| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹47.2 LAccepted-AOC | L1 | Accepted-AOC being L1 | |
| 2 | L2₹49.8 L+₹2.2 L (4.59%)Rejected-Finance NO 7 3RD MAIN ROAD MUNI REDDY LAYOUT HORAMAVU MAIN ROAD BANASAWADI BANGALORE 560043 | BENGALURU URBAN | KARNATAKA | 560043 | L2 | Rejected-Finance Rejected. Quoted rates are higher than L1 | |
| 3 | L3₹53.4 L+₹5.8 L (12.1%)Rejected-Finance NO 83 THAMMAIAH GARDEN ABBIGERE CHIKKABANAVARA PO BANGALORE 560 090 | BENGALURU URBAN | KARNATAKA | 560090 | L3 | Rejected-Finance Rejected. Quoted rates are higher than L1 | |
| 4 | L4₹53.6 L+₹6.0 L (12.7%)Rejected-Finance 4 94D RAJA COTTAGE 1ST FLOOR KANYAKULAM PARVATHIPURAM NAGERCOIL KANNIYAKUMARI TAMILNADU 629 003 | KANNIYAKUMARI | TAMIL NADU | 629003 | L4 | Rejected-Finance Rejected. Quoted rates are higher than L1 | |
| 5 | L5₹54.0 L+₹6.4 L (13.5%)Rejected-Finance | L5 | Rejected-Finance Rejected. Quoted rates are higher than L1 |
Tender Value
Refer Docs
EMD Value
₹1 L
Closing Date
22 Nov 2024, 6:00 pmClosed
Garrison Engineer M AF Jalahalli
Garrison Engineer M AF Jalahalli Bangalore 560013
SPECIAL REPAIR SECURITY STREET LIGHTS INFRASTRUCTURE OF VARIOUS LOCATIONS AND PROVN OF TERRACE SHED AT AWSO AT AFS JALAHALLI
2024_MES_681212_1
8966/E8
Open Tender
Electrical and Maintenance Works
Item Rate
181 days
Garrison Engineer M AF Jalahalli
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
Garrison Engineer M AF Jalahalli
₹1 L
6 Dec 2024
25 Oct 2024
29 Nov 2024
25 Oct 2024
22 Nov 2024
8 Nov 2024
25 Oct 2024 - 1 Nov 2024
Amount
Excavation in trenches for laying under ground cable, errection of poles and stays etc in any type of soil not exceeding 1.5 meter wide and not exceeding 1.5 meter deep and getting out complete all as specified and directed.
Returning, filling in including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick complete all as specified and directed.
Removing surplus excavated material to a distance not exceeding 50 meter and depositing where directed at a level not exc 1.50m above the starting point complete all as specified and directed.
Material and labour for Spreading ribbed soil in trenches as in cable cushioning all as per IS 1255-1983, complete all as specified and directed. Note :- (i) Excavated approved soil shall be ribbed by using sieve to separate composite particles etc. as per IS and refilling in trenches before laying of cable 8 CM and 15 CM after laying of cable. This is then gently punned down to a depth of 10 cm above the top of upper most cable (ii) For the purpose of measurement only punned thickness shall be considered for payment.
M & L for Bricks covering with width equal to length of brick as mechanical protection to cable with well burnt sub class ‘B’ bricks laid dry flat complete all as specified and directed.
Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including HDPE pipe of 40 mm dia suitable for 0.4 mpa working pressure complete all as specified and directed.
Material and labour for Cutting existing road/PCC/Drain for laying of GI or any type of pipe including necessary earth work, excavation exc 600mm depth but not exc 1mtr depth, 800 mm wide including making good existing surface with 150 mm thick PCC 1:2:4 type B1 using 20mm graded stone aggregate, complete all as specified and directed. Note :- The tenderer shall take into consideration for following points while quoting rate for this item and the unit rate is deemed to be inclusive for :- (i) Earth work and excavation in any type of soil (ii) Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc. 25 cm thick complete all as specified and as directed. (iii) Removing excavated material to out side MD. (iv) Laying of any type/any bore of pipe in trenches including taking down. Supply of pipe shall be measured and paid separately (v) 150 mm thick PCC 1:2:4 type B1 using 20mm graded stone aggregate as in road to make good existing disturbed surfaces.
Supply and fix in replacment for GI pipe light grade 40 mm dia for cable protection on road crossings /plinth protection etc fixed to the pole, wall etc along with suitable fittings for cable protection complete all as specified and directed.
Material and labour for 4 core 10 Sqmm XLPE insulated heavy duty electric cable with aluminium multi stranded conductor 1100 volts grade served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall sheathed laying in trenches/cable ducts, fixed to wall/pole, including taking down of unserviceable one complete all as specified and directed. Make:- Havells/ Polycab/ RPG Asian Note - Earthwork and bricks to be paid separately in respective items.
Material and Labour for plain cement concrete (1:4:8) type D2 using 40mm graded stone aggregate for foundation of poles and mass concrete etc, complete all as specified and as directed.
Material and Labour for plain cement concrete (1:3:6) type C1 using 20mm graded stone aggregate for coping for poles including necessary form work to exposed surfaces finished smooth and even complete all as specified and as directed.
Supply and fix bracket for street light fitting made out of 40 mm dia light grade GI tubing bent to required shape 1.5m long including necessary GI clamps, nuts bolts and washers and fixing to the pole complete including taking down old or old U/S bracket from the pole complete all as specified and as directed.
Supply and fix in replacement weather proof PVC junction box approved by CPRI for street light control box made out of not less than 2mm thick of size 250mm x 200 mm x 105mm (approx) complete with hinged door locking arrangement and consisting of 2 Nos of suitable size cable glands consisting of 01 No. panel mounted connector 4 pole MCB 6A 10KA 01No. including connecting up with the electrical connections and fixing and clamping complete all as specified and as directed.
Supply & Erecting of Mild steel tubular swaged poles of 9.0 meter long 410, SP-31 complete with cast iron base plate, bracket, finial taper plug, bolt, nuts & screws and painted on both side (internally & externally), external surface painted with two coat of aluminum paint over coat of red oxide primer and painting with black up to 1.5 meter from top of PCC coping white colour paint as in strips of equal width including marking pole numbers with one coat of synthetic enamel paint complete all as specified and as directed.
Supply and fix of LED street light fittings 70 watts pressure die cast aluminium housing with toughened glass and high power LEDs with option of secondary optic with IP-66 ingress protection with 4/5KV surge protection device, Manufacturers logo embossed on the housing for traceability (stickering/ printing not acceptable), system level efficacy of the luminarie is 120lm/W . The color temparature is arround 6500K with a color rendering index of 70. The luminaire if IP:66 protected with impact rasistence IK05 impact resistance, electronic driver compliant to IEC safety standards with power factor greater than 0.9, voltage variation range 120-270V, THD less than 20%, high and LED with individual peanut lens and lens plate for better optics. The product should be tested for IEC60598 safety standards, LM80 report for LED, entire product including taking down old u/s one complete all as specified and directed. Make : Bajaj/Philips/CG/Halonix.
Supply and fix of LED street light fittings 45 watts pressure die cast aluminium housing with toughened glass and high power LEDs with option of secondary optic with IP-66 ingress protection with 4/5KV surge protection device, Manufacturers logo embossed on the housing for traceability (stickering/ printing not acceptable), system level efficacy of the luminarie is 120lm/W . The color temparature is arround 6500K with a color rendering index of 70. The luminaire if IP:66 protected with impact rasistence IK05 impact resistance, electronic driver compliant to IEC safety standards with power factor greater than 0.9, voltage variation range 120-270V, THD less than 20%, high and LED with individual peanut lens and lens plate for better optics. The product should be tested for IEC60598 safety standards, LM80 report for LED, entire product including taking down old u/s one complete all as specified and directed. Make : Bajaj/Philips/CG/Halonix.
Supply, installation,commissioning and testing of factory assembled ,floor mounted ,free standing type tested LT Feeder pillar panels,with canopy ,as per electrical specifications for outdoor installation to be made of IP65 Polycarbonate modular enclosures. The enclosures made of polycrabonate,should be weather vermin proof, anti -acid,anti-corrossive,UV resistance in accordance with IEC 61439-1,fire retardant and self extingushing in accordance with IEC 60695-2-11 ,UL subject 94 for flammability V-0, should pass glow wire test for 960 degree in accoardance with 60695-2-11.Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262,IP65 in accordance with IEC-60529 and IEC- 60439-1, should have dielectric properties ,RoHS compliants & Halogen free. The manufacturer of boards/panels shall submit a copy of type test reports as per above mentioned norms either from UL/ERDA/CPRI/NABL labs in india.The panel should be modular and compartmentalized in construction with opaque and transparent doors, properly tight to base with thermoplastic screw having sealing gaskets of extruded silicon rubber to withstand adverse weather effects. The depth of modular enclosuser should be above 200mm for air circulation & to minimize temp rise. Panel shall be fitted with one No. of polycarbonate IP 65 9 W LED transperent bulk head luminaire 6500K,PF > 0.95 under canopy for easy maintenance . Panel should be fitted outside with one No. of 16 Amp 3 Pole IP65 industrial socket and 01 No. of 32 Amp 5P IP 65 industrial socket. 3 Phase and neutral 600 Amp current carrying capacity of aluminium bus bar insulated with colour coded heat shrinkable sleeves with SMC/DMC insulators,complete with the following swtich gears and mounting the panel board on ground with PCC (1:3:6) type C-1 using 20mm graded stone aggreate for bedding upto a height of 45 CM above ground level ,including dismanting and taking out old U/s LT panel board and reconnecting existing LT UG Cable with new panel board, complete all as specified and directed :-
(a) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 400 Amp, 36 KA - 01 No (Incomer). (b) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 200 Amp,25 KA - 05 Nos. (c) Multifunction Meter (V,I,PF) with suitable capacity of CT's - 01 No (d) Indicating lamp (R-Y-B) set LED type with backup MCB for 3 Phase Supply - 01 set. (e) Space for spare feeder - 01 No. Note :- (i) The Contractor shall submit the drawing for approval of GE before executing the work. (ii) Insulators, bus bar sleeves, lugs, gland etc including complete wiring with suitable size of copper wire are all inclusive in unit quoted rate. (iii) Make of Switch gear : Schneider/L&T/C&S. (iv) MCCB should be ICu =100% ICs. (v) Make of LT Panel/FPB shall be as mentioned in list of makes (PS).
Supply and fix of LED street light fittings 36 watts pressure die cast aluminium housing with toughened glass and high power LEDs with option of secondary optic with IP-66 ingress protection with 4/5KV surge protection device, Manufacturers logo embossed on the housing for traceability (stickering/ printing not acceptable), system level efficacy of the luminarie is 120lm/W . The color temparature is arround 6500K with a color rendering index of 70. The luminaire if IP:66 protected with impact rasistence IK05 impact resistance, electronic driver compliant to IEC safety standards with power factor greater than 0.9, voltage variation range 120-270V, THD less than 20%, high and LED with individual peanut lens and lens plate for better optics. The product should be tested for IEC60598 safety standards, LM80 report for LED, entire product including taking down old u/s one complete all as specified and directed. Make : Bajaj/Philips/CG/Halonix.
Supply and fixing in repair LED flood light 70 watt 230 V AC outdoor type including necessary bracket with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp, complete all as specified and directed. Make : Bajaj/Philips/CG/Halonix.
Supply and fixing in repair LED flood light 50 watt 230 V AC outdoor type including necessary bracket with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp, complete all as specified and directed. Make : Bajaj/Philips/CG/Halonix.
Supply, installation,commissioning and testing of factory assembled ,floor mounted ,free standing type tested LT Feeder pillar panels,with canopy ,as per electrical specifications for outdoor installation to be made of IP65 Polycarbonate modular enclosures. The enclosures made of polycrabonate,should be weather vermin proof, anti -acid,anti-corrossive,UV resistance in accordance with IEC 61439-1,fire retardant and self extingushing in accordance with IEC 60695-2-11 ,UL subject 94 for flammability V-0, should pass glow wire test for 960 degree in accoardance with 60695-2-11.Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262,IP65 in accordance with IEC-60529 and IEC- 60439-1, should have dielectric properties ,RoHS compliants & Halogen free. The manufacturer of boards/panels shall submit a copy of type test reports as per above mentioned norms either from UL/ERDA/CPRI/NABL labs in india.The panel should be modular and compartmentalized in construction with opaque and transparent doors, properly tight to base with thermoplastic screw having sealing gaskets of extruded silicon rubber to withstand adverse weather effects. The depth of modular enclosuser should be above 200mm for air circulation & to minimize temp rise. Panel shall be fitted with one No. of polycarbonate IP 65 9 W LED transperent bulk head luminaire 6500K,PF > 0.95 under canopy for easy maintenance . Panel should be fitted outside with one No. of 16 Amp 3 Pole IP65 industrial socket and 01 No. of 32 Amp 5P IP 65 industrial socket. 3 Phase and neutral 300 Amp current carrying capacity of aluminium bus bar insulated with colour coded heat shrinkable sleeves with SMC/DMC insulators,complete with the following swtich gears and mounting the panel board on ground with PCC (1:3:6) type C-1 using 20mm graded stone aggreate for bedding upto a height of 45 CM above ground level ,including dismanting and taking out old U/s LT panel board and reconnecting existing LT UG Cable with new panel board, complete all as specified and directed :-
(a) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 200 Amp, 36 KA - 01 No (Incomer). (b) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 100 Amp, 10 KA - 01 No. (c) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 63 Amp, 25 KA - 01 No. (d) Multifunction Meter (V,I,PF) with suitable capacity of CT's - 01 No. (e) Indicating lamp (R-Y-B) set LED type with backup MCB for 3 Phase Supply - 01 set. (f) Space for spare feeder - 01 No. Note :- (i) The Contractor shall submit the drawing for approval of GE before executing the work. (ii) Insulators, bus bar sleeves, lugs, gland etc including complete wiring with suitable size of copper wire are all inclusive in unit quoted rate. (iii) Make of Switch gear : Schneider/L&T/C&S. (iv) MCCB should be ICu =100% ICs. (v) Make of LT Panel/FPB shall be as mentioned in list of makes (PS).
Supply, installation, testing and commissioning of smart street light control system using GSM/Lux based technology having 20 KW 3 phase 64 Amp load capacity per phase and can be operated by IVRS/SMS/lux based infrared sensor etc complete with following:- (i) Nature switch operation should be based on natural light lux level. Require illuminnance level for switching on is ≤ 60 lux and for switching off ≥ 10 lux. The smart unit should have 4 timers that can be set via SMS. (ii) Surge protection device (SPD) should provide protection agaist indirect lightning & switching surges. It should conform to IEC61643-11 and should have 40 KA capacity. (iii) The sensor & SPD along with suitable power contactors and incoming-outgoing MCCB/MCBs should be enclosed in a enclosure made of rust proof, electric shock proof , metal weather proof conforming to IP65 with angle iron frame of suitable size 04 Nos legs 600 mm long , PCC 1:2:4 type B 1using 20 mm graded aggregate for grouting of base including taking down old unserviceable panel. The scope of work also comprising the following :- The GPRS shall have seven segment display to show voltage, current, network and street light status , it should also have indicator for showing supply status , timer , overload or high low voltage. It should also able to measure voltage, current and automatic set street light overload current. Unit have facility to call back to registered number for power on/off and if any fault occurs at site.in SMS it should also monitor power/on/off time light on off time, ampere, voltage, unit mode, network percentage date and mobile number who called device number. The device should also have battery backup with minimum 24 hours backup capacity. The panel should have three operation mode :- 1. GSM mode -in this mode light should be switched as per GSM controller's preset time by user by sms , 4 clock base timer facility should be availble 2. Nature switch based-in this mode light will be switched as per nature light lux level 3. Bypass mode -in this mode light will switched on directly for testing purpose and emeregncy switching .In GSM controller there should be facility to register 4 user by sms/call and alerts will be sent on all registered number and also call back on power on/off and faults on first registered number.The GSM controller should also compatible for cloud based data transmission for interfacing with web for future use, Password protection for Accessing the control of device via SMS/IVRS, complete all as specified and directed including the following subcomponent, supply and fixing features :-
(a) TPN MCCB 100 Amps capacity, 10 KA, 415 Volts -01 No. (Incoming) with separate SPD of 40 KA capacity. (Make of MCCB- L & T, C&S Havells) (b) Supply Resign cast CT'S - set of 3 (c) GSM based smart street light controller. (d) Lux based sensor to operate external as per light intensity. (e) Line Contactor, AC 3 duty, 3 phase, 415 volts. 50 Hz , 32 Amps -02 Nos (make - L & T, BCH, Havells) (f) MCB SP 32 Amps- 06 Nos (make -L & T, BCH, Havells) (g) Terminal block suitable for 100 Amp rating with brass contacts for INPUT/ and 63 Amp for OUTPUT termination. (h) GSM/Timer/Bypass Mode switch. (j) Panel wiring for control circuit with copper flexible 1.5 Sqmm & power wiring 10 Sqmm flexible. Make- Tricolite/ Kewintech/HPL
Supply, installation, testing & commissioning of maintenance free chemical earthing system comprising of 17mm dia copper bonded rod 3 mtr long horizontally pre welded T-terminal rod with provision for connection size of 50 x 150mm long, 6mm thickness with equal space either side, with 12mm dia hole of 02 numbers each on either side of the terminal clamp with 250 microns (average) coating thickness, tested and certified by CPRI India alongwith 50 Kg earth energizer compound and 10 litres earth resistance reducing liquid. The earthing energizer compound and resistance reducing earthing liquid shall be tested as per IEC-62561-7 read with ASTM G57-06, CI 3.4 Amp by any NABL accredited lab. The above mentioned rod shall be installed in 4-6 inch bore, 12 feet depth with a distance of minimum 3 meters between each installation including taking down existing one, complete all as specified and directed. Make : Model HTSP 317 of safeTrode or equivalent in OBO Betterman/ FURSE/ERICO.
The quoted rate shall also deemed to be included the following :- (i) Prior to installation of maintenance free chemical earthing, soil resistivity test to be carried out at the location where earthing work to be done in presence of Engr-in- Charge/JE (E/M),user and the report has to submit to Garrison Engineer with recommendation of manufacturer, if required additional interconnection of earthing (not more than 08 number of earthing) to achive earth result less then 1 Ohms. The arrangement done for soil resistivity testing and submission of report with recommendation deemed to be included in the quoted rate.
(ii) The description/ size/ qty of items mentioned in above are for indicating only however qty/ size may vary at site condition to maintain the earth resistance 1 ohm. The contractor shall quote rate by considering all factors.
(iii) Rate of earth energizer compound of 25 Kg of 02 bags and earth resistance reducing liquid 10 litre per cane for each pit deemed to be included in the quoted rate.
(iv) Resistivity of earth energizer compound and resistance reducing earthing liquid shall be certified by any NABL accredited lab carried out as per IEC-62561-7 read with ASTMG57-06, CI-3.4A and the certificate of same shall be submitted by the contractor before commencement of work.
(v) Earth enhancing material should not leach into the adjacent soil or underground water channels and its PH value should be in neutral range complete all as specified and as directed. It should solidify when mixed with water and set like concrete.
(vi) Copper strip of size 20 x 3 mm shall be fixed on proper post insulator at the instrument end ( copper strip upto 7.5 RM shall be considered in unit quoted rate and extra will be measured and paid separately).
(vii) Testing of earth shall be carried out in presence of departmental and user representative and report shall be submitted to Garrison Engineer duly signed by all concerned.
(viii) Earth resistance tester will be provided by the contractor. Tester should be calibrated from authorised company/ lab.
(ix) Earthing shall be tested after completion of work by the contractor in presence of Engr-in-charge, user and proper record shall be maintained duly signed by all concerned. After testing if the desired earth resistance of less than 1 Ohm is not obtained, the earthing will be redone at no extra cost to Govt. till desired result is obtained.
(x) The contractor shall give a written guarantee of minimum three years for maintaining the earth resistance less than 1 Ohm after certified date of completion.
(xi) No further maintenance or periodic watering or recharge shall be required in earthing during its guarantee period of over 03 years in all type of soil including soft/ disintegrated or hard rock.
(xii) During the guarantee period, if earth resistance is not maintained less than 1 ohm the contractor has to redo or rectify at no extra cost to Govt till desired result is maintained.
(xiii) A security deposit of value equal to 2.5 % of the rate quoted for chemical earthing for each earthing shall be retained from payment due to the contractor from final bill for the guarantee period.
(xiv) The electrode shall carry manufacturer's name .
(xv) The connection clamp shall be permanentlly welded to the copper bounded rod to avoid any kind of connectivity loss,.The pre-welded copper bounded rod shall not need any additional clamp for termination.
(xvi) The acceptable earth resistance at earth busbar/ test point shall not be more than 0.1 ohm.
(xvii) Earth work such as auguring and making good the surrounding area shall carried out in any type of soil.
(xviii) The contractor shall submit CPRI India certified document for copper bounded rod to ensure genuineness of material.
(xix) Sign board of mild steel sheet 2 mm thick duly painted with two coats of synthetic enamel paint over a coat of red oxide Zinc chrome primer showing result of earthing shall be fixed near the earth pit after completion as directed by engr -in- charge.
Earth pit cover made of heavy duty poly plastic of high grade polypropylene tested and certified by any NABL accredited lab for load bearing capacity not less than 7.2 tonnes with top dia not less than 250mm, bottom dia not less than 330 mm and height not less than 260 mm for each electrode pit, complete including taking down, old U/S pit cover complete all as specified and directed. Make : Model SEPC 250 of SAFE TRODE/ Electrogrip Model/ EGTEK3LC of ISG Global or equivalent in OBO Betterman/ ERICO. Note :- The contractor shall submit load bearing capacity certificate from the manufacturer.
Material and labour as for Earth pit indicator for existing earthing pit made out of 16 mm dia and 60 cm long MS Square bar embeded in PCC (1:3:6) type C-1 using 20 mm graded stone aggregate in PCC block of size 30 X30 X30 cm including CI/MS plate of size 250X300X 3 mm thick fixed on side of earth pit cover complete painting and writing over the plate ie. Type , Result, Date of measurement and pit number with Black back ground with white letters complete all as specified and as directed.
S&F Copper strip 20 x 3mm thick (99.99% molecularly copper) as earthing lead fixed to wall/roofs etc including taking down existing one all as directed. NOTE : All Joints should be joined by Exothermic Welding or Brazing.
Supply and fixing in repair LED flood light 30 watt 230 V AC outdoor type including necessary bracket with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp, complete all as specified and directed. Make : Bajaj/Philips/CG/Halonix.
Supply and fixing in repair LED flood light 100 watt 230 V AC outdoor type including necessary bracket with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp, complete all as specified and directed. Make : Bajaj/Philips/CG/Halonix.
Supply and fixing in repair LED flood light 200 watt 230 V AC outdoor type including necessary bracket with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp, complete all as specified and directed. Make : Bajaj/Philips/CG/Halonix.
Supply and fix in replacement for wiring to suitable street light fitting connection tapping from the line / connecting up from the junction box to the fitting etc with1.5 sqmm multistranded PVC insulated copper conductor including taking down old cable all as directed. Note:-Two run of cable copper conductor and non metallic PVC Rigid/ flexiable conduit(20mm dia) shall be measured as one unit length.
Supply, installation, commissioning and testing of factory assembled, floor mounted, free standing type tested LT Feeder pillar panels, with canopy, as per electrical specifications for outdoor installation to be made of IP65 Polycarbonate modular enclosures. The enclosures made of polycarbonate, should be weather/vermin proof, anti -acid, anti-corrossive, UV resistance in accordance with IEC 61439-1, fire retardant and self extingushing in accordance with IEC 60695-2-11, UL subject 94 for flammability V-0, should pass glow wire test for 960 degree in accoardance with 60695-2-11.Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262,IP65 in accordance with IEC-60529 and IEC- 60439-1, should have dielectric properties, RoHS compliants & Halogen free. The manufacturer of boards/panels shall submit a copy of type test reports as per above mentioned norms either from UL/ERDA/CPRI/NABL labs in india.The panel should be modular and compartmentalized in construction with opaque and transparent doors, properly tightened to base with thermoplastic screws having sealing gaskets of extruded silicon rubber to withstand adverse weather effects. The depth of modular enclosure shall be above 200mm for air circulation & to minimize temp rise. Panel shall be fitted with one No polycarbonate IP 65, 9 W LED translucent bulk head luminaire color lamp not less than 6500K, PF > 0.95 under canopy for easy maintenance. Panel should be fitted outside with one No. of 16 Amp 3 Pole IP65 industrial socket and 01 No. of 32 Amp 5P IP 65 industrial socket. 3 Phase and neutral 400 Amp current carrying capacity of aluminium bus bar insulated with colour coded heat shrinkable sleeves with SMC/DMC insulators,complete with the following swtich gears and mounting the panel board on ground with PCC (1:3:6) type C-1 using 20mm graded/ stone agregate for bedding upto a height of 45 CM above ground level, including dismanting and taking out old U/s LT panel board of any size and description, reconnecting existing LT UG Cable with new panel board, complete all as specified and as directed :-
(a) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 200 Amp, 36 KA - 02 Nos (Incomer). (b) On Load Changeover front operated of capacity 250 Amps,4 Pole ,415 Volts 01 No. (c) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 160 Amp,25 KA - 02Nos. (d) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 63 Amp,10 KA - 02 Nos. (e) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 40 Amp,10 KA - 01 No. (f) Multifunction Meter (V,I,PF) with suitable capacity of CT's - 01 No (g) Indicating lamp (R-Y-B) set LED type with backup MCB for 3 Phase Supply - 01 set. (h) Space for spare feeder - 01 No. Note :- (i) The Contractor shall submit the drawing for approval of GE before executing the work. (ii) Insulators, bus bar sleeves, lugs, gland etc including complete wiring with suitable size of copper wire are all inclusive in unit quoted rate. (iii) Make of Switch gear : Schneider/L&T/C&S. (iv) MCCB should be ICu =100% ICs. (v) Make of LT Panel/FPB shall be as mentioned in list of makes (PS).
Supply, installation, commissioning and testing of factory assembled, floor mounted, free standing type tested LT Feeder pillar panels, with canopy, as per electrical specifications for outdoor installation to be made of IP65 Polycarbonate modular enclosures. The enclosures made of polycarbonate, should be weather/vermin proof, anti -acid, anti-corrossive, UV resistance in accordance with IEC 61439-1, fire retardant and self extingushing in accordance with IEC 60695-2-11, UL subject 94 for flammability V-0, should pass glow wire test for 960 degree in accoardance with 60695-2-11.Degree of protection against mechanical load should be IK08 (5 Joule) in accordance with IEC 62262,IP65 in accordance with IEC-60529 and IEC- 60439-1, should have dielectric properties, RoHS compliants & Halogen free. The manufacturer of boards/panels shall submit a copy of type test reports as per above mentioned norms either from UL/ERDA/CPRI/NABL labs in india.The panel should be modular and compartmentalized in construction with opaque and transparent doors, properly tightened to base with thermoplastic screws having sealing gaskets of extruded silicon rubber to withstand adverse weather effects. The depth of modular enclosure shall be above 200mm for air circulation & to minimize temp rise. Panel shall be fitted with one No polycarbonate IP 65, 9 W LED translucent bulk head luminaire color lamp not less than 6500K, PF > 0.95 under canopy for easy maintenance. Panel should be fitted outside with one No. of 16 Amp 3 Pole IP65 industrial socket and 01 No of 32 Amp 5P IP 65 industrial socket. 3 Phase and neutral 600 Amp current carrying capacity of aluminium bus bar insulated with colour coded heat shrinkable sleeves with SMC/DMC insulators,complete with the following swtich gears and mounting the panel board on ground with PCC (1:3:6) type C-1 using 20mm graded/ stone agregate for bedding upto a height of 45 CM above ground level, including dismanting and taking out old U/s LT panel board of any size and description, reconnecting existing LT UG Cable with new panel board, complete all as specified and as directed :-
(a) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 400 Amp, 36 KA - 01 No. (Incomer). (b) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 250 Amp,25 KA - 01No. (c) MCCB with thermal magnetic release 4 Pole, 415 V of capacity 200 Amp,25 KA - 04 Nos. (d) Multifunction Meter (V,I,PF) with suitable capacity of CT's - 01 No (e) Indicating lamp (R-Y-B) set LED type with backup MCB for 3 Phase Supply - 01 set. (f) Space for spare feeder - 01 No. Note :- (i) The Contractor shall submit the drawing for approval of GE before executing the work. (ii) Insulators, bus bar sleeves, lugs, gland etc including complete wiring with suitable size of copper wire are all inclusive in unit quoted rate. (iii) Make of Switch gear : Schneider/L&T/C&S. (iv) MCCB should be ICu =100% ICs. (v) Make of LT Panel/FPB shall be as mentioned in list of makes (PS).
Excavating in post holes in soft/ loose soil (or similar holes) each n exc 0.50 cum getting out, and removing surplus soil to a distance n exc 50 m and all as specified and as directed
M&L Cement Concrete 1:2:4 type B-1 (using 20 mm graded crushed stone agg) as in foundation, filling, coping or for mass concrete etc including necessary formwork complete all as specified and directed.
S & F MS Steel work in tubular trusses including special shaped washer etc. complete using ERW or induction butt welded tubes conforming to I. S.1161 1979 grade St.-240 complete all as specified and directed.
S&F Rolled mild steel sections as in main and cross beams, Post ,hip and jack rafters;purlins where connected to common rafters and running rails and guides for sliding doors;fixed with angle cleats or other connecting plates conforming to , Fe-410-W(Gde-E-250)quality A complete all as specified and directed.
M & L for 0.50mm thick Pre painted Galvalume aluminium zinc coating GI based corrugated steel sheet AZ 150 of any colour having tensile strength of 550 Mpa as in roof covering/cladding to wall ,including ridges fixed with self tapping screws all as specified and directed.
M&L for providing two coats of synthetic enamel paint over a coat of red oxide primer on new steel surfaces of any description, over 10cm in width or girth,not otherwise described complete all as specified and directed.
Surface excavation n.exc 30cm deep and averaging 15 cm deep and getting out in soft soil complete all as specified and directed.
M&L 100 mm thick PCC (1:4:8) type D2 using 40mm graded aggregate 100mm thick as in sub base of floor, finished even and rough to receive top layer complete all as specified and directed.
Material and labour for 40 mm thick PCC 1:2:4 type B-1(using 20 mm graded crushed stone aggregate )as in flooring laid in panels, surfaces finished even and smooth using extra cement complete all as specified and directed. Note :- An amount of Rs 44545.00 on account of credit schedule for schedule 'A' part II shall be deducted from the total amount of BOQ to arrive at the contract sum.
ARUNOTHAYA TRADERS (BID ID -3171493)
M/S SRI BALAJI ENTERPRISES (BID ID -3164711)
ADR ENTERPRISES (BID ID -3171509)
SRINIDHI DIESELS & ELECTRICALS (BID ID -3161963)
Forge Engineering & Electricals (BID ID -3171558)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .