Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹20.2 LAccepted-AOC DANGRA TOLI CHOWK PURULIA ROAD RANCHI | RANCHI | ₹20.2 L Quoted ₹20.8 L | L1 | Accepted-AOC L1 |
| 2 | L2₹21.4 LRejected-AOC | ₹21.4 L | L2 | Rejected-AOC L2 |
| Sl No | Description | Qty | Unit | Blaca Corporations L1 | CHANDRA BROTHERS L2 |
|---|---|---|---|---|---|
| 1.00 | Supplying and installation of horizontal split casing centrifugal pump having discharge of 30000 G.P.H (136.2 M³ / HR ) clear water against a total head of 36.57 M meters (120 feet) Make- Kirloskar/Mather and Platt/ jyoti / Wilo with a suitable squirrel cage induction motor 3 ph, 415 V ± 10% , 1480 r.p.m, Make- Kirloskar/Mather and Platt/ jyoti/ Crompton /ABB coupled by means of tyre coupling on a common base plate with N.R valve, sluice valve rating PN- 1, ISI marked , foot valve, pressure gauge etc. all complete. | 2 | SET | 8,20,554.3 ₹16.4 L | 8,50,000 ₹17 L |
| 2.00 | Cost towards supply and fitting 40 H.P fully automatic air break star delta starter , Make- L&T /Havell’s/ Siemens / Schneider/ BCH | 2 | EACH | 32,000 ₹64,000 | 33,000 ₹66,000 |
| 3.00 | Cost towards replacement of damaged parts of panel by new supply and fitting 200 amp T.P.N DTH MCCB-1no incoming feeder and 160 amp T.P.N DTH MCCB-2 nos. outgoing ,0 to500v voltmeter - 2 nos., 0to 200 amp ammeter-2 nos. with selector switch ,indicating lamp 3 Nos., making internal connection with copper wire etc. | 1 | JOB | 85,000 ₹85,000 | 85,000 ₹85,000 |
| 4.00 | Cost towards dismantling 2 nos. 30 H.P C/F pump set with all accessories such as suction and delivery pipe line ,foot valve ,sluice & N.R valve, base plate etc ,including demolish old foundation -1 nos. for installation of new pump set, including keeping pump set in store or as per direction of E/I and throwing broken foundation outside the pump house including cost of labors , tools, tackles. | 2 | JOB | 14,500 ₹29,000 | 15,000 ₹30,000 |
| 5.00 | Cost towards making new P.C.C foundation with supplying stone chips, sand, cement, in the ratio 3:2:1 respectively about 5’x4’x3’for above pump sets including foundation bolts with nut and washer and curing plastering of foundation ,all complete . | 2 | JOB | 22,000 ₹44,000 | 22,000 ₹44,000 |
| 6.00 | Supplying and laying of 95 mm sq. 1.1 K.V grade,3.5 core P.V.C insulated and sheathed armored Al. cable , make – polycab, havell’s /,KEI, ISI marked | 30 | METRE | 960 ₹28,800 | 1,000 ₹30,000 |
| 7.00 | Cost towards doing cable socketing with Al lugs 95 mm sq. Al. cable | 2 | ENDS | 305 ₹610 | 310 ₹620 |
| 8.00 | Cost of supply & laying, commissioning of 3 core 25 mm² copper conductor cable 1.1 KV grade PVC insulated and PVC sheathed unarmored from panel to starter and starter to motor with lugs socketing, | 60 | METRE | 1,350 ₹81,000 | 1,400 ₹84,000 |
| 9.00 | Cost towards making chemical earthing as per I:E Rules ,etc. all complete. | 2 | JOB | 17,000 ₹34,000 | 17,300 ₹34,600 |
| 10.00 | Cost towards making suction & delivery pipe line with supply of 125 m.m dia. heavy duty M.S pipe 40 feet , 125 m.m dia. M.S flange- 8 nos. , 125 m.m dia. heavy duty M.S bend -4 nos., 100 m.m dia. heavy duty M.S pipe -15 ft., 100 m.m dia. heavy duty M.S flange -8 nos. 100 m.m dia. heavy duty M.S bend -4 nos. including cutting welding , required nut bolts, washer, rubber insertion, testing on load , all complete . | 1 | JOB | 43,000 ₹43,000 | 35,000 ₹35,000 |
Tender Value
₹20.4 L
EMD Value
₹41,000
Closing Date
22 Apr 2026, 2:00 pmClosed
EXECUTIVE ENGINEER
D W AND S MECH DIVISION HAZARIBAG
Supplying Installation Commissioning Testing of HSC Centrifugal pump set and associated works at Koderma Tower water supply pumping plant for urban water supply Koderma under D W and S Mech Sub Division Jhumaritilaiya
2026_DWSD_112851_1
DWSD/HZB/MECH/TILAIYA/SUPPLY-2 GROUP B
Open Tender
Pumps/Motors
90 days
JHUMRI TELAIYA
Please refer Tender documents.
2 documents required · 2 mandatory
₹5,000
₹41,000
Yes
27 Jun 2026
15 Apr 2026
23 Apr 2026
15 Apr 2026
22 Apr 2026
15 Apr 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supplying and installation of horizontal split casing centrifugal pump having discharge of 30000 G.P.H (136.2 M³ / HR ) clear water against a total head of 36.57 M meters (120 feet) Make- Kirloskar/Mather and Platt/ jyoti / Wilo with a suitable squirrel cage induction motor 3 ph, 415 V ± 10% , 1480 r.p.m, Make- Kirloskar/Mather and Platt/ jyoti/ Crompton /ABB coupled by means of tyre coupling on a common base plate with N.R valve, sluice valve rating PN- 1, ISI marked , foot valve, pressure gauge etc. all complete. | - | SET | - | - |
| 2 | Cost towards supply and fitting 40 H.P fully automatic air break star delta starter , Make- L&T /Havell’s/ Siemens / Schneider/ BCH | - | EACH | - | - |
| 3 | Cost towards replacement of damaged parts of panel by new supply and fitting 200 amp T.P.N DTH MCCB-1no incoming feeder and 160 amp T.P.N DTH MCCB-2 nos. outgoing ,0 to500v voltmeter - 2 nos., 0to 200 amp ammeter-2 nos. with selector switch ,indicating lamp 3 Nos., making internal connection with copper wire etc. | - | JOB | - | - |
| 4 | Cost towards dismantling 2 nos. 30 H.P C/F pump set with all accessories such as suction and delivery pipe line ,foot valve ,sluice & N.R valve, base plate etc ,including demolish old foundation -1 nos. for installation of new pump set, including keeping pump set in store or as per direction of E/I and throwing broken foundation outside the pump house including cost of labors , tools, tackles. | - | JOB | - | - |
| 5 | Cost towards making new P.C.C foundation with supplying stone chips, sand, cement, in the ratio 3:2:1 respectively about 5’x4’x3’for above pump sets including foundation bolts with nut and washer and curing plastering of foundation ,all complete . | - | JOB | - | - |
| 6 | Supplying and laying of 95 mm sq. 1.1 K.V grade,3.5 core P.V.C insulated and sheathed armored Al. cable , make – polycab, havell’s /,KEI, ISI marked | - | METRE | - | - |
| 7 | Cost towards doing cable socketing with Al lugs 95 mm sq. Al. cable | - | ENDS | - | - |
| 8 | Cost of supply & laying, commissioning of 3 core 25 mm² copper conductor cable 1.1 KV grade PVC insulated and PVC sheathed unarmored from panel to starter and starter to motor with lugs socketing, | - | METRE | - | - |
| 9 | Cost towards making chemical earthing as per I:E Rules ,etc. all complete. | - | JOB | - | - |
| 10 | Cost towards making suction & delivery pipe line with supply of 125 m.m dia. heavy duty M.S pipe 40 feet , 125 m.m dia. M.S flange- 8 nos. , 125 m.m dia. heavy duty M.S bend -4 nos., 100 m.m dia. heavy duty M.S pipe -15 ft., 100 m.m dia. heavy duty M.S flange -8 nos. 100 m.m dia. heavy duty M.S bend -4 nos. including cutting welding , required nut bolts, washer, rubber insertion, testing on load , all complete . | - | JOB | - | - |
stage.html
html • 0.04 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.52 MB
BOQ_152412.xls
BOQ • 0.24 MB
TC.pdf
Tender Documents • 0.77 MB
Download all tender documents and submit your bid