Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹31.5 LAccepted-AOC | L1 | Accepted-AOC Accepted | |
| 2 | L2₹33.6 L+₹83,303.60 (2.54%)Rejected-Finance NEAR GYAN DEEP SCHOOL 1 DHARAM KANTA GOVERDHAN ROAD DISTT MATHURA U P 281001 | MATHURA | MATHURA | U P | 281001 | L2 | Rejected-Finance Other than Lowest | |
| 3 | L3₹34.0 L+₹1.3 L (3.86%)Rejected-Finance NO 9 BYRAVESHWARA INDUSTRIAL ESTATE ANDRAHALLI MAIN ROAD NEAR PEENYA 2ND STAGE BENGALURU 560 091 | BENGALURU URBAN | KARNATAKA | 560091 | L3 | Rejected-Finance Other than Lowest | |
| 4 | L4₹36.4 L+₹3.6 L (11.0%)Rejected-Finance 37 PUNJABI COLONY NEAR RAILWAY CROOSING ARYA SAMAJ ROAD MATHURA U P | MATHURA | MATHURA | UTTAR PRADESH | 281001 | L4 | Rejected-Finance Other than Lowest | |
| 5 | L5₹37.7 L+₹4.9 L (15.0%)Rejected-Finance | L5 | Rejected-Finance Other than Lowest |
| Sl No | Description | Qty | Unit | Vijay Electricals L3 | krishna Associate L5 | shyam construction L4 | M/s Ranaji Construction Co L1 | M/S MAKHIJA TRADERS L6 | M/S BAJRANG CONSTRUCTIONS L2 |
|---|---|---|---|---|---|---|---|---|---|
| 1.00 | Material and labour for design ,supply, fabrication, Installation, testing and commissoning Factory made LT panel outdoor type totally enclosed, dust and vermin proof, suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 50 Hz AC supply system, fully compartmentalized, both side openable, made out of 3.15 mm thick CRCA sheet, protection of enclousure IP-54 as per IS: 2147 of 1962 with pre-treatment and powder coated of approved colour including suitable frame work/support made out of suitable size angle iron/flat iron, front opening type with provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded copper conductor FRLS cable of adequate size(minimum 1.5 sqmm), including required civil works/anchoring bolts for fixing, PCC foundation 45cm above ground level etc with and including following complete all as specified | 4 | Each | 1,50,000 ₹6,00,000 Lowest | 1,80,000 ₹7,20,000 | 1,60,000 ₹6,40,000 | 1,61,000 ₹6,44,000 | 2,10,000 ₹8,40,000 | 1,60,000 ₹6,40,000 |
| 1.10Busbar Chamber: Electrically grade aluminium shrouded busbar of current density 550 amp including interconnection of all switch gears, fixed on DMC insulators and provisions of extension (Incoming) (a) MCCB 04 Pole, 415 V 50Hz 350 Amps adjustbale overload with 36 KA breaking capacity for main supply -01 No. (b) Ammeter square type (0-400Amp) with inbuilt selector switch and CT’s of suitable ratio – 01 No (c) Voltmeter with inbuilt seleCtor switch (0-500) volt - 01 Set (d) Phase (RYB) indicating LED lamp - 01 set (e) MCB SP 6 Amps "C" Series for control protection RYB phases (Set of 3) - 01 Set (Outgoing) (a) MCCB 04 Pole, 415 V 50Hz 160 Amps adjustbale type with 27/25 KA breaking capacity -02 Nos (b) MCCB 04 Pole, 415 V 50Hz 100 Amps adjustbale type with 27/25 KA breaking capacity -02 Nos (c) MCCB 04 Pole, 415 V 50Hz 63 Amps adjustbale type with 27/25 KA breaking capacity -02 Nos (d) MCB 04 Pole 415 volts 40 Amps – 02 Nos Note :-Changeover/MCCB/MCB should be mounted vertically in panel | |||||||||
| 2.00 | Material and labour for design ,supply, fabrication, Installation, testing and commissoning Factory made LT panel outdoor type totally enclosed, dust and vermin proof, suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 50 Hz AC supply system, fully compartmentalized, both side openable, made out of 3.15 mm thick CRCA sheet, protection of enclousure IP-54 as per IS: 2147 of 1962 with pre-treatment and powder coated of approved colour including suitable frame work/support made out of suitable size angle iron/flat iron, front opening type with provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded copper conductor FRLS cable of adequate size(minimum 1.5 sqmm), including required civil works/anchoring bolts for fixing, PCC foundation 45cm above ground level etc with and including following complete all as specified | 2 | Each | 85,000 ₹1,70,000 | 1,50,000 ₹3,00,000 | 80,000 ₹1,60,000 Lowest | 1,25,000 ₹2,50,000 | 1,80,000 ₹3,60,000 | 80,000 ₹1,60,000 Lowest |
| 2.10Busbar Chamber: Electrically grade aluminium shrouded busbar of current density 300 amp including interconnection of all switch gears, fixed on DMC insulators and provisions of extension (Incoming) (a) MCCB 04 Pole, 415 V 50Hz 160Amps adjustbale overload with 27/25 KA breaking capacity for main supply -01 No. (b) Ammeter square type (0-250Amp) with inbuilt selector switch and CT’s of suitable ratio – 01 No (c) Voltmeter with inbuilt seleCtor switch (0-500) volt - 01 Set (d) Phase (RYB) indicating LED lamp - 01 set (e) MCB SP 6 Amps "C" Series for control protection RYB phases (Set of 3) - 01 Set (Outgoing) (a) MCCB 04 Pole, 415 V 50Hz 100 Amps adjustbale type with 27/25 KA breaking capacity -01 No (b) MCCB 04 Pole, 415 V 50Hz 63 Amps adjustbale type with 27/25 KA breaking capacity -02 Nos (c) MCB 04 Pole 415 volts 40 Amps – 02 Nos Note :-Changeover/MCCB/MCB should be mounted vertically in panel | |||||||||
| 3.00 | M& L for Earthing complete with galvanised mild steel plate electrode 600x600x6 mm thick buried directly in ground vertically (earth pit not less than 2.25 m deep below normal ground level) with the top edge of the earth plate electrode at a depth not less than 1.5m below normal ground level and including GI earth strip 32x6 mm bolted (with GI nuts, bolts & check nuts) and riveted to earth plate electrode at one end connected to metallic bodies of HT/LT equipment etc at the other and earth strip encased in and including 40mm bore GI light grade pipe with all fittings from top of earth plate electrode to body of equipment fixed with and including 25x6 mm flat iron clamps bolts, nuts and washers and including providing watering pipe 20mm bore GI Pipe electrode complete all as specified and shown in elctrical plate No 3 of MES SSR Part-I. the scope of work includes necessary excavation and earth work in any type of soil. removal of soil upto 50 metre PCC pit with precast RCC cover, charcoal/salt funnel, CI frame etc complete all as specified & directed.
NOTE:(I) The concrete pit shall be made in PCC 1:2:4 type B-O, using 12.50 mm graded crushed stone aggregate 40mm thick precast cover slab of RCC(1:2:4), type B-1, using 20mm graded crushed stone aggregate with suitable MS handle in lieu of CI cover. Reinforcement in cover shall be of 8mm dia TMT bars @ 150mm c/c both ways.
(ii) Item includes the cost of 7.5 metre GI pipe for protection of earth strip.
(iii) Item includes cost of 7.5 metre earth lead strip
(iv) Earth electrode shall be surrounded by adequate quantity of charcoal dust and salt to a packed thinkness of 15 cm on all sides. | 6 | Each | 3,000 ₹18,000 Lowest | 3,000 ₹18,000 Lowest | 3,000 ₹18,000 Lowest | 3,500 ₹21,000 | 4,000 ₹24,000 | 3,000 ₹18,000 Lowest |
| 4.00 | S&F in repair 4 Pole 63 Amp power contactor, AC 3 rating, fixed in existing panel & connecting complete all as specified | 4 | Each | 3,500 ₹14,000 | 1,000 ₹4,000 Lowest | 1,800 ₹7,200 | 2,000 ₹8,000 | 1,200 ₹4,800 | 3,000 ₹12,000 |
| 5.00 | Excavation in trenches, n. exc 1.5 Mtr wide and n. exc 1.5 Mtr in depth for foundation/laying of cable and getting out in soft/loose soil complete all as specified | 607 | Cum | 99 ₹60,093 | 200 ₹1,21,400 | 100 ₹60,700 | 80 ₹48,560 | 91 ₹55,237 | 70 ₹42,490 Lowest |
| 6.00 | Returning, filling in including spreading, levelling, watering and well ramming in layers n. Exc 25 cm thick complete all as specified. | 281 | Cum | 19 ₹5,339 Lowest | 40 ₹11,240 | 20 ₹5,620 | 30 ₹8,430 | 51 ₹14,331 | 30 ₹8,430 |
| 7.00 | Removing of excavated soil to a distance n. Exc 50 Mtr and depositing where directed at a level n. Exc 1.5 Mtr above the starting point complete all as specified | 326 | Cum | 19 ₹6,194 Lowest | 40 ₹13,040 | 20 ₹6,520 | 30 ₹9,780 | 52 ₹16,952 | 30 ₹9,780 |
| 8.00 | Supply & spread unwashed dry river sand for sand cushioning for covering the under ground cable in trenches complete all as specified. (Note :- Punning thickness shall be measured.) | 243 | Cum | 280 ₹68,040 | 200 ₹48,600 Lowest | 400 ₹97,200 | 400 ₹97,200 | 300 ₹72,900 | 350 ₹85,050 |
Tender Value
₹45 L
EMD Value
₹90,000
Closing Date
16 Jun 2026, 6:00 pmClosed
GE Bharatpur
GE Bharatpur
REPAIR AND MAINTENANCE OF LT PANELS LT CABLE MCCBs AND CONNECTED WORKS AT 39 FAD AT MIL STN BHARATPUR MIL STN
2026_MES_767747_1
8632/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE Bharatpur
AS PER NIT
8 documents required · 8 mandatory
₹500
Yes
GE Bharatpur
₹90,000
Yes
10 Jul 2026
25 May 2026
18 Jun 2026
25 May 2026
16 Jun 2026
9 Jun 2026
26 May 2026 - 6 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Material and labour for design ,supply, fabrication, Installation, testing and commissoning Factory made LT panel outdoor type totally enclosed, dust and vermin proof, suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 50 Hz AC supply system, fully compartmentalized, both side openable, made out of 3.15 mm thick CRCA sheet, protection of enclousure IP-54 as per IS: 2147 of 1962 with pre-treatment and powder coated of approved colour including suitable frame work/support made out of suitable size angle iron/flat iron, front opening type with provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded copper conductor FRLS cable of adequate size(minimum 1.5 sqmm), including required civil works/anchoring bolts for fixing, PCC foundation 45cm above ground level etc with and including following complete all as specified | 4 | Each | - | - |
| 1.1 | Busbar Chamber:
Electrically grade aluminium shrouded busbar of current density 550 amp including interconnection of all switch gears, fixed on DMC insulators and provisions of extension
(Incoming)
(a) MCCB 04 Pole, 415 V 50Hz 350 Amps adjustbale overload with 36 KA breaking capacity for main supply -01 No.
(b) Ammeter square type (0-400Amp) with inbuilt selector switch and CT’s of suitable ratio – 01 No
(c) Voltmeter with inbuilt seleCtor switch (0-500) volt - 01 Set
(d) Phase (RYB) indicating LED lamp - 01 set
(e) MCB SP 6 Amps "C" Series for control protection RYB phases (Set of 3) - 01 Set
(Outgoing)
(a) MCCB 04 Pole, 415 V 50Hz 160 Amps adjustbale type with 27/25 KA breaking capacity -02 Nos
(b) MCCB 04 Pole, 415 V 50Hz 100 Amps adjustbale type with 27/25 KA breaking capacity -02 Nos
(c) MCCB 04 Pole, 415 V 50Hz 63 Amps adjustbale type with 27/25 KA breaking capacity -02 Nos (d) MCB 04 Pole 415 volts 40 Amps – 02 Nos
Note :-Changeover/MCCB/MCB should be mounted vertically in panel | - | - | - | - |
| 2 | Material and labour for design ,supply, fabrication, Installation, testing and commissoning Factory made LT panel outdoor type totally enclosed, dust and vermin proof, suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 50 Hz AC supply system, fully compartmentalized, both side openable, made out of 3.15 mm thick CRCA sheet, protection of enclousure IP-54 as per IS: 2147 of 1962 with pre-treatment and powder coated of approved colour including suitable frame work/support made out of suitable size angle iron/flat iron, front opening type with provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded copper conductor FRLS cable of adequate size(minimum 1.5 sqmm), including required civil works/anchoring bolts for fixing, PCC foundation 45cm above ground level etc with and including following complete all as specified | 2 | Each | - | - |
| 2.1 | Busbar Chamber:
Electrically grade aluminium shrouded busbar of current density 300 amp including interconnection of all switch gears, fixed on DMC insulators and provisions of extension
(Incoming)
(a) MCCB 04 Pole, 415 V 50Hz 160Amps adjustbale overload with 27/25 KA breaking capacity for main supply -01 No.
(b) Ammeter square type (0-250Amp) with inbuilt selector switch and CT’s of suitable ratio – 01 No
(c) Voltmeter with inbuilt seleCtor switch (0-500) volt - 01 Set
(d) Phase (RYB) indicating LED lamp - 01 set
(e) MCB SP 6 Amps "C" Series for control protection RYB phases (Set of 3) - 01 Set
(Outgoing)
(a) MCCB 04 Pole, 415 V 50Hz 100 Amps adjustbale type with 27/25 KA breaking capacity -01 No
(b) MCCB 04 Pole, 415 V 50Hz 63 Amps adjustbale type with 27/25 KA breaking capacity -02 Nos (c) MCB 04 Pole 415 volts 40 Amps – 02 Nos
Note :-Changeover/MCCB/MCB should be mounted vertically in panel | - | - | - | - |
| 3 | M& L for Earthing complete with galvanised mild steel plate electrode 600x600x6 mm thick buried directly in ground vertically (earth pit not less than 2.25 m deep below normal ground level) with the top edge of the earth plate electrode at a depth not less than 1.5m below normal ground level and including GI earth strip 32x6 mm bolted (with GI nuts, bolts & check nuts) and riveted to earth plate electrode at one end connected to metallic bodies of HT/LT equipment etc at the other and earth strip encased in and including 40mm bore GI light grade pipe with all fittings from top of earth plate electrode to body of equipment fixed with and including 25x6 mm flat iron clamps bolts, nuts and washers and including providing watering pipe 20mm bore GI Pipe electrode complete all as specified and shown in elctrical plate No 3 of MES SSR Part-I. the scope of work includes necessary excavation and earth work in any type of soil. removal of soil upto 50 metre PCC pit with precast RCC cover, charcoal/salt funnel, CI frame etc complete all as specified & directed.
NOTE:(I) The concrete pit shall be made in PCC 1:2:4 type B-O, using 12.50 mm graded crushed stone aggregate 40mm thick precast cover slab of RCC(1:2:4), type B-1, using 20mm graded crushed stone aggregate with suitable MS handle in lieu of CI cover. Reinforcement in cover shall be of 8mm dia TMT bars @ 150mm c/c both ways.
(ii) Item includes the cost of 7.5 metre GI pipe for protection of earth strip.
(iii) Item includes cost of 7.5 metre earth lead strip
(iv) Earth electrode shall be surrounded by adequate quantity of charcoal dust and salt to a packed thinkness of 15 cm on all sides. | 6 | Each | - | - |
| 4 | S&F in repair 4 Pole 63 Amp power contactor, AC 3 rating, fixed in existing panel & connecting complete all as specified | 4 | Each | - | - |
| 5 | Excavation in trenches, n. exc 1.5 Mtr wide and n. exc 1.5 Mtr in depth for foundation/laying of cable and getting out in soft/loose soil complete all as specified | 607 | Cum | - | - |
| 6 | Returning, filling in including spreading, levelling, watering and well ramming in layers n. Exc 25 cm thick complete all as specified. | 281 | Cum | - | - |
| 7 | Removing of excavated soil to a distance n. Exc 50 Mtr and depositing where directed at a level n. Exc 1.5 Mtr above the starting point complete all as specified | 326 | Cum | - | - |
| 8 | Supply & spread unwashed dry river sand for sand cushioning for covering the under ground cable in trenches complete all as specified. (Note :- Punning thickness shall be measured.) | 243 | Cum | - | - |
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.63 MB
BOQ_859791.xls
BOQ • 0.44 MB
tender8632.pdf
Tender Documents • 1.66 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .