GE (AF) Gurgaon
GE AF GURGAON
REPAIR COMPREHENSIVE MAINTENANCE OF VRV AC A and B GROUP CASSETTE AC PRECISION AIR CONDITIONER HI-WALL SPLIT AC UPS AND OTHER ALLIED WORKS AT IMAC STN NTS GURGAON UNDER AGE EM AF GURGAON OF GE AF GURGAON
2021_MES_445466_1
GE/GUR-/NIT-06/2021-22
Open Tender
Miscellaneous Works
Works
335 days
GE (AF) Gurgaon
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE (AF) Gurgaon
Yes
20 Jul 2021
24 May 2021
23 Jun 2021
24 May 2021
21 Jun 2021
7 Jun 2021
Amount
Comprehensive, preventive and periodical maintenance of VRV AC A&B Group(Make: VOLTAS, Model: VDV-450(16) W/DRNI C) of capacity (total outoodoor of capacity -96 HP or total Indoor capacity- 97.5 TR, (indoor unit -2TR-12 Nos, 03 TR-7 Nos, 04 TR-7 Nos, 1.5 TR-8 Nos, 2.5 TR-5 Nos) by Inspecting the plant system and carry out quarterly inspection as a part of preventive maintenance with relevant PM checklists, Checking the refrigeration system, motor and starters and ensuring healthy condition of the plant,Checking the system for any leaks and rectification of leaks found, Taking set of readings and evaluating to ensure satisfactory performance of the plant, Checking the Refrigeration control system for operation and adjusting the settings, Checking the functioning of compressors and its accessories, Cleaning the IDU evaporator ODU condenser coils once, Lubricating the bearings of motors, & fans when found necessary, Quarterly inspection of belts adjusting the tension and replacing the worn out belt as and when found required, Replenishment of refrigeration gas as a result of fare wear and tear, Overhauling the components of the equipment at site or in service station as and when required, Checking of the microprocessors PCBs and sensors of IDU/ODU units for its proper functioning and repair replacement of the same if found necessary, Attending to complain breakdown calls whenever required, Reporting the healthiness of the plant and suggesting improvements if any, all as per OEM Insruction and directed by Engr-in-Chage.
The fwg Ser Item No 2.01 to 2.19 for replacement not included in the quoted rates by the contractor under comprehensive/preventive/periodical maintenance for VRV AC A&B group under item Ser No 1 shall be measured and paid separately.
Fan motor Inverter PCB 8 - 16 HP
Electronic Expansion Valve wire
Main IPM Service Pack
Fan relay control board
Lightning Proof Board
Aluminium Electorally capacitor
Magnetic Contactor A26D-30-01
DC fan motor ZKSP-560-8-1
AC fan YKS-380-4-1
Solenoid valve
Electronic Expansion Valve
Axial Flow Fan
Main Control IPM Card
Compressor IPM Card
Inverter Compressor
Fix Compressor
Four -way reverse valve
Refrigerant R410A
Copper condenser coil of existing make
Comprehensive, preventive and periodical maintenance of 3 Nos Precision AirConditioner of capacity each 23 TR Each (Make: STULZ Chspl INdia, Model No-SEC852A, Microprocessor type C-7000) ,by Inspecting the plant system and carry out preventive maintenance as per the standard practice monthly in contract period, Checking the refrigeration system, motor and starters and ensuring healthy condition of the plant,Checking the system for any leaks and rectification of leaks found,ensure drain is not clogged Taking set of readings and evaluating to ensure satisfactory performance of the plant, Checking the Refrigeration control system for operation and adjusting the settings, Checking the functioning of compressors and its accessories, Cleaning up of units & air filters, check the proper functioning of controllers , Lubricating the bearings of motors, & fans when found necessary,Replenishment of refrigeration gas as a result of fare wear and tear, attend all breakdowncalls with in 2-4 hours, replaced worn out parts with in 24 hours subject to normal working days, Overhauling the components of the equipment at site or in service station as and when required, Checking of the microprocessors PCBs and sensors of IDU/ODU units for its proper functioning and repair replacement of the same if found necessary, Attending to complain breakdown calls whenever required, Reporting the healthiness of the plant and suggesting improvements if any, all as per OEM Insruction and directed by Engr-in-Chage.
Notes for item No 03.00 (a) Following component replacement are deemed to be included in the rate quoted by the contractor under comprehensive maintenance against item Srl no 3.00 (b) Contractor is responsible for repair/replacement of existing make/model of following components:- (c) Compressor, main controller of PAC Units, switch gear components in the unit, Fan motor (Indoor), Fan motor(outdoor), filter drier, solenoid valve, expansion valve, microprocessors PCBs and sensors of IDU/ODU units, condensor coil, charging of Refrigerant gas at any time/specified qty, sensors, capacitors, all worn out PCB card, indicators, wiring/connectors, Door, sob components belts,coils,including all minor/major spare parts. Notes :-(i) The tenderer shall have to replace the U/s material with OEM material only. The cost of replaced major/minor spare parts included in comprehensive maintenance of contract.Old material will be contractor property . (ii) In case any accident occur of any Indl like Mechanic/Helpers/users during maintenance/operation of above mentioned Airconditioner/unit, contractor is liable to pay compensation to the Indl as decided by the competent authority. Principal Employer will not be responsible for the same. (iii) If complaint is not attended by contractor with in five hour the penality of Rs 1000 / per hour to be imposed and amount of penality will be deducted from RAR.
Comprehensive, preventive and periodical maintenance of total 4 Nos UPS of capacity (60 KVA- 02 Nos, Sr No. 201306NR0525, 201306NR0526, 200 KVA- 02 Nos Sr No. 201311NR0591, 201302NR0420) make/model Liebert.NXr/VERTIV Energy Private Limited, by Cleaning up of Unit, Visual Inspection to check any deformation, Checking and Adjustment (If needed) of Power parameters like input. Output, DC voltage & Current, Checking and Adjustment of Control parameters on different PCBs,Tightness of all connection,Functional Checking up of Rectifier section, Functional Checking up of Inverter section, Functional Checking up of Static Switch Section, With user approval, perform operational test of the system including unit transfer and battery discharge, Attending to complain breakdown calls whenever required, UPS failing to transfer to battery mode in the event of incoming power failure, Battery Breaker tripping due to battery failure, Battery Failure, UPS unable to transfer load on to the parallel UPS (Redundancy Failure), UPS tripping on High temperature conditions, Control Card, major components failure such as IGBT’s, SCR’s & Wire wound Components within the UPS, Module Failure, Wire Harness damage, Reporting the healthiness of the plant and suggesting improvements if any, all as per OEM Insruction and directed by Engr-in-Chage. Defective parts discovered during maintenance repaired or replaced by new or as new parts. Spares replaced will be either of the same make or equivalent. Old/U/sParts removed shall be property of contractor. Batteries, Switch gears & Wound components is not part of Comprehensive AMC Contract.
Notes for item No 04.00 (i) The tenderer shall have to replace the U/s material with OEM material only. The cost of replaced major/minor spare parts included in comprehensive maintenance of contract.Old material will be contractor property . (ii) In case any accident occur of any Indl like Mechanic/Helpers/users during maintenance/operation of above mentioned Airconditioner/unit, contractor is liable to pay compensation to the Indl as decided by the competent authority. Principal Employer will not be responsible for the same. (iii) If complaint is not attended by contractor with in five hour the penality of Rs 1000 / per hour to be imposed and amount of penality will be deducted from RAR. (iv) The cost of transportation (to and fro) for all kind of necessary equipment / T&P shall be arranged/brought by contractor to complete the job at site , stationary for maintenance of record, no extra cost shall be paid to the contractor to this effect. (v) Complaint shall be lodged by telephonically ,so contractor to specify the telephone no who will receive the complaint round the clock. After attending the complaint contractor will obtain the signature from rep of User/AGE/GE every day as a token of complaint attended.
Supply and charging refrigerant R-22 Gas of approved make in new sealed cylinder complete all as specified and as directed.
Supply only AC remote suitable for 2.00 ton split AC complete all as specified and as directed.
Disconnecting and taking down old U/S compressor of capacity 2.0 TR from AC and S&F new compressor unit with charging of refrigerent after dehydration testing and vaccumming as per existing model and site requirement complete all as directed. Make: Voltas, Hitachi
M&L for detecting the cause of leakage in any type/capacity of 2.0 tonne AC and ensuring the complete system leak proof and charging of refrigerant gas with appropriate quantity as directed including testing for smooth functioning complete all as specified and as directed. Notes :- (i) Dismantling of unserviceable compressor , cost of refrigarent gas and re-installation of serviceable compressor after repairing are deeemed to be included in the quoted rates.
M&L for rewinding of the blower motor 1/6,1/5,&1/8 HP of AC any type /capacity with same gauge super enamelled copper wire complete including taking out old unserviceable winding kit complete all as specified and as directed.
M&L for comprehensive maintenace of Split type AC capacity 2.0 ton , cleaning of Indoor / outdoor unit , cooling /condensing coil , reinsulation of refrigerant tubing , replacement of worn out spare parts of AC complete all as specified and as directed. Note: Worn out spare parts shall be measured and paid separately under respective items of the Schedule.
Supply & Fixing starting relay of existing makes and capacity duly ISI marked for split type 2.0 Ton capacity complete all as specified and as directed.
Supply & Fixing starting capacitor of existing make and capacity duly ISI marked for split type 2.0 Ton ( 100-120 Mfd) complete all as specified and as directed.
All as per item No-12 but running capacitor 36-45 Mfd ISI marked for split type AC capacity 2.0 ton
M&L for refrigerant tubing 1/4" for suction /discharge including insulation tubing all as per site requirement and as directed by Engr-in-Charge.
All as per item No 14 but 1/2"
S&F in replacement of capacitor 4 Mfd ISI marked complete all as specified and as directed.
S&F PCB card suitable for existing split type AC 2 Ton AC of any make/model -Voltas, Hitachi complete all as specified and as directed.
S&F in replacement hand shut valve suction for split 2 Ton complete all as specified and as directed.
Ditto- but hand shut valve discharge for split AC 2 Ton complete all as specified and as directed.
S&F in replacemnt of condensor coil complete suitable for outdoor unit of split AC 1.5/2.00 ton capacity complete all as per existing make and model complete all as specified and as directed at site by Engineer in charge.
S&F in replacement of cooling coil for split AC 1.5 /2.0 TR capacity complete all as per existing make and model installed at site/ location complete all as specified and as directed at site by Engineer in charge.
M&L for shifting of split AC 2.00 TR includng dismantiling all accessories, indoor outdoor unit and copper insulation, voltage stabiliser and re-installing the all acessories at new location as directed of new copper pipe suction and discharge including insulation and electric cable 3 core , 4 Sqmm as per site requirement is included in the quoted rate complete all as specified and as directed.
M&L for 3 core flexible PVC insulated cord sheathed 2.5 Sqmm including connection all as directed
S&F of cable PVC insulated unarmored for connection 4 Sqmm 3 core copper conductor duly drawn from indoor to outdoor and indoor unit to power point in PVC Flexible pipes complete all as specified and directed. MAKE- 1. Havells 2.phinolex 3. polycab
Taking down old U/S indoor unit after complete opening and S&F in replacement of with new indoor unit of Split type AC of capacity 2.0 TR of existing/or equivalent make model as per requirement including all connections complete all as specified and directred
Taking down old U/S outdoor unit after complete opening and S&F in replacement of with new oudoor unit of Split type AC of capacity 2.0 TR of existing/or equivalent make model as per requirement including all connections complete all as specified and directred
Taking down old u/s AC boxes and S&F new sheet metal enclosure with single pole and neutral enclousure with a two pin and earth plug and socket complete with single pole MCB 20-32 Amps complete all as specified and directed.
national engineering
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .