Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹32.7 LAccepted-AOC | ₹32.7 L | L1 | Accepted-AOC Accepted being L1 |
| 2 | L2₹34.0 L+₹1.3 L (3.89%)Rejected-Finance 1389 RADHETENAMENT SOCIETY SARDAR ROAD SURENDRANAGAR SURENDRA NAGAR GUJARAT 363001 | SURENDRANAGAR | GUJARAT | 363001 | ₹34.0 L+₹1.3 L (3.89%) | L2 | Rejected-Finance Rejected being L2 |
| 3 | L3₹34.2 L+₹1.5 L (4.63%)Rejected-Finance AT ROAD NEAR RENUKA CINEMA P O DIST TINSUKIA ASSAM PIN 786125 | TINSUKIA | TINSUKIA | ASSAM | 786125 | ₹34.2 L+₹1.5 L (4.63%) | L3 | Rejected-Finance Rejected being L3 |
| 4 | L4₹34.4 L+₹1.7 L (5.28%)Rejected-Finance | ₹34.4 L+₹1.7 L (5.28%) | L4 | Rejected-Finance Rejected being L4 |
| 5 | L5₹34.7 L+₹2.0 L (6.24%)Rejected-Finance A T ROAD CHABUA NEAR ST LUKAS HOSPITAL PO CHABUA DIST DIBRUGARH ASSAM 786 184 | CHABUA | DIBRUGARH | ASSAM | 786184 | ₹34.7 L+₹2.0 L (6.24%) | L5 | Rejected-Finance Rejected being L5 |
Tender Value
₹33 L
EMD Value
₹66,000
Closing Date
17 Jul 2023, 6:00 pmClosed
GE (AF) Chabua
GE (AF) CHABUA, POST-CHABUA AIR FIELD, DIST-DIBRUGARH, ASSAM-786102
REPAIR/MAINTENANCE OF INTERNAL ELECTRIFICATION, SECURITY LIGHTS, DG SETS AND WATER SUPPLY AT AF STATION BALIJAN UNDER GE (AF) CHABUA
2023_MES_605616_1
483/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE (AF) Chabua
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
GE (AF) CHABUA
₹66,000
Yes
18 Aug 2023
26 Jun 2023
24 Jul 2023
26 Jun 2023
17 Jul 2023
10 Jul 2023
26 Jun 2023 - 3 Jul 2023
Amount
SCH 'A' PART-I
Taking down copper/aluminium point wiring (light, fan, bell, socket or power point) including fixture and fittings such as switches, ceiling roses, pendent, regulators, sockets, light fitting etc. including making good distrubed surfaces of walls, floors etc complete all as specified and directed.
Taking down carefully copper/aluminium Sub main wiring of any size from surface/concealed/existing conduit of any height and removing materials at site and making good disturbed surfaces of walls, floors roofs etc complete all as specified and directed.
Taking down old/unserviceable distribution board by disconnection of electric connection carefully SPN DBs/TPN DBs/Main Switch including old unserviceable MCCBs/MCBs, Isolators, etc and making good to disturbed surface all as specified and directed.
M&L for point wiring with 1.5 Sqmm single core PVC insulated FRLSH unsheathed copper multi stranded conductor in and including PVC casing capping including sunk Anodized pressed steel box 1.6 mm thick concealed in wall with white laminated colour 3 mm thick sheet cover of suitable size complete including PVC insulated multi stranded copper conductor of 1.5 Sqmm as earth wire to common earth dolly for connection to ceiling rose to earth terminal incl cutting, chasses and making good disturbed surface to match with existing finish with plaster for One light /Fan point controlled by one one way switch complete all as specified and directed.
All as per srl item No. 4 here-in-before but for one 3 pin socket outlet 5 Amps on the same board complete all as specified and directed.
All as per srl item No. 4 here-in-before but point wiring with 2.5 sqmm for one 3 pin socket outlet 5 Amps on the Independent board complete all as specified and directed.
All as per srl items No. 4 here-in-before but point wiring with 2.5 Sqmm for 15 Amp socket outlet with 2.5 sqmm earth continuity conductor complete all as specified and directed.
All as per srl items No. 4 here-in-before but point wiring with 4 Sqmm for Heater or electric equipment/AC 1.5/2 Ton/more than or equal to 3 KW load with 4.0 sqmm earth continuity conductor complete all as specified and as directed.
All as per item No. 4 above but for one light point controlled by two way switch with 1.5 sqmm copper conductor complete all as specified and directed.
All as per item No. 4 above but for one bell/buzzer point with 1.5 sqmm copper wire controlled by one push button on the independent board complete all as specified and directed.
S&F switch Piano type two way 5 amp 230 Volts complete all as specified and as directed.
S&F switch bell push piano type 5 amp 230 Volts complete all as specified and as directed.
S&F switch Piano type single pole 5 amp 230 Volts complete all as specified and directed.
S&F socket outlet 2 in 1, 5 pin, 5 amp complete all as specified and directed.
S&F switch Piano type single pole 15 amp 230 Volts complete all as specified and directed.
S&F socket outlet 2 in 1, 6 pin, 5 and 15 amp complete all as specified and directed.
S&F ceiling rose surface type Bakelite 65x50mm three terminals complete all as specified and directed.
S&F stepped type electronic fan regulator flush type complete all as specified and directed.
M&L for lamp holder, PVC/Polycarbonate type with back plate suitabl for batten fittings complete all as specified and directed.
S&F in repair switch modular type, one way, 6 Amps/10 Amps, 1 module 230 Volts complete all as specified and directed.
S&F in repair switch modular type, one way, 16 Amps/20 Amps, 1 module 230 Volts complete all as specified and directed.
S&F in repair socket outlet, modular type, multipurpose, multipin, 6 amps, 2 module, 230 Volts complete all as specified and directed.
S&F in repair socket outlet, modular type, multipurpose, multipin, 6 Amps/16 amps, 2 module, 230 Volts complete all as specified and directed.
S&F in repair modular type fan regulator, two module, 230 Volts complete all as specified and directed.
S&F call bell Ding-Dong AC, 230 volts single pole complete all as specified and as directed.
Supply and Fixing in replacement LED light fittings 36 watt Recess Mounting type, with mounting arrangement (Recess suitable for, 2x2 Grid, Hanging) Sheet aluminium housing with high quality LGP and PMMA diffuser, Separate HPF driver suitable for Armstrong and grid ceiling LED 240 Volts along with fixing arrangements complete all as specified and as directed.
Supply and fixing in repairs surface and wall mounted LED light batten fitting energy efficient of 20 watt, including LED light, provision of PVC insulated sheathed round flexible wire with multi strand copper conductor of size 1.5 sqmm 3 core 1100Volts grade all as specified and directed.
Supply and fixing in replacement surface and wall mounted LED batten fitting energy efficient fittings 10 watt complete, including provision of PVC insulated sheathed round flexible wire with multi stranded copper conductor of size 1.5 sqmm 3 core 1100 Volts grade complete all as specified and as directed.
Supply & Fix in replacement Factory made, distribution boards, sheet metal enclosure VTPN, 4 Ways, 415 Volts double door type, protection class (IP-43) suitable for mounting MCCBs DBs confirming to IS-13032, IS-8623, BS-5484 with min 200 Amps rating copper bus bar complete all as specified and as directed.
Supply and fixing, in replacement of MCBs Distribution board, sheet metal enclosure, SPN 240 Volts, 08 ways with 200 Amps rated bus bar, double door for MCBs, with IP 43 protection, complete all as specified and directed.
Supply and fix in replacement MCCB, 4 Pole, 63 Amps, with breaking capacity 16KA, Thermal magnetic trip Unit, fixed thermal Fixed magnetic (FTFM), Ics=100% Icu, AC 415 volt ,50 HZ complete all as specified and as directed.
S&F in repair MCB SP 240 volt 6 to 32 Amps 'C' series 10 KA complete all as specified and directed.
S&F in repair MCB DP 240 volt 63 Amps 'C' Series 10 KA complete all as specified and directed.
S&F in repair MCB DP 240 volt 40 Amps 'C' Series 10 KA complete all as specified and directed.
Supply and draw submain wiring with two single core 6 sqmm FRLS PVC insulated copper cable 1100 volts grade multistranded, unsheathed conductor drawn into PVC concealed conduit and all necessary fittings including 6 sqmm multi strand FRLS PVC insulated copper wire for earth continuity conductor connected to common earth dolly complete all as specified and directed.
Supply and draw submain wiring with two single core 4 sqmm FRLS PVC insulated copper cable 1100 volts grade multistranded, unsheathed conductor drawn into PVC concealed conduit and all necessary fittings including 4 sqmm multi strand FRLS PVC insulated copper wire for earth continuity conductor connected to common earth dolly complete all as specified and directed.
M&L for earthing complete with galvanized mild steel earth electrode plate 600 X 600 X 6 mm thick buried directly and vertically in ground connected to galvanized earth lead wire 4 mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical Plate No 3 of MES SSR Part-I connected to main switch board or main control board all as specified and testing on completion including provision of earth wire protected by galvanized iron 15 mm bore medium grade pipe with all fittings from the earth electrode fixed along pole or wall with and including 25 x 6mm flat iron clamp, bolts, nuts and washers and watering pipe shall be 20 mm bore GI medium grade from top of the earth pit to top of earth plate electrode including all excavation and earth work in any type of soil and removal of soil upto 50 metre, PCC pit with pre-cast RCC cover with handle, charcoal/salt, funnel, CI frame etc including taking down old unserviceable earthing complete all as directed. Notes:- (i) The concrete pit shall be made in PCC 1:2:4 type B-0, using 12.5 mm graded crushed stone aggregate 40mm thick precast cover slab of RCC (1:2:4), type B-1, using 20mm graded crushed stone aggregate with suitable MS handle in lieu of CI cover (ii) Item includes the cost of 7.5 metre GI pipe for protection of earth wire. Any variation in length shall be adjusted through deviation order (iii) Items includes cost of 7.5 metre earth lead wire. Any variation in length shall be adjusted through deviation order. (iv) Earth electrode shall be surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides.
S&F in repairs blanking Plates for covering of MCCB DB open space complete all as specified and directed.
Supply and fix in repairs LED Lamps 9 Watts B 22 base 3 star rating suitable for batten holder complete all as specified and directed.
SCH 'A' PART-II
Dismantling/taking down carefully defective any type LED street light/security light/ flood light light fitting from pole/structure/bldg from any height and repair/checking and identifying of faulty spares, wrings, cleaning of fittings, cover etc and reassembling the same after repair, testing and refixing in original position and reconnecting with the electrical line complete all as directed. Note:- (i) Materials required for replacement such as driver, wires, etc will be measured and paid separately under relevant items. (ii) If E-N value on security feeder is high, it should be checked and rectified without extra claim.
Supply and fix in repair LED driver suitable for 45 watt LED street light fitting complete all as specified and directed.
Supply and fix in repair LED driver suitable for 60 watt LED street light fitting complete all as specified and directed.
Supply and fix in repair LED driver suitable for 70 watt LED street light fitting complete all as specified and directed.
S&F in replacement of LED street light energy saving & environmental friendly long life made up of pressure die-cast housing with toughened glass and high power LEDs with secondary optics and IP66 protection of 45 W capacity after taking down the old unserviceable one complete all as specified and directed.
S&F in replacement of LED street light energy saving & environmental friendly long life made up of pressure die-cast housing with toughened glass and high power LEDs with secondary optics and IP66 protection of 60 W capacity after taking down the old unserviceable one complete all as specified and directed.
S&F in replacement of LED street light energy saving & environmental friendly long life made up of pressure die-cast housing with toughened glass and high power LEDs with secondary optics and IP66 protection of 70 W capacity after taking down the old unserviceable one complete all as specified and directed.
Taking down old unserviceable post top lantern fittings and supply & fixing post top luminaire LED type of 25 W of post top lantern with aluminium die-cast housing cum heat sink in IP-65 protection including all fixinging arrangement complete all as specified and as directed.
Supply and fix in repairs, 8 watts LED bolards light IP-65 protection, resistant to corrosion better optics for uniform distribution including all fixing arrangements complete all as specified and as directed.
S&F in replacement of MCB SP 240 volt 6 to 32 Amps 'C' series 10 KA complete all as specified and directed.
Dismantling and taking down old aluminium strip 25x3.15 mm (lighting conductor) with saddles and air termination from roof/wall and making good the surface of wall/roof and white/colour washing to match with the existing surface complete all as specified and directed.
Supply and fix in repairs Air termination, single pointed aluminium rod 12 mm dia and 300 mm long complete all as specified and directed.
Supply and fix in repairs aluminium strip 25x3.15 mm with PVC/porcelain insulators, nut bolts, fixing screws etc for roof conductors and down conductors on wall/roof all as specified and directed.
M&L for manual horizental boring by passing GI protection pipe up to 50 mm bore dia under road/footpath, not exc 6 mtr in a single length complete all as specified and as directed.
Dismantling and taking down carefully the defective High mast light fittings by mechanically/manually and removing the unserviceable HPSV/HPMV/MH/LED/FTL/T5 street light/security light fitting and fixing new LED fitting/driver and servicing/cleaning checking connections including PVC insulated copper conductor multistranded twin core 1.5 sqmm cable from connector block to street light fitting approximately 0.30 m length and reassembling, and 1.5 sqmm twin core service wire from connector to junction box or OH conductor and refixing at its originatal location, including reconnections and testing/commissioning complete all as specified and directed. Note:- LED street light /security light fitting and LED driver shall be measured and paid separately under relevant items
S&F flood light fitting mounted on high mast light of 100 watt energy saving, environmental friendly, long life, made up of pressure die-cast aluminium housing with toughened glass and high power LEDs IP66 protection, suitable for highlighting architectural facade and general purpose lighting complete all as specified and directed.
Taking down old unserviceable service wires of any description complete all as specified and as directed.
Supply and laying or fixing or passing through pipe, 1100 volts grade heavy duty cable with PVC insulated aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall PVC sheathed of size 4 sqmm nominal cross section in service connections complete all as specified and as directed.
All as per srl item No. 57 here in before but size of cable 6 Sqmm, 2 core complete all as specified and as directed.
All as per srl item No. 57 here in before but size of cable 10 sqmm, 2 core complete all as specified and as directed.
M&L for painting of tubular poles 9 mtr long in two coats of aluminium paint over one coat of red oxide as primer including writing of pole Nos. complete all as specified and as directed.
Taking down old unserviceable UG cable of size 16 Sqmm, 2 core complete all as specified and as directed.
Supply and laying in trenches or drawn through pipe or fixed on wall/poles, LT UG cable heavy duty XLPE insulated, screened, PVC bedded, galvanised steel strip or wired armoured with aluminium conductor of size 16 Sqmm x 2 core complet all as specified and as directed.
Supply and fixing steel tubular pole, swaged, complete with cast iron base plate, final tapper plug, bolts, nuts, washer and screws including painting with two coats of aluminium paints over one coat of red oxide primer on all exposed surfaces and tarring with black bituminous paints to portion embedded in PCC including numbering of poles with to coats of synthetic enamel paints, type 410-SP-31 (9 mtr long) complete all as specified and directed. Note:- Earthwork and PCC shall be measured and paid separately under respective items.
Excavation in trenches, in soft/loose soil, nexc 1.5 m wide and nexc 1.5 m in depth; for foundation or for shafts, wells, manholes, pier holes, cable laying, sewage/water lines etc complete all as specified and directed.
Excavation in trenches not exceeding 1.5 mtrs wide and exceeding 1.5mtr and nexc 3.0 mtr in depth as in soft/ loose soil & getting out complete all as spfd & directed.
Returning, filling in including spreading, levelling, watering and well ramming in layers not exc 25 cm in soft/loose soil complete all as specified and directed.
Removing surplus excavated soil nexc 50 mtr and depositing where directed at a level nexc 1.5 mtr above the starting point complete all as specified and directed.
Supply and spreading dry coarse sand in trenches for protection of underground electric cable, spread in uniform 23 cm thickness and punned down gently to 18 cm complete all as specified and as directed.
Supply and laying well burnt Sub Class 'B' locally available best quality laid in trenches perpendicular to UG cable above sand cushioning for cable protection complete all as specified and directed.
M&L for cement concrete 1:4:8 type D-2 using 40 mm graded stone aggregate in foundation, filling and mass concrete complete all as specified and directed.
M&L for cement concrete 1:3:6 type C-2 using 40 mm graded stone aggregate in foundation, filling and mass concrete complete all as specified and directed.
M&L for Cement concrete 1:2:4 type B-1 using 20 mm graded stone aggregate in copping complete all as specified and directed.
Supply and fixing steel tubes, galvanised, light grade, ISI marked 50 mm bore for protection of cable under floor, road and on wall complete.
Cutting bituminous road/path for passing of elect cable through GI pipes and making good to the cut surfaces by concreating with PCC 1:3:6 to match with the adjescent surfaces complete all as directed.
M&L for Earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6mm thick, buried directly in ground (earth pit not less than 2.25m below normal ground level) with top edge of earth plate not less than 1.5m below normal ground level connected to main earth lead GI strip 25 x 4 mm as earth lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical plate No.3, including exc & earth work in any type of soil, disposal of soil, providing alternate layer of charcoal and common salt, construction of pcc earth chamber in mix 1:3:6 type C-1 with 40mm thick RCC 1:2:4 type B1 cover reinforced with 8mm dia MS bars both ways with lift hook made out of 8 mm dia bar, watering arrangement with funnel and wire mesh and watering pipe of 20mm dia GI light grade and 15mm dia light grade pipe for earth lead protection and testing on completion including taking down old unsverviceable one complete all as specified and directed. Note:- (i) Main earth lead beyond 7.5 meter shall be measured and paid separately through deviation order.
M & L for maintenance free chemical earthing system complete with 03 (three) nos copper bonded rods, 17.2 mm dia 3000 mm long electrode buried at suitable distance apart directly in ground, to bore holes of 120 mm dia vertically to a depth not less than 3.60 mtr deep below ground level with top edge of earth electrode at a depth not less than 100 mm below normal ground level, provision of clamps or brazed or both for each copper bonded rods made of copper and copper strip of size 25 x 3 mm & strip connection on the top of the electrode and copper strip of size 25 x 3 mm for inter connection of 03 nos copper bonded rods and laying at least 500 mm below in the ground and further connected to test point terminal block, including back filling of bore holes with advanced earth enhancing compound 96 kilogram (minimum) for artificial treatment to soil so as to achieve earth resistance below 01 Ohms as specified in para 19.140 of SSR Part-1 (2009), including provision of earthing pit in PCC(1:3:6) type C1 pre-cast cover RCC slab of size 400 x 400 x 50 mm with one handle made out of 8 mm dia round bar, including necessary earth work and three coats of white wash on plastered surface (exposed surfaces) and testing complete all as directed and including necessary earth work and testing complete all as specified and directed. Note:- Taking down old unserviceable dilapidated chemical earthing are included in quoted rate.
M&L for earthing complete with copper earth plate electrode 60 x 60 cm x 3.15 mm thick buried directly in ground vertically (earth pit not less than 2.25 m deep below normal ground level) with the top edge of the earth plate electrode at a depth not less than 1.5m below normal ground level and including copper earth strip of size 20 x 3 mm bolted (with GI nuts, bolts & check nuts) and riveted to earth plate electrode at one end and connected to metallic bodies of HT/LT equipments etc at the other end, earth strip encased in and including 50 mm bore GI medium grade pipe with all fittings from top of earth plate electrode to body of equipment fixed with and including 25x 6mm flat iron clamps, bolts, nuts and washers and including providing watering pipe 20mm bore GI pipe medium grade from Bottom of concrete pit to top of earth plate electrode complete all as specified and shown in electrical plate No 3 of MES SSR Part-I. The scope of work includes necessary excavation and earth work in any type of soil, removal of soil upto 50 metre, PCC pit with precast RCC cover, charcoal/salt, funnel, CI frame etc including taking down old unsv one complete all as specified and as directed. NOTES:- (i) The concrete pit shall be made in PCC 1:3:6 type C-1, using 20mm graded crushed stone aggregate 40mm thick precast cover slab of RCC (1:2:4), type B-1, using 20mm graded crushed stone aggregate with suitable MS handle in lieu of CI cover shown in electrical plate No 3 of MES SSR Part-I shall be provided. Reinforcement in RCC cover shall be of 8mm dia TMT bars laid @150mm c/c both ways. (ii) Item includes the cost of 7.5 metre GI pipe for protection of earth strip. Any variation in length shall be measured and paid through deviation order. (iii) Item includes cost of 7.5 metre earth strips. Any variation in length shall be adjusted through deviation order. (iv) Earth plate electrode shall be surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides.
Supply and fix street light GI bracket, bend to 120 degree angle, made out of 40 mm bore, GI pipe, light grade (approx 1.5 mtr in length) including necessary two nos suitable size of clamps with nuts, bolts and washers etc and two coat of synthetic enameled paint over a coat of red oxide primer including taking down the old rusted one complete all as specified and directed.
S&F in repairs junction box 200x140x95 mm in size, made out of thermoplastic sheet having IP 65 protection for outdoor installation fixed on poles with flat aluminium clamps of size 20 x 3 mm, nuts, bolts, washers etc. & taking down of old unsv cable junction box complete all as specified and as directed.
SCH 'A' PART-III
Labour only for servicing of 160 KVA DG Set with replacement of engine oil/lubricant, coolant, Oil Filter element, Fuel filter element, fuel flexible pipe, V belt for water pump and alternator, air filter element, etc. complete all as specified and as directed. Note:- (i) Engine oil, coolant and Spares to be measured and paid under respective items here in after and necessary servicing should be done after an interval of runnig 500 Hrs or six months which will be earlier. (ii) Spare parts shall be of OEM or equivalent in approved make.
(a) Lub Oil Filter element (Primary & secondary)
(b) Fuel Filter element (Primary & secondary)
(c) Air Filter Element (Primary & secondary)
(d) 'V' Belt
(e) Hose Rubber
(f) Gasket water pump
Labour only for servicing of 100 KVA DG Set with replacement of engine oil/lubricant, coolant, Oil Filter element, Fuel filter element, fuel flexible pipe, V belt for water pump and alternator, air filter element, etc. complete all as specified and as directed. Note:- (i) Engine oil, coolant and Spares to be measured and paid under respective items here in after and necessary servicing should be done after an interval of runnig 500 Hrs or six months which will be earlier. (ii) Spare parts shall be of OEM or equivalent in approved make.
(a) Lub Oil Filter element (Primary & secondary)
(b) Fuel Filter element (Primary & secondary)
(c) Air Filter Element (Primary & secondary)
(d) 'V' Belt
(e) Hose Rubber
(f) Gasket water pump
Labour only for servicing of 40 KVA DG Set with replacement of engine oil/lubricant, coolant, Oil Filter element, Fuel filter element, fuel flexible pipe, V belt for water pump and alternator, air filter element, etc complete all as specified and as directed. Note:- (i) Engine oil, coolant and Spares to be measured and paid under respective items here in after and necessary servicing should be done after an interval of runnig 500 Hrs or six months which will be earlier. (ii) Spare parts shall be of OEM or equivalent in approved make.
(a) Lub Oil Filter element (Primary & secondary)
(b) Fuel Filter element (Primary & secondary)
(c) Air Filter Element (Primary & secondary)
(d) 'V' Belt
(e) Hose Rubber
(f) Gasket water pump
Labour only for servicing of 30 KVA DG Set with replacement of engine oil/lubricant, coolant, Oil Filter element, Fuel filter element, fuel flexible pipe, V belt for water pump and alternator, air filter element, etc. complete all as specified and as directed. Note:- (i) Engine oil, coolant and Spares to be measured and paid under respective items here in after and necessary servicing should be done after an interval of runnig 500 Hrs or six months which will be earlier. (ii) Spare parts shall be of OEM or equivalent in approved make.
(a) Lub Oil Filter element (Primary & secondary)
(b) Fuel Filter element (Primary & secondary)
(c) Air Filter Element (Primary & secondary)
(d) 'V' Belt
(e) Hose Rubber
(f) Gasket water pump
Supply and fixing in repair water Pump for disel generator set of capacity 160 KVA complete all as per specified and directed.
M&L for repair/rewinding of Battery charging Alternator Heavy duty 24 volt with super enamelled/paper coated copper wire of existing gauge incluiding all connected insulating material such as separator etc, varnishing, replacement of carbon bushes including disconnection/dismantling of electrical connections, foundation bolts, pulling out and reinsulation of burnt out winding after rewinding work including re-assembling and testing complete all as directed.
Supply and fixing in repair Engine mounting for DG set of any capacity with complete Nuts bolts washer etc complete all as per specified and directed.
S&F in repair hinges of doors of DG set of any capacity including welding of defective portion and provision of fixing of new MS hinges of suitable size for hanging of door complete all as directed.
M&L for rewiring of DG control panel of any cpacity with 10 sqmm, 6 sqmm, 4sqmm, 1.5 sqmm copper wire with proper size of lugs/socket/clamps etc complete all as specified and as directed.
Supply and fixing in repair of 4 Pole Power Contactors, type MCX 32, 2 NO + 2 NC, complete all as per specified and directed.
Supply and fixing in repair of 4 Pole Power Contactors, type MCX 22, complete all as per specified and directed.
Supply and fix in repairs of side mounting Add-on aux contact block MNX/MCX complete all as per specified and directed.
Supply and fix in repairs of front mounting Add-on aux contact block 1NO+1NC complete all as per specified and directed.
Supply and fixing in replacement of maintenance free battery with initially charged of capacity 150 AH, 12 Volt complete all as specified and as directed.
Supply and fixing in replacement of maintenance free battery with initially charged of capacity 90 AH, 12 Volt complete all as specified and as directed.
Calibration of FIP of 100 to 250 KVA DG set including minor repair complete all as specified and as directed.
Supply only Engine oil 15W40 to top up/refilling of all DG set of various capacity, model & location as directed by engr-in-charge complete all as specified.
Supply only Coolant suitable for DG complete all as specified and as directed.
M&L for rewinding of Stator/Rotor coil of alternator/Rectifier Coil Unit of DG set with super enamelled/paper coated copper wire of existing gauge including all connected insulating material such as separator etc, varnishing, replacement of carbon bushes including disconnection/dismantling of electrical connections, foundation bolts, pulling out of rotor with proper care and reinsulation of burnt out rotor/stator after rewinding work including re-assembling and testing complete all as specified and as directed.
M&L for replacement of defective alternator assembly by new alternator assembly 24 volts suitable for DG set of capacity 100 KVA complete all as specified and as directed.
Labour only for repair of self starter 24 volt, dismantling from DG set of Capecity 100 to 160 KVA and shifting to workshop and back for and including carrying out following repair works complete all as specified and as directed. Note:- (i) Spares to be measured and paid under respective items here in after. (ii) Spare parts shall be of OEM or equivalent in approved make.
(a) Armature
(b) Bush
(c) Brush
(d) Carbon soldering
(e) Solonoid switch Assy
(f) Carbon recker
(g) Drive Assy
Labour only for repair of self starter 12 volt, dismantling from DG set of Capecity 30 to 75 KVA and shifting to workshop and back for and including carrying out following repair works complete all as specified and as directed. Note:- (i) Spares to be measured and paid under respective items here in after. (ii) Spare parts shall be of OEM or equivalent in approved make.
(a) Bush
(b) Bush soldering
(c) Solonoid switch Assy
(d) Carbon recker
(e) Drive Assy
(f) Field coil
(g)Battery terminal
Dismantling the engine of 100 KVA DG set for overhauling by taking out cylinder head, water cooler pump, front engine cover plate and engine full servicing of all the fuel and cleaning operation oil lines, replacement of spares as necessary and reassembling the same after necessary repair works and testing complete all as specified and directed. Note:- (i) Spares to be measured and paid under respective items here in after. (ii) Spare parts shall be of OEM or equivalent in approved make.
(a) Cylinder Head sealing
(b) valve seal
(c) Engine valve
(d) Set of joint
(e) Nozzle
(f) Injector
(g) Cylinder Liner
(h) Piston
(j) Piston Ring
(k) Front Oil seal
(l) Rear Oil seal
Supply & fix in repair AVR of 12 Volts complete all as specified and as directed.
Dismantling the cylinder head from DG set of Capacity 160 KVA and shifting to workshop and back for and including carrying out following repair works:- (a) Decarbonising and cleaning the cylinder head assy. (b) Head grinding and polishing (c) Sheet cutting and fitting of cylinder head (d) Fixing value guide
Dismantling of radiator assembly from generating set and re-fixing of the same after and including proper cleaning of the same with caustic soda and brazing the tube if any leakage complete all as directed for 100 to 160 KVA DG set complete all as specified and as directed.
S&F in repairs DG control unit suitable for 30 to 40 KVA Capacity Kirloskar make DG sets including neccessary connections and testing complete all as specified and as directed.
S&F in repairs DG control unit suitable for 100 to 160 KVA Capacity Kirloskar make DG sets incl neccessary connections and testing complete all as directed.
M & L for maintenance free chemical earthing system complete with 03 (three) nos copper bonded rods, 17.2 mm dia 3000 mm long electrode buried at suitable distance apart directly in ground, to bore holes of 120 mm dia vertically to a depth not less than 3.60 mtr deep below ground level with top edge of earth electrode at a depth not less than 100 mm below normal ground level, provision of clamps or brazed or both for each copper bonded rods made of copper and copper strip of size 25 x 3 mm & strip connection on the top of the electrode and copper strip of size 25 x 3 mm for inter connection of 03 nos copper bonded rods and laying at least 500 mm below in the ground and further connected to test point terminal block, including back filling of bore holes with advanced earth enhancing compound 96 kilogram (minimum) for artificial treatment to soil so as to achieve earth resistance below 01 Ohms as specified in para 19.140 of SSR Part-1 (2009), including provision of earthing pit in PCC(1:3:6) type C1 pre-cast cover RCC slab of size 400 x 400 x 50 mm with one handle made out of 8 mm dia round bar, including necessary earth work and three coats of white wash on plastered surface (exposed surfaces) and testing complete all as directed and including necessary earth work and testing complete all as specified and directed. Note:- Taking down old unserviceable dilapidated chemical earthing are included in quoted rate.
M&L for earthing complete with copper earth plate electrode 60 x 60 cm x 3.15 mm thick buried directly in ground vertically (earth pit not less than 2.25 m deep below normal ground level) with the top edge of the earth plate electrode at a depth not less than 1.5m below normal ground level and including copper earth strip of size 20 x 3 mm bolted (with GI nuts, bolts & check nuts) and riveted to earth plate electrode at one end and connected to metallic bodies of HT/LT equipments etc at the other end, earth strip encased in and including 50 mm bore GI medium grade pipe with all fittings from top of earth plate electrode to body of equipment fixed with and including 25x 6mm flat iron clamps, bolts, nuts and washers and including providing watering pipe 20mm bore GI pipe medium grade from Bottom of concrete pit to top of earth plate electrode complete all as specified and shown in electrical plate No 3 of MES SSR Part-I. The scope of work includes necessary excavation and earth work in any type of soil, removal of soil upto 50 metre, PCC pit with precast RCC cover, charcoal/salt, funnel, CI frame etc including taking down old unsv one complete all as specified and as directed. NOTES:- (i) The concrete pit shall be made in PCC 1:3:6 type C-1, using 20mm graded crushed stone aggregate 40mm thick precast cover slab of RCC (1:2:4), type B-1, using 20mm graded crushed stone aggregate with suitable MS handle in lieu of CI cover shown in electrical plate No 3 of MES SSR Part-I shall be provided. Reinforcement in RCC cover shall be of 8mm dia TMT bars laid @150mm c/c both ways. (ii) Item includes the cost of 7.5 metre GI pipe for protection of earth strip. Any variation in length shall be measured and paid through deviation order. (iii) Item includes cost of 7.5 metre earth strips. Any variation in length shall be adjusted through deviation order. (iv) Earth plate electrode shall be surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides.
M&L for Earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6mm thick, buried directly in ground (earth pit not less than 2.25m below normal ground level) with top edge of earth plate not less than 1.5m below normal ground level connected to main earth lead GI strip 25 x 4 mm as earth lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical plate No.3, including exc & earth work in any type of soil, disposal of soil, providing alternate layer of charcoal and common salt, construction of pcc earth chamber in mix 1:3:6 type C-1 with 40mm thick RCC 1:2:4 type B1 cover reinforced with 8mm dia MS bars both ways with lift hook made out of 8 mm dia bar, watering arrangement with funnel and wire mesh and watering pipe of 20mm dia GI light grade and 15mm dia light grade pipe for earth lead protection and testing on completion including taking down old unsverviceable one complete all as specified and directed. Note:- (i) Main earth lead beyond 7.5 meter shall be measured and paid separately through deviation order.
SCH 'A' PART-IV
Opening of top and bottom cover of pressure feed type filteration plants 5000 to 10000 gallons capacity per hours, taking out old filter media including old strainer etc and removing and disposing at nearest dump complete all as specified and directed.
Scraping and cleaning the surface bed, inner and outer surfaces of the IR plant shell for complete removal of scales, rust, old paint etc and painting with two coats of anti corrosive bituminous lead free paint suitable for storage of potable water (for internal surfaces) and two coats of aluminium paint for external surfaces and two coats of synthetic enamel paint with connected valves,frontel pipes as per colour code and write (size of lettering 65 mm height) on indicated space ie. DATE OF CHANGING FILTER MEDIA............., CAPACITY OF TANK ...........,MES NO ............, SM NO ........etc.) in white synthetic enamel paint over black back ground synthetic enamel paint of 10000 gallons capacity filtration plant complete all as specified and directed.
Supply and fixing in repairs of strainer, PP/LDPE double deck type PP (3/8" or 1/2") suitable for filtration plant, complete all as specified and as directed.
Supplying and charging in layers special coarse sand (Barakar sand) suitable for use in filtration plant of size 1/8''x 1/16'' mesh, complete all as specified and as directed.
All as per srl item No. 114 here in before but 1/16''x1/24'' mesh complete all as specified and directed.
Supplying and charging in layers new washed, cleaned, dust free graded gravels filter media suitable for use in filtration plant of size above 20mm to 40mm complete all as specified and directed.
All as per srl item No 116 here in before but size above 12 mm to 20mm complete all as specified and directed.
All as per srl item No 116 here in before but size above 6 mm to 12 mm complete all as specified and directed.
All as per srl item No 116 here in before but size above 3 mm to 6 mm complete all as specified and directed. Note for item Nos. :- (i) Before charging of filter media contractor shall carry out raw water testing for all parameters. (ii) After complition of the change of filter midia the treated water is to be send for water testing for all parameters with in 10 days. (iii) All testing connected with water should be done from Govt/Govt approved laboratory . (iv) The water testing cost is demed to be included in quoted rates.
Supply and charging in layers Manganese dioxide (MnO2) of approximate sizes 20 mm to 25 mm containing at least 65% of manganese, suitable for use in filtration plant complete all as specified and as directed. Note:- Samples of raw material (MnO2) should be got tested in Govt approved laboratory before using in the oxidation chamber for determining the MnO2 purity, which shall not be less than 65% (MnO2 contents minimum 65% purity), testing charge for the same is deemed to be included in the cost quoted by the controctor.
Supply and fixing in repair butterfly valve 80 mm bore including taking out old valve complete all as specified and as directed.
Supply and fixing in repair butterfly valve 100 mm bore including taking out old valve complete all as specified and as directed.
Material and labour for Cleaning, desludging and removing of all scales and dirt from external surface of OH Pressed Steel Tank of capacity 9600 gallons installed at height of 40' staging by complete removal of old paint/rust by appllying detergent and scrapping/wire brushing/sand papering and washing with clear water and painting of external/internnal surface of PS OH tank complete with two coats of aluminium paint over a coat of red oxide primer including painting of structure and connected all pipe lines (rising mains and delivery lines) from tank as per colour coading and write (Size of letters 75 mm height) on indicated space at a height 3.5 mtr from ground level (i.e. DATE OF CLEANING................, CAPACITY OF TANK ..................etc.) in black synthetic paint over white synthetic enamel paint all as directed and specified. Note:- (a) Cost of staging/working platform involved shall be deemed to be included in the unit rate quoted. (b) Consumption of bleaching powder for cleaning of each tank shall not be less than 12 Kg. (c) Maximum two times cleaning of each tank in entire CA period. (Measured separately each time). (d) Work shall be carried out in safety norms and all safety shall be provided by the contractor and no extra claim shall be admissable at later stage.
Construction of brick masonry valve pit/chamber of internal dimension 90 cm x 90 cm x 90 cm depth with sub class 'B' old size bricks in CM (1:4) and 10 mm thick plastering in CM (1:4), PCC (1:4:8) type D2 (Using 40 mm graded broken stone aggregate) as in foundation lean concrete, PCC (1:3:6) type CI (using 20 mm graded broken stone aggregate) as in bedding and copping MS frame with 40 x 40 x 6 mm angle iron 3 mm thick MS sheet cover plate with locking arrangements, hinges and two coats of synthetic enamel paint over one coat of red oxide primer including preparation of surface, three coats of white wash on plastered surface (exposed to view) including necessary breaking of the existing old chamber, excavation in soft loose, soil, returning filling in and removal of surplus soil to a distance not exceeding 50 m, complete all as specified and as directed.
All as per item No. 124 here-in-before but valve pit chamber of internal dimension size 60 x 60 x 60 cm, complete all as specified and as directed.
Attending emergency breakdown of water supply installation where directed, taking out defective submersible pump set of capacity 7.5HP/10HP/15HP/ 20 HP including column pipes from bore well, transporting pump set from site to work shop for repairs and back and lowering the pump set including column pipes and making water and electric connection as per existing for running of pump motors complete all as directed. Note:- Spare Parts shall be measured and paid under relevant items.
Supply only Mitchel thrust bearing gunmetal for 15 HP Submersible pump & motor (water supply & sewage), complete all as specified and as directed.
Supply only Mitchel thrust bearing gunmetal V6 for 20 HP Submersible pump & motor (water supply & sewage), complete all as specified and as directed.
Supply only Rotor for, 15 HP Submersible pump & motor (water supply & sewage), complete all as specified and as directed.
Supply only Intermediate piece for 10 HP Submersible pump & motor (water supply & sewage), complete all as specified and as directed.
Supply only Gun metal impeller 140 mm for 15 HP Submersible pump & motor (water supply & sewage), complete all as specified and as directed.
Supply only Pump NRV 200 mm inner dia for 15/20 HP Submersible pump & motor (water supply & sewage), complete all as specified and as directed.
Supply only Pump shaft gunmetal for 15 HP Submersible pump & motor (water supply & sewage), complete all as specified and as directed.
Rewinding of stator of submersible motor for 20 HP capacity with water proof insulated copper wire of existing guage to achieve the specified/required RPM including taking out old unserviceable winding, complete all as specified and as directed.
Rewinding of stator of submersible motor for 15 HP capacity with water proof insulated copper wire of existing guage to achieve the specified/required RPM including taking out old unserviceable winding, complete all as specified and as directed.
Supply, fiixing, testing and commissioning pressed steel plates of size 1.25m x 1.25m x 6mm thick on existing PS OH Tank installed on 40' to 50' height staging with required number of holes on the plates according to existing plate of PS tank incluiding all necessary joining materials i.e. lead wire, tape, lead wool, gasket, putty/jointing compound, new machine made bolts, nuts, washers, MS cleat etc of required size to make the joining portion absolutly leak proof complete including painting of two coats of lead free black bituminous paint suitable for storage of drinking water internally and two coats of Alluminium paint over one coat of red oxide zink chrome primer externally including preparation of surface and refixing/reconnecting of existing pipe line connection, complete all as specified and as directed. Note:- Cost of staging/working platform involved shall be deemed to be included in the unit rate quoted.
Repairing of joints of plates in position by loosing the jointing bolts, unscrewing jointing materials such as lead wire/tapes, lead wool gasket, bituminous compound and replacing with new matching made bolts, nuts, washers bituminous compound suitable for potable water and MS cleats wherever required complete all as specified and as directed.
S&F in repairs of 3 mm thick MS sheet cover plate with locking arrangement fixed at any position of PS overhead tank installed on 40' to 50' height staging including necessary welding, jointing materials to make the jointing portion absolutely leak proof complete all as specified and as directed.
Repairs to existing 9600 Gallons water tank installed on 40/50 feet height staging by disconnecting pipe connection carefully taking down the existing PS plates by cutting welding, nut bolts etc and refixing the same with existing serviceable plate/new plate of size 1.25 m x 1.25 m x 6 mm (PS plates refixed/new shall measured and paid separately under respective items), painting the tank after repair work with 2 coats of aluminium paint outside the tank including staging (staging painted by black synthetic enamel paint both side) top to bottom and two coats of lead free black bituminous paint inside the tank (suitable for storage of drinking water) and scraping smoothly by scraper & sand paper to remove all loose paints, scales, rust and restoration of pipe lines, lettering with white synthetic enamel paint over the black painted surfaces of indicated plates (i.e. capacity of tank, date of cleaning etc) complete all as directed. Note:- (a) The cost for the refitting of pipeline connections in new or old positions with necessary GI fittings, flanges and jointing materials etc includes in the unit rate quoted by the firm to make the joint leak proof. (b) Plates shall be measured and paid separately. (c) The PS tank shall be painted with two coats of alluminium paint out side incl staging and two coats of black bituminous (lead free) paint inside complete, Cost of staging/working platform & painting (inside / outside) invoived shall be deemed to be included in the unit rate quoted.
Taking down old unserviceable corroded/rusted GI pipe of size upto 20mm bore complete all as specified and directed.
All as per ser item no 140 here in before but size of GI pipe 25 mm bore complete all as specified and directed.
All as per ser item no 140 here in before but size of GI pipe 32 mm bore complete all as specified and directed.
All as per ser item no 140 here in before but size of GI pipe 40 mm bore complete all as specified and directed.
All as per ser item no 140 here in before but size of GI pipe 50/63 mm bore complete all as specified and directed.
All as per ser item no 140 here in before but size of GI pipe 80/90 mm bore complete all as specified and directed.
All as per ser item no 140 here in before but size of GI pipe 100 mm bore complete all as specified and directed.
S&F GI pipe medium grade galvanised, with all fittings laid in trenches of size 20 mm bore complete all as specified and as directed. Note:- Excavation and earth work if required will be measured and paid seperately.
All as per slr item No. 147 here in before but size of pipe 25 mm bore complete all as specified and directed.
All as per slr item No 147 here in before but size of pipe 32 mm bore complete all as specified and directed.
All as per slr item No 147 here in before but size of pipe 40 mm bore complete all as specified and directed.
All as per slr item No 147 here in before but size of pipe 50 mm bore complete all as specified and directed.
All as per slr item No 147 here in before but size of pipe 80 mm bore complete all as specified and directed.
All as per slr item No 147 here in before but size of pipe 100 mm bore complete all as specified and directed.
Supplying and laying 32 mm bore 3 layer PP-R (Polypropylene Random Copolymer) pipes, SDR-7.4 (PN-16) UV stabilized and antimicrobial fusion welded having thermal stability for hot and cold water supply including all PP-R plain & brass threaded poly propylene fittings fixed complete to walls ceiling or in floors complete all as specified and as directed. Note:- Excavation and earth work if required will be measured and paid seperately.
All as per ser item No 154 here in before but size of PP-R pipe 63 mm bore complete all as specified and as directed.
All as per ser item No 154 here in before but size of PP-R pipe 90 mm bore complete all as specified and as directed.
Supply and fixing in repairs gun metal, globe or gate valves, with iron wheel head, screwed both ends for iron pipe and fixed for 20 mm bore pipe complete all as specified and as directed.
All as per ser item No 157 here in before but size of gate valve 25 mm complete all as specified and as directed.
All as per ser item No 157 here in before but size of gate valve 32 mm complete all as specified and as directed.
All as per ser item No 157 here in before but size of gate valve 40 mm complete all as specified and as directed.
All as per ser item No 157 here in before but size of gate valve 50 mm complete all as specified and as directed.
Supply and fixing in repairs 32 mm bore PP-R gate valves (brass insert) as per site requirement of the site complete all as specified and directed.
All as per srl item No. 162 here in before but size of PP-R gate valve 63 mm complete all as specified and directed.
Supply and fixing in replacement, sluice valve with cast iron body and gun metal/steel spindle and hand operated iron wheel, both ends flanged and drilled including nuts, bolts, washers and gaskets, PN 1.6 ISI Marked of 80 mm bore size complete all as specified and directed.
All as per srl item 164 here in before but of size 100 mm bore complete all as specified and directed.
Excavating in trenches nexc 1.5m wide and n exc 1.5m deep and getting out in soft/loose soil complete all as specified and directed.
Returning, filling in including spreading, leveling, watering and well ramming in layers nexc 25cm complete all as specified and directed.
Removing excavated material nexc 50m and depositing where directed at a level nexc 1.5m above the starting point complete all as specified and directed.
Taking up GI water mains from trenches for repair/rectification of leakage of GI water line of sizes 15 to 25 mm dia including bailing out water, mud etc and relaying the same after repair in position and testing of leakage complete all as specified and directed. Note:- Excavation & earthwork will be measured and paid for separately but GI fitting and jointing material deemed to be included in the quoted rate.
Taking up GI water mains from trenches/wall for repair/rectification of leakage of GI water line of sizes 40 to 50 mm dia including bailing out water, mud etc and relaying the same after repair in position and testing of leakage complete all as specified and directed. Note:- Excavation & earthwork will be measured and paid for separately but GI fitting and jointing material deemed to be included in the quoted rate.
Taking up GI water mains from trenches/wall for repair/rectification of leakage of GI water line of sizes 80 to 100 mm dia including bailing out water, mud etc and relaying the same after repair in position and testing of leakage complete all as specified and directed. Note:- Excavation & earthwork will be measured and paid for separately but GI fitting and jointing material deemed to be included in the quoted rate.
S&F in repairs Fully Automatic Star Delta Starter in sheet steel Enclosure with contactor rating & Pneumatic timers, 3 phase 415 volts, Relay range (12-18 Amps) suitable for 15 HP pump, and connection, testing, complete all as specified and as directed.
S&F in repairs Fully Automatic Star Delta Starter in sheet steel Enclosure with contactor & Pneumatic timers, 3 phase 415 volts, Relay range (15-22 Amps) suitable of 20 HP pump and connection, testing, complete all as specified and as directed.
S&F in repairs relay for automatic star delta submersible pump starter overload relay, range (13.2 Amps-20 Amps), 415 volts complete all as specified and as directed.
S&F in repair's relay for automatic star delta submersible pump starter overload relay range (22 Amps-30 Amps), 415 volts complete all as specified and as directed.
Supply and fixing in repair power contactors 4 pole rating 20 Amps, with auxilary contact 01 NO+01 NC complete all as specified and as directed.
Supply and fixing in repair power contactors 4 pole rating 25 Amps, with auxilary contact 01 NO+01 NC complete all as specified and as directed.
Supply and fixing in repair power contactors 4 pole rating 32 Amps, with auxilary contact 01 NO+01 NC complete all as specified and as directed.
S&F in repairs front mounted add on aux contact block 1 NO+1 NC suitable for power contactor MNX 45 complete all as specified and as directed.
S&F in repairs side mounted add on aux contact block 1 NO+1 NC suitable for power contactor MNX 45 complete all as specified and as directed.
Supply and fixing in repair digital voltmeter, ranging from 0 to 500 Volts, including providing necessary electrical connections (to accommodate in panel board) complete all as directed.
Supply and fixing in repair digital ammeter, ranging from 0 to 400 Amps (with CT of suitable ratio), including providing necessary electrical connections (to accommodate in panel board) complete all as directed.
S&F in repairs Indicator Lamps (LED type) including providing necessary electrical connections (to accommodate in panel board) complete all as directed.
Testing of water sample as per IS-10500, water sample collection from distribution point and getting tested at approved district testing laboratory once as and when required complete all as specified. Note:- Testing from one source shall be considered as one job.
Schedule of Credit
M/S S. P. ENTERPRISE
STANDARD ELECTRIC WINDERS
FREEZCON
M/s Sashi Enterprise
M/s PRABIR ENTERPRISE
MAA COMMUNICATION
M/s HALDER ENTERPRISE
M/S MAHATO ENTERPRISE
stage.html
html • 0.06 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .