Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹44.0 LAccepted-AOC | 1 | Accepted-AOC Acceptance Of Tender | |
| 2 | 2₹45.1 L+₹51,443 (1.15%)Rejected-Finance 10TH FLOOR TOWER A3 FLAT NO 1001 MI RUSTLE COURT GOMTI NAGAR EXTENSION GOMTI NAGAR LUCKNOW UP 226010 | LUCKNOW | LUCKNOW | UP | 226010 | 2 | Rejected-Finance Not L1 | |
| 3 | Rejected-Technical NH 17 MAIN ROAD BINAGA BAZAR KARWAR 581307 | KARWAR | UTTARA KANNADA | KARNATAKA | 581307 | - | Rejected-Technical Rejected for opening of cover 2 due to not enlisted in requisite category |
| Sl No | Description | Qty | Unit | Prime power system L1 | HS ASSOCIATES L2 |
|---|---|---|---|---|---|
| 1.00 | Material and labour for perodical servicing ,repairing & testing of 33 KV outdoor VCB including relay and control panel of capacity 800/400 Amps and rating 36 KV complete as details mentioned as under:-
(a) Details of periodical servicing of breaker :-
(i) Checking of Closing/Tripping coil assembly
(ii) Adjustment of mechanism if required.
(iii) Clean the circuit breaker to remove dust and dirt. The envelope of the vacuum interrupter and
insulating materials shall be wiped with a clean cloth.
(iv) Checking the contact for wear. Replace if the contact piece has worn out.
(v) Apply a small amount of oil to rotary sections, sliding surfaces, pins, coupling section, etc.use grease for the operating shaft and bearings, and machine oil for other parts.
(vi) Check for rust and wear.
(vii) Checking of spring charge mechanism
(viii) Visual check for rust and deformation.
(ix) Check for loosened bolts and nuts, broken spring washers and snap pins etc.
(x) Check for loosened connections, rust, damaged lead wires including repacement of vintage control wiring.
(xi) Checking of control circuit & tighten the connections if any.
(xii) Check close & trip coil.
(xiii) Replacement of Dashpot/shock absorbers .
(xiv) Replacement of carbon brush of spring charging motor
(xv)Cleaning of porcelain bushing
(xvi)Checking of limit switch | 5 | Each Job | 15,000 ₹75,000 | 13,600 ₹68,000 Lowest |
| 1.01(b) The following test shall be carried out:- (i) Primary Injection Test of outdoor CT / PT (ii) Closing & Opening Timing Test for all three poles. (iii) IR Test with megger in open and closed condition. (iv) Contact resistance test for all three poles (v) Testing VCB bottle (vi) Closing coil resistance (vii) Tripping coil resistance. (viii) High voltage test. (ix)Testing of Over current and earth fault numeriacal relay of control panel with Secondary Injection Kit ,checking, programming & coordination of relay as directed by Engr-in-Charge. (x) Testing of auxilary relays such as DC Supply supervision relay, Master trip relay ,Buchholz relay , WTI relay,OTI relay & etc. Note- . The rates for Nuts, bolts, washers, lugs, thimble, wires and minor items required for efficient and smooth functioning of the equipment shall deemed to be included in in the quoted item. Rates for testing equipments and accessories required at site for condcuting above tests shall deemed to be included in quoted rates by contractor. | |||||
| 2.00 | Supplying , installation & testing in replacement Isolator (horizontal type ) suitable for oudoor type three phase double break,centre rotating type suitable manual operation 3 moving contact of all isolator (roatate through 90 degree from their fully collosed position to fully open position so that the break is distinct and clearly visible from ground lever conforming to IS 9921/IEC-62271-102, phase, rated nominal/ maximum rated voltage 33/36 KV, rated current 1250 Amp including taking down old unserviceable isolator etc complete as specified and directed | 5 | Set of 3 | 70,000 ₹3,50,000 | 62,000 ₹3,10,000 Lowest |
| 3.00 | Supplying , installation & testing in replacement a single piece non linear resister type lightening arrester suitable for three wire 33 KV overhead lines with rated voltage of 33 KV (rms) 10 KA descharge current with a (station class) with clamp, bolts, nuts and washers as required including taking down of old unserviceable lightening arrester. | 3 | Set of 3 | 25,000 ₹75,000 | 21,000 ₹63,000 Lowest |
| 4.00 | Supply installation, testing in replacement Potential Transformer (PT) oil cooled out door single phase ( Earthed type) of voltage ratio 33 KV/110 V class 3P - 0.5-3, burden 50 VA insulation level of 70/170 KV as specified below:-
(a) Normal System Voltage-33 KV
(b) Highest System Voltage-36 KV
(c) Rated Primary voltage- 33 KV/√3
(d) Rated secondary voltage- 110 V/√3
(e) Nos of Lt winding 2
(f) Metering Core Accuracy class - 0.5
(g) Metering Core Rated Burden- 50 VA
(h) Nos of Phase- Single (Earthed Type)
(j) Protection core accuracy class - 3P
(k) Protection core rated Burden - 50 VA
(l) Rated Voltage Factor - 1.2 continuous & 1.5 for 30 Sec
(m) Insulation Level- 36/70 KV.170 KVP
(n) Temp rise at rated contineous thermal current over ambient at site - 45 0C
(o) Porcelain Bushing type - Hollow Cylinder
(p) 1.2/50 mcro second impulse withstand test vol -170 KV (Peak)
(q) Creepage distance of HV bushing - 900 mm (min)
(r) Primary & Secondary winding material - Copper | 1 | Set of 3 | 2,00,000 ₹2,00,000 | 1,78,000 ₹1,78,000 Lowest |
| 5.00 | Supply, installation, testing in replacement 33 KV current transformer oil cooled out door single phase, oil immersed and self cooled type of ratio 100-50/5-5-5-5/1-1-1-1 suitable for metering and protection equipment installed on control panels terminal block as specified below :-
(a) Normal System Voltage-33 KV
(b) Highest System Voltage-36 KV
(c) Rated Primary current- 100-50 Amp
(d) Rated secondary current- 5 Amp/1 Amp
(e) Nos of Core - 4
(f) Core01: Accuracy class 5P10, 10VA, ALF ≥10
(g) Core02: Accuracy Class 1.0, 10VA, ISF ≤ 5
(h) Core 03 Protection core accuracy class -PS,Protection knee point voltage- 300 Volt at lower ratio
(j) Core 04-Spare
(k) Continuous thermal current rating 120 % of rated primary current
(l)Temp rise at rated contineous thermal current over ambient at site - Less than or equal to 45 degree C
(m) Insulation Level- 36/70 KV.170 KVP
(n) 1.2/50 Micro second impulse withstand test voltage- 170 KV (peak)
(o) Short time thermal current rating for one second - 25 KA/1 Second
(p) Dynamic Current Rating - 62.5 KA ( peak)
(q) Porcelain Bushing type - Hollow Cylinder
(r) Creepage distance of HV bushing - 900 mm (min)
(s) Primary & Secondary winding material - Copper | 1 | Set of 3 | 2,10,000 ₹2,10,000 | 1,78,000 ₹1,78,000 Lowest |
| 6.00 | Supplying , installation & testing in replacement Post insulator suitable for rated nominal/ maximum rated voltage 33/36 KV, rated current 1250 Amp including taking down old unserviceable Post insulator complete as specified and directed. | 6 | Each | 3,000 ₹18,000 Lowest | 4,000 ₹24,000 |
| 7.00 | M&L for periodical servicing, repairing & testing of HT Potential Transformer (33 KV / 110 Volt) by cleaning of bushing and terminal of HT potential transformer 33000 / 110 volts (outdoor type) by CTC liquid and checking of oil level incl rectify the any leakage and proper connection checking and testing with following :-
(i) Insulation resistance test between phase to phase & phase to earth
(ii) Checking output voltage
(iii) Testing the oil dielectric strength (BDV test)
Note- . The rates for Nuts, bolts, washers, lugs, thimble, wires and minor items required for efficient and smooth functioning of the equipment shall deemed to be included in in the quoted item. Rates for testing equipments and accessories required at site for condcuting above tests shall deemed to be included in quoted rates by contractor. | 5 | Set of 3 | 1,500 ₹7,500 Lowest | 4,400 ₹22,000 |
| 8.00 | M&L for periodical servicing, repairing & testing of HT 33 KV Current Transformer (CT) by cleaning of bushing and terminal by CTC solution of CT rating 100 / 5 + 5 + 1 Amp rating, 33 KV and checking of oil level , rectify the leakage if any and testing the oil strength (BD test) and proper connection checking and testing with following :-
(i) Insulation resistance test between phase to phase& phase to earth.
Note- . The rates for Nuts, bolts, washers, lugs, thimble, wires and minor items required for efficient and smooth functioning of the equipment shall deemed to be included in in the quoted item. Rates for testing equipments and accessories required at site for condcuting above tests shall deemed to be included in quoted rates by contractor. | 5 | Set of 3 | 1,500 ₹7,500 Lowest | 4,400 ₹22,000 |
| 9.00 | M&L for periodical servicing, repairing & testing of line isolator, 33 KV (Horizontal type) ,Servicing of line isolator (Horizontal break outdoor type) including cleaning of contact (knife) by CTC liquid proper oiling greasing on contacts & moving rod / handle for proper function of moveable rod for smooth ON / OFF position and checking,tightining the incoming and outgoing connection (terminal lugs to be replaced if required as per existing size with GI nut bolts,washer) and testing with following :-
(i) Insulation resistance test between phase to phase & phase to earth .
(ii) High voltage test of isolator as directed by Engr -in-Charge.
Note- . The rates for Nuts, bolts, washers, lugs, thimble, wires and minor items required for efficient and smooth functioning of the equipment shall deemed to be included in in the quoted item. Rates for testing equipments and accessories required at site for condcuting above tests shall deemed to be included in quoted rates by contractor. | 14 | Set of 3 | 2,000 ₹28,000 Lowest | 3,800 ₹53,200 |
Tender Value
₹45 L
EMD Value
₹90,000
Closing Date
22 Sept 2025, 10:00 amClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE LUCKNOW
HQ CWE Lucknow, 229 MG Road, LucknowCantt, Lucknow-226002
REPAIR/MAINT OF 33 KV YARD , POWER TRANSFORMERS,33 KV/11 KV BREAKERS AND CONNECTED ITEMS AT OLD MRS AND NEW MRS IN THE AREA OF AGE E/M EXT (ELECT) UNDER GE E/M LUCKNOW.
2025_MES_717415_2
CWE/LKO/EM/T-30 OF 2025-26
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
LUCKNOW
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE E/M LUCKNOW
₹90,000
Yes
11 Nov 2025
26 Aug 2025
24 Sept 2025
26 Aug 2025
22 Sept 2025
2 Sept 2025
26 Aug 2025 - 2 Sept 2025
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .