HQ CE (AF) WAC PALAM
HQ CE (AF) WAC PALAM
PROVN OF INFRASTRUCTURE FOR IAF CERT IN TECH AREA AT MCC AFS BASANTNAGAR
2022_MES_555129_1
CEWAC/PAL/T-22/2022-23
Open Tender
Civil Works
Lump-sum
540 days
GE (AF) FARIDABAD
AS PER NIT
9 documents required · 9 mandatory
₹3,000
GE (AF) FARIDABAD
₹5.8 L
Yes
20 Jul 2023
11 Oct 2022
5 Jun 2023
11 Oct 2022
29 May 2023
15 May 2023
Amount
SCHEDULE `A' PART - I (Building Works) is not prepriced by MES and prepriced rates indicates 0.0 under column 6 signified this fact only.
Lum Sum Price worked out by the contractor for Construction of TECH OFFICE ACCN (CERT), CONTROL BLDG DOUBLE STOREY (G+1) complete all as specified and shown on drawings.
Lum Sum Price worked out by the contractor for Construction of SECURITY WATCH TOWER (THREE STOREY) complete all as specified and shown on drawings.
Lum Sum Price worked out by the contractor for Construction of SENTRY POST complete all as specified and shown on drawings.
Lum Sum Price worked out by the contractor for Construction of SUB-STATION BLDG FOR 125KVA TRANSFORMER complete all as specified and as shown on drawings.
NOTE: Schedule ‘A’ Part II to XI under are Prepriced by MES.
Lump sum price worked out by the Contractor for “SITE CLEARANCE INCL EARTHWORK & EXCAVATION” as listed in Schedule ‘A’ Part II
Lump sum price worked out by the Contractor for “INTERNAL ELECTRIFICATION" as listed in Schedule ‘A’ Part III
Lump sum price worked out by the Contractor for “INTERNAL WATER SUPPLY" as listed in Schedule ‘A’ Part IV
Lump sum price worked out by the Contractor for “ROAD/PATH & CULVERT” as listed in Schedule ‘A’ Part V
Lump sum price worked out by the Contractor for “EXTERNAL ELECTRIFICATION WORK” as listed in Schedule ‘A’ Part VI
Lump sum price worked out by the Contractor for “LIGHTNING PROTECTION” as listed in Schedule ‘A’ Part VI A
Lump sum price worked out by the Contractor for “EXTERNAL WATER SUPPLY ” as listed in Schedule ‘A’ Part VII
Lump sum price worked out by the Contractor for “SEWAGE DISPOSAL” as listed in Schedule ‘A’ Part VIII
Lump sum price worked out by the Contractor for “BOUNDRY WALL, FENCING AND GATE” as listed in Schedule ‘A’ Part IX
Lump sum price worked out by the Contractor for “AREA DRAINAGE” as listed in Schedule ‘A’ Part X
SCHEDULE `A' PART - XII MISC B/R & E/M ITEMS is not prepriced by MES and prepriced rates indicates 0.0 under column 6 signified this fact only.
MISC ELECTRIFICATION ITEMS
S&F ceiling fan 5 star rated 1200mm sweep complete without fan regulator , 230 volts (single phase) and provision of flexible cable cord three core PVC insulated and overall sheathed 3 core flexible copper conductor cable of size 0.50 Sqmm from ceiling rose to fan for giving connection complete all as specified and directed.
S&F energy saving decorative box type batten light fitting 230volts surface mounted with high efficiency PMMA diffuser soft glare free light LED tube light 20watt, blue coloured end caps with all accessories, pre-wired, incl provison of flexible copper wire 3 core cable PVC insulated sheathed complete all as specified and directed.
S&F LED sleek mirror light fitting 10 watts surface mounted provided with high output diffuser 2 feet long, 230 volts complete with all accessories, pre-wired including lamp and providing flexible copper wire, three core cable PVC insulated sheathed complete all as specified and directed.
S&F LED Light fitting Bulk head with high output diffuser 10watt 220 VAC with driver holder PDC housing with opal diffuser equipped with 2KV in built surge protection with IP65 ingress protection rating complete with all accessories pre-wired and connecting electrically with ceiling rose using PVC insulated and overall sheathed flexible copper conductor cable of size 0.75sqmm 3 core complete all as specified and directed.
S&F metal body exhaust fan of size 300mm sweep, 1400 RPM, 1050 CMH (Air delivery) 230 volts, single phase AC supply with louvers complete with nut, bolt & washers, suitably embedded in the wall incl making suitable opening and provision of flexible cable cord three core PVC insulated and overall sheathed 3 core flexible copper conductor cable of size 0.50 Sqmm from ceiling rose to fan for giving connection complete all as specified and directed.
S&F metal body exhaust fan of size 450mm sweep, 1400 RPM, 6120 CMH (Air delivery) 230 volts, single phase AC supply with louvers complete with nut, bolt & washers, suitably embedded in the wall incl making suitable opening and provision of flexible cable cord three core PVC insulated and overall sheathed 3 core flexible copper conductor cable of size 0.50 Sqmm from ceiling rose to fan for giving connection complete all as specified and directed.
S&F braket for street light fitting made out of 40mm GI pipe light grade 1.2mtr long each bent to required shape & size, fixed to pole with and incl flat iron clamps 02 Nos made out of 32x6mm flat iron incl GI nuts, bolts & washer incl painting with 2 coats of aluminium paint over a coat of red oxide primer complete all as specified and directed.
S&F LED security light fitting 30 watts 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection incl fixing to GI bracket and making connections complete all as specified and directed.
M&L incl fixing of modular telephone socket outlet on switch box and plate including making connections as required complete all as specified and directed.
Ditto all as per Srl item No.3.10 above but for RJ-45 COMPUTER socket outlet complete all as specified and directed.
Ditto all as per Srl item No.3.10 above but for TV outlet complete all as specified and directed.
S&F sheet metal enclosures DB Double door Verticle distribution type, 04 way, TPN DB , IP43, 415V & suitable for MCCB TP as incomming including shruded neutral bar & Pan assy with earthing terminal as provided by manufacturer, IP-43 protection ,with 100 Amps rated bus bar breaking capacity 25 kA ,415 volt complete all as specified and directed.
Supply, installation, testing and commissioning of indoor type, floor mounted step down transformer, AC 3 phase, 50 Cycles, 315 KVA, core type, double copper wound, oil immersed, naturally cooled, Oil Natural-Air Natural (ON:AN), with external cooling tubes, delta connected on primary side (HV) and star connected on secondary side (LV) in accordance with vector group DYn-11 with Neutral brought out on secondarv side (LV side) with tap changing arrangement on HV side in TAPPING RANGE ±7.5% IN STEPS OF 2.5% each with Standard Accessories as per IS 1180 with latest amendments & first filling of Transformer Oil. All the technical parameters such as Losses, Impedance, Temperature Rise etc shall be strictly as per IS 1180 or as per latest ammended BIS . Transformer shall be finished with Enamel/Polyurethane paint of a shade corresponding to No 632/631 of IS. The inside of the tank in contact with oil shall be given a coat of hot oil resistant Varnish/Zinc Chromate paint. The maximum temperature rise should not exceed 45 degree celsius in oil and 55 degree celsius in HV/LV winding when measured by resistance method after continuous full load run on an ambient temp of 40 degree celsius. The maximum total losses at 50% load and full load shall be 955 W and 2750 W respectively at 75 degree celcius . The transformer shall comprise of the following:-
(a) One cable box on HT side (primary side) consisting of three nos porcelain bushing with copper rods, complete with nuts and washers, with cable glands. (b) One cable box on LT side (Secondary side) consisting of four nos porcelain bushing with copper rods, complete with nuts and washers, with cable glands. (c) Oil conservaior with filter type drain valve and oil level guage incl first fill with DE-Hydrated transformer oil. (d) De-hydrating breather with first fill of dehydrating agent (silica gel). (e) Explosive vent, Thermometer pocket on tank cover. Oil level gauge, Oil drain fiiter-valve, Lifting lugs, Oil filling hole with cap/plug with connection plate complete, Air release valve plug and four nos plain solid cast steel detachable rollers. (f) One no dial type thermometer, vapour pressure type, having range 0-120 degree celsius with metal guard having maximum perimeter temperature reading indicator with re-setting device. (g) Two earthing terminals on tank cover to facilitate fixing of 32mm x 6 mm galvanised iron earth strip for earthing of body. (h) Rating plate and terminal marking plate. (j) Extra bushing for neutral, in the LT cable box for providing independent set of earthing for neutral. (k) Providing adequate size and nos of channels. embeded in floor, for movement of transformer. Notes:- (i) Drawing of transformers shall be approved by GE before fabrication. (ii) Pre-dispatch inspection of transformer at OEM premises shall be carried out by Rep of accepting officer. Quoted rates will be deemed to include this factor.
M&L for Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure complete all as specified.
Supply, installation, Testing and commissioning of factory made Front operated cubical type compartmentalised, front access Free standing/Wall mounted, dust and vermin proof (IP 42 ingress protection) main LT Panel (indoor type) suitable for use at 415 volts, 3 phase 4 wire 50 Hertz system suitable for fault level of 50 KA for 1 sec, fabricated from 2 mm thick CRCA sheets with hinged, gasketted (metal based neoprene) and lockable doors having structural reinforcement mounted on angle iron frame made out of 50x50x6 mm frame with 6 nos legs not less than 45 cm fixed with nuts bolts of suitable size, including 3 mm thick gland plates on top and bottom and including lifting hooks and including GI earth strip of required size with 2 nos earthing terminals and including powder coated paint finish of approved shade over metal surface cleaned and treated with seven tank process complete with interconnections etc as per specifications, as required and as below:- a) LT Panel shall have provision for entry of cables from the top or bottom as required. b)All live accessible parts shall be shrouded and all equipment shall be finger touch proof. The Busbars insulation shall be with heat shrinkable sleeves. SMC/DMC shrouds and busbar supports shall be used. Padlocking facility shall be provided on all outgoing feeders doors and switch handles shall be lockable in OFF position. (c) Suitable arrangement shall be made for termination of multiple incoming cable. d) All kA values indicated shall be lcs breaking capacity. e) General Arangement drawings shall be got approved by GE before fabrication.
INCOMING a) ACB 4 Pole 630 Amps, 415 Volts with breaking capacity 35KA microprocessor based release type - 02 No. (Incomer from DG Set - 01 Nos, Incomer from T/R-01 No) b) 630 Amp Automatic Advance Version Automobile Load Transformer Switch changeover switch, incorporate 3 stable positions (1-0-11) changeover ensuring· isolation of 2 asynchronous power supply. Position - 0- Circuit I and II Open (Neutral Position), I- Circuit-I close and circuit II open (transformer supply "ON" and genrator supply "OFF"), II- Circuit I open and Circuit 00 close (genertor supply) "ON" and transformer supply "OFF"). Conformity - IS/IEC : 60497-3 & IEC: 60947-6-1, CE Marked, RoHS Compliant. - 01 Nos ( Electrically connected to 1000 Amp Bus bar) c) Multifunctional digital panel meter with LCD backlit display flush mounting type of size 96x96 mm, accuracy class O.5cl, frequency 50 Hz confirming to IP52 with suitable CT having provision of display parameters such as voltage, Amp, Frequency, Power factor, KW, KV etc - 1 No. d) Three phase (red, yellow, blue) indicating lamps -1 No. ( set of Three) BUSBAR Electrolytic high conductivity Aluminium bus bar duly drilled holes for connections and mounted on epoxy based post insulator for 3 phase 4 wire 50 Hz AC supply rated at 1000A suitable to with stand fault level of 50 kA.
OUTGOING a) 250 A, 415V, 35 kA, 4Pole MCCB with thermal magnetic releases control unit for protection -2 Nos (Ground floor -01 Nos, 1st Floor-01 Nos) b) 40 A, 415V, 10 kA, 4Pole MCB with thermal magnetic releases control unit for protection-4 Nos (S/S Bldg - 01 Nos, Watch Tower - 01 Nos , High Mast light - 01 Nos & santry post - 01 Nos) c) Time switches astro type (Having longitude and latitude of Indian cities in memory) 230 V single phase of 20 Amps rating with suitable contactor- 01 Nos. The Panel shall be complete with all inter connections, risers, internal wiring, labels etc complete as required
M&L for providing route indicator made out of PCC 1:2:4 and MS Bar 8 mm of size 90cmx35cmx50mm duly painted in the requisite colour sceam for HT 11 KV underground cable complete all as specified and directed.
S&F factory made junction box of size 300x160x250mm made out of 2mm thick CRCA powder coated sheet, including 63 Amp three phase 4 wire having 4 nos of aluminium bus bar including 6 Amp SP MCB. The box should have auto door lock facility with magnetic lock fixed on pole using using necessary fixing arrangement such as clamps, nuts, bolts , washer etc complete all as specified and directed.
Supply and connecting Single core FRLS, PVC insulated copper stranded cable of size 1.5 Sqmm for street light/flood lights passing thorugh pole hole/GI Pipe /PVC Conduit to junction box and connected electrically complete all as specified and directed by Engineer-in-charge
Supply and installation of 16M high mast shaft in two sections suitable for 47 m/s wind speed, with .Each Latching type head frame, winch mounting bracket, luminaries carriage suitable for installation of 8nos of 150w Flood light luminaries in symmetrical arrangement comprising of following:- HIGH MAST SYSTEM Height of mast: 16 Meter, No. of sections: Two Material construction : S 355 grade as per BSEN 10025 Base dia. and top diameter (A/F) : Top 200mm , Bottom:460mm Plate thickness : Top: 3 mm, Bottom: 4mm Cross section of Mast : 20 side polygon. Standard for of galvanisation : As per BS EN ISO 1461 Size of opening and door at base: 1200 x 250 mm Diameter of base plate : 670 mm , Thickness of base plate : 25 mm Lightning protection finial : G.I single spike Max.wind speed : As per IS: 875 (Part - Ill) for Delhi Area Number of foundation bolts : 08 nos. , PCD of foundation bolts : 590 mm Type /diameter/ length of foundation bolts : TS 600 / 30 mm dia / 85 mm long LUMINAIRES CARRIAGE: Material of construction : 40 NB (50mm) ERW Class B - M.S.Pipe Dia of Carraige ring (mm) - As per OEM Recommendation
Construction - As per OEM Recommendation Raising lowering system comprising double drum winch, 6mm diameter SS wire rope, trailing cable, connector, integral power tool motor, manual handle, junction box, lightening finial. TRAILING CABLE Conductor : Copper, 5 core, 2.5 sqm, Insulation : EPR insulated PCP sheath No. of circuits per mast : One no. cable per mast WINCH/ POWER TOOL Type/ SWL of winch : Double drum, SWL 750 Kg Method of operation : Integral Motor , Motor capacity: 1 HP No of speeds: 6 Pole, Single speed STAINLESS STEEL WIRE ROPE Grade/ construction : AISI 316, 7/19 Construction , Diameter (mm): 6 mm Number of ropes: 2/3 Wire Rope , Breaking load capacity: 2350 kg x 2 Foundation bolt manufactured form special steel along with nuts, washers, anchor plate and common template as per OEM Recommedations. Note:- The quoted rate is deemed to include the cost of aviation obstruction light, Lightening arrestor spike, required suitable size of RCC Foundation for the high mast pole and 4mm GI Wire for earthing connection fro LA spikes at the top of the pole to the earthing point. (i) Erection of the high Mast with the help of suitable equipments and wiring of luminaires with all wiring M&L. (ii) Installation of Control panel on suitable foundation incl M&L. (iii) Detailled specification/Technical data sheet shall be submitted befor erection of High mast. (iv) High Mast must be installed by authorised OEM rep only.(v) Provision of switch socket/starter point with plugtop for power trailling cable in included in unit rate. (iv) Foundation PCC 1:2:4 incl coping of poles.
Supply, instalation, testing and commissioning of Eco freindly not less than 315 KVA Diesel Engine driven generating set with acoustic enclosure made out of CRCA Sheet powder coated, specially designed lifting arrangement/hooks, meet the latest CPCB, norms of 75 dBA @ 1 mtr distance and as per the testing guide line of CPCB, DG Set shall be conforming to IS:10001/10002 and alternator as per IS:13364 , water cooled type, self starting system with 24 volt DC Supply, 3 phase 4 wire AC 415 volt ± 5% at 1500 RPM, 50 Hz, 0.8 PF self exciled, self regulated, Automatic voltage regulation, class 'H' insulation type alternator, With AMF (Automatic mains failure) panel for automatic starting at mains failure installed with the following accessories. (a) Engine:- Adequate capacity of Diesel. Engine suitable to not less than 315 KVA based on manufacturer reccomedation , Eco freindly for emission and noise (CPCB NORMS COMPLIANCE) diesel engine confirming to BS/IS standard developing suitable BHP as per OEM @ 1500 RPM water cooled complete under NTP condition with a provision for 10 % overload for one hour on 12 hours running complete with standard accessories all as specified and directed for safe handling and operation, salient features shall be as under :- (i) Fly Wheel with housing (ii) Cooling System - Mounted radiator with fan & belts. (iii) Cooling Water Pump:- Centrifugal type belt Driven
iv) Exhaust System :- Exhaust System complete with exhaust piping of 200 mm dia with MS pipe light grade upto and away (as per CPCB norm) from the enclosure to be errected, covered with asbestos rope and aluminium foil of 28 SWG complete with in the enclosure for safe exhaust without transforming vibration to the wall of the enclousre.a) Exhaust gas turbo charger type. b) Exhaust manifold c) Silencer:- Residential type d) Bellows v) Fuel System :- {a) Fuel injection system with fuel injectors, fuel injection solenoid switch/ nozzles/governer electronic type capable for 1% speed/ frequency regulation. b) Fuel Filters c) Fuel hoses. vi) Lub oil System :- a) Lubricating oil filters b) Lubricating oil pump. vii) Air intake system:- a) Air intake manifold b) Air cleaner dry type viii) Governer:- Electronic governer ix) Starting System:- Electric self startor with maintenance free batteries incl battery chargings set. x) Batteries:- (a) 2 Nos, maintenece free Batteries of 12 VOLT, 180 AH capacity complete with copper conductor multistranded leads of suitable length from self starter to the battary terminals complete with initial charge and initial fill of electrolite complete. b) Starter gear ring c) Start and stop push button. d) Iginition key/ switch xi) Handling and operation : Salient features of accessories shall be as under:- a) Radiator with blower fan b) Corrosion inhibitor coolant. c) Paper element filters for fuel, lub oil and by pass. d) Electronic governer controlled direct fuel injection system. xii) Generator Monitoring Panel:- Comprising of following:- a) Microprocessor based genset contoller (POWER COMMAND for metering, monitoring, governing and protection).
b) Engine protection for low lub oil pressure, high coolant temperature (alarm & shutdown) c) Alternator protection parameters like under voltage, over current, under frequency, over frequency ( alarm & shut down). d) Relay drivers for remote communications. e) Cyclic cranking f) Auto/ manual start/stop g) Alternator trim adjustment form the front key pad. h) Operates with a temp range 0-60 degree C and humidity upto 95%. J) Remote monitoring capability through separate interface modules. (k) Genset metering parameters like lube oil pressure, coolant temperature, engine speed (rpm), run hours, DC voltage, intake manifold temperature, 3 phase volts and 3 phase amperes, frequency, KW, KVA, power factor etc. xiii) Safety Controls : - Engine low lube oil pressure, high water temparature and over speeding of engine. xiv) Coupling arrangement: - Flexible coupling, fly wheel to suit flexible coupling fly wheel housing. xv) Accessories:- AVM Pads built or separtely mounted to manufacturer base frames. xvi) Base Frame : - Made out of ISMC 250 of sturdy design made of MS channel with necessary reinforcement and predetermined holes. xvii) Fuel Tank:- Daily service fuel tank of capacity 400 Ltrs made out of 3mm thick HR sheet top and bottom with caliberated level indicating arrangement, stop cock, drain plug, fuel pump of suitable capacity complete on a common base within the Acoustic Enclosure.
(B) Alternator:- Standard design alternator rated at not less than 315 KVA net output at site after considering derating as per site conditions at 0.8 (lag) power factor AC, 3 - phase 4 - wire 415 volts 50 Hz, 1500 RPM, self exicited self regulated screen protected drip proof IP 23 enclosure brush less design with winding in pole faces, insulating class 'H' and voltage regulation of ± 1 % at rated voltage from no load to full load. The alternator shall be confirming to BS 2613 and shall be inposition to generate supply with frequency regulation with in ± 1% tolerace. The alternator will be suitable for tropical climate and shall generally confirm to BS - 2613 & IS - 4722. a) Insulation Class - 'H' b) Temperature Rise class - 'H' c) Excitation - Self Excited d) Regulation performance:- The voltage is kept with + 1%, manual voltage adjustment within + 5%. e) Frequency regulation + 1%. C) Auto Main Failure (AMF) :- Microprocessor based cubical panel indoor type made out of CRCA sheet of 2mm thick conforming to IS 8623 totally enclosed dust and vermin proof with front and rear openings of 415 Volts, 3 phase, 4 wire, AC 50Hz having cupper bus bar required to carry current at 110% load of capacity not less than 315 KVA DG set with three phase and half neutral colour coded, prewired with copper cable of suitable size all as per standard practice of manufacturer specifications with the following accessories:-
(i) Custom built product for various equipments, with ensure the optimum performance (ii) Rugged in construction maintenance free and modular designs which facilitate easy at site. (iii) 16 SWG (l.6 mm) thick CRCA sheets to be used for enclosure panel to ensure longer life against weathering action. High quality acoustic insulation materials to be used for maximum sound proofing. (iv) Sheet metal components of the enclosure should undergo various stages of surface treatment prior to painting which leads to be better life of the enclosure against weathering action. (v) Special paint treatment with pure polyester powder/ epoxy to be provided for better weather resistance. (vi) Well designed ventilation system to be provided to pump up the heat in the chamber efficiently. (vii) For effective acoustic/ weather sealing a special type weather sealing gaskets, new frame rubber gaskets to used. (viii) Working space is to be provided around the equipment for easy maintenance/ repairs. (ix) Necessary cut out provision for entry and exist of fuel lines cable to be incorporated in the enclosure as per the requirement. (x) A see through transparent window (glass or acrylic) in front of engine panel to provided for monitoring the operation. (xi) Ducting if required, bellows, mechanical hardware like locks, hinges fasteners etc to be provided. (xii) Deliverables. 75 dBA@ lmtr at 75% load under free field conditions. The temp inside the enclosure will be within 7 Degree above ambient temp. (xiii) The enclosure should be provided with bulk head light fitting for inside illumination. (xiv) The battaries should be placed inside the enclosure beside the DG Set on a suitable inlsulated plat form.
(xv) The DG Set should be provided with external Emergency stop push button.(xvi) The acoustic enclosure parts shall be of powder coated after pre treatment process. The powder coating shade should be Genset Green. The base frame should be painted with epoxy based black shade. Notes:- a) Pre commissioning test shall be carried out by Rep of AO with in over all cost quoted. (b) Drawings shall be approved by GE before placement of order by contractor. (c) Cost of OEM specified all civil works including PCC plat form and related to foundations of DG Set including making good of distrubed surface after installtion and commissioning of genset is including in the overall cost quoted. (d) Complete DG Set alongwith acaustic shall be supplied by the same OEM.
MISC B/R ITEMS
M&L for preperation of new or previously untreated surface to recieve thermoplastic paint and making of guide lines,dashes,arrows,letters etc with reflective thermoplastic paint 2.0 to 2.50 mm thick white,golden,yellow or black colour as required,using glass beads necessary for achieving reflection on roads, pavements and the like of any description and any width all as per MOST clause 803.4 and BS 6068 complete all as specified and directed.
M&L for RCC septic tank designed to carry sewage and slluage water,excavation in any type of soil, PCC 1:4:8 below foundation, RCC-M30 Design mix walls, Base slab, baffle walls and roof slab incl beam etc with vent shaft, manhole openings with cover connection etc complete with effective depth of 1.5 meter and over all depth of meter for 50 users conventional type complete all as specified and as directed.(Complete all as per As per TD Drawing No.CEAF/STD-ST/118/22 , Sheet 1/3 to 3/3)
M&L for soakage well incl excation in any type of soil, foundation in PCC, 1:6 walls of honey combed masonry with top ring of M-25 concrete including intercepting chamber and screen chamber made of brick masonry in CM, RCC cover slab in M-25/ SFRC interconnecting pipe of RCC/DWC complete filled with brick bats of size 3.6 M dia and 4.5 M effective depth complete all as specified and directed. (Complete all as per As per TD Drawing No.CEAF/STD-301/90 , Sheet 1/4 to 4/4)
S&F concertina coil of 600 mm dia fixed on angle iron frames over RCC/Brick walls including securing or tying at crossings with and provision of galvanised mild steel wire, staples or steel pins etc complete all as specified and as direted.
MISC AIR CONDITIONING ITEMS
Supply and install Automatic boost/buck transformer for low and high voltage correction, equipped with electronic transistored relay suitable for correction on single phase 50 cycles AC supply complete with voltmeter and designed for input voltage 90 to 300V and output voltage stabilized 230V with accuracy of ± 5% and of capacity 5 KVA wall mounted all as specified and directed.
Ditto all as per Srl item No.5.01 above but of capacity 4KVA complete all as specified and directed.
Supply and install Hi wall split AC units indoor/outdoor with inverter Power Supply (V/Hz/Ph] 230 /5O/1 Phase complete with cordless remote control unit and with in built air ioniser, blue fins and Plasma filter for better indoor air quality with Twin Rotary compressor - BLDC, Copper Condenser Coil, Variable speed compressor which adjusts power depending on heat load energy efficient and lowest- noise operation Capacity: 1.5 Ton, Energy Rating: 5 Star rated, ISEER not less than 5.2 Refrigerant gas: R-134a Environment friendly -no ozone depletion potential & low global warming potential with suitable MS mounting stands factory made for indoor and outdoor unit including connecting Copper tubings, drain pipe, including extra refrigerant, electric cable, copper inlet and outlet tubing complete all as required at site & as specified and directed.
Ditto all as per Srl Item No.5.03 above but of 2.00 Ton capacity with ISEER rating not less than 5.5 complete all as specified and as directed.
S&F Single pole and neutral enclosure with a two pin and earth Plug and socket complete including one single pole MCB 20-32 Amp SP MCB "B" Curve 10 KA complete all as specified and directed.
S&F drain pipes 25mm dia heavy duty rigid PVC from indoor unit to exit point as per design including accessories clamps fastener etc complete all as specified and directed.
Supply, installation and testing of FLOOD Light luminaire 150watts 230V AC outdoor type with poly carbonate optics die cast housing, IP66 ingress protection. Efficiancy 110 lm/W complete suitable for input voltage 140 Volt to 280 Volt. The LED Flood light shall have power factor more than 0.95, 70 degree complete all as specified and directed.
M&L for GI Pipe 50mm bore dia medium Grade incl all fittings complete all as specified and directed.
Supply and laying of synthetic rubber insulated mats 2.5mm thick for voltage upto 11KV for electrical purpose as per IS 15652-2006 suitable for electrical shock safety complete all as specified and directed.
S&F LED luminaire 600 mm x 600 mm, 36 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete all as specified and as directed.
S&F post top lantern LED type 40 watt 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp incl making connections complete all as specified and directed.
M/s KUMAR BUILDERS
M/s Innovative Coolings and Constructions
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .