Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹32.1 LAccepted-AOC 1001 B BHAVESHWAR BLDG NO 03 BHAVESHWAR LANE GHATKOPAR EAST MUMBAI 400077 | MUMBAI SUBURBAN | MAHARASHTRA | 400077 | L1 | Accepted-AOC BEING L1 | |
| 2 | L2₹45.6 L+₹11.8 L (34.8%)Rejected-Finance 00 C O PARMOD SINGH BAKTA BARHI CHINTAMAN SITAMARHI BIHAR 843315 | SITAMARHI | BIHAR | 843315 | L2 | Rejected-Finance BEING L2 | |
| 3 | L3₹46.4 L+₹12.6 L (37.3%)Rejected-Finance 1101 A WING SACHDEV COMPLEX JANGAL MANGAL RAOD BHANDUP W MUMBAI 400078 | MUMBAI SUBURBAN | MAHARASHTRA | 400078 | L3 | Rejected-Finance BEING L3 |
Tender Value
₹49.5 L
EMD Value
₹99,000
Closing Date
8 Jun 2023, 6:00 pmClosed
GE AF THANE
Office of Military Engineer Services ,Garrison Engineer (AF) Thane, Kolshet Road, Sandoz Baugh Post, Thane 400607
REPAIR AND MAINTENANCE LT CABLE , EXTERNAL ELECTRIC POWER TRANSMISSION SYSTEM AND ALLIED WORKS SITE P under GE AF STATION THANE
2023_MES_587905_2
8280/E8
Open Tender
Electrical and Maintenance Works
Item Rate
330 days
THANE
AS PER REVISED NIT UPLOADED ALONG WITH TENDER DOCUMENT
8 documents required · 8 mandatory
₹500
GE AF THANE
₹99,000
Yes
28 Jul 2023
18 May 2023
9 Jun 2023
18 May 2023
8 Jun 2023
27 May 2023
18 May 2023 - 27 May 2023
Amount
Taking down carefully existing aluminium/Copper point wiring light, fan socket or power bell complete with fitting such as sockets, ceiling roses, pendants batten holders regulators socket, call bells & making good to the disturbed surfaces of walls, matching the colour with existing Surface all as spd and directed by Engr-in-Charge. Note: Rate for making good shall be deemed to be included in quoted rate.
Supply and fix distribution board made out of sheet metal, powder coated, factory made enclousure, double door type, TPN 4 way vertical type, with 200 Amps rated copper bus bar, neutral bar, earth bar, TP 43 protection including provision of housing of incomer MCCB 63 Amps, triple pole and neutral, 415V, 16 KA breaking capacity and fixing of DB flush to wall surface complete all as specified and directed.
M&L for Point wiring complete with 1100 volts grade FRLS insulated unsheathed cable of copper conductor cable multi stranded of size 1.5 Sqmm single core including PVC rigid concealed conduit medium grade of suitable size (not less than 20mm dia) with all accessories such as bend reducers /MS hooks, MS junction box 1.2mm thick MS pressed sunken terminal boxes of suitable sizes for mounting of switches sockets, fan regulators etc covered with 3.15 mm thick bakelite laminated (Hylem/Anchor) top cover including continuous earth wire of size 1.5 Sqmm PVC strandedcopper conductor unsheathed, insulated stranded (Green colour) connected to common earth point dolly ,complete all as specified and as directed by Engr-in-charge .for the following:-
One light point/call bell point/fan point to be controlled by one number one way PT switch
Switch socket combination 5 Pin 5 Amps 230 Volts point controlled by one switch and wiring with 1.5 Sqmm PVC unsheathed copper conductor cable 1.5 Sqmm PVC insulated earth wire on independent board
Ditto as per Srl item No 3.02 above but on same board
Switch socket combination (multi purposes) 6 Pin 15 Amps point to be controlled by one switch & wiring with 2.5 Sqmm PVC- unsheathed copper conductor cable 2.5 Sqmm PVC insulated earth wire on independent board.
M & L for point wiring with FRLS PVC insulated 1100 Volts grade IS-694 single core multistranded Copper conductor cable 1.5 Sqmm drawn in and including PVC casing capping with accessories, fixed on wall/ ceiling etc with necessary fixing accessories and earth continuity copper conductor cable of size 1.5 Sqmm green colour Connected to common earth dolly including pressed mild steel terminal boxes 16 gauge thick of adequate size concealed in wall Covered with 3.15 mm thick bakelite laminated (Hylem/Anchor) for mounting switches/ sockets/ fan regulators / bell push buttons etc fixed with cadmium plated machine steel screws and washers all as specified for the following :-
One Light point/fan point/Bell point controlled by one switch .
One 3 pin 5 Amps socket out let on independent board
One 3 pin 5 Amps socket out let on same board
Ditto as per Srl item No 4.00 above but for 2.5 Sqmm wire for 15 Amp socket outlet on independent board
One light point controlled by two 2-way switches
S&F switch Piano type single pole one way 5 Amp,230 VAC ,complete all as specified and as directed by Engr-in-charge.
S&F switch Piano type single pole two way 5 Amp,230 VAC ,complete all as specified and as directed by Engr-in-charge .
Supply and fixing bell push flush type 5 Amp ,complete all as specified and as directed by Engr-in-charge .
S&F socket two in one ,3 Pin 5 Amps 230 VAC ,complete all as specified and as directed by Engr-in-charge .
S&F switch Piano type single pole one way 15 Amp on laminated sheet top cover ,complete all as specified and as directed by Engr-in-charge (Sheet top cover incl in point wiring) .
S&F socket Pinao type 6 Pin 16 amp,230 VAC ,complete all as specified and as directed by Engr-in-charge.
S&F bell ding dong AC 230V single pole ,complete all as specified and as directed by Engr-in-charge.
S&F Ceiling rose, two to three terminals with bakalite 20mm back plate,complete all as specified and as directed by Engr-in-charge.
S&F fan regulator electronic socket type 5 speed for ceiling fan 1200/1400 mm sweep ,complete all as specified and as directed by Engr-in-charge .
Supply & fixing PVC Lamp holder suitable for and including batten fittings ,CFL/Electric lamp with backalite 20mm back plate ,complete all as specified and as directed by Engr-in-charge .
S&F LED tube rod,environmental friendly energy efficient ready to use 18/20W LED 6000k(4') ,complete all as specified and as directed by Engr-in-charge .
S&F Batten for LED tube light fixture with extruded aluminium heat sink,environmental friendly energy efficient ready to use with 18/20W LED 6000K(4') including electric connection with PVC copper flexible three core cable 24/.0076 from ceiling rose to light fitting ,complete all as specified and as directed by Engr-in-charge .
S & F ,in repair, modular switch 1 way 6A, 1 module ,complete all as specified and as directed by Engr-in-charge .
S & F ,in repair, Switch piano, flush type, single pole, one way, 5 Amp,240V ,complete all as specified and as directed by Engr-in-charge.
S & F ,in repair, modular switch 1 way 16A, 1 module ,complete all as specified and as directed by Engr-in-charge .
S & F ,in repair,ceiling roses, surface bakelite 65x50mm ,3 terminals 3 phase, PVC/Polycarbonate, isolated body all as specified and directed at site,complete all as specified and as directed by Engr-in-charge.
S & F ,in repair,Modular socket 6A/16A-2/3 pin combined 2 modulas flush type 220 V ,complete all as specified and as directed by Engr-in-charge .
S & F ,in repair, capping casing 20mm width ,complete all as specified and as directed by Engr-in-charge.
S & F ,in repair, Modular fan regulator Electronics step type 80 watts 2 moduls and connecting ,complete all as specified and as directed by Engr-in-charge .
S & F ,in repair, fan regulator Electronics step type 80 watts and connecting,complete all as specified and as directed by Engr-in-charge .
S & F ,in repair, Modular Bell push button flush type 5 Amps ,complete all as specified and as directed by Engr-in-charge .
S & F ,in repair, Bell push button flush type 5 Amp,240v ,complete all as specified and as directed by Engr-in-charge .
S & F ,in repair, and fix bell multi musicAC 230 volt single pole ,complete all as specified and as directed by Engr-in-charge .
S & F ,in repair, Modular switch socket combination 16A,6 pin.3 module flush type 220 V ,complete all as specified and as directed by Engr-in-charge .
S & F ,in repair, switch socket combination 2 in 1,3 pin,5 and 15 Amps flush type 220 V ,complete all as specified and as directed by Engr-in-charge .
S & F ,in repair, switch socket combination 2 in 1,3 pin,5 Amps flush type 220 V ,complete all as specified and as directed by Engr-in-charge .
S & F ,in repair, switch flame proof rotary type with termination box in LM-6,16A,single pole 250Volt ,complete all as specified and as directed by Engr-in-charge .
S & F ,in repair, lamp holder,PVC/Polycarbonate type with back plate suitable for batten fitting ,complete all as specified and as directed by Engr-in-charge .
S & F ,in repair, LED lamp 7 watt,220 volt ,complete all as specified and as directed by Engr-in-charge .
S & F ,in repair, Modular white cover plate with frame suitable for 1 module ,complete all as specified and as directed by Engr-in-charge.
S & F ,in repair, Modular white cover plate with frame suitable for 2 module, complete all as specified and as directed by Engr-in-charge.
S & F ,in repair, Modular white cover plate with frame suitable for 3 module ,complete all as specified and as directed by Engr-in-charge.
S & F ,in repair, Modular white cover plate with frame suitable for 4 module ,complete all as specified and as directed by Engr-in-charge.
S & F ,in repair, Modular white cover plate with frame suitable for 6 module ,complete all as specified and as directed by Engr-in-charge.
S & F ,in repair, Modular white cover plate with frame suitable for 8 module ,complete all as specified and as directed by Engr-in-charge.
S & F ,in repair, Modular Metal flush box suitable for 1/2 module, complete all as specified and as directed by Engr-in-charge.
S & F ,in repair, Modular Metal flush box suitable for 3 module ,complete all as specified and as directed by Engr-in-charge.
S & F ,in repair, Modular Metal flush box suitable for 4 module ,complete all as specified and as directed by Engr-in-charge.
S & F ,in repair, Modular Metal flush box suitable for 6 module, complete all as specified and as directed by Engr-in-charge.
S & F ,in repair, Modular Metal flush box suitable for 8 module, complete all as specified and as directed by Engr-in-charge.
Taking down the ceilling fan with and including cleaning the dust,drit ,greasing,serviceing ,repairing and refixing the original position , complete all as specified and as directed by Engr-in-charge. Note:- Necessary spare for repairing will be measured and paid in respective items of Sch A as a supply only.
Taking down unserviceable wall mounted fan of any capacity or size,including cleaning the dust,drit ,greasing,serviceing ,repairing and refixing the original position , complete all as specified and as directed by Engr-in-charge. Note:- Necessary spare for repairing will be measured and paid in respective items of Sch A as a supply only.
Supply only Gun metal bush suitable for particular make of fan of 1200mm sweep ,complete all as specified and as directed by Engr-in-charge.
Supply only Gun metal bush suitable for particular make of exhaust fan of 400/450 mm sweep,complete all as specified and as directed by Engr-in-charge.
Supply only ball bearing suitable for particular make of fan of 1200 mm sweep ,complete all as specified and as directed by Engr-in-charge.
Supply only ball bearing suitable for particular make of exhaust fan of sweep 300mm/450 mm ,complete all as specified and as directed by Engr-in-charge.
Re winding ceilling fan with super enamelled copper wire suitable gauge to get designed condition of speed for the particular make of fan including insulating, varnishing, providing sleeves to copper wire and testing for good running condition of sweep1200 mm ,220 volt ,50 HZ,single phase, complete all as specified and as directed by Engr-in-charge
Re winding exhaust fan with super enameled copper wire suitable gauge to get designed condition of speed for the particular make of fan including insulating, varnishing, providing sleeves to copper wire and testing for good running condition of sweep 300 mm ,220 volt ,50 HZ,single phase,all as directed
Re winding wall mounted fan with super enameled copper wire suitable gauge to get designed condition of speed for the particular make of fan including insulating, varnishing, providing sleeves to copper wire and testing for good running condition of sweep 400/450 mm ,220 volt ,50 HZ,single phase, all as directed
Repair/replacement of industrial type exhaust fan from its position with rusted frame and flap and repair with super enameled copper wire suitable gauge to get designed condition of speed for the particular make of fan including insulating, varnishing, providing sleeves to copper wire with frame and flap and testing for good running condition of sweep 300/450 mm ,220 volt ,50 HZ,single phase, complete all as specified and as directed by Engr-in-charge.
S&F ceilling fan of size 1200 mm sweep 5 star rating complete all as specified and as directed by Engr-in-charge.
S&F fresh air fan steel body of size 300 mm sweep ,complete all as specified and as directed by Engr-in-charge.
Supply & fix condenser 2.5 Mfd/3.5 Mfd capacity ,complete all as specified and as directed by Engr-in-charge.
Supply & fix Capacitor 4Mfd suitable for exhaust fan of sweep 300mm/450mm ,complete all as specified and as directed by Engr-in-charge.
Taking down sub main wiring of any size complete and making good disturbed surface of walls/floors etc ,complete all as specified and as directed by Engr-in-charge.
M & L for submain wiring with two runs of single core PVC insulated unsheathed FRLS copper conductor as mentioned below of similar type cable multistranded copper conductor 1100 volts grade IS:694 marked drawn in and including 25mm dia PVC non metallic PVC conduit , medium grade, ISI marked complete with all acessories and fittings laid/fixed concealed in wall/ceiling or surface conduit on wall/ceiling, and connecting to common earth dolly ,complete all as specified and as directed by Engineer-in-Charge. (Note : Cutting chases for counduit and sinking for boxes and making good to walls ,floors etc for sub main wiring will be measured & paid separately in respective items). of the following sizes:-
Cable of size 2X4 sq mm and 1X4 sq mm earth continuity conductor
Cable of size 2X6 sq mm and 1X6 sq mm earth continuity conductor
Cable of size 2X6 sq mm and 1X6 sq mm earth continuity conductor
M & L for submain wiring with two runs of single core PVC insulated unsheathed FRLS copper conductor as mentioned below of similar type cable multistranded copper conductor 1100 volts grade IS:694 marked drawn in CASING CAPPING , medium grade, ISI marked complete with all acessories and fittings laid/fixed concealed in wall/ceiling or surface capping on wall/ceiling, and connecting to common earth dolly ,complete all as specified and as directed by Engineer-in-Charge.of the following sizes:-
Cable of size 2X4 sq mm and 1X4 sq mm earth continuity conductor
Cable of size 2X6 sq mm and 1X6 sq mm earth continuity conductor
Taking down unserviceable and dislocated conductor strip of any type from wall/floor/roof/ inter connection grid for of any size , complete all as specified and directed by Engr-in-charge.
Refixing the Old serviceable copper strip 20x3.15 mm on the existing location after necessary repair , complete all as specified and directed by Engr-in-charge. Note-Copper strip to be jointed through brass nut,bolt and washer only
S&F,in repair, aluminium strip of 25x3mm as roof conductor and down conductor till test point all as directed by.Note-Aluminium strip to be jointed through nut,bolt and washers only ,complete all as specified and as directed by Engineer-in-Charge.
S&F,in repair,copper strip of 20x3.15 mm as roof conductor and down conductor till test point ,complete all as specified and as directed by Engineer-in-Charge. Note-Copper strip to be jointed through brazzing only
S&F,in repair, Porcelain insulators of Copper/Aluminium strip on wall / on Roof building with necessary screws washers and nut bolts etc complete all as specified and as directed by Engr-in-charge. Note - Rates are inclusive of copper screws with washers for fixing copper strip on Porcelain insulator with minimum size 1 inch and maximum size 1.5 inch with max external dia of screw is 8mm and 2 nos of GI nut for fixing insulator on wall all as per site requirement ,complete all as specified and as directed by Engineer-in-Charge.
Taking down unserviceable and dislocated air termination rod of any type from floor of any size ,complete all as specified and as directed by Engineer-in-Charge.
Refixing Old serviceable copper air termination rod on the existing location after necessary repair,complete all as specified and directed by Engr-in-charge. Note- Copper strip to be jointed through brass nut,bolt and washer only
S&F single pointed soild aluminium rod 300mm long and 12mm dia fixed on suitable flat mounted plate and connected with roof/dowen conductor all as specified and directed.
S&F single pointed soild copper rod 300mm long and 12mm dia fixed on suitable flat mounted plate and connected with roof/down conductor all as specified and directed.
Material and labour for earth pit chamber of size 0.6mx0.6mx0.6m made with PCC 1:2:4 type B-2 including HDPE earthing pit cover inspection chamber of size 200 mm depth, 300mm length and 300mm width ,complete all as specified and as directed by Engineer-in-Charge.
M&L for periodical testing and measuring the earth resistance value of the existing earthings / Down conductor / air terminal by means of wheat stone bridge method after disconnecting the earth continuity conductor from the test point , applying secondary voltage across the terminals, maintaining proper record of the measurement in presence of the users rep, MES rep, submitting the test records, pouring saline water in the earth pit to achieve low earth resistance, observing the same complete for monthly/Quarterly/Half yearly L2/L3 eqpts/E&M installations/Lightning arresters test ,complete all as specified and as directed by Engineer-in-Charge.
S&F in repair, MCB distribution board double Door of sheet metal TPN 4 way with 200 amps rated bus bar 415 volts ,complete all as specified and as directed by Engineer-in-Charge.
S&F in repair, MCB distribution board double Door of sheet metal Single pole and neutral 8 way with 200 amps rated bus bar 240 volts ,complete all as specified and as directed by Engineer-in-Charge.
S&F MCB ,SPN 240 volt 32/40/63 Amp ,complete all as specified and as directed by Engineer-in-Charge.
S&F MCB ,TPN 415 volt 63 Amp ,complete all as specified and as directed by Engineer-in-Charge.
S&F MCB single Pole 240 Volts 6 to 40 Amp ,complete all as specified and as directed by Engineer-in-Charge.
S&F,in repair, Test point terminal block made of gun metal or phosphorus bronze of size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw ,complete all as specified and as directed by Engineer-in-Charge.
M & L for Earthing complete with galvanised steel earth plate electrode of size 600 x 600 x 6mm thick burried directly in ground earth pit not less than 2.25 mtr deep below normal ground level with top edge of the plate vertically to a depth of not less than 1.5 mtr below ground level connection to and including 4mm dia (8 SWG) GI earth wire from earth plate to main switch board including necessary GI bolts, nuts, check nuts, washers, thimble etc to the extend 7.5 mtr as earth lead by means of GI bolts & nuts etc, connecting to LT panel wlith provision of charcoal and salt all as per electrical plate No 3 of SSR Part-I including PCC chamber in 1:3:6 type C2 , CI cover, protection and watering pipe, funnel, mesh etc all as required at site ,water arrangement with GI pipe 20mm dia (medium grade) excavation and earth work returning , filling, ramming and remove of soil to a distance not exc 50 mtr, make good to match with existing surface and testing on completion.Note: (i) 7.5 RM GI earth wire is deemed to be included in quoted rates beyond 7.5 RM shall be measured and paid separately. (ii) Earth resistance of earth pit should be less than 1.0 Ohms. On testing after completion if the desired earth resistance is not obtained the earthing will be redone at no extra cost.(iii) Rate quoted by the tenderer is deemed of include salt & charcoal upto & above 450 mm top of eathing plate (iv) PCC chamber shall be constructed at least 1.5 m away from the earth electrode and pipe for watering shall be in slanting manner.
Ditto as per Srl Item no 79.00 above but GI Strip of size 25X4mm
Ditto as per Srl Item no 79.00 above but GI Strip of size 32X6mm
Ditto as per Srl Item no 79.00 above but copper plate 60×60cm ×3.15mm thick electrode and 20×3mm copper strip as earthing lead
M & L for maintenance free chemical Gel based earthing, Pure Copper type having 50 mm dia 3 mtr long copper pipe(Wall thickness of 3.2 mm) and 7.50 m long Copper strip earthing electrode of size 25 x 3 mm with 60 Kg ENNOV back fill compound , Model No ELE-350-CU of INNOV Infra Solution Ltd including necessary excavation and earth work in any type of soil, perforated watering pipe, funnel with wire mesh, earth lead protection pipe light grade, PCC Chamber 1: 3 :6 type C1 ( for even finish on both the faces ) and RCC cover 1:2:4 type B1, 550 x 550 x 50 mm thick with 8 mm dia TMT bars 150 mm c/c both ways with 2 Nos of handles of 10 mm dia all as required at site including testing on completion and taking down of old earthing all as directed by Engr in-Charge Note : (1) 7.50 RM copper earth strip including GI pipe of 40mm dia light grade is deemed to be included in the quoted rates, beyond 7.50 RM shall be measured and paid separately. (2) Earth resistance of earth pit should be less than 1.0 Ohms on testing after completion. If the desired earth resistance is not obtained the earthing will be redone at no extra cost.
Supply and fix distribution board made out of sheet metal, powder coated, factory made enclousure, double door type, TPN 4 way vertical type, with 200 Amps rated copper bus bar, neutral bar, earth bar, TP 43 protection including provision of housing of incomer MCCB 63 Amps, triple pole and neutral, 415V, 16 KA breaking capacity and fixing of DB flush to wall surface complete all as specified and directed.
Taking out old unservicable LT UG cable of 4/3.5 core x 10Sqmm to 150 Sqmm size and shall be deposited to place where as directed ,complete all as specified and as directed by Engineer-in-Charge.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 150 sq mm 3½core ,complete all as specified and as directed by Engineer-in-Charge.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 sq mm 3½core ,complete all as specified and as directed by Engineer-in-Charge.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 70 sq mm 3½core ,complete all as specified and as directed by Engineer-in-Charge.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 sq mm 3½core ,complete all as specified and as directed by Engineer-in-Charge.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35 sq mm 3½core ,complete all as specified and as directed by Engineer-in-Charge.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 sq mm 4 core.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 sq mm 4 core.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 6 sq mm 4 core.
Excavation in trenches, n exc 1.5 mtr wide and n,exc 1.5 mtr in depth; for foundation etc. or for shafts, wells cesspit, manholes, pier holes,etc n,exc 10 Sqm on plan and n exc 1.5mtr in depth and getting out as in Soft/loose Soil,complete all as specified and directed by Engg-in-Charge.
Returning, Filling in including Spreading, Levelling, Watering, Well Ramming in Layers not exc. 25 Cm, in Soft/Loose Soil, complete all as specified and directed by Engg-in-Charge.
Removing excavated material n exc. 50m in soil and depositing where directed at a level n exc. 1.5 m above the starting point , including loading, unloading and stacking at the destination , complete all as specified and directed by Engr-in-charge.
M&L for Sand cushioning for UG cable protection/ducts, consolidated sand compacted with clean dry sand , complete all as specified and directed by Engr-in-charge.
M & L for Boring of road crossing in any kind of soil/rock strata , complete all as specified and directed by Engr-in-charge.
Supply and laying un reinforced precast concrete cable cover class LV, type-I, flat size 250mm x 150mm x 40mm laid in trenches ,complete all as specified and as directed by Engineer-in-Charge.
Supply & laying,in repair, GI pipe light graded of size 50mm dia in trenches and fixing on wall / pole with help of suitable size MS clamp for cable protection with all fitting; complete all as specified and directed by Engr-in-charge.
S&F ,in repair, GI pipe light grade of size 15 mm dia fixing on pole/laid in trenches
S&F ,in repair, GI pipe light grade of size 40mm dia fixing on pole/laid in trenches
S&F ,in repair, GI pipe light grade of size 80mm dia fixing on pole/laid in trenches
Supply, perform, testing, commissioning ,in repair, of LT cable straight through joint kit heat shrinkable of 4 core x 10/16/25 Sqmm size , complete all as specified and directed by Engg-in-Charge. Make : Denson Part No : XSS-02/Raychem / M-Seal/ Birla-3M
Supply, perform, testing, commissioning ,in repair,of LT cable straight through joint kit heat shrinkable of 3.5 core x 35/50 Sqmm , complete all as specified and directed by Engg-in-Charge. Make : Denson Part No : XSS-02/Raychem / M-Seal/ Birla-3M
Supply, perform, testing, commissioning ,in repair, of LT cable End through joint kit heat shrinkable of 3.5 core x 50/70 Sqmm size complete all as specified. Make : Denson Part No : XSS-02 /Raychem / M-Seal/ Birla-3M
M&L for providing Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts,ashers,welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint , complete all as specified and directed by Engg-in-Charge.
Disconnecting of LT supply and opening bus bar chamber / Cable box chamber of outdoor/ indoor LT kiosks / Panel , removing of burnt out lugs, MCB / isolators of any capcity/ size and cleaning of bus bar with CTC solutions, insulating the bus bar by taping with RYB colours, necessary nuts bolts of existing size and refixing after rapairs,complete all as specified and directed by Engineer in charge. (Note: Aluminium lugs and MCCB as required for repair shall be measured and paid separately under relevent item of Sch A as supply only.)
Supply only aluminum lugs suitable for Cable of the following sizes:- Make : Denson/Raychem / M-Seal/ Birla-3M
Of size 10 Sqmm to 16 Sqmm
Of size 25 Sqmm.
Of size 35 Sqmm.
Of size 50 Sqmm.
Of size 70 Sqmm.
Of size 95 Sqmm.
Of size 120 Sqmm.
Of size 150 Sqmm.
Supply only MCCB 4 pole 63 A , 415 V, 50Hz having breaking capacity 16 KA with adjustable thermal & magnetic setting complete all as spd and directed by Engr-in-Charge.
Supply only MCCB 4 pole 100 A , 415 V, 50Hz having breaking capacity 16 KA with adjustable thermal & magnetic setting complete all as spd and directed by Engr-in-Charge.
Supply only MCCB 4 pole 160 A , 415 V, 50Hz having breaking capacity 35 KA with adjustable thermal & magnetic setting complete all as spd and directed by Engr-in-Charge.
Supply only MCCB 4 pole 200 A , 415 V, 50Hz having breaking capacity 36 KA with adjustable thermal & magnetic setting , complete all as specified and directed by Engr-in-Charge.
Supply only MCCB 4 pole 250 A , 415 V, 50Hz having breaking capacity 35 KA with adjustable thermal & magnetic setting , complete all as specified and directed by Engr-in-Charge .
S&F Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for LT, 20x15cm size complete all as spd and directed.
Inspection/checking & testing after repair of APFC panel 3 Phase,440 voltage 50Hz AC supply system to improve power factor 0.80 to 0.99 automatic step wise switched capacitor panel to make it serviceable in auto and maunal mode, with the help of connecting relays, capacitors,contactors,MCB's.,CTs, re-wiring burnt/worn out control wires etc and rectifying the defects, replacement of unserviceable parts as required at site and cleaning of AMF panel as detecting during inspection or pointed out by department and carry out maintenance complete all as specified as directed by Engineer-in-Chrage. (Notes :-This items includes the cost of cleaning & rewiring of panel. Fixing of new Spare parts and removing old spares shall be included in Quoted rate only spares (i.e Material) use for repair shall be measured and paid separately under respective items as supply only)
Supply only in replacement of APFC microprocessor based relay 8 stage PFC controller ,230 volts complete all as specified and directed by Engineer-in-Charge. Make- L&T/EPCOS/Siemens
Supply only Heavy duty capacitor 3 Phase,415 Volt, AC, 50 Hz of capacity 10 KVAR complete all as specified and as directed by Engineer-in-Charge.
Supply only of Heavy duty capacitor 3 Phase,415 Volt, AC, 50 Hz of capacity 15 KVAR complete all as specified and as directed by Engineer-in-Charge.
Supply only capacitor duty contactor 3 phase suitable upto 20 KVAR capacity 240 volts complete all as specified and as directed by Engineer-in-Charge.
Supply only capacitor duty contactor 3 phase suitable upto 16 KVAR capacity duty contactor 1NO1NC 240 volts complete all as specified and as directed by Engineer-in-Charge.
Supply only current transformer of ratio 200/5, 10 VA with accuracy of 1.0 including connection with 2.5 Sqmm twin core PVC cable complete all as specified and as directed by Engineer-in-Charge.
Supply only current transformer of ratio 100/5, 10 VA with accuracy of 1.0 including connection with 2.5 Sqmm twin core PVC cable complete all as specified and as directed by Engineer-in-Charge.
Supply & fixing in repair of MCB 6 to 32 Amps, 3 Pole,10 KA coplete all as specified and directed by Enginner-in-Charge.
Supply & fixing in replacement indictor lamp assembly LED type complete including connection with 2.5 Sqmm twin core PVC cable complete all as specified and as directed by Engineer-in-Charge.
Supply & fixing Start/stop push button complete including connection with 2.5 Sqmm twin core PVC cable complete all as specified and as directed by Engineer-in-Charge.
Supply & fixing in replacement of digital type voltmeter 96 mm x96 mm, of range 0-500 Volts,Class-I complete all as specified and as directed by Engineer-in-Charge.
Supply & fixing in replacement of digital type ammeter 96 mm x96 mm, of range 0-200 Amps,Single Phase complete all as specified and as directed by Engineer-in-Charge.
M& L for preparation of existing painted surface of panel board/feeder pillar box (inddor/outdoor type), area not exeeding 10 Square metre each and applying one coat of synthetic enamel paint after preparation of surfaces on external and internal surfaces of approved tint by using spray machine (not exceeding of height 5 cm each) including welding of broken panel, tightening electric connection of switch gear and cleaning of vegetation all around the panels upto one meter from all sides complete all as specified and as directed by Engineer-in-Charge.
S&F in replacement heavy duty TPN bus bar chamber 100 Amps,4 way fixed with hinges and locking arrangments for 4 Nos incoming/outgoing connection each bus bar fixed on wall complete all as specified and directed by Engr-in-Charge.
M&L for fixing MS sheet 2mm thick to existing LT panels / feeder pillar box including necessary straightening /correcting the distorted parts, cuttings, welding / riveting,drilling bend to shape as required, welding of hinges, sliding door bolts, locking arrangement, nut, bolts, washers etc and appying two coats of synthetic enamedled paint over a coat of red oxide primer to match with the existing surfaces comlepte including butt hinges sliding door bolts and taping , thimbling disconnecting all incoming and outgoing complete all as specified and as directed by Engineer-in-charge. Note :- Supply only butt hinges and sliding door bolts shall be measured and paid seperately.
Material and labour for carrying out repair/maintenance through manufacturer or authorised service center of Auto servo control voltage stabilizer 300KVA capacity located at HQ area . (i)Opening of stabilizer and maintanance of spare parts,fixing of new/repaired parts after repair in place of defective parts,repairing the defective control system etc and assembling complet all as specified and directed. (ii) Testing of stabilizer after repair on existing location to desired and rated output. Note:- All defective parts maint and cost of labour for maint is deem too be included in unit rate .
Taking down Defective street light of LED of Capacity 25/30/60/90 W, flood light and bldg security light fitting of any type from their existing postion ie. Poles and bldg and re-fixing the same after carried out repairs/replacement of LED driver and SPD,PVC Wire etc all as specified and directed by Engr In Chrarge. Note: LED Driver,SPD and 3 core cable for replacement shall be measured and paid separatly under relevent item of Sch 'A' as supply only.
Supply only Surge protection device (SPD) of capacity as mentioned below, with phase ,neutral and earth wire in incoming and out going both sides, complete all as specified and directed by Engg.in.Charge. Make: Bajaj/Havells/Crompton.Of the following Capacity:-
Of capacity 8 KV
Of capacity 5 KV
Supply only LED driver for LED Street light Fitiing ,of the following,complete all as specified and directed by Engg-in-Charge.Make: Bajaj/Havells/Crompton
for 25 Watt
for 30 Watt
for 60 Watt
for 90 Watt
Supply only 3 core 1.5 Sqmm, 1100 volt grade heavy duty cable PVC insulated copper conductor, served with inner sheathing of PVC tap and over all PVC sheathed in service connection for street light from FRP junction box to street light ,complete all as specified and directed by Engg-in-Charge.
Supply, fixing and testing LED street light fitting including LED lamps complete with body robust,corrosion resistant,superior finish and without any cracks or through holes,made in a single piece by high pressure die cast aluminium alloy.The luminaries shall be monolithic construction totally enclosed dust and water proof with minimum IP -66 protection as per IS - 10322-1982(Part -I) with latest amendments and input voltage range 140 - 270 V, AC, frequency 50 - 60 Hz ,P.F should be more than 0.9 with Total Harmonic Distoration THD(I) less than 10% ,cool white colour and lamp starting time should not be more than 10 second. Fitting should be provided with 10 KV surge protection.Driver should be constant current constant voltage driver .Driver should have high voltage withstanding capacity upto 300 V, AC. Driver should also have double phase protection,no load , open circuit and short circuit protection .LED light fitting should be suitable for ambient temperature from -10 degreeCentrigrade to 50 degree Centrigrade and humidity level 10% to 90 % RH. Covers should be polycarbonate/toughened glass to ensure minimum IP 65 degree protection.Cover should not degrade due to heating and ageing.The efficiency of LED luminaries system shall be more than 85 lumens per watt and must be certified by the LM-79 test report ,complete all as specified and directed by Engg-in-Charge .Of the following:-
For 25 Watt
For 60 Watt
Supply, fixing and testing LED Flood light fitting in repair/replacement of existing high mast lights including LED lamps complete with body robust,corrosion resistant,superior finish and without any cracks or through holes,made in a single piece by high pressure die cast aluminium alloy.The luminaries shall be monolithic construction totally enclosed dust and water proof with minimum IP -66 protection as per IS - 10322-1982(Part -I) with latest amendments and input voltage range 140 - 270 V, AC, frequency 50 - 60 Hz ,P.F should be more than 0.9 with Total Harmonic Distoration THD(I) less than 10% ,cool white colour and lamp starting time should not be more than 10 second. Fitting should be provided with 10 KV surge protection.Driver should be constant current constant voltage driver .Driver should have high voltage withstanding capacity upto 300 V, AC. Driver should also have double phase protection,no load , open circuit and short circuit protection .LED light fitting should be suitable for ambient temperature from -10 degreeCentrigrade to 50 degree Centrigrade and humidity level 10% to 90 % RH. Covers should be polycarbonate/toughened glass to ensure minimum IP 65 degree protection.Cover should not degrade due to heating and ageing.The efficiency of LED luminaries system shall be more than 85 lumens per watt and must be certified by the LM-79 test report ,complete all as specified and directed by Engg-in-Charge . Of the following:-
Of 120 Watt
Of 80 Watt
Cutting/Trimming of tree branched not exc 10 cm girth touching /approaching the LT/HT Over head line (having each span of 45 mtr) upto 3 mtr width on each side with cutting machine or manually to clear the LT/HT line including disposal of trimmed branches 100 mtrs away inside the cantonment area & cleaning site ,complete all as specified and directed by Engg-in-Charge. ( Note : All tools and plant required for cutting shall included in quoted rates)
S&F 1100 volts grade heavy duty cable PVC insulated aluminium conductor, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 metre apart including 4mm suspension wire, one twin core cable flat , complete all as specified and directed by Engg-in-Charge.of the following sizes:-
For flat of size 6 Sqmm
For flat of size 10 Sqmm
Supply and fixing HOT moulded (FRP) junction box for street light pole with locking arrangement with IP 65 protection of size 280 x 200 with 32 Amp 4 way heavy duty terminal block with 10Amp MCB SP and two number of cable entry gland of standard size with suitable stainless steel bracket to fix with pole, including taking down existing , complete all as specified and directed by Engg-in-Charge.
Supply & Fixing LED Bollard light 9/10 watts with opal acrylic diffuser and IP-65 protection , pressure die cast housing with PC diffuser, suitable for garden and pathway complete with internal connection including suitable size of stand for LED garden light of 9/10 Watts capacity , complete all as specified and directed by Engg-in-Charge. Make: Bajaj cat part No. BGBOM 650 9W LED/Halonix Cat Part No.HLOB-03-10 CW/Crompton Cat part No.LBLA2-10-CDL Note : Warranty and test certificate of LED light fittings to be produced as and when asked by Engr-in-charge.
Supply and fixing MCB DB single door vertical type for 2 way 240 volt SPN confirming to IP-45 protection and IS 13032 , complete all as specified and directed by Engg-in-Charge.
M&L for PCC 1:2:4 type B-1 using 20mm graded stone aggregate, in lintels upto 1.5 m clear span, cills, steps; seismic and other similar bands, plinth courses, string courses, lacing courses, parapets and railings upto 60 cm in height, copings, kneelers, apex stones, bed plates, kerbs not provided for in Item 04028, water troughs and the like including weathering, slightly rounded for chamfered angles and throating, complete all as specified and directed by Engr-in-charge.
M&L for Plain Cement concrete in foundations, filling and mass concrete , type D-2 (1:4:8) using 40mm graded stone aggregate as in foundations, filling & mass concrete, complete all as specified and directed by Engr-in-Charge.
Taking down complete defective high mast light system by using suitable size of Crane reach up to 20 mtr height and removing complete defective rope of 6 mm dia 97/19 gauge with 3 phase power motor, electrical cable 6 sqmm 3 phase and gear box including Supply and fix the same with new one and checking , servicing complete high Mast system like electrical wiring , greasing in all moveable parts as specified by Engr in Charge.
M/S KHUSHI ENTERPRISES
sapana enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .