Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Fee/PreQual/Technical | Admitted-Fee/PreQual/Technical |
| 2 | Admitted-Fee/PreQual/Technical KHANDRA BARDHAMAN 713363 WEST BENGAL INDIA | KHANDRA | BARDHAMAN | WEST BENGAL | 713363 | Admitted-Fee/PreQual/Technical |
| 3 | Admitted-Fee/PreQual/Technical 59 R G S ROAD USHAGRAM DURGAMANDIR ASANSOL BARDHAMAN 713303 WEST BENGAL INDIA | ASANSOL | BARDHAMAN | WEST BENGAL | 713303 | Admitted-Fee/PreQual/Technical |
| 4 | Admitted-Fee/PreQual/Technical | Admitted-Fee/PreQual/Technical |
Tender Value
₹6.7 L
EMD Value
₹8,500
Closing Date
8 Aug 2026, 11:00 amClosed
Area Engineer ENM,JHANJRA AREA
OFFICE OF THE GENERAL MANAGER, JHANJRA AREA, PO-LAUDOHA, BO, DIST. - PASCHIM BARDHAMAN, PIN-713385
Supply, Installation and Commissioning of Neutral Grounding Resistance along with Fail Safe Arrangement for System Voltage 3300 Volt, 1500 KVA, 6.6 KV/3.3 KV, Make Marsons Electricals Pvt Ltd, Oil Transformer SL No 27415 at 3 and 4 Incline under Jhan
2026_ECL_362602_1
ECL/GM/JNR/EnM/A2/26-27/26 dated 25.07.2026
Open Tender
Miscellaneous Works
Item Rate
21 days
JHANJRA
Please refer Tender documents.
5 documents required · 5 mandatory
₹8,500
10 Aug 2026
28 Jul 2026
10 Aug 2026
28 Jul 2026
8 Aug 2026
29 Jul 2026
28 Jul 2026 - 4 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1.01 | Supply of steel punched resistor with Ms enclosure duly,pre-trated from anti corrision,covered and duly coloured with powder-coated paint,having technical specifications: (A) Service: Outdoor,Humid Jand dusty enviorment.(B) Rated Resistor: 190.52 Ohms (+ 10%),100Kw.(D) Power |frequency voltage withstand Test: 2Kv to 10Kv AC RMS for 1 Minute.(E) Temparture rise:-350 Deg.C ambient Temparture. (F) Degree of Protection:IP 33as per IS 2147.(G) Reference stantard 32. | - | WORK | 1 | - |
| 1.02 | Supply of Fail safe NGR Monitoring system to detect arny open connection between star/Neutral point of the Transformer &Earth Pit via Neutral grounding resistance and initate asingal for Tripping and also should comprise an inbuilt Earth Leakge protection system(Time Setting 0.1 Sec to 15 Sec)Leakage |current Setting: (1A,2A,4A,6A,8A,10A) | - | WORK | 1 | - |
| 2Total impact of GST for the purpose of CTC | |||||
stage.html
html • 0.02 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Tendernotice_1.pdf
PDF • 1.35 MB
Tendernotice_2.pdf
PDF • 1.22 MB
BOQ_375511.xls
BOQ • 0.24 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .