2026
13 Jul 2026
Item Breakup - 1-NS Schedule
Supply and recessing/fixing of PVC Conduit pipe Metre 25 mm (Medium) conforming to IS 9537/ Part III/1983 (Latest version) with accessories,junction box, etc including making chase, plastering/ clamping etc as per technical specifications.Inspection by- Consignee. PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
Supply of PVC insulated multi stranded copper Metre conductor single core FRLSH cable 2.5 Sq. mm conforming to IS: 694 (latest version), and drawing in laid (recessed /surface) PVC conduit pipe for wiring of point wiring/ circuit wiring/sub main/ Main as required as per technical specification including connections, testing and commissioning.Inspection by- Consignee.
Supply of PVC insulated multi stranded copper Metre conductor single core FRLSH cable 4.0 Sq. mm conforming to IS: 694(latest version), and drawing in laid (recessed /surface) PVC conduit pipe for wiring of point wiring/ circuit wiring/sub main/ Main as required as per technical specification including connections, testing and commissioning.Inspection by- Consignee.
Supply of PVC insulated multi stranded copper Metre conductor single core FRLSH cable 6.0 Sq. mm conforming to IS: 694 (latest version), and drawing in laid (recessed /surface) PVC conduit pipe for wiring of point wiring/ circuit wiring/sub main/ Main as required as per technical specification including connections, testing and commissioning.Inspection by- Consignee.
Supply of PVC insulated multi stranded copper Metre conductor single core HRFR cable 1.5 Sq. mm conforming to IS: 694 (latest version), and drawing in laid (recessed /surface) PVC conduit pipe for Earth wire as required as per technical specification including connections, testing and commissioning.Inspection by- Consignee.
Supply and Installation of Ceiling rose 3 plate as Numbers 800.00 per IS No. 371/1999 (Latest Version) including connections, Testing and commissioning as per Tech. Specification. Inspection by- Consignee.
Supply and recessing/fixing on surface of 6 SWG Metre GI wire conforming to IS: 280/2006 (Latest Version) for loop earthing as required for earthing of installation as per IE Rule.Inspection by- Consignee.
Supply, installation, testing, connecting and Numbers commissioning of LED base name board of different stations (01 set includes 01 No Hindi, 01 No English & 01 No Urdu name board) with power LEDs, Drivers & wiring of board. The signage board should have alphabet of vertical peak height of 600 mm and proportionate horizontal span. Approximate size of Hindi, English signage panel shall have Length 6400 mm, Height- 912 mm. Note - 01 set includes, a. Hindi board 01 No, b. English board 01 No, c. Urdu board 01 No. Inspection by-RITES.
Supply, Installation, Testing and Commissioning Numbers of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CM/M/W) minimum 6.00, Air delivery minimum 210 Cum/Min , 350 RPM (tolerance as per IS : 374-2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required. Inspection by- Consignee. PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
Termination of LT XLPE cables of various sizes Job (One Job means all 4 cores of cables). Inspection by- Consignee.
Supply and laying of B class, 50 mm dia, GI pipe Metre of for cable riser/road crossing as required and as per relevant technical specification. Inspection by- Consignee.
Collecting, Transporting from SSE/PS/ store to Metre site, laying, testing, and commissioning of above LT cable . Laying direct in ground (Including excavation, sand cushioning, protection brick covering and refilling the trench etc.), direct in RCC/Metal pipes in rod/track crossings and on surface/required in wall/in concrete floor by cutting recessed and finished originally as required as per relevant technical specifications.
Drilling of bituminous road/track and laying Metre charges of cable in road crossing for laying 110 mm dia HDPE pipe through it.
Supply and laying of HDPE Pipes (Upto PN 8.0 Metre Pressure Rating Material Grade: PE 63, Pressure Rating: PN 8.0, Nominal Dia(mm): 110) as per IS- 4984:2016 suitable for HT/LT XLPE cable & as required and as per relevant technical specification. Inspection by- Consignee
Excavation of cable duct by horizontal boring Metre method 1.4 to 2.1 mtr depths from the bottom of sleeper for trench less track crossing and laying of 120 mm outer dia. DWC pipe. The work shall be done as per extent practice and instruction of site engineer. It includes supply of DWC/DHPE pipes conforming to IS : 14930 (Part 2, 2001).( Rex Poly Extrusion or similar make
Design, Manufacturing, Supply, Erection, testing Numbers and commissioning of LT switchgear panel board of 02 mm Tk. Dia pressed CRS steel sheet panel shall be treated for anti corrosion treatment and finished with smoke gray paint as per technicalspecification no. Sr.DEE/G/ALD/Panel- 94/113 Comprising with as under:-........MCCB of 400 A, 36 kA Standard breaking capacity, 415 volt, 3 Phase 4 Pole current rating 400 Amp.
MCCB of 125A, 36 kA Standard breaking Numbers capacity, 415 volt, 3 Phase 4 Pole currentrating 125 Amp.
MCCB of 63A, 36 kA Standard breaking capacity, Numbers 415 volt, 3 Phase 4 Pole current rating 63 Amp.
Supply of Indicator lamps with suitable holder. PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
Supply, commissioning of Outgoing/Feeder Panel Mounted Multi-function Mtrs. with Accuracy Class 1 as per IEC 62053-21 or Class 0.5, 0.5S as per IEC 62053-22.LED Mtrs. Cl 1 with RS485: Mtrs. should have following features built-in LED • Flush mounting 96 x 96 mm • True RMS measurement • Password protection provision for security • Site selectable for 3 Phase 4 wire, 3 Phase 3 wire, 1 Phase, CT Secondary 1A/5A, Universal Auxiliary Supply 80-300 VAC/DC, Input Voltage Measurement 50-500 VAC, 64 samples/ cycle The Mtrs. should be able to read/display following paraMtrs.s Instantaneous ParaMtrs.s (V1, V2, V3, V12, V23, V31, Avg (VLN, VLL), A1, A2, A3, Aavg, F, PF-1, PF-2, PF-3, PF (Avg) W1, W2, W3, W (total) VA1, VA2, VA3, VA (total) Cumulative ParaMtrs.s (Import Wh, Import Vah, Import load hours, Reset (old) Cumulative paraMtrs.s (Import Wh, Import load hours, Communication (RS485 Modus RTU).complete with all accessories.
Fabrication works and insulated Aluminum bus Numbers bars of 800A capacity for phases & 800A capacity for neutral Bus bar shall be suitably insulated with heat shrinkable sleeves/ epoxy coating/insulating tap to withstand the test voltage of 2.5 KV Copper strip for connection outgoing as well as incoming with suitable size be provided. Item no. 16 to 21 Inspection by consignee. PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
Supply, replacement, fixing, testing, connecting Numbers 500.00 and commissioning of energy efficient luminaries complete with all accessries of capacity 18/20 watt, 4 feet length, T8 LED lamps with sutable current control driver circuit ,suitable for surface/recessed mounting.LED Luminaries:-(1) A complete LED lighting unit consisting of a light source and potted driver together with parts of distribute light,to position and protect the light source,and to connect the light source to a branch circuit.The light source itself may be an LED array and LED module, or an LED lamp. (2):- Supplied LED luminaries shall confirm to IS:16101(2012) IS :16106(2012) .Light Source (LED) in the Luminaries should be of make:- (1):- NICHIA/ CREE/OSRAM/ SEOUL/ PHILIPS/LUMILEDS /LEDNIUM. (2):-LEDs to IS: 16105(2012). IS:16108(2012), IEC:62471.1.Input operating voltage :-105-295 V AC. 2:-Normal Voltage-220V AC.3.Driver type: constant current driver with short circuit protection(For tube light). 4.Control of distribution:-Full cut off. 5.Drive component :Industrial grade only .6.Efficiency of driver electronic: > 85% (For tube light).7.Colour temperature:5000-6500K(For tube light). 8.Colour rendering index(CRI):>75(For tube light). 9.Ingress protection :IP-20. 10.Lumen output: >100 lumens/[email protected] drive current(For tube light). 11.Power factor:- >0.90(For tube light). 12.Total hormonics distrotion(THD):-<20% (For tube light). 13. Lamp cover :Acrylic cover which does not result in loss of lumens. 14. Finishing:Power coated /Anodized. 15.Secondry optics:poly corbonate reflector/ poly carbonate lens. 16. Construction of housing: extruded aluminum/CRCA/Pressure die cast aluminum. 17.Mounting :Suitable for surface mounting/recessed mounting. 18. Certificate: Firm to submit LM80(In respect of LED used) & LM79 (In respect of luminare used) test certificate from National/International accredited Laboratory and OEM certificate for complience of BIS/IEC. 19.Warranty:Firm to submit warranty certificate for five year along with the supply.All fittings shall be fitted as surface mounting/recessed mounting with twisted twin flexible cord of minimum size 16/0.2 mm copper conductor as per relevant technical specification. Materials praMtrs.s must remain unchanged during entire warranty period. 1x18/20 watt. Inspection by- Consignee.
Supply, erection, testing and commissioning of Numbers One phase distribution board comprising of one no. 32/40 amps DP MCB with 40 A ELCB/RCCB as incoming and 4 nos. 10 amps SP MCB , 4 nos. 20 A SP MCB as outgoing complete with copper bus bars, neutral link and other accessories housed in CRCA sheet enclosure with double door type. Inspection by- Consignee. PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
Supply, replacement, fixing, testing, connecting Numbers and commissioning of 72 Watt or above LED street lights fittings as per IS:10322. LED Luminaries:-(1) A complete LED lighting unit consisting of a light source and potted driver together with parts of distribute lights,to position and protect the light source,and to connect the light source to a branch circuit. The light source itself may be an LED array and LED module, or an LED lamp.(2):-Supplied LED luminaries shall confirm to IS:16101 (2012) IS :16106(2012). Light Source(LED) in the Luminaries should be of make:- (1):-NICHIA/ CREE/OSRAM/ SEOUL/ PHILIPS/LUMILEDS /LEDNIUM. (2):-LEDs to IS:16105(2012). IS:16108(2012), IEC:62471. Type LED:- High power LED,SMD(Surface Mounting device)/COB(Clip on board). 1.Input operating voltage :-105-295 V AC.2:- Normal Voltage-220V AC,3.Driver type: constant current driver with short circuit protection. 4.LED life:- >50000 burning hours. 5.Depreciation:- 30% max.after 50000 burning hours.6.Control of distribution:-Full cut off. 7.Surge protection:4KV. 8.Drive component :Industrial grade only.9.Efficiency of driver electronic: > 85%.10.Beam angle:>=140 degree along with road and >=80 degree across the road.11.Colour temperature:5000-6500K. 12.Colour rendering index(CRI):>=75. 13.Ingress protection :IP-66.14.Lumen output: >120 lumens/watt.15.Power factor:->0.95. 16.Total harmonics distortion(THD):- <15%.17.Lamp cover :Toughened glass or UV stabilised poly carbonate. 18.Finishing:Power coated/Anodized. 19.Secondry optics:poly carbonate reflector/ poly carbonates lens. 20.Construction of housing: extruded aluminum/ CRCA/Pressure die cast aluminum. 21.Mounting :Suitable for existing pole/ Truss/ Lantern mounted. 22.Certificate:Firm to submit LM 80(In respect of LED used) & LM79 (In respect of luminare used) test certificate from National/ International accredited Laboratory and OEM certificate for compliance of BIS/IEC. 23.Warranty:Firm to submit warranty certificate for five year along with the supply. All fittings shall be fitted with new suitable bend/elbow with clamp and proper nut and bolt and connection with twisted twin flexible cord of minimum size 16/1 mm copper conductor as per relevant technical specification. Material paraMtrs.s must remain unchanged during entire warranty period. Inspection by- Consignee.
Supply and erection of 6 Mtr. Galvanized (as per Numbers BS EN ISO 1461) octagonal pole with base plate 220x220x12mm, top 70mm and bottom 130mm of 3mm thick sheet suitable for maximum wind speed upto 160 Km/Hr. including foundation bolts and foundation with M 20 grade RCC and FE 415 grade reinforcement (450x450x800 mm deep ) (foundation should be as per design approved by pole manufacturer) GI base plate G.I. anchor plate etc.as required including supplying and fixing of double arm hot dipped galvanized bracket suitable for street light fittings and supplying and drawing of 3x2.5Sq.mm FRLS copper conductor single core cable from junction box with two Nos 6/10AMP MCB to luminaire complete including termination with copper lugs as required.Inspection by- Consignee. PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
Supply, erection, testing and commissioning Numbers ofsingle earth electrode of 50 mm. dia 4000mmlong GI pipe class B complete with earth boxwith CI cover hinged to CI frame includingconnection from earth electrode toMDB/SDB/poles/with 8 swg GI wire/strip as perattached drawing. Inspection by-Consignee.
Supply and instalation of 1-phase 5KVA, Numbers 120/96Volt DC input UPS with Battery Bank of 12V, 10 Nos tubular battereies of Okaya or any superior approved make each of 150AH for Emergency Supply of Metring system and sub- station lightings .After completion of the works all materials to be deposited to the concern SSEs stores. Inspection by- RITES.
Supply of heavy duty aluminium stool type Numbers folding ladder having "C" shapes section of size 16"x12" on top suitable for height upto 12 feet complete similar to Sumer make design no. AL- 201/8818 (heavy duty) or equivalent. Inspection by- Consignee
Supply, laying, fixing, testing and commissioning Metre of 10.0 sq mm FRLS, PVC insulated multi stranded copper conductor single core cable 1100 Volts confirming to IS-694 (latest version) of approved make in the existing PVC conduit for wiring of point wiring/circuit wiring/sub main/main as per Tech Spec-I attached, IS & IE rules.Inspection by- Consignee. .
Supply, G.I.perforated type cables trays with perforation not more than 17.5%)including suspending from ceiling with MSangle, rods connection pieces, (L pieces, T pieces, 90/45 degree any other fitting required) G.I. nutbolts, G.I. washers,fasteners etc.complete in all respects required at site andas per PCEE/NR specification at Tech Spec-I. 150 mmwide, 50mm depth 2mm thick with protective cover. Inspection by- Consignee.
Supply, commissioning of storage type water cooler similar to Model SDLX 100, Cooling Capacity-170 litre per hour, 380 or above litre Storage with foundation/platform & cage. Inspection by- Consignee.
Electric Pole cutting (Pole to be deposited in Numbers Consigence's office.)
Supply, fixing, testing and commissioning of wall Numbers mounted LT distribution board made up of steel sheet, phosphatised powder painted complete with neutral link,earth point, Din rail and prewired confirming to IS:13032 & 8623:1991 withfollowing items to be fixed in distribution board, confirming to IS:8828 :1996 orlatest, IE rules and site requirement. 4P, MCCB 125 Amps. 10 kA 'C' series= 01 No.(Incoming) DP RCCB (25, 40 Amps., three nos. each) 10 kA 'C' series = 06 Nos.(Outgoing). Inspection by- Consignee.
Supply, fixing, testing and commissioning of wall Numbers mounted LT distribution board made up of steel sheet, phosphatised powder painted complete with neutral link,earth point, Din rail and prewired confirming to IS:13032 & 8623:1991 with following items to be fixed in distribution board, confirming to IS:8828 :1996 orlatest, IE rules and site requirement. 4P, MCCB 125 Amps. 10 kA 'C' series= 01 No.(Incoming) DP RCCB (40 & 63 Amps., two nos. each) 10 kA 'C' series = 04 Nos.(Outgoing). Inspection by- Consignee. PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
Supply erection, testing & commissioning of Set basic Earthing Kit 1set as per RDSO spec. No RDSO/PE/SPEC /PS/0109(REV.0)-2008, Amendment '1' or latest specification.Inspection by- Consignee.
Supply, fixing, testing and commissioning of wall Numbers mounted/recessed LT Double door 4Way distribution board made up of steel sheet, phosphatised powder painted complete with neutral link, earth point, Din rail and prewired with following items to be fixed in distribution board and site requirement. Inspection by- Consignee.
Supply, fixing, testing and commissioning of wall Numbers mounted/recessed LT Double door 6Way distribution board made up of steel sheet, phosphatised powder painted complete with neutral link, earth point, Din rail and prewired with following items to be fixed in distribution board and site requirement. Inspection by- Consignee.
Provision of Thermal Imager Model Testo 872 Numbers (Testo 3.5" Colour Touchscreen Thermal Imager 76800 Pixel) or similar make. Inspection by- Consignee
Supply, fixing, testing and commissioning of DP Numbers RCBO's 10 (2P, 30 mA) Amp outgoing confirming to IS: 12640-2,IEC-61009-1 or latest. Inspection by-Consignee.
Supply, fixing, testing and commissioning of DP Numbers RCBO's 16 (2P, 30 mA) Amp outgoing confirming to IS: 12640-2,IEC-61009-1 or latest. Inspection by-Consignee.
Supply, fixing, testing and commissioning of DP Numbers RCBO's 20 (2P, 30 mA) Amp outgoing confirming to IS: 12640-2, IEC-61009-1 or latest. Inspection by-Consignee.
Supply, fixing, testing and commissioning of DP Numbers RCBO's 25 (2P, 30 mA) Amp outgoing confirming to IS: 12640-2, IEC-61009-1 or latest. Inspection by-Consignee.
Supply ,of Auto change Over pannel for CLS Numbers 25KVA 150A capacity as per RDSO specification no.TI/SPC/PSI/CLS/0023.Inspection by- Consignee.
Erection ,Testing commissioning of Auto change Numbers Over pannel for CLS 25KVA 150A capacity as per RDSO specification no.TI/SPC/PSI/CLS/0023
Supply of Auto change Over panel for CLS Numbers 10KVA 60A capacity as per RDSO specification no.TI/SPC/PSI/CLS/0023.Inspection by- Consignee.
Erection ,Testing commissioning of Auto change Numbers Over panel for CLS 10KVA 60A/63A capacity as per RDSO specification no.TI/SPC/PSI/CLS/0023
Supply & Erection of LT XLPE Straight through Numbers Joint 1.1 kV ( make- Dension or similar) a) 3.5/4x70-150 Sqmm. Inspection by- Consignee.
Supply & Erection of LT XLPE Straight through Numbers Joint 1.1 kV ( make- Dension or similar) b) 3.5/4x185-240 Sqmm.Inspection by- Consignee. PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
Supply, Installation and commissioning of LT Metre XLPE insulated aerial bunched cable with Termination and connection having associated given accessories LT XLPE insulated aerial bunched cable with bare messenger as per IS:14255-1995 up to the latest ammendments of sizes (3x150+1x120+1x16) sqmm. Inspection by-RITES.
LT Shackle Insulator with Inspection by-Consignee.
Shackle Strip 12''. Inspection by-Consignee.
I-Hook. Inspection by-Consignee.
Dead End clamp. Inspection by-Consignee.
Suspension Clamp. Inspection by-Consignee.
Piericing Connector 90/120 sqmm. Inspection Numbers by-Consignee.
Distribution boxes with accessories. Inspection Numbers by-Consignee.
1x35 sqmm Consignee.
1x16 sqmm Consignee.
Supply, erection and commissioning of steel Numbers tubular pole conforming to IS: 2713/1980 (latest version) complete with base plate, earthing bolt, digging of pit in ground, making foundation as per drawing, erection of pole vertically, earthing, painting as per Technical specification of 11 Meter long - (Designation 410 - SP 54). Inspection by- Consignee.
Supply and erection of stay sets complete with Numbers 19 mm dia 1800 mm long GI stay rod, galvanized anchor plate 300 x 300 x 6 mm, stay insulator, double screwed tighter with 7/3.15 GI stay wire and provision of foundation to take the load on stay wire by 1:3:6 ratio of cement concrete and sand as per relevant technical specification. Inspection by-Consignee. PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
Design, Survey, Proposal with Technical Square Elevation Drawings & 3D layout, Foot Supply,Manufacture, Erection, Installation, testing and Display of wall / hanging / floor /pole mounting type LED illuminated, Modular, Changeable Aluminium extrudedprofile signage / direction board in full/half Parabolic and Elliptical square and multiangle shape and flat, with die molded internal structural brackets (Nylon/SS) andaluminium extruded heat sink. Suitable size end cap PC/ SS304 should be providedwith provision of illuminated Logo. The display sheet shall be of unbreakable 040 translucent polycarbonate sheet of 2-3 mm thickness. The text / graphics mattervision angle shall not be less than 160 degree and visibility not be less than 75%.The approved color text and graphics shall be printed / router cut on monomericcalendered vinyl of 100 um thickness and shall be firmly pasted on display sheets.A pole with grooves for tricolor LED/Neon light installation. The mountingarrangement shall be hanging, wall mounting, ceiling mounting, pole mounting orfloor mounting and as per site requirement. The signage shall have the integralmounting arrangements with sturdy structural frame and ACP cladding on the backside of the signage to avoid rusting and entry of dust. The LED board shall haveuniform illumination with 4-8 W / sq. ft and with brightness more than ambientlight. It shall confirm the latest specification issued by railway board (alsouploaded). Specification to be read with explanatory Note uploaded. Inspection by- Consignee.
Design, supply, fixing, testing andcommissioning Numbers of front operateddouble door type weather proof feederpillar feeder (MCCB - Incoming & MCCB- Outgoing) comprising with thefollowing MCCB's fixed in it conformingto IS-60947:2 with digital measuringinstrument & bus-bar arrangement asper IS, IE rules and site requirement.4P MCCB 250 Amps 36 kA withadjustable thermal & fixed magneticrelease = 01 No. (Incoming), 4P MCCB125Amps 36 kA with adjustablethermal & fixed magnetic release = 02No. (Outgoing) 4P MCCB 63 Amps 36kA with adjustable thermal & fixedmagnetic release = 04 No. (outgoing) Inspection by- Consignee
"Design, fabrication, supply and fixing of GI Numbers 450.00 perforated horizontal cable- tray with all connected accessories viz- bend, tree, cross, reducer, 45° horizontal bend, coupler plates etc. including painting besides clamping, shifting of existing cables i n t o t h e trenches along with t a g g i n g a n d l a b l i n g o f shifted cables with numbering sleeve sfo t easy identification. size 300 mm width, 150 mm depth, 2mm thickness. Inspection by- RITES. PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
Supply, replacement, fixing, testing, connecting Numbers 180.00 and commissioningof Inverter LED batten with square profile and poly carbonate/Extruded Aluminimum channel. Lithium Ion battery with chargingtime 8 hours-10 hours and back up time upto 3 to 4 hours energyefficient luminaries complete with all accessories of capacity 20 watt,4 feet length, LED lamps with suitable current control driver circuit,suitable for surface/recessed mounting as per IS:10322. LEDLuminaries:-(1) A complete LED lighting unit consisting of a lightsource and driver together with parts of distribute light,to positionand protect the light source,and to connect the light source to abranch circuit. The light source itself may be an LED array and LEDmodule, or an LED lamp. (2):-Supplied LED luminaries shall confirmto IS:16101(2012) IS :16106(2012).Light Source(LED) in theLuminaries should be of make:- (1):-NICHIA/ CREE/OSRAM/ SEOUL/PHILIPS/LUMILEDS /LEDNIUM. (2):-LEDs to IS:16105(2012). IS:16108(2012),IEC:62471.1.Input operating voltage :-105-295 V AC.2:-Normal Voltage- 220V AC.3.Driver type:constant current driver with short circuit protection(For tubelight).4.Control of distribution:-Full cut off.5.Drive component:Industrial grade only .6.Efficiency of driver electronic:>= 85% (Fortube light).7.Colour temperature:5000-6500K(For tubelight).8.Colour rendering index(CRI):>75(For tube light).9.Ingressprotection :IP-20.10.Lumen output: >=100lumens/[email protected] drive current(For tube light).11.Powerfactor:- >0.90(For tube light). 12.Total harmonics distrotion(THD):-<20%(For tube light).13.Lamp cover :Acrylic cover which does notresult in loss of lumens.14.Finishing:Power coated/Anodized.15.Secondry optics:poly corbonate reflector/ polycarbonate lens.16.Construction of housing: extrudedaluminum/CRCA/Pressure die cast aluminum.17.Mounting :Suitablefor surface mounting/recessed mounting.18.Certificate:Firm tosubmit LM80(In respect of LED used)& LM79(Inrespect of luminareused) test certificate from National/International accreditedLaboratory and OEM certificate for complience ofBIS/IEC.19.Warranty:Firm to submit warranty certificate for five year. Inspection by- Consignee.
Supply, Erection, Testing and Commissioning of Numbers following Modular Type switch 1 0 A (1-way) c o m p l e t e i n a l l respect. Inspection by- Consignee.
Supply, Erection, Testing and Commissioning of Numbers following Modular type Plug socket outlet 2/3 Pin
Supply, Erection, Testing and Commissioning of Numbers f o l l o w i n g M o d u l a r Type switch 20 A (1- way)complete i n all respect.Inspection by- Consignee.
Supply, Erection, Testing and Commissioning of Numbers following Modular type Plug socket outlet 5/3 Pin
Consignee. PRAYAGRAJ DIVISION-ELECTRICAL/NORTH CENTRAL RLY
Supply a n d Erection o f Modular t y p e switch Numbers blanking set to fill the blank space White finished m o u n t i n g c o v e r p l a t e c o m p l e t e in all respect.Inspection by- Consignee.
S u p p l y a n d Erection o f w h i t e fi n i s h single Numbers mounting cover plate with base frame suitable 3 module suitable f o r mounting of Modular type piano switches/ plug Socket, fan regulator and connection to wiring. Inspection by- Consignee.
"Supply and Erection o f Junction Box cover POP Numbers type complete in all respect including hardware material for fixing. Inspection by-Consignee."
S u p p l y a n d Erection o f w h i t e fi n i s h single Numbers mounting cover plate with base frame suitable 8 module suitable f o r mounting of Modular type piano switches/ plug Socket, fan regulator and connection to wiring. Inspection by- Consignee.
S u p p l y a n d Erection o f w h i t e fi n i s h single Numbers mounting cover plate with base frame suitable 12 module suitable for mounting of Modular type piano switches/ plug Socket, fan regulator and connection to wiring. Inspection by- Consignee.
Supply a n d Erection o f Modular Metal boxes Numbers concealed Boards suitable for mounting o f 3 module white finish single mounting cover plate w ith Frame and Modular type piano switches/ plug Socket, fan regulators. Metal board boxes a r e t o be concealed i n w a l l . Inspection by- Consignee.
Supply a n d Erection o f Modular Metal boxes Numbers concealed Boards suitable for mounting o f 8 module white finish single mounting cover plate w ith Frame and Modular type piano switches/ plug Socket, fan regulators. Metal board boxes a r e t o be concealed i n w a l l . Inspection by- Consignee.
Supply a n d Erection o f Modular Metal boxes Numbers concealed Boards suitable for mounting o f 12 module white finish single mounting cover plate w ith Frame and Modular type piano switches/ plug Socket, fan regulators. Metal board boxes a r e t o be concealed i n w a l l . Inspection by- Consignee. Total 9686047.27
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
GCC_April-2022_2022__27_04_227.pdf
ATTACHMENT
GCC CORRECTION
ATTACHMENT
CTIndianRailwaysStandardGeneralConditionsofContractApril-
ATTACHMENT
CTIndianRailwayStandardGeneralConditionsofContractApril-
ATTACHMENT
CTIndianRailwayStandardGeneralConditionsofContractApril-
ATTACHMENT
GCC CORRECTION
ATTACHMENT
2024_05_14ClarificationregardingsubmissionofAnnexure-VofGCC.pdf
ATTACHMENT
Annexure-VA.pdf
ATTACHMENT
AnnxVIB.pdf
ATTACHMENT
GCCACS2022CORRECTION1.pdf
ATTACHMENT
Likelysourceofsupply.pdf
ATTACHMENT
2026_03_13AdvanceCorrectionSlipNo_111.pdf
ATTACHMENT
03QTYbifurcation.pdf
ATTACHMENT
TNDoclatest.pdf
ATTACHMENT
2022_12_13RBCE_CE-I-CTIndianRailwaysStandardGeneralConditionsofContractApril2022ACSNo_2.pdf
ATTACHMENT
2023_04_26RBCE_CE-I-CTIndianRailwaysStandardGeneralConditionsofContractApril-2022AdvanceCorrectionSlipNo_3ACS-3113.pdf
ATTACHMENT
2023_08_07RBCE_CE-I-CTIndianRailwayStandardGeneralConditionsofContractApril-2022AdvanceCorrectionSlipNo_4ACS-4.pdf
ATTACHMENT
2023_10_20RBCE_CE-I-CTIndianRailwayStandardGeneralConditionsofContractApril-2022AdvanceCorrectionSlipNo_5ACS-5.pdf
ATTACHMENT
2023_12_21IndianRailwaysStandardGeneralConditionsofContractApril-2022AdvanceCorrectionSlipNo_6ACS-6.pdf
ATTACHMENT